This document outlines a federal contract opportunity for replacing a fire alarm system. The General Services Administration (GSA) Region 5 is seeking a contractor to replace the fire alarm and notification system in the Bricker Federal Building and Bricker Federal Building Garage in Columbus, Ohio. The performance period is 357 calendar days for the Federal Building and 140 calendar days for the Federal Garage upon receipt of the Notice to Proceed. Offerors must demonstrate significant experience with fire alarm projects in large office buildings and parking garages. The anticipated award date is September 2022, with an estimated construction cost between $1-5 million. The NAICS code is 236220 and set aside for small businesses under $39.5 million. Proposals will be evaluated based on past experience, key personnel, project management plan, and past performance, with technical factors weighted more than price.
View the file
Other files for this federal contract opportunity
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
230 West Monroe, Suite 630, Chicago, IL 60606 ● 616.378.6215 Phone ● www.TRCcompanies.com
Asbestos and Lead Paint Inspection
John W. Bricker Federal Office Building (OH0208) 200 North High Street Columbus, OH 43215
Inspection Date: May 2, 2019 Report Date: August 27, 2019
Prepared For
GSA
Facility Management and Services Programs 230 South Dearborn Street, Suite 200 Chicago, Illinois 60604-1696
Prepared By:
230 West Monroe, Suite 630 Chicago, IL 60606
TRC Project Number: 314614.0000.P9 i July 2019
Table of Contents
Executive Summary .................................................................................................................... ii
General Building Information
Disclaimer
List of Tables
Table 1 List of Homgenous Sample Areas (HSAs) of Suspect and Asbestos Containing
Materials (ACMs) or Presumed (not sampled) Asbestos Containing Materials by URS (2004/2005), Versar (2006) and TRC (2019)
Table 2 List of Asbestos Containing Materials (ACMs) by URS (2004/2005), Versar (2006) and
TRC (2019)
Table 3 List of Lead Paint as sampled by URS (2004/2005), Versar (2006) and TRC (2019)
List of Appendices
Appendix A
Appendix B
Appendix C
Appendix D
Appendix E
Appendix F
Appendic G
Asbestos Containing Materials and Lead Paint Abatement Costs
TRC General Photo Log
TRC Supplemental Asbestos and Lead Lab Reports and COC May 2019
Historical ACM and Lead Reports: URS (2004/2005) & Versar (2006)
Diagrams of ACM Locations
Periodic Surveillance Form
Certifications ii
Executive Summary
In response to your request, TRC has completed the supplemental visual and limited testing of suspect asbestos-containing materials (ACM) and lead paint at the John W. Bricker Federal Office
Building (OH0208) Building located at 200 North High Street, Columbus, Ohio TRC met with GSA
Property Management team (Mr. Phil Ramos Facility Management and Services Programs
Environmental Engineer and Mr. Harry Sharp GSA Facility Management) for the initial kick-off meeting prior to conducting the re-inspection/visual inspection walk through. The TRC team was
Mr. Heath Howard (CIH) and Mr. Lonnie Lyro for the initial kick-off meeting.
TRC’s Mr. Lonnie Lyro was then accompanied by TRC’s Mr. Heath Howard who is a State of
Ohio-licensed, Asbestos Hazard Evaluation Specialist (license number ES36200) for the supplemental and limited testing of suspect asbestos containing materials and lead paint inspection on May 2, 2019.
TRC reviewed, utilized and relied upon the previous inspection report completed by URS
(2004/2005) & Versar (2006) February 2006 Asbestos and Lead-Based Paint Survey report and drawings. It should be noted that not all the inspectors associated with the asbestos inspection from Versar were licensed. It appears that the inspectors worked under the direction of one Ohio
Licensed asbestos inspector. The report can be found in Appendix D.
TRC also performed supplemental limited asbestos testing and lead paint observations on May
2, 2019(TRC 2019) and that information can be found in Appendix C. The asbestos samples were collected from the various floors. TRC also utilized various limited inspection and abatement reports provided by the Property Management Office at the building. TRC utilized that information to identify which areas of the building have had asbestos abatement activities performed in the past 14 years since the GSA report. This information and the historical reports by URS and Versar assisted TRC in creating the attached Asbestos Location Drawings that are found in Appendix E of this report.
The sample locations of TRC asbestos samples, combined with the historical asbestos and lead sampling drawings by URS and Versar can be found in Appendix E. TRC utilized the diagrams of the previous surveys and complied new diagrams noting all ACM identified on each floor.
Additional diagrams include TRC asbestos sampling locations.
The Periodic Surveillance Form can be found in Appendix F. This form notes the ACM in the building, location, quantity and condition of the material as noted by TRC in 2019.
iii
Asbestos Summary
According to the historical report by URS and Versar reviewed by TRC, and the materials verified onsite by TRC on May 2, 2019, the following asbestos containing materials are present on-site (see below Table 1 and Table 2 for locations).
• Black Mastic Associated with Tan with Streaks 12” x 12” Floor Tile
• Black Mastic Associated with Light Tan with Swirled 12” x 12” Floor Tile
• Black Mastic Associated with Brown/Tan with Swirled 12” x 12” Floor Tile
• Beige Duct Sealant
• Drywall System
• Insulating Cement – Ends of pipe
• Tank insulation
• Roofing Materials (Presumed, not sampled)
• Fire Doors (Presumed, not sampled)
• Mirror Mastics (Presumed, not sampled)
• Sink Undercoating
It should be noted that drywall system samples that were collected by Versar in 2006 of various floors of the building with the none detect, trace and one sample results reported as 2% Chrysotile on the 2nd floor lobby. TRC recommends collecting drywall system samples on every pre-alteration survey to confirm/deny the presence of asbestos
Any materials uncovered during renovation or demolition activities that are not addressed in this inspection report, or presumed asbestos containing materials, must be sampled by an accredited asbestos inspector prior to any disturbance, or they must be treated as asbestos containing (ACM). TRC recommends the GSA continue to engage qualified firms to sample for asbestos and lead paint utilizing their standard of practice of a pre-alteration survey for area-specific renovations and demolitions.
Lead Paint Summary
According to the historical report by Versar (2006), reviewed by TRC, the following Lead Containing Paints (LCP) are present on-site (see below Table 3 for locations). The drawings that depict the lead paint sampling by TRC and Versar (2006) can be found in Appendix C, TRC Supplemental Asbestos and Lead Inspection Report August 2019.
Versar
• Yellow Paint on the cooling tower platform, found on the penthouse mezzanine, reported as <0.01%, by weight.
• Gray Paint on the Floors found throughout the penthouse #1 mezzanine, reported at 0.03%, by weight.
• White Paint on the walls found on the penthouse #1 mezzanine, reported as <0.01%, by weight.
TRC
• Cream Paint on the I-beam, found in the penthouse, reported as 5,500 ppm.
