472_24059.SAA - WHV VMS Genetec Phase 2 Cameras - Drawings Part 1 of 3.pdf

PDF 3 MB Posted

Attached to
472/24059. SAA; WHVCF - VMS Genetec Phase 2 Cameras
Solicitation number
RFQ 171 260000000347 3
Issued by
Washtenaw County, Michigan

About this file

This is a technical drawings document for a Video Management System (VMS) Genetec Phase 2 Cameras project in Michigan, specifically related to contract 472/24059.SAA for the Whitehall Village Center Facility (WHVCF). The document constitutes Part 1 of 3 drawings and contains architectural and technical specifications for the camera installation system. The drawings provide detailed layouts and installation requirements for the Genetec Phase 2 camera system, which represents the second phase of a video surveillance infrastructure upgrade at the facility. The document establishes the physical specifications and spatial requirements necessary for bidders to understand the scope of equipment installation and integration.

The technical drawings serve as the basis for vendors to develop accurate bids for supplying and installing the specified Genetec Phase 2 camera system and related VMS infrastructure. These drawings are critical for ensuring that all bidders understand the exact installation locations, mounting requirements, cable routing, and integration points within the existing facility infrastructure. The multi-part drawing series (Part 1 of 3) indicates a comprehensive system design requiring detailed technical documentation across multiple document sections to capture all aspects of the camera placement and system architecture.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATE OF MICHIGAN

WOMEN'S HURON VALLEY CORRECTIONAL FACILITY

VMS GENETEC PHASE 2 CAMERAS

FILE NUMBER: 472/24059.SAA

SECURITY DESIGN

COMMTECH DESIGN

6585 BELDING RD. NE, SUITE B

ROCKFORD, MI 49341

(616) 863-8132

3201 BEMIS RD, YPSILANTI, MI 48197

WOMEN'S HURON VALLEY CORRECTIONAL FACILITY

SECURITY DRAWING INDEX

DRAWING LIST:

TC101 WHV SECURITY LEGENDS, DETAILS AND SCHEDULES

TC102 WHV CABLING AND SECURITY MOUNTING DETAILS

TC103 WHV CABLING AND CAMERA DETAILS

TC104 WHV SECURITY MOUNTING DETAILS

TC105 WHV NEW CAMERA ON POLE, SURGE PROTECTION & A.V. DETAILS

TC106 WHV MDOC CONDUIT STANDARDS

TC107 WHV LCD DISPLAY AND SURFACE RACEWAY DETAILS

TC108 WHV FIBER BACKBONE AND CONNECTIVITY

TC109 WHV RACK LAYOUTS

TC110 WHV RACK LAYOUTS

TC111 WHV RACK LAYOUTS

TC112 WHV RACK LAYOUTS

TC113 WHV RACK LAYOUTS

TC114 WHV RACK LAYOUTS AND FIBER DETAILS

TC115 WHV WEST ADMIN CORE DESIGN

TC116 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC117 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC118 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC119 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC120 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC121 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC122 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC123 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC124 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC125 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC126 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC127 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC128 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC129 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC130 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC131 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC132 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC133 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC134 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC135 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC136 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC137 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC138 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC139 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC140 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC141 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC142 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC143 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC144 WHV SECURITY CAMERA ONE LINE DIAGRAMS

TC145 WHV SECURITY CAMERA ONE LINE DIAGRAMS - PERIMETER

TC146 WHV SECURITY CAMERA ONE LINE DIAGRAMS - PERIMETER

TC147 WHV SECURITY CAMERA ONE LINE DIAGRAMS - PERIMETER

TC148 WHV SECURITY CAMERA ONE LINE DIAGRAMS - PERIMETER & PASS THRU DETAILS

TC300 WHV WEST ADMINISTRATION BLDG. - NEW & ADDITIONAL

TC301 WHV WEST FOOD SERVICE - NEW & ADDITIONAL

TC302 WHV WEST PRISONER SERVICES - FIRST & SECOND FLOORS - NEW & ADDITIONAL

TC303 WHV WEST PROGRAMS BLDG. - FIRST FLOOR - AREA A - NEW & ADDITIONAL

TC304 WHV WEST PROGRAMS BLDG. - FIRST FLOOR - AREA B & BASEMENT - NEW & ADDITIONAL

TC305 WHV WEST FIELD HOUSE - NEW & ADDITIONAL

TC306 WHV WEST MAINTENANCE - NEW & ADDITIONAL

TC307 WHV WEST HOUSING UNIT 1 - LOWER LEVEL - NEW & ADDITIONAL

TC308 WHV WEST HOUSING UNIT 1 - MAIN LEVEL - NEW & ADDITIONAL

TC309 WHV WEST HOUSING UNIT 2 - LOWER LEVEL - NEW & ADDITIONAL

TC310 WHV WEST HOUSING UNIT 2 - MAIN LEVEL - NEW & ADDITIONAL

TC311 WHV WEST HOUSING UNIT 3 - LOWER LEVEL - NEW & ADDITIONAL

TC312 WHV WEST HOUSING UNIT 3 - MAIN LEVEL - NEW & ADDITIONAL

TC313 WHV WEST HOUSING UNIT 4 - LOWER LEVEL - NEW & ADDITIONAL

TC314 WHV WEST HOUSING UNIT 4 - MAIN LEVEL - NEW & ADDITIONAL

TC315 WHV WEST HOUSING UNIT 5 - LOWER LEVEL - NEW & ADDITIONAL

TC316 WHV WEST HOUSING UNIT 5 - MAIN LEVEL - NEW & ADDITIONAL

TC317 WHV EAST POWER PLANT - BASEMENT & GROUND FLOORS - NEW & ADDITIONAL

TC318 WHV EAST RGC - LOWER LEVEL - NEW & ADDITIONAL

TC319 WHV EAST RGC - UPPER LEVEL & RGC MODULAR UNIT - NEW & ADDITIONAL

TC320 WHV EAST MSI BUILDING NEW & ADDITIONAL

TC321 WHV EAST ADMIN. - FIRST FLOOR AREA A - NEW & ADDITIONAL

TC322 WHV EAST ADMIN. - FIRST FLOOR AREAS B & C - NEW & ADDITIONAL

TC323 WHV EAST ADMIN. - SECOND FLOOR - NEW & ADDITIONAL

TC324A WHV EAST CALHOUN HALL - FIRST FLOOR AREAS A & B - NEW & ADDITIONAL

TC324B WHV EAST CALHOUN HALL - ATTIC AREAS A & B - NEW & ADDITIONAL

TC325A WHV EAST DICKINSON HALL - FIRST FLOOR AREAS A & B - NEW & ADDITIONAL

TC326B WHV EAST DICKINSON HALL - SECOND FLOOR A & B - NEW & ADDITIONAL

TC326C WHV EAST DICKINSON HALL - ATTIC AREAS A & B - NEW & ADDITIONAL

TC327A WHV EAST EMMETT HALL - FIRST & SECOND FLOORS - NEW & ADDITIONAL

TC327B WHV EAST EMMETT HALL - ATTIC - NEW & ADDITIONAL

TC328A WHV EAST FILMORE HALL - FIRST & SECOND FLOORS - NEW & ADDITIONAL

TC328B WHV EAST FILMORE HALL - ATTIC - NEW & ADDITIONAL

TC329A WHV EAST GLADWIN HALL - FIRST & SECOND FLOORS - NEW & ADDITIONAL

TC329B WHV EAST GLADWIN HALL - ATTIC - NEW & ADDITIONAL

TC330A WHV EAST HARRISON HALL - FIRST & SECOND FLOORS - NEW & ADDITIONAL

TC330B WHV EAST HARRISON HALL - ATTIC - NEW & ADDITIONAL

TC331 WHV EAST JENNINGS HALL - IRST & SECOND FLOORS AREA A - NEW & ADDITIONAL

TC332 WHV EAST JENNINGS HALL - FIRST FLOOR AREA B - NEW & ADDITIONAL

TC333 WHV EAST KENT HALL - FIRST FLOOR NEW & ADDITIONAL

TC334 WHV EAST KENT HALL - SECOND FLOOR NEW & ADDITIONAL

TC335 WHV WEST SIDE SITE PLAN - NEW & ADDITIONAL

TC336 WHV EAST SIDE SITE PLAN - NEW & ADDITIONAL

TC337 WHV SITE PLAN - TUNNEL LAYOUT - CAMERAS TO REMAIN

ELECTRICAL ENGINEER

MATRIX CONSULTING ENGINEERS, INC.

1601 E CESAR E. CHAVEZ AVENUE

LANSING, MI 48906

(517) 487-2511

ELECTRICAL & MECHANICAL

DRAWING INDEX

DRAWING LIST:

M-100 MECHANICAL SYMBOLS, NOTES, ABBREVIATIONS, AND SCHEDULES

M-300 PARTIAL FIRST FLOOR PLAN WEST ADMINISTRATION BLDG - MECHANICAL/PIPING DEMOLITION

M-400 PARTIAL FIRST FLOOR PLAN WEST ADMINISTRATION BLDG - MECHANICAL/PIPING NEW

E-100 WHV ELECTRICAL SYMBOLS, ABBREV & NOTES

E-200 WHV- WEST - SITE PLAN - ELECTRICAL

E-201 WHV EAST - SITE PLAN - ELECTRICAL

E-500 WEST ADMINISTRATION FLOOR PLAN - POWER

E-600 ELECTRICAL RISER DIAGRAM + PANEL SCHEDULES

E-700 ELECTRICAL ENLARGEMENTS WEST ADMINISTRATION

E-800 ELECTRICAL DETAILS

E-801 ELECTRICAL DETAILS

TITLE

C om m te ch

D es ig n

B

EL

D

IN

G R

O

AD

N E.

, S U

IT

E

B R

O C

KF

O

R D

, M

IC

H

IG

AN

W W

W .C

O M

M

TE

C H

D

ES

IG

N

.C O

M

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

M a t r ix

AutoCAD SHX Text

SHEET NUMBER

AutoCAD SHX Text

472/24059.SAA

AutoCAD SHX Text file no.