• Yellow Paint on the I-beam, found in the penthouse, reported as 32,000 ppm.
• Grey Paint on the floor, found in the penthouse, reported as <230 ppm.
iv
• White Paint on the wall, found in elevator lobby near room FL7, 7th floor, reported as <89 ppm.
• Light yellow Paint on the wall, found on the 4th floor, reported as <84 ppm.
• Pink Paint on the steel, found in the parking garage, reported as 500 ppm.
Based on historical reports, age of the building, some paints sampled in the building by Versar and TRC had detectable amounts of lead and are considered Lead-Containing paints (LCP). Any paint over 5,000 ppm are considered Lead Based Paints (LBP) by definition.
Lead-based paint is defined by the United States Department of House and Urban Development (HUD) as any paint, varnish, stain, or other applied coating that has one mg/cm2 or more of lead or 0.5% by weight (5,000 micrograms per gram [ug\g] or 5,000 parts of lead per million [ppm]).
According the OSHA Program Directive, Lead: Exposure in Construction, "For all occupational exposure to lead occurring in the course of construction work, the standard (1926.62) does not specify a minimum amount or concentration of lead that triggers a determination that lead is present and the potential for occupational exposure exists." Therefore any paint containing less than 0.5% by weight, or less than 5,000 ppm, but greater than the laboratory detection limit is considered to be a LCP.
TRC recommends the GSA continue to engage qualified firms to sample for asbestos and lead paint utilizing their standard of practice of a pre-alteration survey for area-specific renovations and demolitions.
General Building Information John F. Bricker Federal Office Building (OH0208) 200 North High Street, Columbus, Ohio 44308
Facility Project Manager: Harry Sharp harry.sharp@gsa.gov
Type of Facility: Commercial Building – Offices: The John W. Bricker Federal Office Building located at 200 High Street, Columbus, Ohio is a seven-story concrete structure that includes: primarily offices, two penthouses, basement and, three roof levels (main, elevator and penthouse). The facility was constructed in 1977 and comprises approximately 261,257 total square feet. The interior walls and ceilings are covered with plaster, sheetrock and suspended ceiling tiles. The floors are covered with floor tile, carpet over concrete or solely painted concrete floor. Painted surfaces are located throughout the building.
mailto:harry.sharp@gsa.gov
Table 1 List of Homogenous Sample Areas (HSAs) of Suspect and Asbestos Containing Materials (ACMs) or Presumed (not sampled) Asbestos Containing Materials by URS (2004/2005), VERSAR (2006) and TRC (2019).
HSA #
By Versar, URS or TRC
MATERIAL
DESCRIPTION
MATERIAL LOCATION(S)
ACM or
NON -DETECT
(ND) or Presumed
% ACM and Type
TYPE OF
MATERIAL
CAT 1,
CAT 2, RACM
CONDITION
Versar
12”x12” Tan Floor
Tile w/Streaks
Penthouse -P1
ND NA Cat 1 Good 7th Floor – North Landing
6th Floor – North Landing
Black Mastic Associated w/12”x12” Tan Floor Tile w/Streaks
Penthouse -P1
ACM 5% Chrysotile Cat 1 Good 7th Floor – North Landing
6th Floor – North Landing
3 Fiberglass Pipe Run Throughout
NOT SAMPLED
PRESUMED
NEGATIVE –
GSA
Presumed – Negative NA Good
Fiberglass Pipe
Fittings Throughout
NOT SAMPLED
PRESUMED
NEGATIVE –
GSA
Presumed– Negative NA Good
Tank Insulation –
Mudd Over Fiberglass
Penthouse – P1 Tank #1
ND NA RACM Good
Tank Insulation –
Mudd Over Fiberglass
Penthouse – P1 Tank #2
ND NA RACM Good
URS
7 Spray-on Insulation
7th Floor - Corridor
ND NA RACM Good
6th Floor - Corridor 5th Floor - Corridor
3rd Floor - Corridor
Penthouse – Boiler Room
Corridor Outside Suite 407 3rd Floor - Corridor
2nd Floor – Elevator Lobby
2nd Floor – Messer Office
Basement – TCJ Equipment Room 6th Floor – GSA Office
Versar
Muffler Exhaust
Insulation P1 – Emergency Generator Room ND NA RACM Good
Chilled Water Tank
Insulation Air Handling Room – East Side
NOT SAMPLED
PRESUMED
Positive – GSA Presumed Positive RACM Good
10 Roofing Elevator Roof
NOT SAMPLED
PRESUMED
Positive – GSA
Presumed Positive Cat 2 Good
11 Roofing Penthouse Roof
NOT SAMPLED
PRESUMED
Positive – GSA
Presumed Positive Cat 2 Good
12 Roofing Main Roof
NOT SAMPLED
PRESUMED
Positive – GSA
Presumed Positive Cat 2 Good
13 Exterior Caulk Mezzanine ND NA Cat 2 Good
URS
14 Exterior Caulk Mezzanine – P1 Parapet Walls ND NA Cat 2 Good
Versar
15 Exterior Caulk – Gray Cooling Tower Piping Wrap ND NA Cat 2 Good
2’x4’ Fissured Ceiling
Tile
Telephone Room – P1 ND NA Cat 2 Good
Basement
URS
17 Duct Sealant – Tan
2nd Floor - Corridor
ACM 2%Chrysotile Cat 2 Good
6th Floor - Corridor
6th Floor - Corridor
2nd Floor – Elevator Lobby
3rd Floor - Corridor
4th Floor – Corridor Outside Room
7th Floor - Corridor
2’x2’ Smooth Ceiling
Tile/Panels
6th Floor - Corridor
ND NA Cat 2 Good 3rd Floor - Corridor
20’x60’ Fissured
Ceiling Tile(existing)
2nd Floor-Messer Office-Basement Stockpile
ND
NA Cat 1 Good 2nd Floor-Messer Office-Basement
Stockpile
7th Floor-HUD Foyer
7th Floor-HUD Foyer
7th Floor-HUD Foyer
3rd Floor-Room 307 Conference
3rd Floor-Room 307 Conference
3rd Floor-Room 307 Conference
7th Floor Corridor
Basement Elevator Lobby
2’x4’ Smooth Ceiling
Tile(New)/Ceiling Panels Per URS
Basement Elevator Lobby
ND Cat 1 Good
12’x12’ Brown/Tan Swirled Floor Tile
Throughout Building Not Sampled- Per GSA
ND ND Cat 1 Good
Mastic Associated with 12’x12’
Brown/Tan Swirled Floor Tile
7th Floor Corridor ACM 2% Chrysotile Cat 1 Good
Versar
23 Vinyl Baseboard 3rd Floor Smoking
Area/Corridor(Dining Room) Presumed Presumed Negative Cat 1 Good
URS
Vinyl Baseboard
Mastic 3rd Floor Smoking
Area/Corridor(Dining Room) ND ND Cat 1 Good
Versar
12’x12’ Bright Blue
Tile 3rd Floor Cafeteria
NOT SAMPLED
PRESUMED
NEGATIVE
Presumed Negative Cat 1 Good
Mastic Associated with 12’x12’ Bright
Blue Tile 3rd Floor Cafeteria
NOT SAMPLED
PRESUMED
NEGATIVE
Presumed Negative Cat 1 Good
3’x3’ Sheets Dark
Blue Flooring 2nd Floor Social Security Kitchen
NOT SAMPLED
PRESUMED
NEGATIVE-
Presumed Negative Cat 1 Good
Mastic Associated with 3’x3’ Sheets
Dark Blue Flooring 2nd Floor Social Security Kitchen
NOT SAMPLED
PRESUMED
NEGATIVE-
Presumed Negative Cat 1 Good
12’x12’ Gray Floor
Tile 2nd Floor Social Security Kitchen
Cat 1
Good
2nd Floor Social Security Kitchen
Mastic Associated with 12’x12’ Gray
Floor Tile
2nd Floor Social Security Kitchen
Good Throughout
1st Floor – IRS Space
31 Sink Coating 1st Floor Receiving Area Not Sampled
Presumed Positive per GSA
Presumed Good
2’x2’ Rough Ceiling
Tile 1st Floor Receiving Area
Not Sampled Presumed
Negative per
GSA
Presumed Good
Tan Vinyl Flooring
(Sheeting) Basement Gun Range(Basement
Former Firing Range)
ND ND
Non-Friable
Good
Mastic Associated with Tan Vinyl Flooring (Sheeting)
Basement-Room 42 ND ND Good
35 1’x1’ Wall Board Basement Gun Range(Basement
Former Firing Range) ND ND Good
12’x12’ Light Tan Swirl Floor Tile
Basement-Room 42 ND NA Good
Mastic Associated with 12’x12’ Light
Tan Swirl Floor Tile Basement-Room 42 ACM 8% Chrysotile Good
Storm Sewer Pipe
Fitting Insulation (on Fiberglass Pipe Run)
Basement-Room 23
ND NA Good Basement Gun Range(Basement –
Former Firing Range Storage)
7th Floor Corridor
Mastic Associated with 1’x1’ Wall Board 6th Floor Corridor ND NA Good
40 Carpet Mastic
3rd Floor Corridor
ND
(throughout the
Building)
ND
Good 2nd Floor- Messer Office
7th Floor-Corner Across From Room
4thFloor Elevator Lobby
41 Drywall System
3rd Floor Across From Room 346 Good
Penthouse- Boiler Room Good
5th Floor Corner At Room 531B Trace Trace <1% Chrysotile Trace Good
4th Floor-Elevator Lobby ND ND Good
3rd Floor Corridor ND ND Friable Good
2nd Floor-Elevator Lobby ACM 2% Chrysotile Good
6th Floor-GSA Office Trace Trace <1% Chrysotile Friable Good 6th Floor-Adjacent to URS Field
Office Trace Trace <1% Chrysotile
Good
6th Floor-Room 609 East Trace Trace <1% Chrysotile Good 5th Floor-USDA 507 Trace Trace <1% Chrysotile Good 5th Floor –UFS 540 Trace Trace <1% Chrysotile Good 4th Floor –IRS 403B Trace Trace <1% Chrysotile Good
4th Floor-IRS NW Corner Trace Trace <1% Chrysotile Good 3rd Floor- Foyer Area Trace Trace <1% Chrysotile Good
3rd Floor Inspector General Trace Trace <1% Chrysotile Good
3rd Floor- Cafeteria Trace Trace <1% Chrysotile Good 2nd Floor – USDA Trace Trace <1% Chrysotile Good
2nd Floor Social Security East wall Trace Trace <1% Chrysotile Good 1st Floor – US Army Recruiting Trace Trace <1% Chrysotile Good
1st Floor – IRS Trace Trace <1% Chrysotile Good 7th Floor – Column #22 Trace Trace <1% Chrysotile Good
7th Floor – HUD East Wall ND Good 2nd Floor - Public Health Corridor Trace Trace <1% Chrysotile Good 2nd Floor - Public Health Corridor Trace Trace <1% Chrysotile Good 2nd Floor - Public Health Corridor
Friable Good 2nd Floor- South Corridor ,Janitor’s
Closet Friable Good
2nd Floor- South Corridor ,Janitor’s Closet
Friable Good
2nd Floor- Restroom Friable Good 2nd Floor- Restroom Friable Good
3rd Floor-Janitor Closet Friable Good 3rd Floor-Janitor Closet Friable Good 3rd Floor-Janitor Closet Friable Good 3rd Floor-Janitor Closet Friable Good 3rd Floor-Janitor Closet Trace <1% Chrysotile Friable Good 3rd Floor-Janitor Closet
ND ND
Friable Good 3rd Floor-North Corridor Friable Good 3rd Floor-North Corridor Friable Good
3rd Floor-Women’s Restroom Friable Good 3rd Floor-Women’s Restroom Friable Good 3rd Floor-Women’s Restroom Friable Good 3rd Floor-Women’s Restroom Friable Good 3rd Floor-Women’s Restroom Friable Good 3rd Floor-Women’s Restroom Friable Good 3rd Floor-Women’s Restroom Friable Good 3rd Floor-Women’s Restroom Trace <1% Chrysotile Friable Good 3rd Floor –West Foyer Ceiling
ND ND
Friable Good 3rd Floor –West Foyer Ceiling Friable Good 3rd Floor –West Foyer Ceiling Friable Good 3rd Floor –West Foyer Ceiling Friable Good
3rd Floor Men’s Restroom Ceiling Friable Good 3rd Floor Men’s Restroom Ceiling Friable Good
2nd Floor-Vending Area Ceiling Friable Good 2nd Floor-Vending Area Ceiling Friable Good 2nd Floor-West Foyer Ceiling Friable Good 2nd Floor-West Foyer Ceiling Friable Good 2nd Floor-West Foyer Ceiling Friable Good 2nd Floor Unisex Restroom Friable Good 2nd Floor Unisex Restroom Friable Good
3rd Floor-Foyer Ceiling Friable Good 3rd Floor-Foyer Ceiling Friable Good
2nd Floor-Electric Closet B Friable Good 2nd Floor –Electric Closet B Friable Good
2nd Floor-Electric Closet #233 Friable Good 2nd Floor-Electric Closet #233 Friable Good
3rd Floor Electric Closet C-Lobby Friable Good 3rd Floor Electric Closet C-Lobby Friable Good 3rd Floor Electric Closet B-North
Corridor Friable Good
3rd Floor Electric Closet B-North Corridor
Friable Good
3rd Floor –Electric Closet A- Kitchen Friable Good 3rd Floor –Electric Closet A- Kitchen Friable Good
7th Floor Electric Closet B-North Corridor
Friable Good
7th Floor Electric Closet B-North Corridor
Friable Good
6th Floor Electric Closet -North Corridor
Friable Good
6th Floor Electric Closet North Corridor
Friable Good
6th Floor Electric Closet- 631A-South Elevator
Friable Good
6th Floor Electric Closet- 631A-South Elevator
Friable Good