AutoCAD SHX Text checked by

AutoCAD SHX Text drawn by

AutoCAD SHX Text consultant

AutoCAD SHX Text issue date

AutoCAD SHX Text acctg template.

AutoCAD SHX Text contract order no.

AutoCAD SHX Text 472WHVMaintproj

AutoCAD SHX Text consultant job no.

AutoCAD SHX Text 1065_24B

AutoCAD SHX Text sheet title

AutoCAD SHX Text

VIDEO SECURITY FLOOR PLANS

AutoCAD SHX Text

VMS GENETEC PHASE 2 CAMERAS

AutoCAD SHX Text

WOMEN'S HURON VALLEY CORRECTIONAL FACILITY

AutoCAD SHX Text

YPSILANTI ,MICHIGAN

AutoCAD SHX Text Y22432

AutoCAD SHX Text

VIDEO SECURITY UPGRADES

AutoCAD SHX Text P

AutoCAD SHX Text L

AutoCAD SHX Text U

AutoCAD SHX Text R

AutoCAD SHX Text I

AutoCAD SHX Text B

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text N

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text C

AutoCAD SHX Text I

AutoCAD SHX Text R

AutoCAD SHX Text C

AutoCAD SHX Text U

AutoCAD SHX Text M

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text I

AutoCAD SHX Text C

AutoCAD SHX Text E

AutoCAD SHX Text S

AutoCAD SHX Text I

AutoCAD SHX Text Q

AutoCAD SHX Text U

AutoCAD SHX Text E

AutoCAD SHX Text R

AutoCAD SHX Text E

AutoCAD SHX Text I

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text I

AutoCAD SHX Text N

AutoCAD SHX Text S

AutoCAD SHX Text U

AutoCAD SHX Text L

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text O

AutoCAD SHX Text E

AutoCAD SHX Text N

AutoCAD SHX Text A

AutoCAD SHX Text M

AutoCAD SHX Text 06/11/26

AutoCAD SHX Text

ISSUED FOR BID

AutoCAD SHX Text

CONSULTING ENGINEERS, INC

AutoCAD SHX Text

FAX: 517.487.2544

AutoCAD SHX Text

PHONE: 517.487.2511

AutoCAD SHX Text

LANSING, MI 48917

AutoCAD SHX Text

544 CHERBOURG DRIVE

AutoCAD SHX Text

MATRIX PROJECT:

AutoCAD SHX Text WEB: www.matrixceinc.com

GENERAL HVAC NOTES

1. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,

LATEST APPLICABLE EDITION.

2. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER

MANUFACTURERS WRITTEN INSTRUCTIONS.

3. BOTTOM OF EQUIPMENT ON ROOF SHALL BE A MINIMUM OF 18"

ABOVE ROOF MEMBRANE. CONTRACTOR SHALL COORDINATE

ASSOCIATED ROOF CURB HEIGHT AS REQUIRED.

4. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION

THAT MAY AFFECT NORMAL OPERATION OF OTHER AREAS.

5. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT MAY

CONFLICT WITH NEW CONSTRUCTION AND RELOCATE AS

NEEDED.

6. LOCATIONS OF THE THERMOSTATS TO BE VERIFIED IN FIELD.

7. SMOKE DETECTORS SHALL BE FURNISHED AND CONNECTED

BY ELECTRICAL CONTRACTOR, INSTALLATION BY MECHANICAL

CONTRACTOR.

8. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER

DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.

9. OFFSET PIPING TO ACCOMMODATE LARGE DUCTWORK.

10. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,

ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT

MAY AFFECT THE WORK.

11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING

THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"

CONDITION DURING CONSTRUCTION.

12. ALL WORK SHALL BE PERFORMED BY LICENSED

CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.

13. ALL CONDENSATE DRAIN PIPING SET @ MIN. 1% SLOPE.

14. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA

AIR GAP.

15. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR

SPECIFICATIONS THE MORE STRINGENT AND GREATER COST

ITEM SHALL BE USED.

16. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF

TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.

IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL

NECESSARY OFFSETS. INSTALL WORK IN MANNER TO

CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE

HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.

DO NOT SCALE FROM DRAWINGS.

17. ANY INFORMATION FOUND ON THE DRAWINGS AND NOT IN THE

SPECIFICATIONS, OR FOUND IN SPECIFICATIONS AND NOT IN

THE DRAWINGS, SHALL BE CONSTRUED AS TO BE INCLUDED IN

BOTH THE SPECIFICATIONS AND THE DRAWINGS. ANY

CONFLICT BETWEEN THE PLANS AND THE SPECIFICATIONS

WILL BE INTERPRETED BY THE ARCHITECT. IN THE EVENT OF

CONFLICT, FOR THE PURPOSE OF BIDDING, THE CONTRACTOR

SHALL PRESUME THE MOST EXPENSIVE COMBINATION OF

QUALITY AND QUANTITY OF WORK SHALL PREVAIL.

18. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS,

REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE

STATUTES, ORDINANCES, CODES OR REGULATIONS OF

FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING

JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.

19. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY

OSHA, UNDERWRITERS, LABORATORIES, AMERICAN CODES,

ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION

BODY, NFPA OR OTHERS, THESE STANDARDS SHALL BE

FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING

AND SPECIFICATIONS.

20. DUCT/PIPING LAYOUT IS SCHEMATIC. EXACT LOCATION OF

DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH

BUILDING STRUCTURE, EQUIPMENT FURNISHED,

ARCHITECTURAL DRAWINGS, AND ALL OTHER TRADES PRIOR

TO INSTALLATION. ANY CONTRACTOR INSTALLING WORK

WITHOUT PRIOR COORDINATION SHALL RELOCATE HIS WORK

AT HIS EXPENSE TO ALLOW PROPER INSTALLATION OF ANY

AND ALL TRADES WORK.

21. UNLESS OTHERWISE NOTED, ALL DUCT/PIPING SHALL BE

CONCEALED WHEREVER POSSIBLE. PROVIDE CHROME

ESCUTCHEON OR ALUMINUM DUCT COLLAR AT EACH

PENETRATION OF A FINISHED SURFACE.

22. DUCT/PIPING SHALL NOT BE RUN ABOVE ELECTRICAL GEAR IN

THE SERVICE SPACE REQUIRED BY THE NATIONAL ELECTRICAL

CODE.

23. ANY ADDITIONAL LOW VOLTAGE CONTROL WIRING THAT IS

REQUIRED SHALL BE PROVIDED BY THE HVAC CONTRACTOR.

CONTROL WIRING SHALL BE RUN IN CONDUIT IF REQUIRED BY

LOCAL CODES OR THE SPECIFICATIONS. POWER SHALL BE

PROVIDED BY THE ELECTRICAL CONTRACTOR.

24. PROVIDE TRAP FOR CONDENSATION DRAIN LINES.

25. PROVIDE VIBRATION ISOLATION AT EACH CONNECTION TO A

MOTORIZED PIECE OF EQUIPMENT BY THE HVAC

CONTRACTOR.

26. MOUNT THERMOSTAT/SENSORS AT 48" AFF UNLESS NOTED

OTHERWISE.

27. THE HVAC CONTRACTOR SHALL CLOSELY COORDINATE AIR

DEVICE AND DUCTWORK LOCATIONS WITH REFLECTED CEILING

PLANS.

21. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL

USE TAMPERPROOF SCREWS.

22. CONTRACTOR TO ATTEND A 6 MONTH AND AN 11 MONTH POST

CONSTRUCTION MEETING WITH THE ENGINEER AND OWNER

TO REVIEW AND FIX ISSUES DURING THE WARRANTY PERIOD.

23. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO

OWNER OF THE AMOUNT OF MATERIAL BEING RECYCLED

THROUGHOUT THE PROJECT.

24. CONTRACTOR TO PATCH EXISTING ROOF AS REQUIRED TO

MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN EXISTING

WARRANTIES WHERE DEMOLITION AND/OR NEW WORK IS

COMPLETED.

25. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING

WALLS/CEILINGS AS REQUIRED TO MATCH EXISTING WHERE

DEMOLITION AND/OR NEW WORK IS COMPLETED.

26. CONTRACTOR TO NOTIFY THE FACILITY AT LEAST 1 DAY IN

ADVANCE FOR ANY HOT WORK TO ALLOW THE OWNER TO

DISABLE THE FIRE ALARM.

27. CONTRACTOR TO REFER TO ALL ELECTRICAL CONSTRUCTION

DOCUMENTS AND DIVISION 26 SPECIFICATIONS FOR CONTROL

WIRING RACEWAYS. ALL CONTROL WIRING RACEWAYS ARE TO

MEET MDOC REQUIREMENTS.

28. CONTRACTOR TO CONNECT ALL NEW EQUIPMENT TO THE

EXISTING BASS DDC CONTROL SYSTEM. CONTRACTOR TO

PROVIDE ALL REQUIRED CONTROLS, CONTROL WIRING, AND

EQUIPMENT/ACCESSORIES NEEDED TO CONNECT NEW

EQUIPMENT TO THE EXISTING BASS DDC CONTROL PANEL AND

INTEGRATE THE NEW EQUIPMENT ONTO THE EXISTING

FRONT-END GRAPHICS.

29. CONTRACTOR TO PROVIDE AND INSTALL NEW CEILING TILES

(SAME MAKE/MODEL AS THE EXISTING CEILING TILES) AS

REQUIRED TO ENSURE A COMPLETED LAY-IN CEILING SYSTEM

AFTER ALL DEMOLITION/NEW WORK IS COMPETED.