5th Floor Electric Closet-531A-South Corridor
Friable Good
5th Floor Electric Closet-531A-South Corridor
Friable Good
4th Floor-Electric Closet-South Corridor
Friable Good
4th Floor-Electric Closet-South Corridor
Friable Good
Penthouse-Ceiling Friable Good Penthouse-Ceiling Friable Good Penthouse-Ceiling Friable Good Penthouse-Ceiling Friable Good
Good
Versar
Wall Seam Caulk –
Exterior
Exterior – North
ND NA Cat 2 Good Exterior – East
Exterior – West
URS
43 Boiler Breeching Boiler Room – Penthouse ACM 25% Chrysotile RACM Reported as
Abated
44 1’x1’ Ceiling Tile Room 334D – 3rd Floor
ND NA Cat 2 Good Adjacent to curved room – 4th Floor
45 Gasket
Boiler Room - Penthouse
ND NA Cat 2 Good West End of North Boiler – Penthouse
Debris on Floor of
Pipe Chase
Pipe Chase – 7th Floor
ND NA RACM NA Pipe Chase – 4th Floor
Pipe Chase – 3rd Floor
47 Wallboard Elevator Lobby – 2nd Floor ND NA Cat 2 Good
48 Diffuser Insulation Messer Office – 2nd Floor ND NA Cat 2 Good
49 Duct Tape Messer Office – 2nd Floor ND NA Cat 2 Good
Packing Material Behind Fire Door
Throughout ND NA Cat 2 Good
51 Waterproofing South Entry – 1st Floor ND NA Cat 2 Good
52 Pipe Insulation Parking Garage – 2nd Floor ND NA RACM Good
Insulating Cement –
Pipe Ends
Parking Garage – 2nd Floor ACM 3% Chrysotile RACM Good
Parking Garage – 7th Floor
54 Sealant Penthouse – AHU#2 ACM 4% Chrysotile RACM Good
55 Plaster Adhesive Lobby – 1st Floor ND NA Cat 2 Good
TRC
Black Sink
Undercoating S 200 – 2nd Floor ACM 3% Chrysotile Cat 2 Good
2 Mirror Mastic Throughout Presumed Presumed Cat 2 Good
3 Fire Door Throughout Presumed Presumed Cat 2
Table 2 List of Asbestos Containing Materials (ACMs) by URS (2004/2005), Versar(2006) and TRC (2019) and Presumed (not sampled materials) Asbestos Containing Materials
HSA’s John W. Bricker Federal Office Building (OH0208) HSA by URS, Versar and TRC MATERIAL LOCATION(s) QUANTITY
REPORT or
CONSULTANT
TYPE CONDITION
Black mastic Associated w/12” x 12” Tan w/Streaks
Floor Tile
Elevator Entryway – Penthouse
~1,700sf Versar (2006)
Cat 1 Non-
Friable Good
All Stair Ladings
17 Duct Sealant Throughout ~12,000sf
URS
(2004/2005) Cat 2 Good
Black mastic Associated w/12” x
12” Brown/Tan Swirled Floor Tile
Throughout – Elevator Lobby’s ~6,500sf
URS
(2004/2005)
Cat 1 Non-
Friable Good
Black mastic Associated w/12” x
12” Light Tan Swirled Floor Tile
Basement – Room 42 ~650sf Versar (2006)
Cat 1 Non-
Friable Good
41 Drywall Systems Elevator Lobby – 2nd Floor ~1,000 sf
URS
(2004/2005) Cat 2 Good
Insulating Cement –
Pipe Ends Parking Garage ~1,000sf
URS
(2004/2005
Cat 2 Good
54 Duct Sealant AHU#2 – Penthouse ~2,000lf
URS
(2004/20 05 Cat 2 Good
1 Sink Undercoating Throughout Unknown
TRC
(2019) Cat 2 Good
PRESUMED ACM
9 Tank Insulation Chilled Water – Air Handling Room ~250cf Versar
(2004/2005) RACM Good
10 Roofing Elevator Equipment Room – Roof ~1,000sf Versar
(2004/2005) Cat 2
Good
11 Roofing Penthouse – Roof ~1,000sf Versar
(2004/2005) Cat 2 Good
12 Roofing Main Roof ~28,000sf Versar
(2004/2005) Cat 2 Good
2 Mirror Mastic Throughout Unknown
TRC
(2019) Cat 2 Good
3 Fire Door Throughout Unknown
TRC
(2019) Cat 2 Good
31 Sink Undercoating Throughout Unknown Versar
(2004/2005) Cat 2 Good sf = Square Foot lf = Linear Foot NA = Not Applicable
Asbestos Conclusion
TRC recommends the GSA continue to engage qualified firms to sample for asbestos and lead paint utilizing their standard of practice of a pre-alteration survey for area specific renovations and demolitions.
Subcontractors and employees working within the structures at the site should be made aware of the locations of the ACM and possibility of concealed ACMs that could be found during renovation/demolition activities. Any materials uncovered during future renovation or demolition activities that were not addressed in this inspection report, or any presumed asbestos containing materials, must be sampled by an accredited asbestos inspector prior to any disturbance, or they must be treated as ACM.
It should be noted that drywall system samples that were collected by Versar in 2006 of various floors of the building with the none detect, trace and one sample results reported as 2%
Chrysotile on the 2nd floor lobby. TRC recommends collecting drywall system samples on every pre-alteration survey to confirm/deny the presence of asbestos
Table 3 List of Lead Paint as sampled by Versar (2006) and TRC (2019)
According to reports reviewed, See Appendix D, the following paint was sampled and tested for lead.
Lead Conclusion
Based on historical reports, age of the building, some of paints sampled in the building have a detection of lead and are considered LCP. Other samples collected were below the limited of detection or less that 5,000 ppm or 0.5 % by weight reported by the lab.
Lead-based paint (LBP) is defined by the United States Department of House and Urban Development (HUD) as any paint, varnish, stain, or other applied coating that has one mg/cm2 or more of lead or 0.5% by weight (5,000 micrograms per gram [ug\g] or 5,000 parts of lead per million [ppm]). According the OSHA Program Directive, Lead: Exposure in Construction, "For all occupational exposure to lead occurring in the course of construction work, the standard (1926.62) does not specify a minimum amount or concentration of lead that triggers a determination that lead is present and the potential for occupational exposure exists." Therefore any paint containing less than 0.5% by weight, or <5,000 ppm, but greater than the laboratory detection limit is considered to be a LCP.
Occupational Safety and Health Administration regulations for lead in construction apply when disturbing materials which contain any amount of lead, and such activities must be conducted according to the regulations set forth in 29 CFR 1926.62. All paints that contain any level of lead are regulated by the OSHA Lead in Construction Standard 29 CFR 1926.62, Construction work covered by this standard includes demolition or salvage f of structures where lead-containing materials are present; removal or encapsulation of lead containing materials; renovation of structures, substrates, or portions thereof that have lead-containing materials; installation of materials containing lead; lead contamination cleanup; transportation, storage, and disposal of lead containing materials; and maintenance operations associated with these construction activities.
In performing these activities, OSHA requires an initial determination that the construction activities used at the job site do not create airborne emissions of lead above the Action Level of 30ug/m3 (i.e., negative exposure assessment). This exposure assessment may include initial exposure monitoring, historical data that meet certain requirements, or objective data demonstrating that a particular produce or material containing lead or a specific process cannot result in employee exposures to lead above the Action Level.
PAINT
COLOR,
CONDITION
SUBSTRATE,
COMPONENT
SAMPLE
LOCATION
LOCATION
IN BUILDING
LEAD RESULTS
(PARTS PER
MILLION)
(OVER 5,000
PPM or >0.50% by weight IS
LEAD BASED
PAINT)
REPORT OR
CONSULTANT
Cream, Good Metal, I-Beam I-Beam Penthouse 5,500ppm TRC (2019)
Yellow, Good Metal, I-Beam I-Beam Penthouse 32,000ppm TRC (2019)
TRC recommends the GSA continue to engage qualified firms to sample for asbestos and lead paint utilizing their standard of practice of a pre-alteration survey for area-specific renovations and demolitions.
August 2019
Disclaimer
The content presented in this report is based on data collected during the Site survey, review of pertinent regulations, requirements, guidelines and commonly followed industry standards, and information provided by Client, their clients, agents, and representatives.
The work has been conducted in an objective and unbiased manner and in accordance with generally accepted professional practice for this type of work. TRC believes the data and analysis to be accurate and relevant but cannot accept responsibility for the accuracy or completeness of available documentation or possible withholding of information of other parties.
This report is designed to aid the property owner, architect, construction manager, general contractor, and asbestos abatement contractor in locating ACM. This report is not intended for and may not be utilized as a bidding document or as an abatement project specification document or management plan. The listed materials and respective locations given are specific only to those areas. TRC makes no representation regarding the extent of ACM or conditions pertaining thereto of areas located outside the renovation scope of work.
TRC appreciates the opportunity to be of continued service to GSA.
Sincerely, TRC Environmental Corporation
Heath Howard, CIH, CSP Lonnie Lyro Senior Project Manager Project Manager
Mitch Pendergrass Senior Project Manager
Appendix A Asbestos Containing Materials and Lead
Paint Abatement Costs The asbestos abatement costs (below) estimates listed in this report include removal only. The quantities were obtained from the URS (2004/2005), Versar (2006) reports and site visit by TRC (2019)
OH0208 JOHN W. BRICKER FEDERAL OFFICE BUILDING
MATERIAL LOCATION QUANTITY
PRICE PER
SF, TOTAL*
Black Mastic Associated w/12”x12” Tan Floor Tile with Streaks
Entry Landing - Penthouse ~1,700 sf
$6.00 ~$10,200 Entry Landings on All Floors
Sink Undercoating
Throughout Unknown Abatement per sink ~$2,500
Duct Sealant Throughout AHUs ~12,000sf $5.00
~$51,000
Black Mastic Associated w/12”x12” Brown/Tan Floor Tile with Swirls
Elevator Lobby’s – Throughout ~6,500 sf $6.00
~$39,000
Black Mastic Associated w/12”x12” Light Tan Floor Tile with Swirls
Room 42 – Basement ~650 sf $6.00
~$3,900
Drywall Systems Elevator Lobby – 2nd Floor ~1,000 sf $10.00/sf $10,000
Insulating Cement – Pipe Ends Parking Garage ~1,000 sf $10.00
~$10,000
Duct Sealant Penthouse AHUs ~2,000sf $5.00
~$10,000
PRESUMED ACM UNTIL SAMPLED
Tank Insulation Air Handling Room ~250cf $15.00cf ~$3,750
Roofing Materials Roof ~30,000 sf $5.00, ~$150,000
Mirror Mastics Restroom Mirrors Unknown Abatement per mirror ~$2,500
Fire Doors Throughout Unknown Disposal per door ~$1,500
• Prices do not include 3rd Party Oversight Consulting Services, typically $1,250 a day
Lead Based Paint Abatement Costs
Lead Based Paint Encapsulation and/or Abatement Costs widely vary as a factor of project location, condition and location of lead-based paint within a structure, and project specific scope-of-work and typically range up to $2.00-$5.00 a square foot and do not include 3rd Party Oversight
Consulting Services, typically, $1,250 a day.
Note: If applicable, delaminating, chalking, and peeling LBP must be cleaned up and stabilized by a licensed lead abatement contractor using certified workers and supervisors, and must be done according to EPA and State of Ohio lead abatement regulations prior to any demolition activities. LBP components in good condition may be removed intact by lead trained personnel in accordance with all applicable federal state and local regulations. These requirements include, but are not limited to, the following: Exposure Assessments; Methods of Compliance (including work practices administrative, and engineering controls); Respiratory Protection; Protective
Clothing and Equipment; Housekeeping; Hygiene Facilities; Medical Surveillance; and Employee
Information and Training. The waste materials generated must be segregated accordingly and must be subjected to waste Characterization testing and appropriately disposed.
Appendix B TRC General Photo Log
July 29, 2019
OH0208 ASBESTOS SURVEY – PHOTOGRAPHIC LOG
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample Numbers
N/A
Material Description
Vinyl Floor Tile 12" X 12" Tan
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos Detected
Positive
Asbestos Type
5% Chrysotile
Homogeneous Area
Elevator Penthouse, Entry Landing, All Stair Landings
Total Approximate Quantity
1700 SF
Condition Good
Material Type Misc.
NESHAP
Category
Cat I
Notes Not Applicable
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
Insulation Tank Chilled Water
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos Detected
Positive
Asbestos Type
Assumed
Homogeneous Area
Air Handling Room (East Side)
Total Approximate Quantity
250 CF
Condition Good
Material Type TSI
NESHAP
Category
RACM
Notes Not Applicable
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
Roofing
Accessible
Accessible
Reason Inaccessible
Asbestos Detected
Positive
Asbestos Type
Assumed
Homogeneous Area
Throughout Elevator Roof
Total Approximate Quantity
1000 SF
Condition Good
Material Type Misc.
NESHAP
Category
Cat I
Notes Not Applicable
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
Roofing
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos Detected
Positive
Asbestos Type
Assumed
Homogeneous Area
Penthouse Roof
Total Approximate Quantity
1000 SF
Condition Good
Material Type Misc.