MECHANICAL SYMBOLS LEGEND

HVAC PIPING SYMBOLSHVAC PIPING

HVAC DUCTWORK

F/S

F/S s s

TEMPERATURE CONTROL SYMBOLS

MISCELLANEOUS NOTES

HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES

MECHANICAL ABBREVIATIONS

AFF ABOVE FINISH FLOOR

AC AIR COMPRESSOR

AHU AIR HANDLING UNIT

AS AIR SEPARATOR

A.T.C. ARCHITECTURAL TRADES CONTRACTOR

B BOILER

B.A.S. BUILDING AUTOMATION SYSTEM

CAF COMBUSTION AIR FAN

CC COOLING COIL

CFM CUBIC FEET PER MINUTE

CHLR CHILLER

CHP CONSOLE HEAT PUMP

CONV CONVECTOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONTROL VALVE

CWP CHILLED WATER PUMP

DB DRY BULB

DFU DUCT FURNACE

DIA DIAMETER

DN DOWN

DPR DAMPER

DS DUCT SILENCER

EAT ENTERING AIR TEMPERATURE

EF EXHAUST FAN

EG EXHAUST GRILLE

E.T.C. ELECTRICAL TRADES CONTRACTOR

EVR EVAPORATOR

EWT ENTERING WATER TEMPERATURE

EXH EXHAUST

EXIST EXISTING

FF FINISH FLOOR

FPM FEET PER MINUTE

FT FEET

FTR FINNED TUBE RADIATION

FU FURNACE

GAL GALLON

GFRH GAS FIRED RADIANT HEATER

GR GRILLE

H HUMIDIFIER

HC HEATING COIL

HD HEAD (FT)

HP HORSE POWER

HHP HORIZONTAL HEAT PUMP

HTG HEATING

HVAC HEATING, VENTILATION, & AIR CONDITIONING

HWP HEATING WATER PUMP

HX HEAT EXCHANGER

ID INSIDE DIAMETER

I.E. INVERT ELEVATION

IAH INTAKE HOOD

LAT LEAVING AIR TEMPERATURE

LH LATENT HEAT (MBH)

LWT LEAVING WATER TEMPERATURE

MAX MAXIMUM

MBH BTU PER HOUR (THOUSAND)

MIN MINIMUM

M.T.C. MECHANICAL TRADES CONTRACTOR

N.C. NOISE CRITERIA

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NTS NOT TO SCALE

P PUMP

PCR PUMPED CONDENSATE RETURN

PD PRESSURE DROP

RCP RADIANT CEILING PANEL

REQ'D REQUIRED

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RLH RELIEF HOOD

RTU ROOF TOP UNIT

SD SUPPLY DIFFUSER

SF SUPPLY FAN

SG SUPPLY GRILLE

SH SENSIBLE HEAT (MBH)

SM SHEET METAL

SQ. FT. SQUARE FEET

SST SATURATED SUCTION TEMPERATURE

STR STRAINER

TC TOTAL COOLING (MBH)

TCL TEMPERATURE CONTROL

T&P TEMPERATURE & PRESSURE RELIEF VALVE

TYP TYPICAL

UH UNIT HEATER

VAV VARIABLE AIR VOLUME BOX

VRH VARIABLE AIR VOLUME REHEAT BOX

FPVAV FAN POWERED VARIABLE AIR VOLUME BOX

V.F.D VARIABLE FREQUENCY DRIVE

ZD ZONE DAMPER

X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)

ITEM

EXISTING

CHILLED WATER SUPPLY

CHILLED WATER RETURN

CONDENSATE DRAIN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

COOLING TOWER WATER SUPPLY

COOLING TOWER WATER RETURN

DIRECT EXPANSION

HEAT PUMP WATER SUPPLY

HEAT PUMP WATER RETURN

HEATING WATER SUPPLY

HEATING WATER RETURN

SUCTION (REFRIGERANT)

LIQUID (REFRIGERANT)

SUCTION (DIRECT EXPANSION)

LIQUID (DIRECT EXPANSION)

LOW PRESSURE STEAM (0-20 LBS.)

MEDIUM PRESSURE STEAM (21-75 LBS.)

HIGH PRESSURE STEAM (76 LBS. & ABV.)

STEAM CONDENSATE (GRAVITY)

PUMPED STEAM CONDENSATE

STEAM CONDENSATE BOILER FEED

GATE VALVE

GAS COCK

CHECK VALVE

BALANCE COCK

CIRCUIT SETTER

TWO-WAY CONTROL VALVE

THREE-WAY CONTROL VALVE

GLOBE VALVE

BALL VALVE

SOLENOID VALVE

EXPANSION VALVE WITH

THERMOSTATIC BULB

PLUG VALVE

BUTTERFLY VALVE

RELIEF VALVE

HOSE & DRAIN END VALVE

PRESSURE RELIEF VALVE

PRESSURE REDUCING VALVE

TRIPLE DUTY VALVE

GAS PRESSURE REGULATOR

STRAINER (BLOW-OFF)

FLOW DIRECTION

PIPING DROP

PIPING RISE

INLINE PIPING DROP

INLINE PIPING RISE

PIPING TEE

PIPING ELBOW

THERMOMETER

PUMP

UNION

PIPE ANCHOR

PIPE GUIDE

BACK FLOW PREVENTER

PIPE CAP

PIPE BREAK

THERMOMETER WELL

EXPANSION LOOP

EXPANSION COMPENSATOR

FLOAT & THERMOSTATIC STEAM TRAP

INVERTED BUCKET STEAM TRAP

THERMOSTAT

PROGRAMMABLE THERMOSTAT

THERMOSTAT (W/ NIGHT SETBACK)

ROOM SENSOR

HUMIDISTAT

PRESSURE GAUGE

DAMPER (ELECTRIC OPERATION)

DAMPER (PNEUMATIC OPERATION)

DAMPER BLADES

SUPPLY AIR DUCT

EXIST SUPPLY AIR DUCT

RETURN AIR DUCT

EXIST RETURN AIR DUCT

OUTSIDE AIR DUCT

EXIST OUTSIDE AIR DUCT

EXHAUST AIR DUCT

EXIST EXHAUST AIR DUCT

SUPPLY AIR DUCT RISER

RETURN AIR DUCT RISER

OUTSIDE AIR DUCT RISER (AS NOTED)

EXHAUST AIR DUCT

INSULATED DUCTWORK (AS NOTED)

SUPPLY AIR DIFFUSER (SQUARE)

SUPPLY AIR DIFFUSER (INLINE)

TURNING VANES

SURFACE MTD. GRILLE

SUPPLY AIR DIFFUSER (ROUND)

90° TEE W/45° APPROACH

CONICAL TAKE-OFF

CONICAL TAKE-OFF W/ DAMPER

BALANCE DAMPER

RETURN AIR DUCT BOOT

ECCENTRIC REDUCER

CONCENTRIC REDUCER

VERTICAL FIRE DAMPER

EXISTING VERTICAL FIRE DAMPER

HORIZONTAL FIRE DAMPER

EXISTING HORIZONTAL FIRE DAMPER

VERTICAL SMOKE DAMPER

HORIZONTAL SMOKE DAMPER

VERTICAL FIRE / SMOKE DAMPER

HORIZONTAL FIRE / SMOKE DAMPER

DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,

PROVIDED & WIRED BY E.T.C.

UNIT HEATER

CEILING EXHAUST FAN

ROOF MOUNTED EXHAUST FAN

DEMOLITION

POINT OF CONNECTION BETWEEN NEW AND

EXISTING

POINT OF EXISTING TO REMAIN AND EXISTING

TO BE REMOVED

INDICATES PLAN NOTE

INDICATES DEMOLITION NOTE

DETAIL BUBBLE

DETAIL NUMBER

PAGE LOCATION INDICATES

DIRECTION OF DETAIL SECTION

X

X

XX

XXXX

XX

XXXX

SA

OA

X-OA

X-EA

EA

X-SA

X-RA

RA

SCP

SC

DXS

DXL

HR

CR

CD

CS

DX

CTR

HPR

HS

HPS

CTS

CWR

CWS

S

L

LPS

MPS

HPS

SC (BF)

TAG CFM

NECK REMARKS

SIZE

BT

FT

SD-1 250

8"ø ---

P

H

S

T

T P

T N

M

M

SD

1. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING

DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH BUILDING

STRUCTURE, EQUIPMENT FURNISHED, ARCHITECTURAL DRAWINGS AND ALL

OTHER TRADES PRIOR TO DEMOLITION.

2. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS,

AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES,

CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES

HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.

3. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,

UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC,

STATE FIRE INSURANCE REGULATION BODY, NFPA OR OTHERS. THESE

STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE

DRAWING AND SPECIFICATIONS.

4. COORDINATE CUTTING AND PATCHING WITH GENERAL CONTRACTOR.

5. ALL BOLD DASHED LINES INDICATE ITEMS TO BE REMOVED UNLESS NOTED BY

KEYNOTE. ALL OTHER EXISTING SYSTEMS SHOWN FOR REFERENCE ONLY.

6. PATCH AND REPAIR ALL FLOOR AND WALL SURFACES LEFT DAMAGED OR

INCOMPLETE FROM REMOVAL OF EXISTING PARTITIONS, MILLWORK,

CASEWORK, OR OTHER FIXED ACCESSORIES AND EQUIPMENT WITH

MATERIALS TO MATCH EXISTING, AS ACCEPTABLE TO THE OWNER.

7. NOTATIONS ARE MADE IN VARIOUS PLACES ON THE DRAWINGS TO CALL

ATTENTION TO DEMOLITION WHICH IS REQUIRED. HOWEVER, THESE

DRAWINGS ARE NOT INTENDED TO SHOW EACH AND EVERY ITEM TO BE

REMOVED. CONTRACTOR SHALL REMOVE ALL MATERIALS RELATED TO THEIR

RESPECTIVE TRADES AS REQUIRED TO PERMIT THE CONSTRUCTION OF THE

NEW WORK AS SHOWN.

8. THE GENERAL CONTRACTOR SHALL COORDINATE THE EXTENT OF THE

REQUIRED DEMOLITION OF THE EXISTING BUILDING AS REQUIRED TO

FACILITATE THE CONSTRUCTION OF THE PROJECT AS SHOWN AS PART OF

THIS WORK.