NESHAP
Category
Cat I
Notes Not Applicable
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
Roofing
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos
Positive
Asbestos Type
Assumed
Homogeneous Area
Main Roof
Total Approximate Quantity
28000 SF
Condition Good
Material Type Misc.
NESHAP
Category
Cat I
Notes Not Applicable
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
No Image Available
Duct Sealant
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos Detected
Positive
Asbestos Type
2% Chrysotile
Homogeneous Area
All Ducts And AHUs Throughout Building
Total Approximate Quantity
12000 SF
Condition N/A
Material Type N/A
NESHAP
Category
N/A
Notes Not Applicable
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
Vinyl Floor Tile 12" X 12" Brown / Tan Swirled
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos
Asbestos
2% Chrysotile (Mastic)
All Floors
Total Approximate Quantity
6500 SF
Condition Good
Material Type Misc.
NESHAP
Category
Cat I
Notes Not Applicable
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
Sink Undercoat
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos Detected
Positive
Asbestos Type
3% Chrysotile
Homogeneous Area
All Sinks Throughout Building
Total Approximate Quantity
TBD
Condition Good
Material Type Misc.
NESHAP
Category
Cat II
Notes Not found on all sinks inspected
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
Vinyl Floor Tile 12" X 12" Light Tan Swirl
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos
Asbestos
8% Chrysotile (Mastic)
Basement Room 42
Total Approximate Quantity
650 SF
Condition Good
Material Type Misc.
NESHAP
Category
Cat I
Notes Not Applicable
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
Wallboard Gypsum With Joint Compound
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos Detected
Positive
Asbestos Type
2% Chrysotile
Homogeneous Area
Throughout Building
Total Approximate Quantity
TBD
Condition Good
Material Type Misc.
NESHAP
Category
RACM
Notes Not Applicable
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
Insulating Cement - Ends Of Pipes
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos
Asbestos
3% Chrysotile
Parking Garage Ends Of Horizontal Pipe Runs
Total Approximate Quantity
100 SF
Condition Damaged
Material Type TSI
NESHAP
Category
RACM
Notes We estimate 100 sf
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
Sealant
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos Detected
Positive
Asbestos Type
4% Chrysotile
Homogeneous Area
Penthouse AHU #2
Total Approximate Quantity
2000 LF
Condition Good
Material Type Misc.
NESHAP
Category
Cat I
Notes Not Applicable
SUSPECT ASBESTOS CONTAINING MATERIAL
Sample
01, 02, 03
Sink Undercoat Black
Accessible Material
Accessible
Reason Inaccessible
N/A
Asbestos
Asbestos
No Asbestos Detected
Suite 200
Total Approximate Quantity
TBD
Condition N/A
Material Type N/A
NESHAP
Category
Notes Not Applicable
OH0208 LCP SURVEY – LEAD CONTAINING PAINT PHOTOGRAPHIC LOG
SUSPECT PAINT
Sample
L-01
Sample Location
P2 Structural Steel
Description Cream Paint
Laboratory Result
5,500 PPM – Lead-based Paint
Substrate Metal
Paint Locations
Throughout Structural Steel
Quantity of Deteriorated Paint
TBD
SUSPECT PAINT
Sample
L-02
P2 Elevator Machine Room
Description Yellow Paint
Laboratory Result
32,000 PPM – Lead-based Paint
Substrate Metal
Paint Locations
P2 Elevator Machine Room Steel
Quantity of Deteriorated Paint
TBD
SUSPECT PAINT
Sample
L-03
P2 Elevator Machine Room
Description Gray Paint
Laboratory Result
<230 PPM – No Lead
Substrate Concrete
Paint Locations
P2 Elevator Machine Room Floor
Quantity of Deteriorated Paint
TBD
SUSPECT PAINT
OH0208 LCP SURVEY – LEAD CONTAINING PAINT PHOTOGRAPHIC LOG
Sample
L-04
Floor 7 Elevator Lobbg
Description White
Laboratory Result
<89 PPM – No Lead
Substrate Drywall
Paint Locations
Throughout Freight Elevator Lobbies
Quantity of Deteriorated Paint
TBD
SUSPECT PAINT
Sample
L-05
4th Floor Freight Elevator Lobby
Description Light Yellow / Tan Paint
Laboratory Result
<84 PPM – No Lead
Substrate Drywall
Paint Locations
Throughout Interior Core Walls
Quantity of Deteriorated Paint
TBD
SUSPECT PAINT
Sample
L-06
Parking Floor 7
Description Pink Paint
Laboratory Result
500 PPM – Lead-in Paint
Substrate Metal
Paint Locations
Parking Garage Steel
Quantity of Deteriorated Paint
TBD
Appendix C TRC Lab Reports and COC April 2019
OrderID: 151903190
OrderID: 151903190
EMSL Analytical, Inc.
5950 Fairbanks N. Houston Rd. Houston, TX 77040
Tel/Fax: (713) 686-3635 / (713) 686-3645 http://www.EMSL.com / houstonlab@emsl.com
151903190EMSL Order:
Customer ID: TRCE75
Customer PO:
Project ID:
Attention: Phone:Lonnie Lyro (512) 329-6080
Fax:TRC Environmental Corp. (512) 329-8750
Received Date:505 E. Huntland Dr. 05/08/2019 8:30 AM
Analysis Date:Suite 250 05/13/2019
Collected Date:Austin, TX 78752-3740 05/02/2019
Project: GSA Bricker 200 N High Street, Columbus, OH / 314614.000009
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
151903190-0001
3% ChrysotileNon-fibrous (Other)97%Black
Non-Fibrous
Homogeneous
Fl 2 S. 200 - Black
Sink Coating
151903190-0002
3% ChrysotileNon-fibrous (Other)97%Black
Non-Fibrous
Homogeneous
Fl 2 S. 200 - Black
Sink Coating
151903190-0003
3% ChrysotileNon-fibrous (Other)97%Black
Non-Fibrous
Homogeneous
Fl 2 S. 200 - Black
Sink Coating
Analyst(s)
Jenny Drapela (2)
Wanda Porch (1)
Michelle Leggett, Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Houston, TX NVLAP Lab Code 102106-0, AZ 0925, CO AL-15355, LA 04126, TX 300159
Initial report from: 05/13/2019 16:38:11
Page 1 of 1ASB_PLM_0008_0001 - 1.78 Printed: 5/13/2019 3:38 PM
OrderID: 161908851
OrderID: 161908851
ConcentrationAnalyzed Weight RDL LeadClient SampleDescription Collected
Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*
EMSL Analytical, Inc.
6340 CastlePlace Dr., Indianapolis, IN 46250 Phone/Fax: (317) 803-2997 / (317) 803-3047 http://www.EMSL.com indianapolislab@emsl.com
Attn: Lonnie Lyro TRC Environmental Corp.
505 E. Huntland Dr.
Suite 250 Austin, TX 78752-3740
Received: 05/09/19 9:00 AM
GSA BRICKER / COLUMBUS, OH / 314614.000009
Fax: (512) 329-8750 Phone: (512) 329-6080
Project:
5/2/2019Collected:
161908851 CustomerID: TRCE75 CustomerPO:
ProjectID:
EMSL Order:
Site: CREAM ON I BEAM RENTAL - PENTHOUSE 5500 ppm5/15/2019 0.2422 g
161908851-0001 21005/2/2019TRCL-01 ppm
Site: YELLOW ON BEAMS METAL - PENTHOUSE 32000 ppm5/15/2019 0.0892 g
161908851-0002 56005/2/2019TRCL-02 ppm
Site: GREY FLOOR CONCRETE - PENTHOUSE <230 ppm5/15/2019 0.0865 g
161908851-0003 2305/2/2019TRCL-03 ppm
Site: WHITE WALL FREIGHT LOBBY ELEV. ROOM FL 7 <89 ppm5/15/2019 0.2253 g
161908851-0004 895/2/2019TRCL-04 ppm
Site: LIGHT YELLOW TAN FLOOR ON DRYWALL T/O BUILDING <84 ppm5/15/2019 0.2374 g
161908851-0005 845/2/2019TRCL-05 ppm
Site: PINK PARKING GARAGE ON METAL 500 ppm5/15/2019 0.2285 g
161908851-0006 885/2/2019TRCL-06 ppm
Page 1 of 1Test Report PB w/RDL-2.0.0.0 Printed: 5/16/2019 11:02:34 AM
Doug Wiegand, Laboratory Manager or other approved signatory
*Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.010 % wt based on the minimum sample weight per our SOP. Unless noted, results in this report are not blank corrected. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities. Samples received in good condition unless otherwise noted. "<" (less than) result signifies that the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. The QC data associated with the sample results included in this report meet the recovery and precision requirements unless specifically indicated otherwise.
Definitions of modifications are available upon request.
Samples analyzed by EMSL Analytical, Inc. Indianapolis, IN AIHA-LAP, LLC--ELLAP 157245, OH E10040
Initial report from 05/16/2019 11:02:34 http://www.EMSL.com mailto:indianapolislab@emsl.com
Appendix D Historical ACM and Lead Reports: URS
(2004/2005) &Versar (2006)
U.S. General Services Administration
Asbestos and Lead-Based Paint Survey
Bricker Federal Office Building 200 North High Street
Columbus, Ohio
GSA Building No.: OH-0208 GSA Location 1
Prepared By:
Versar, Inc.
100 West 22nd Street, Suite 151 Lombard, IL 60148
February 2, 2006
Versar Project Number: 104700.4971.130 i
TABLE OF CONTENTS
1.0 EXECUTIVE SUMMARY
2.0 INTRODUCTION
3.0 ASBESTOS SURVEY PROTOCOL
3.1 Asbestos Information
3.2 Asbestos Survey
3.3 Asbestos Analysis
3.4 Asbestos Survey Results
4.0 LEAD-BASED PAINT SURVEY PROTOCOL
4.1 Lead Paint Survey
4.2 Lead Paint Analysis
4.3 Lead Paint Survey Results
5.0 CONCLUSIONS AND RECOMMENDATIONS
6.0 STUDY LIMITATIONS
Tables
Table 1 Asbestos Survey Analytical Summary
Table 2 Asbestos Inventory and Management Assessment
Table 3 Lead-Based Paint Survey Summary
Attachments Attachment A Facility Maps: Location of ACM/Location of LBP
Attachment B Asbestos and Lead Analytical Reports
Attachment C Photographs
Attachment D Field Notes and Drawings
Attachment E Cost Estimates
Attachment F Terminology
1.0 EXECUTIVE SUMMARY
Versar has completed an asbestos-containing material (ACM) and lead-based paint (LBP) survey of the Bricker Federal Office Building (subject building), 200 North High Street, Columbus, Ohio.
The facility was inspected by State of Ohio Department of Health Licensed Asbestos Hazard Evaluation Specialist and Illinois Department of Public Health (IDPH) Licensed Asbestos and Lead Inspector and Asbestos Management Planner, Ms. Shaun Terranova (#ES34257, #100- 03064, #L-002600, respectively), and IDPH Licensed Asbestos and Lead Inspector Mr. Curtis Cannon (#100-03976, #L-001190), on October 5, 2005. The survey was conducted in accordance with the Occupational Safety and Health Administration (OSHA) General Industry Standard (29CFR1910.1001), and the Environmental Protection Agency (EPA) National Emission Standard for Asbestos (40 CFR Part 61), applicable local and state requirements, and in conformance with the scope and limitations of U.S. General Services Administration (GSA) specifications.
The asbestos survey included identification of friable and non-friable asbestos-containing materials (ACMs) on an area-by-area basis, assessment of friability, current condition and potential for future disturbance of the material, estimate of the amount of ACM, and overall condition rating of the material. Versar has incorporated into this report data from previous inspections conducted by URS Corporation (URS) of Columbus, Ohio. URS data incorporated in this report was collected during the period of November 2004 to October 2005. During the inspections, URS identified 26 separate asbestos homogenous sampling areas (HSAs) and collected a total of 172 samples of suspect ACMs. URS samples were analyzed by Environmental Hazards Services, L.L.C. (EHS) of Richmond, Virginia.
During Versar’s October 5, 2005 inspection, 29 additional HSA’s were identified and 47 samples of suspect ACMs were collected. Versar’s samples were analyzed by EMSL Analytical, Inc.
(EMSL) in Chicago, Illinois. Some materials were not sampled at the time of either Versar’s or URS’s surveys and are assumed to be non-ACMs or ACM’s, or until sampling proves otherwise.
HSAs 3, 4, 9, 10, 11, 12, 23, 25, 26, 27, 28, 31, and 32 were not sampled during the surveys since sampling would have caused damage to these materials, or the materials were not suspect materials.