9. ALL DEMOLITION SHALL BE APPROVED BY THE OWNER/TENANT PRIOR TO

COMMENCEMENT AND SHALL BE PERFORMED UNDER REQUIREMENTS AND

APPROVAL OF THE LOCAL CODE JURISDICTIONS.

10. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN AN

APPROVED MANNER ANY SUCH WORK WHICH BECOMES DAMAGED.

11. RUBBISH AND DEBRIS RESULTING FROM THE WORK SHALL BE REMOVED

IMMEDIATELY FROM THE SITE IN A SAFE AND LEGAL MANNER BY THE

CONTRACTOR.

12. DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT BUILDING

REPRESENTATIVE TO CLARIFY ANY ITEMS NOT SHOWN ON THESE

DOCUMENTS OR SHOWN NOT MATCHING FIELD CONDITIONS.

GENERAL DEMOLITION NOTES

9"x15.25" POLYCARBONATE

ROOF MOUNTING PADS

12 GA. HOT DIPPED

GALVANIZED STRUT

12 GA. HOT DIPPED

GALVANIZED STRUT NOTES:

1. ROOF MOUNTED EQUIPMENT STAND BASED ON

MIRO-HD(R) OR APPROVED EQUIVALENT.

2. CONTRACTOR TO COORDINATE WITH SIZE OF HEAT

PUMP PRIOR TO ORDERING EQUIPMENT STAND TO

ENSURE PROPER FITMENT.

3. CONTRACTOR TO MOUNT HEAT PUMP TO ADJUSTABLE

FRAME RAILS WITH TAMPERPROOF CORROSION

RESISTANT HARDWARE.

4. CONTRACTOR TO ENSURE THE BOTTOM OF THE HEAT

PUMP IS AT LEAST 18" ABOVE THE ROOF.

1 ROOF MOUNTED HEAT PUMP STAND DETAIL

SCALE: NTS

2 INSULATION HANGER DETAIL

SCALE: NTS

14 GAUGE ZINC

COATED SHEET

STEEL SADDLE, AT

LEAST 12" LONG

PIPE

INSULATION

THERMAL HANGERS

SHIELD INSERTS

(360-DEG)

C om m te ch

D es ig n

472/24059.SAA

file no.

checked by drawn by consultant issue date acctg template.

contract order no.

consultant job no.

sheet title

Y22432

C O

U R

TL

AN

D S

T.

, S

U

IT

E

R

O C

KF

O

R D

, M

IC

H

IG

AN

W W

W .C

O M

M

TE

C H

D

ES

IG

N

.C O

M

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

M a t r ix

06/11/26 ISSUED FOR BID

1065_24B

472/24059.SAA

472WHVMaintproj

Y22432

VIDEO SECURITY

UPGRADES

M-100

MECHANICAL SYMBOLS,

NOTES, ABBREVIATIONS,

AND SCHEDULES

CAT

DBP

T

X-SD ---

X-SD ---

X-SD ---

X-RG ---

24x24 ---

X-RG ---

24x12 ---

X-AC

X-CU

(ON ROOF)

X-AC

X-RG ---

24x24 ---

M

M

X-AC-4

X-AC-3

X-SA

X-SA

X-SA

X-SA

X-SA

X-SAX-SA

X-SAX-SA

X-SA

X-SA

X-SA

X-CU-3

(ON ROOF)

X-CU-4

(ON ROOF)

X-SD ---

X-SD ---

X-RA

X-AC

X-CU

(ON ROOF)

X-AC

X-CU

(ON ROOF)

X-AC

X-AC-4

X-AC-3

X-CU-3

(ON ROOF)

X-CU-4

(ON ROOF)

X-CU

(ON ROOF)

X-CD PUMP

X-CD PUMP

X-

CD

X-CD X-CD

X-CD

X-CD

X-CD

X-

CD

X-CW X-CW

X-

CW

X-

CW

X-

CW

X-CW

X-

CWX-

DX

X-

DX

X-DX

X-DX

X-DX

X-DX

X-FD

X-CD

X-

CD

X-

DX

X-

DX

X-

CD

X-

DX

X-

DX

X-CD

1 1

MECHANICAL DEMOLITION NOTES

DISCONNECT, REMOVE, AND DEMO EXISTING WALL MOUNTED AC UNIT, ROOF MOUNTED

CONDENSING UNIT, CONDENSING UNIT SUPPORTS, THERMOSTAT, CONTROLS,

CONTROLS WIRING, DX PIPING, CONDENSATE PIPING, VALVES, FITTINGS, AND ALL

ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. CONTRACTOR TO PATCH, PRIME, AND

PAINTED EXISTING WALL AS REQUIRED WHERE THE WALL MOUNTED AC UNIT AND

THERMOSTAT ARE REMOVED TO MATCH EXISTING. CONTRACTOR TO MODIFY AND REUSE

THE EXISTING DX PIPING ROOF PENETRATIONS AS REQUIRED TO INSTALL NEW DX PIPING

SHOWN ON THE NEW DRAWINGS. CONTRACTOR TO PATCH ROOF AS REQUIRED TO

MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN ANY ROOF WARRANTIES.

EXISTING AC UNIT, CONTROLS, CONTROL WIRING, CONDENSATE PUMP, DX PIPING,

CONDENSATE PIPING, AND ALL ASSOCIATED ACCESSORIES TO REMAIN.

EXISTING ROOF MOUNTED CONDENSING UNITS, CONTROLS, CONTROL WIRING, DX

PIPING, AND ALL ASSOCIATED ACCESSORIES TO REMAIN.

DISCONNECT, REMOVE, AND DEMO EXISTING CONDENSATE PIPING, AND ALL

ASSOCIATED ACCESSORIES TO THE EXTENTS SHOWN. MODIFY EXISTING PIPING AS

REQUIRED TO INSTALL NEW CHECK VALVE SHOWN ON NEW DRAWINGS.

GENERAL DEMOLITION NOTES

1. CONTRACTOR TO REMOVE AND RE-INSTALL EXISTING CEILING GRID AND CEILING TILES

AS REQUIRED TO COMPLETE THEIR WORK. THE CONTRACTOR IS RESPONSIBLE FOR THE

REPLACEMENT OF BROKEN/DAMAGED CEILING TILES.

2. CONTRACTOR TO PATCH, PRIME, AND PAINT WALLS AS REQUIRED TO MATCH EXISTING

ONCE ALL DEMOLITION/NEW WORK IS COMPLETE.

3. ALL EXISTING EQUIPMENT, DUCTWORK, GRILLES/DIFFUSERS, CONTROLS, AND ALL

ASSOCIATED ACCESSORIES ARE TO REMAIN UNLESS OTHERWISE NOTED.

4. ALL EXISTING EQUIPMENT, PIPING, CONTROLS, AND ALL ASSOCIATED ACCESSORIES ARE

TO REMAIN UNLESS OTHERWISE NOTED.

5. CONTRACTOR TO PATCH EXISTING ROOF AS REQUIRED TO MATCH EXISTING, SEAL

WATERTIGHT, AND MAINTAIN EXISTING ROOF WARRANTIES ONCE ALL DEMOLITION/NEW

WORK IS COMPLETE.

C om m te ch

D es ig n

472/24059.SAA

file no.

checked by drawn by consultant issue date acctg template.

contract order no.

consultant job no.

sheet title

Y22432

C O

U R

TL

AN

D S

T.

, S

U

IT

E

R

O C

KF

O

R D

, M

IC

H

IG

AN

W W

W .C

O M

M

TE

C H

D

ES

IG

N

.C O

M

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

M a t r ix

06/11/26 ISSUED FOR BID

1065_24B

472/24059.SAA

472WHVMaintproj

Y22432

VIDEO SECURITY

UPGRADES

M-300

PARTIAL FIRST FLOOR PLAN - WEST

ADMINISTRATION BUILDING -

MECHANICAL/PIPING DEMOLITION

N PARTIAL FIRST FLOOR PLAN - WEST ADMINISTRATION - MECHANICAL DEMOLITION

SCALE: 1/4" = 1'-0"

0 1 5 10

N PARTIAL FIRST FLOOR PLAN - WEST ADMINISTRATION - PIPING DEMOLITION

SCALE: 1/4" = 1'-0"

0 1 5 10

6/10/2026CD SET

X-SD ---

X-SD ---

X-SD ---

X-RG ---

24x24 ---

X-RG ---

24x12 ---

X-AC

X-RG ---

24x24 ---

M

M

X-AC-4

X-AC-3

X-SA

X-SA

X-SA

X-SA

X-SA

X-SAX-SA

X-SAX-SA

X-SA

X-SA

X-SA

X-CU-3

(ON ROOF)

X-CU-4

(ON ROOF)

X-SD ---

X-SD ---

X-RA

X-CU

(ON ROOF)

T

AC-7

HP-7

(ON ROOF)

AC-7

AC-5

CU-5

(ON ROOF)

RG-1 ---

24x24 ---

RG-1 ---

24x24 ---

RG-1 ---

24x24 ---

3 3

RG-1 ---

24x24 ---

AC-6

CU-6

(ON ROOF)

RG-1 ---

24x24 ---

RG-1 ---

24x24 ---

8 10

X-AC

X-AC-4

X-AC-3

X-CU-3

(ON ROOF)

X-CU-4

(ON ROOF)

X-CU

(ON ROOF)

AC-7

HP-7

(ON ROOF)

AC-5

CU-5

(ON ROOF)

AC-6

CU-6

(ON ROOF)

DX DX

PIPE

SUPPORTS

CD

CD

3/4"

3/4"

3/4" 3/4" CD

DN TO X-FD

CD PUMP

3/4"

CO

3/4"

PIPE

SUPPORTS

DX DX

CO

CD

CO

X-AC

X-AC-4

X-AC-3

X-CU-3

(ON ROOF)

X-CU-4

(ON ROOF)

X-CU

(ON ROOF)

X-CD PUMP

X-CD PUMP

X-

CD

X-CD X-CD

X-CD

X-CD

X-CD

X-

CD

X-CW X-CW

X-

CW

X-

CW

X-

CW

X-CW

X-

CWX-

DX

X-

DX

X-DX

X-DX

X-DX

X-DX

X-FD

X-CD

X-

CD

X-

DX

X-

DX

X-

CD

CD

CO

CD PUMP

CD

3/4"

3/4"5

BFP

3/4" CW DN

BFP

DX DX

PIPE

SUPPORTS

GENERAL MECHANICAL NOTES

1. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING WALLS AS NEEDED TO

MATCH EXISTING WHERE DEMOLITION AND/OR NEW WORK IS COMPLETED. IF

MODIFICATIONS ARE MADE TO RATED WALLS, CONTRACTOR TO ENSURE

WALLS ARE PATCHED TO MATCH EXISTING AND MAINTAIN THE EXISTING

RATING.

2. CONTRACTOR IS TO REMOVE AND SALVAGE EXISTING CEILING TILES AS

REQUIRED TO INSTALL NEW RETURN GRILLES IN THE LOCATION SHOWN.

CONTRACTOR TO COORDINATE THE LOCATION OF THE NEW RETURN GRILLES

WITH THE EXISTING LIGHTS AND CEILING MOUNTED DEVICES. CONTRACTOR

TO UTILIZE SALVAGED CEILING TILES TO FILL CEILING GRID WHERE CEILING

TILES ARE CURRENTLY MISSING. CONTRACTOR TO PROVIDE ADDITIONAL

CEILING TILES (SAME COLOR/MODEL AS THE EXISTING) AS REQUIRED TO

ENSURE THAT THE ENTIRE CEILING GRID SYSTEM IS FILLED ONCE ALL

DEMOLITION/NEW WORK IS COMPETED.

3. CONTRACTOR IS TO REMOVE, SALVAGE, AND RE-INSTALL EXISTING CEILING

GRID AND CEILING TILES AS REQUIRED TO COMPLETE THEIR WORK.

CONTRACTOR IS RESPONSIBLE FOR REPLACING DAMAGED/BROKEN CEILING

TILES.

4. ALL NEW CONTROL WIRING, RACEWAYS, AND ALL ASSOCIATED ACCESSORIES

TO BE CONCEALED IN WALLS OR ABOVE CEILING SPACE. CONTRACTOR TO

CUT, PATCH, PRIME, AND PAINT WALLS AS NEEDED TO INSTALL CONCEALED

WIRING TO MATCH EXISTING.

5. INSTALL ALL NEW EQUIPMENT PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS. ENSURE ALL MANUFACTURER REQUIRED CLEARANCES ARE

MAINTAINED.

6. CONTRACTOR TO CONNECT ALL NEW EQUIPMENT TO THE EXISTING BASS DDC

CONTROL SYSTEM. CONTRACTOR TO PROVIDE ALL REQUIRED CONTROLS,

CONTROL WIRING, AND EQUIPMENT/ACCESSORIES NEEDED TO CONNECT

NEW EQUIPMENT TO THE EXISTING BASS DDC CONTROL PANEL AND

INTEGRATE THE NEW EQUIPMENT ONTO THE EXISTING FRONT-END GRAPHICS.

7. CONTRACTOR TO PATCH ALL ROOF PENETRATIONS/MODIFICATIONS AS

REQUIRED TO MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN ANY

EXISTING ROOF WARRANTIES.

8. INSTALL 0.020" THICK ALUMINUM, STUCCO EMBOSSED JACKET AROUND ALL

EXPOSED, ROOF ROUTED REFRIGERANT PIPING.

MECHANICAL KEY NOTES

INSTALL NEW FLOOR MOUNTED AC UNIT, ROOF MOUNTED CONDENSING UNIT,

SUPPORTS, CONTROLS, CONTROL WIRING, FIELD INSTALLED CONDENSATE PUMP,

DX PIPING, CONDENSATE PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED

ACCESSORIES IN LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS. CONTRACTOR TO CONNECT NEW AC UNIT AND CONDENSING UNIT

TO THE EXISTING CONTROLS BASS DDC CONTROL PANEL. CONTRACTOR TO

PROVIDE AND INSTALL ALL REQUIRED CONTROLS AND CONTROLS

DEVICES/ACCESSORIES TO INTEGRATE THE NEW AC UNIT AND CONDENSING UNIT

ONTO THE EXISTING FRONT-END GRAPHICS. NEW ROOF MOUNTED CONDENSING

UNIT TO BE INSTALLED ON MANUFACTURER PROVIDED 36" TALL CONDENSER

LEGS.

INSTALL NEW WALL MOUNTED AC UNIT, ROOF MOUNTED HEAT PUMP, HANGERS,

SUPPORTS, THERMOSTAT, CONTROLS, CONTROL WIRING, DX PIPING,

CONDENSATE PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN

THE LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

CONTRACTOR TO CONNECT NEW WALL MOUNTED AC UNIT AND ROOF MOUNTED

HEAT PUMP TO EXISTING BASS DDC CONTROL PANEL. CONTRACTOR TO PROVIDE

AND INSTALL ALL REQUIRED CONTROLS AND CONTROLS DEVICES/ACCESSORIES

TO INTEGRATE THE NEW AC UNIT AND HEAT PUMP ONTO THE EXISTING

FRONT-END GRAPHICS. NEW ROOF MOUNTED HEAT PUMP TO BE INSTALLED ON

NEW CONTRACTOR PROVIDED ELEVATED EQUIPMENT STAND.

INSTALL NEW RETURN AIR GRILLE AND ALL ASSOCIATED ACCESSORIES IN THE

LOCATION SHOWN. CONTRACTOR TO COORDINATE THE LOCATION OF THE NEW

RETURN GRILLES WITH THE EXISTING LIGHTS AND CEILING MOUNTED DEVICES.

CONTRACTOR TO MODIFY EXISTING AC UNIT AND CONDENSING UNIT CONTROLS

AS REQUIRED TO OPERATE PER THE SEQUENCE OF OPERATIONS WITH THE

ADDITION OF AC-5/CU-5 & AC-6/CU-6 SERVING THE CAMERA ROOM SPACE.

CONTRACTOR TO PROVIDE ALL REQUIRED CONTROLS, CONTROL WIRING, AND ALL

ASSOCIATED ACCESSORIES AS NEEDED TO HAVE UNIT OPERATE PER THE

SEQUENCE OF OPERATIONS.

INSTALL NEW CONDENSATE PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED

ACCESSORIES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.

CONTRACTOR TO MAKE NEW ABOVE CEILING WALL PENETRATIONS AS REQUIRED

TO ROUTE NEW CONDENSATE PIPING. CONTRACTOR TO PATCH , PRIME, AND

PAINT EXISTING WALL AS REQUIRED TO MATCH EXISTING. CONTRACTOR TO

CONNECT NEW CONDENSATE PIPING TO EXISTING PIPING IN THE LOCATION

SHOWN. CONTRACTOR TO MODIFY EXISTING PIPING AS REQUIRED FOR NEW

CONNECTION.

SUPPORT REFRIGERANT PIPING ON ROOF WITH PIPE SUPPORTS BASED ON MIRO

#5-RAH-7 OR APPROVED EQUIVALENT. SPACE PIPING SUPPORTS PER

MANUFACTURER'S RECOMMENDATIONS. INSTALL PIPE SUPPORT PAD OR

MANUFACTURER APPROVED EQUIVALENT.

INSTALL NEW DOMESTIC COLD WATER PIPING, VALVES, FITTINGS, AND ALL

ASSOCIATED ACCESSORIES PER THE MANUFACTURER'S INSTALLATION

INSTRUCTIONS. CONTRACTOR TO CONNECT NEW DOMESTIC COLD WATER PIPING

TO EXISTING PIPING IN THE LOCATION SHOWN. CONTRACTOR TO MODIFY

EXISTING PIPING AS REQUIRED FOR NEW CONNECTION.

INSTALL NEW DOUBLE DEFLECTION SUPPLY AIR DIFFUSER (TITUS 272RL OR

APPROVED EQUAL) ON FRONT/BOTTOM DISCHARGE OF THE AC UNIT. OPENING

FOR NEW SUPPLY AIR DIFFUSER IS APPROXIMATELY 26.75" WIDE x 10.75" TALL.

INSTALL NEW DX PIPING, HANGER, SUPPORTS, AND ALL ASSOCIATED

ACCESSORIES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. ROUTE

NEW DX PIPING THROUGH NEW/EXISTING ROOF PENETRATIONS AND THROUGH

NEW CURB AND ROOF BOOT. PATCH ROOF PENETRATIONS TO MATCH EXISTING,

SEAL WATER TIGHT, AND MAINTAIN ANY EXISTING ROOF WARRANTIES.

INSTALL NEW NEW FLOOR MOUNTED AC UNIT AS CLOSE AS POSSIBLE TO X-AC-4

WHILE MAINTAINING ALL MANUFACTURER REQUIRED CLEARANCES.

C om m te ch

D es ig n

472/24059.SAA

file no.

checked by drawn by consultant issue date acctg template.

contract order no.

consultant job no.

sheet title

Y22432

C O

U R

TL

AN

D S

T.