The following materials were found to be asbestos-containing or assumed to be ACMs:
HSA ID Material Description Location Quantity Asbestos %
HSA-2
Mastic Associated with 12"x12" Tan Floor Tile with Streaks
Elevator Penthouse Entry Landing and All Stair Landings
1700 sf 5% Chysotile
HSA-9 Chilled Water Tank Insulation Air handling Room (East Side) 250 cf Assumed Positive
HSA-10 Roofing Material - Elevator Roof Throughout Elevator Roof 1,000 sf Assumed Positive
HSA-11 Roofing Material - Penthouse Roof Throughout Penthouse Roof 1,000 sf Assumed Positive
HSA-12 Roofing Material - Main Roof Throughout Main Roof 28,000 sf Assumed Positive
HSA-17 Duct Sealant All Ducts and AHUs Throughout Building 12,000 sf 2% Chysotile
HSA-22 Mastic Associated with 12"x12" Brown/Tan Swirled Floor Tile All Floors 6,500 sf 2% Chysotile
HSA-31 Sink Coating All Sinks Throughout Building
Throughout Bldg Assumed Positive
HSA-37 Mastic Associated with 12"x12 Light Tan Swirl Floor Tile Basement – Room 42 650 sf 8% Chysotile
HSA-41 Drywall Systems Throughout Building Throughout Building 2% Chysotile
HSA-43 Boiler Breeching Penthouse Boiler Room
Removed Prior to Versar
Inspection
25% Chysotile
HSA-53 Insulating Cement - Ends of Pipe Parking Garage 1,000 sf 3% Chysotile HSA-54 Sealant Penthouse - AHU #2 2,000 lf 4% Chysotile
The lead-based paint (LBP) survey included collection of paint chip samples to provide consistent coverage based on building size, layout, and renovation/abatement history. The number and frequency of samples collected are a representation of the number of different paint colors in each building functional space (i.e., mechanical areas, office space, common areas), and total square footage of painted surfaces within that particular functional space. It should be noted that this LBP survey is not intended to be comprehensive in nature; rather is an attempt to evaluate the lead content of the predominant paint types within the building based on Versar’s observations.
Based upon lead-based paint analytical results, no LBP was identified in the samples collected at the time of this inspection. Lead-based paint is defined by the EPA as a paint that contains lead in concentrations that are equal to or in excess of 0.5 % by weight or 5,000 parts per million (ppm).
The following sections give detailed descriptions of the building, survey methodologies, analytical testing, and conclusions. The tables and attachments provide support information.
2.0 INTRODUCTION
On behalf of the General Services Administration (GSA), Versar, Inc. (Versar) conducted a survey for suspect asbestos-containing materials (ACM) and lead-based paint (LBP) at the Bricker Federal Office Building, 200 North High Street, Columbus, Ohio. The subject building has seven floors, two penthouses, basement, three roof levels (main, elevator, and penthouse roof), and comprises approximately 261,257 total square feet.
Work was conducted in accordance with Versar’s proposal to GSA, dated May 17, 2005 (in response to GSA RFQ 80755) and GSA Contract (GS05P05GAA0169). The inspection was conducted on October 5, 2005. The objective of the asbestos survey was to conduct an AHERA-type building inspection for ACMs and prepare an Asbestos Management Plan to fulfill the asbestos requirements as specified in 29 CFR Part 1910.1001 (OSHA Asbestos General Industry Standard). The lead-based paint (LBP) survey included collection of paint chip samples to provide consistent coverage based on building size, layout, and renovation/abatement history. It should be noted that this LBP survey is not intended to be comprehensive in nature; rather is an attempt to evaluate the lead content of the predominant paint types within the building based on Versar’s observations.
Versar’s State of Ohio Department of Health Licensed Asbestos Hazard Evaluation Specialist, and Illinois Department of Public Health (IDPH) Licensed Asbestos and Lead Inspector and Asbestos Management Planner, Ms. Shaun Terranova (#ES34257, #100-03064, #L-002600, respectively), and IDPH Licensed Asbestos and Lead Inspector Mr. Curtis Cannon (#100-03976, #L-001190) performed the inspection and collected bulk samples of interior friable and non-friable suspect ACM and LBP. Versar was escorted by GSA Project Manager, Mr. Philip Ramos. The ACM survey included a limited inspection of the facility to determine the amount, condition, and general location of suspect ACM within the facility and collection of bulk samples for laboratory analysis.
Suspect asbestos bulk samples were analyzed using Polarized Light Microscopy (PLM) and paint chip samples were analyzed utilizing Atomic Absorption Spectrometry (AAS) by EPA Method 6010. Versar’s samples were analyzed by trained microscopists at EMSL Analytical, Inc.
(EMSL) in Chicago, Illinois.
3.0 ASBESTOS SURVEY PROTOCOL
3.1 Asbestos Information
Asbestos is the generic term used to describe a group of naturally occurring silicate minerals that have the ability to separate into small, fine fibers. The most widely used types of asbestos are chrysotile and amosite. Other types include crocidolite, tremolite, anthophyllite, and actinolite.
Exposure to these fibers has been linked to a number of health problems, including asbestosis, mesothelioma, and lung cancer.
Federal regulatory agencies such as the Occupational Safety and Health Administration (OSHA) have targeted friable asbestos as the primary source for release of and subsequent exposure to asbestos fibers. The U.S. EPA regulations define AACMs@ as materials containing more than one percent (1%) asbestos. ACMs are regulated under the U.S. EPA National Emissions Standard for Hazardous Air Pollutants (NESHAP), Standard for Demolition and Renovation and OSHA regulations.
A list of asbestos terms and their definitions are located in Attachment F. These are intended to provide the reader with a better understanding of the terminology used in the report.
3.2 Asbestos Survey
The ACM survey included an inspection for friable and non-friable suspect ACMs identified throughout the subject property. Friable materials (such as thermal system insulation or TSI), are those which when dry, can be crumbled, pulverized or reduced to powder by hand pressure, thereby releasing airborne fibers. Non-friable materials (such as vinyl floor tile) are those typically bound within a matrix, which do not readily release airborne fibers.
Versar inspectors met with building representatives and assigned Homogeneous Sampling Areas (HSAs) based on type of material, category, and appearance. The inventory of suspect materials identified during the ACM survey includes location of each suspect ACM HSA, description of the material, quantity, and material’s friability, condition, and accessibility (Table 1 - Asbestos Survey and Analytical Summary).
Suspect ACM identified by Versar as part of this survey included:
• Floor Tile and Mastic
• Tank Insulation
• Spray-On Insulation
• Muffler Exhaust Insulation
• Roofing Materials
• Misc. Flooring Materials
• Sink Coating
• Wall Board and Mastic
• Carpet Mastic
• Drywall Systems
• Ceiling Tile
• Duct Tape
• Diffuser Inslation
• Gaskets
• Sealant
• Plastic Adhensive
• Fire Door Packing Materials
• Caulk
• Boiler Breeching
• Pipe and Fitting Insulation
• Waterproofing Material
• Insulating Cement
• Duct Sealant
• Vinyl Baseboard
In accordance with the GSA scope-of-work, roofing materials were not sampled, but were assumed to contain asbestos and therefore, were quantified and included in the report inventory.
The ACM survey did not include identification or sampling of building materials that are unlikely to contain asbestos or materials that appeared to be non-asbestos in nature (e.g., fiberglass, concrete, ceramic, and wood products).
Versar inspectors walked through all accessible areas of the subject building, inventoried materials and quantities, wrote narrative descriptions, and drew sketches of the locations of each suspect ACM.