, S

U

IT

E

R

O C

KF

O

R D

, M

IC

H

IG

AN

W W

W .C

O M

M

TE

C H

D

ES

IG

N

.C O

M

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

M a t r ix

06/11/26 ISSUED FOR BID

1065_24B

472/24059.SAA

472WHVMaintproj

Y22432

VIDEO SECURITY

UPGRADES

M-400

PARTIAL FIRST FLOOR PLAN -

WEST ADMINISTRATION BUILDING

- MECHANICAL/PIPING NEW

N PARTIAL FIRST FLOOR PLAN - WEST ADMINISTRATION - MECHANICAL NEW

SCALE: 1/4" = 1'-0"

0 1 5 10

N PARTIAL FIRST FLOOR PLAN - WEST ADMINISTRATION - PIPING NEW

SCALE: 1/4" = 1'-0"

0 1 5 10

X

X

X

TVSS

VFD

TRANSIENT VOLTAGE SURGE SUPPRESSION

VARIABLE FREQUENCY DRIVEDUPLEX RECEPTACLE

DOCK LIGHT FIXTURE

TELEPHONE / DATA OUTLET

ADDENDUM NOTE

PLAN NOTE

DEMOLITION NOTE

THREE PHASE MOTOR

ELECTRICAL SYMBOLS LEGEND

J

SINGLE RECEPTACLE (120 VOLT)

EMERGENCY RECEPTACLE

DOUBLE DUPLEX RECEPTACLE

FLUSH FLOOR BOX

SURFACE FLOOR BOX

SPECIAL EQUIPMENT RECEPTACLE

TELEPHONE OUTLET

DATA OUTLET

POWER POLE

JUNCTION BOX

WALL JUNCTION BOX

PULL (JUNCTION) BOX

UNDERFLOOR JUNCTION BOX

OUTLETS

LIGHT FIXTURE

STRIP FIXTURE

IN-GRADE LIGHT FIXTURE

SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)

WALL MOUNT LIGHT FIXTURE

CEILING LIGHT FIXTURE

TRACK & FIXTURE

STREET TYPE POLE FIXTURE

POLE MOUNTED LIGHT FIXTURE

EXTERIOR WALL MOUNT LIGHT FIXTURE

WALLPACK LIGHT FIXTURE

SPECIAL PURPOSE LIGHT FIXTURE

HIGH BAY LIGHT FIXTURE

EMERGENCY EGRESS LIGHT FIXTURE

(number of heads shown)

EMERGENCY LIGHT FIXTURE

FIXTURES

SWITCHES

SINGLE-POLE SWITCH

DIMMER SWITCH

TIME SWITCH

KEY SWITCH

MANUAL MOTOR SWITCH

THERMAL OVERLOAD SWITCH

SWITCH WITH PILOT LIGHT

FOUR-WAY SWITCH

THREE-WAY SWITCH

CIRCUITRY and RACEWAYS

UNDERFLOOR DUCT

BUS DUCT

PLUGMOLD AS SPECIFIED

WIREMOLD AS SPECIFIED

FLEXIBLE PIGTAILS/CONNECTIONS

"CONDUIT RUN CONTINUES" INDICATION

END OF CONDUIT RUN, CAP AND STAKE

END OF CONDUIT RUN

HOME RUN (with circuit numbers)

CONDUIT STUB DOWN

CONDUIT STUB UP

CONDUIT INSTALLED

CONDUIT INSTALLED

MECHANICAL

ELECTRIC WATER HEATER

ELECTRIC UNIT HEATER

PIPE TRACE HEATER

RESISTANCE HEATER, KW SHOWN

SINGLE PHASE MOTOR

SERVICE and EQUIPMENT

THERMOSTAT

CAPACITOR

ENCLOSED CIRCUIT BREAKER

TRANSFER SWITCH

WIREWAY

GROUND CONNECTION PER N.E.C.

TELEPHONE TERMINAL BOARD

GENERATOR, KW SHOWN

CURRENT TRANSFORMERS

UTILITY METER, AS REQUIRED

WEATHERHEAD

PANELBOARD, FLUSH MOUNTED

PANELBOARD, SURFACE MOUNTED

COMB. STARTER

MAGNETIC STARTER

DISCONNECT SWITCH

TRANSFORMER

CONTROL

xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt

LIGHTING CONTACTOR

CONTROL TRANSFORMER

buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)

PHOTOCELL (voltage as required)

HUMIDISTAT

DESIGNATIONS

(by E.C.)

(by others)

TT

G

WW

PC

CT

TS

T

H

TC

IC

T

1,3

OR

PM

WM

BD

UFD

F S

J

J

D

WH

PP

J

SWITCH STYLE OCCUPANCY SENSOROC

DIGITAL TIME SWITCH

POWER PACK

DUAL TECHNOLOGY SENSOR - 360° - 500 SQ FT

DUAL TECHNOLOGY SENSOR - 360° - 1000 SQ FT

ULTRASONIC SENSOR - 360° - 2 CIRCUIT

OCCUPANCY SENSOR / PHOTOCELL

WALL MOUNT DUAL TECHNOLOGY SENSOR

OS5

OS4

T

OS2

OS3

OS1

PP

CEILING MOUNTED WIFI

DIGITAL EQUIPMENT METER, AS REQUIRED

POLE

PUMP

PANEL

P

PNL

PVC

PRV-

P-

PB

POLY VINYL CLORIDE

POWER ROOF VENTILATOR

PULL BOX

GENERAL CONTRACTOR

GROUND

HUMIDIFIERH-

GND

GFI

GC

GROUND FAULT INTERUPTER

ABBREVIATIONS LEGEND

POWER

SWITCH

RECEPT

SF-

SWBD

TCC

SPEC

SW

RGC

RTU-

PWR

VOLTS

WATTS

UF

V

W

UL

VL

UNO

UH-

TS

TYP

TR

ROOF TOP UNIT

RECEPTACLE

SWITCHBOARD

UNDER FLOOR

SPECIFICATIONS

RIGID GALVANIZED STEEL CONDUIT

UNLESS NOTED OTHERWISE

UNDERWRITERS' LABORATORIES, INC.

TAMPER PROOF RECEPTACLE

TAMPER PROOF SWITCH

TEMPERATURE CONTROL CONTRACTOR

VERIFY LOCATION WITH OWNER

TYPICAL

UNIT HEATER

SUPPLY FAN

WITH

WITHOUT

W/

XFMR

W/O

WP

TRANSFORMER

WEATHER PROOF

HOUR

LIGHT

JUNCTION BOX

LIGHT CONTROL

ISOLATED GROUND

HORSEPOWER

MINIMUM

MOUNT

MAKE-UP AIR UNIT

MOTOR CONTROL CENTER

MAIN LUG ONLY

MOUNTED

MOUNTING

MAXIMUM

LIGHTING

LT FLEX

MTD

MUAU-

MTG

MLO

MIN

MT

MC

MAX

MCC

LTG

IG

LC

LT

IMC

JB

HR

HVAC

HOA

HP

NORMALLY CLOSED

NOT IN CONTRACT

NORMALLY OPEN

NOT TO SCALE

NIGHT LIGHTNL

NTS

NO

NIC

NC

HAND-OFF-AUTO SELECTOR SWITCH

HEATING/VENTILATING/AIR CONDITIONING

INTERMEDIATE METAL CONDUIT

LIQUID TIGHT FLEXIBLE METAL CONDUIT

MECHANICAL CONTRACTOR

HID HIGH INTENSITY DISCHARGE

A

AC

AFF

ACU-

AHJ

AHU-

AS

B-

BC

AIC

ATS

BLDG

CHLR-

CND (C)

CKT BKR

CKT

CUH-

CU-

DISC

DFU-

EF-

EC

DWH-

EBB-

DWG

CT-

EXIST (E)

EWC

FLEX

FLA

FLR

FSES

FLUOR

EMT

ABOVE FINISHED FLOOR

AIR CONDITIONING UNIT

AMPS

ABOVE COUNTER

AIR HANDLING UNIT

AUTOMATIC TRANSFER SWITCH

AMPS INTERUPTING CAPACITY

AUTHORITY HAVING JURISDICTION

ABOVE SHELF

BOILER

BUILDING

BELOW COUNTER

CHILLER

DOMESTIC WATER HEATER

CABINET UNIT HEATER

CIRCUIT

CIRCUIT BREAKER

CONDUIT

CONDENSING UNIT

COOLING TOWER

DUCT FURNACE

DRAWING

DISCONNECT

FOOD SERVICE EQUIP. SUPPLIER

ELECTRIC WATER COOLER

ELECTRICAL CONTRACTOR

ELECTRIC BASEBOARD

ELECTRICAL METALLIC TUBING

EXISTING

EXHAUST FAN

FLOOR

FLUORESCENT

FLEXIBLE CONDUIT

FULL LOAD AMPS

EM EMERGENCY

F/S FIRE/SMOKE

FU- FURNACE

GENERAL ELECTRICAL NOTES

SOUND and SIGNAL

SSCP

COCCTV

SECURITY SYSTEM CONTROL PANEL

CAMERA

DATA RACK

RACK MOUNTED UPS

BRACKET MOUNTED UPS

POLE

PLUG STRIP (PDU)

P

C

DR

RUPS

BUPS

1. ALL NON-FIRE RATED WALLS ARE TO BE PATCHED WITH LIKE MATERIAL TO MAINTAIN

ORIGINAL RATING.

2. ALL WALL AND FLOOR PENETRATIONS THROUGH FIRE RATED WALLS ARE TO BE

SEALED WITH FIRE CAULK TO MAINTAIN ORIGINAL RATING.

3. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL

STEEL.

4. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID WALK THROUGH TO

DETERMINE THE EXACT EXTENT OF THE WORK REQUIRED BEFORE BIDDING THE

PROJECT.

5. REMOVE ALL EXISTING EXPOSED CONDUIT, WIRE, AND EQUIPMENT NOT TO BE

RE-USED WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.

6. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,

SURFACES SHALL BE PATCHED AND PAINTED TO MATCH ADJACENT.

7. EXISTING WORK WHICH IS PRESENTLY CONCEALED, WHICH WILL REMAIN CONCEALED,

AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED NOT BE

REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE AND

THEN PATCHED AND PAINTED TO MATCH, OR AS NOTED.

8. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED

TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND

PATCHING.

9. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO

MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED EQUIPMENT.

10. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO INSTALLING

SERVICE TO EQUIPMENT.

11. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENTS AND CASUAL FIELD

OBSERVATION PERFORMED ON AUGUST 16, 2024. REPORT ANY DISCREPANCIES TO

ENGINEER FOR CLARIFICATION.

12. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. ALL FLEXIBLE CONDUIT RACEWAYS SHALL

BE LIQUID TITE, MAXIMUM 36" LENGTH. REFER TO SPECIFICATION 260533 - RACEWAY

AND BOXES FOR ELECTRICAL SYSTEMS.

13. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:

13.1. STRAP DISTANCE: 5 FEET.

13.2. FASTENERS: 2 HOLE

13.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.

13.4. FITTINGS: COMPRESSION.

13.5. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.

14. ALL CONDUIT 10 FOOT AND BELOW SHALL MEET THE FOLLOWING REQUIREMENTS:

14.1. STRAP DISTANCE: 3 FEET.

14.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.

14.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.

14.4. FITTINGS: COMPRESSION.

14.5. BELL BOXES: FS TYPE.

14.6. NO KNOCKOUTS.

14.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES

15. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE

CEILINGS IS ACCEPTABLE.

15.1. ALL EXPOSED WIRING ABOVE CEILINGS SHALL BE INSTALLED WITH J-HOOKS. DO

NOT CONNECT TO EXISTING CEILING TIE WIRES.

16. CONDUITS AND WIRES SHALL BE INSTALLED STRAIGHT, LEVEL, AND SHALL BE

PARALLEL OR PERPENDICULAR TO THE BUILDING LINES.

17. CONTRACTOR SHALL VERIFY ALL VOLTAGES BEFORE CONNECTING ANY EQUIPMENT.

18. ALL LOCATIONS WHERE THE WALLS CAN NOT BE FISHED SHALL BE SURFACE

MOUNTED CONDUIT FOLLOWING NOTES 12 THROUGH 14 ABOVE.

19. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.

20. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC, TYPE

EPC-40-PVC. ALL EXTERIOR ABOVE GROUND CONDUIT SHALL BE GRC.

21. ALL ELECTRICAL OUTAGES SHALL NOT LAST OVER 2-HOURS. PORTABLE GENERATORS

SHALL BE USED TO REPLACE ANY ELECTRICAL SERVICE EXCEEDING THAT DURATION.

22. WHEN RELOCATING ANY ELECTRICAL DEVICE, CONTRACTOR SHALL COMPLETE THE

RELOCATION IN ONE DAY AND VERIFY THAT ALL DEVICES RELOCATED ARE WORKING

PROPERLY PRIOR TO LEAVING THE SITE.

23. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED COMPONENTS,

RACEWAYS, WIRE, AND HARDWARE, AS INDICATED ON DRAWINGS.

24. ALL WORK DONE WITHOUT APPROVED SHOP DRAWINGS IS AT CONTRACTORS RISK.

25. CONTRACTOR SHALL CONTACT COMMTECH FOR SPECIFICATIONS FOR CAT6 AND

OTHER LOW VOLTAGE REQUIREMENTS.

26. CONTRACTOR SHALL NOTIFY PSC OF ANY EXISTING INSTALLATIONS NOT MEETING

THESE STANDARDS PRIOR TO STARTING WORK IN THE AREA.

27. THESE DRAWINGS HAVE BEEN SUBMITTED AND APPROVED BY LOCAL AUTHORITIES

HAVING JURISDICTION. ANY COMMENTS THAT WERE PROVIDED BY THE LOCAL

AUTHORITIES HAVING JURISDICTION HAVE BEEN ADDRESSED, AND THE DRAWINGS

MODIFIED ACCORDINGLY. BECAUSE OF THIS, RESPONSIBILITY OF ANY ISSUES THAT

ARISE UPON FINAL INSPECTION SHALL NOT FALL UPON MATRIX CONSULTING

ENGINEERS.

DESCRIPTION AND COMMENTSTYPE MANUFACTURER CATALOG NO.

NEW LIGHT POLE SCHEDULE

D560-70OA140-145-GV-HH-SFBC-AB

WISCONSIN LIGHTING LAB

OR APPROVED EQUAL14

14' TAPERED STEEP POLE WITH BASE, 2"X4" HAND HOLE AT 18" FROM THE BASE TO

HAND HOLE, ANCHOR BOLTS PER MANUFACUTRURE RECOMMENDATIONS.

60KVA UPS- EQUIPMENT SPECIFICATION

60KVA UNINTERRUPTIBLE POWER SUPPLY (UPS) EATON 93PM

PROVIDE UNINTERRUPTIBLE POWER SUPPLY (UPS). UPS SHALL BE

VERTIV APM2 60KVA RATED, HIGH EFFICIENCY, DOUBLE CONVERSION,

CONTINUOUS DUTY, ON-LINE TYPE. INPUT VOLTAGE OF 208VAC, 60HZ,

3-PHASE 4-WIRE PLUS GROUND. OUTPUT VOLTAGE OF 208VAC, 60HZ,

3-PHASE 4-WIRE PLUS GROUND. 65 KAIC RATED. CONTINUOUS DUTY

STATIC BYPASS SWITCH, BACKLIT LCD CONTROL PANEL. INCLUDE FRONT

ACCESS, INDOOR RATED IP-20 ENCLOSURE. 13MIN LITHIUM ION

BATTERIES.

INCLUDE SYSTEM STARTUP SERVICES, USER TRAINING, AND THREE YEAR ON SITE

WARRANTY SERVICE FOR PARTS AND LABOR.

VS-RTSA-25-70-7-LAB-GV-DB-PC

WISCONSIN LIGHTING LAB

OR APPROVED EQUAL25

25' TAPERED STEEL POLE WITH 11" BASE, 2-3/8" TENON, 3"X5" HAND HOLE AT 14"-18",

6"-7" BOTTOM DIAMETER, 3"-4" TOP DIAMETER, 7 GAGE, 55,000 PSI, A153

GALVANIZEDHARDWARE, ANCHOR BOLTS ARE EXISTING TO REUSED, FESTOON

OPENING AT 22', DARK BRONZE FINISH. CONTRACTOR TO FIELD VERIFY ORIENTATION.

E-100

DRK

JFS

ELECTRICAL

SYMBOLS, ABBREV.,

& NOTES

C om m te ch

D es ig n

472/24059.SAA

file no.

checked by drawn by consultant issue date acctg template.

contract order no.

consultant job no.

sheet title

Y22432

C O

U R

TL

AN

D S

T.

, S

U

IT

E

R

O C

KF

O

R D

, M

IC

H

IG

AN

W W

W .C

O M

M

TE

C H

D

ES

IG

N

.C O

M

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

M a t r ix

06/11/26 ISSUED FOR BID

1065_24B

472/24059.SAA

472WHVMaintproj

Y22432

VIDEO SECURITY

UPGRADES

C

C

C

C

C

C C

C C

CC

C C

C

C

C

C

C C

C

C

C

C

C C

C

C

C

C C

C

C

C

C

C

C

C

C C

C

C

C

C

CC

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C C

C

C

C

C

C

C

C

C

C C

C

C

C

C C

CC

C

C

C

C

C

C

C

C

C C

C

C C

CC

C

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P P

PP

P

P

P

P

P

P

P

P

P P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P P

P

P

P

PP

P

P

P P

PPPP

P

P

P

P

P

P

P

P

P

P

C

P

P

P

P C

CAB-001

CAB-002

CA

B-

CA

B-

CAB-005

CAB-006

CAB-007

CAB-008

CAB-017

CAB-018

2 2

C

C

C

C

C2

C

C

C

C 2

C

C

C

CC

C

C

C

C1C 2

C

C2

C

P C

C

C

C

C

C

C

(1) 1" CONDUIT

(1) 1" CONDUIT

C

C

C

C

C2

C

P

P

ELECTRICAL KEY NOTES

REMOVE EXISTING LOW VOLTAGE SURGE PROTECTION

DEVICES. PROVIDE AND INSTALL NEW LOW VOLTAGE SURGE

PROTECTION DEVICES FOR CAMERAS ON POLE. RE-USE

EXISTING JUNCTION BOX. PULL EXISTING CAT 6 CABLE BACK

TO CBAINET AND RE-PULL EXISTING UN-SHIELDED CAT 6

CABLE WITH #10 GND. REPLACE EXISTING SHIELDED CAT 6

WITH UN-SHIELDED AS REQUIRED. TEST AND RE-TERMINATE

LOW VOLTAGE CABLES. ALL POLES ARE EXISTING TO REMAIN

UNLESS OTHERWISE SPECIFIED. REFER TO SHEET E-800

DETAIL 3.

PROVIDE AND INSTALL NEW SURGE PROTECTION DEVICE IN

COMMUNICATIONS ROOM FOR CAMERAS. REFER TO SHEET

E-800 DETAIL 2.

REMOVE EXISTING LINE AND LOW VOLTAGE SURGE

PROTECTION DEVICES. PROVIDE AND INSTALL NEW LINE AND

LOW VOLTAGE SURGE PROTECTION DEVICES (RAYCAP

G29-00-394-OTL-PROTEC-T1-40 AND RAYCAP NJ2010B) IN

PERIMETER CABINET. REFER TO SHEET E-800 DETAIL 1 FOR

COMMUNICATIONS CONNECTIVITY. PROVIDE AND INSTALL

NEW SURGE PROTECTION DEVICE IN ADMIN DATA RACK FOR

FIRST AND LAST CABINETS. PROVIDE AND INSTALL #10 GND

IN 3/4" CONDUIT FOR CAMERA POLE GROUNDING.

CONTRACTOR TO PROVIDE AND INSTALL ANCHOR BOLTS.

PROVIDE AND INSTALL NEW POLE AND BASE FOR NEW 360

DEGREE SALLY PORT DRIVE CAMERA. REFER TO SHEET E-801

DETAILS 4&5 AND POLE SCHEDULE ON SHEET E-100.

PROVIDE (1) 1" CONDUIT TO CAB-018 FOR LOW VOLTAGE AND

GROUND CABLES. REFER TO LOW VOLTAGE DRAWINGS FOR

LOW VOLTAGE CABLE INFORMATION.

PROVIDE AND INSTALL NEW CONCRETE BASE AND POLE FOR

NEW CAMERA. REFER TO SHEET E-100 FOR POLE SCHEDULE.

CONTRACTOR TO PROVIDE AND INSTALL ANCHOR BOLTS.

DIRECTIONAL BORE AND HYDRO-EXCAVATE CONDUITS FOR

LOW VOLTAGE PATHWAYS. REFER TO SPEC 023200 - HYDRO

EXCAVATION. REFER TO LOW VOLTAGE DRAWINGS FOR

CABLE TYPES AND QUANTITIES.

EXISTING DEVICES TO BE REMOVES. REMOVE ASSOCIATED

CONDUIT AND WIRE BACK TO SOURCE.

E-200

DRK

JFS

ELECTRICAL

FLOOR PLAN

NEW POWER

N ELECTRICAL - WEST SITE PLAN - POWER

SCALE: 1" = 60'-0"

400 10 20 80 150

WEST SITE PLAN

ELECTRICAL

C om m te ch

D es ig n

472/24059.SAA

file no.

checked by drawn by consultant issue date acctg template.

contract order no.

consultant job no.

sheet title

Y22432

C O

U R

TL

AN

D S

T.

, S

U

IT

E

R

O C

KF

O

R D

, M

IC

H

IG

AN

W W

W .C

O M

M

TE

C H

D

ES

IG

N

.C O

M

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

M a t r ix

06/11/26 ISSUED FOR BID

1065_24B

472/24059.SAA

472WHVMaintproj

Y22432

ELECTRICAL KEY NOTES

REMOVE EXISTING LOW VOLTAGE SURGE PROTECTION

DEVICES. PROVIDE AND INSTALL NEW LOW VOLTAGE SURGE

PROTECTION DEVICES FOR CAMERAS ON POLE. RE-USE

EXISTING JUNCTION BOX. PULL EXISTING CAT 6 CABLE BACK

TO CBAINET AND RE-PULL EXISTING UN-SHIELDED CAT 6

CABLE WITH #10 GND. REPLACE EXISTING SHIELDED CAT 6

WITH UN-SHIELDED AS REQUIRED. TEST AND RE-TERMINATE

LOW VOLTAGE CABLES. ALL POLES ARE EXISTING TO REMAIN

UNLESS OTHERWISE SPECIFIED. REFER TO SHEET E-800

DETAIL 3.

PROVIDE AND INSTALL NEW SURGE PROTECTION DEVICE IN

COMMUNICATIONS ROOM FOR CAMERAS. REFER TO SHEET

E-800 DETAIL 2.

REMOVE EXISTING LINE AND LOW VOLTAGE SURGE

PROTECTION DEVICES. PROVIDE AND INSTALL NEW LINE AND

LOW VOLTAGE SURGE PROTECTION DEVICES (RAYCAP

G29-00-394-OTL-PROTEC-T1-40 AND RAYCAP NJ2010B) IN

PERIMETER CABINET. REFER TO SHEET E-800 DETAIL 1 FOR

COMMUNICATIONS CONNECTIVITY. PROVIDE AND INSTALL

NEW SURGE PROTECTION DEVICE IN ADMIN DATA RACK FOR

FIRST AND LAST CABINETS. PROVIDE AND INSTALL #10 GND

IN 3/4" CONDUIT FOR CAMERA POLE GROUNDING.

CONTRACTOR TO PROVIDE AND INSTALL ANCHOR BOLTS.

PROVIDE AND INSTALL NEW POLE AND BASE FOR NEW 360

DEGREE SALLY PORT DRIVE CAMERA. REFER TO SHEET E-801

DETAILS 4&5 AND POLE SCHEDULE ON SHEET E-100.

PROVIDE (1) 1" CONDUIT TO CAB-018 FOR LOW VOLTAGE AND

GROUND CABLES. REFER TO LOW VOLTAGE DRAWINGS FOR

LOW VOLTAGE CABLE INFORMATION.

PROVIDE AND INSTALL NEW CONCRETE BASE AND POLE FOR

NEW CAMERA. REFER TO SHEET E-100 FOR POLE SCHEDULE.

CONTRACTOR TO PROVIDE AND INSTALL ANCHOR BOLTS.

DIRECTIONAL BORE AND HYDRO-EXCAVATE CONDUITS FOR

LOW VOLTAGE PATHWAYS. REFER TO SPEC 023200 - HYDRO

EXCAVATION. REFER TO LOW VOLTAGE DRAWINGS FOR

CABLE TYPES AND QUANTITIES.

C

C

C

C

C

C C

C

C

C

C

CCCCC

CCC

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C C

C C C

C

C C

C

C

C C C

CCCC

C C

C

C

C C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

CCC

C

C C

C

C

C

C C

C

C

CC

C

CC

C

C

C

C

C

C

C

C

C C

C

C

C

C

C

C

C C

C

C

C

P

P

P

P

P

P

PPPPPPPPPPPP

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P

P P

P

P

P

P

P

P P P

P

P P P P

P

P

P P P

P

P

P

P

P

P

P

P

P

P

P

P

PPPP

P P P P

P

P

P

P

P

P

P

P

P

P P

P P

P

P

P

P

P

P

P

P

P

PPPPP

PP

P

P P

P

P

P

P

P

P

P

P

P

P

P

P C

P

C

P

P

P

PP

P

CAB-008

CA

B-

CAB-010 CAB-011

CA

B-

CA

B-

CA

B-

CA

B-

CAB-016

CAB-017

1 1

2 2 2 2

3 3

C

C

CCCC

C

CCCC

C

C

C

C C

C

C

C

C

C

C

C

C

C

C C 2 2

C

C 2

C2

C

P

C2

C

C2

P

C

C

C

C

C

C

C

C

C

E-201

JFS

ELECTRICAL

SITE PLAN

N ELECTRICAL - EAST SITE PLAN - POWER

SCALE: 1" = 60'-0"

400 10 20 80 150

DRK

EAST SITE PLAN

ELECTRICAL

C om m te ch

D es ig n

472/24059.SAA

file no.

checked by drawn by consultant issue date acctg template.

contract order no.

consultant job no.

sheet title

Y22432

C O

U R

TL

AN

D S

T.

, S

U

IT

E

R

O C

KF

O

R D

, M

IC

H

IG

AN

W W

W .C

O M

M

TE

C H

D

ES

IG

N

.C O

M

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

M a t r ix

06/11/26 ISSUED FOR BID

1065_24B

472/24059.SAA

472WHVMaintproj

Y22432

DEPUTY

WARDEN

OFFICE

TOILET

DEPUTY

WARDEN

SECRETARY

CLOSET

DEPUTY SUITE

CONFERENCE

ROOM

INSPECTOR

OFFICE

CLOSET

CLOSET

CLOSET

CLOSET

DEPUTY

SUITE

CORRIDOR

MENTAL

HEALTH

NORTH

CORR.

MENTAL

HEALTH

NORTH

CORR.

MENTAL

HEALTH

NORTH

CORR.

MENTAL

HEALTH

NORTH

CORR.

MENTAL

HEALTH

STAFF

TOILET

MENTAL

HEALTH

PRISONER

TOILET MENTAL

HEALTH

OFFICER

DESK

MENTAL

HEALTH

STAFF

TOILET

MENTAL

HEALTH

STAFF

TOILETMENTAL

HEALTH

WEST

CORR.

MENTAL

HEALTH

EAST

CORR.

FIRE

ALARM

PANEL

MED LINE

VEST.

SHIFT COMMAND

TOILET

CONTROL

CENTER

VEST.

CONTROL

CENTER

STAFF

TOILET W. LOBBY

MENS

TOILET

W. LOBBY

WOMENS

TOILET

W. LOBBY

WOMENS

TOILET

CONTROL CENTER

SOUTH CORRIDOR

WEST VISITING/

GATE PASSAGE

WEST GATE

BUBBLE

WEST

GATE

PRISONER

SHAKE DOWN

ARSENAL

VEST.

RECORDS

MENS

STAFF

TOILET

RECORDS

WOMENS

STAFF

TOILET

RECORDS

RESTROOM

PASSAGE

ARSENAL

RESTROOM

MAIN LOBBY

OFFICERS DESK

W. ADMIN

MAIN LOBBY

MAIN LOBBY

VISITOR WAITING MAIN LOBBY

VESTIBULE

STAFF

LUNCH

ROOM

LOBBY PORTER

CLOSET

RECORDS SOUTH

CORRIDOR

WORD

PROCESSING

WARDENS

TOILET

SWITCHGEAR/

ELECTRICAL

ROOM

BASEMENT

STAIR

WEAPONS

DISPENSING

DEPATMENTAL

SPECIALIST

OFFICE

CENTER

RECORDS

CORRIDOR

RECORDS

EAST

CORRIDOR

RECORDS

CAUSTIC EAST

ENTRY

VEST.

NORTH RECORDS

CORRIDOR

DEPUTY WARDEN

SUITE STORAGE

DEPARTMENTAL

TECHNICIAN

OFFICE

DEPUTY SUITE

COPY ROOM

PHONE

ROOM

INTEVIEW

ROOM 1697

CRITICAL TOOL

STORAGE

RUM OFFICE

H.I. OFFICE

GROUP ROOM

D

GROUP ROOM

C

GROUP ROOM

B

TELEMED

OFFICE

MENTAL HEALTH

SUPERVISER OFFICE

CLOSET

STORAGE

STORAGE

PORTER

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

MEETING

ROOM

OFFICE

OFFICE

OFFICE

PASSAGE

OFFICE

GROUP ROOM

#2

GROUP ROOM

#3

MED. STORAGE

MED. ROOM

GROUP ROOM

OFFICE

OFFICE

OFFICE

OFFICE

STORAGE

OFFICE

CLOSET

ELECTRICAL/

STORAGE

STORAGE

CAPT.

OFFICE

CLOSET

CAMERA ROOM

MONITOR

ROOM

SHIFT

COMMAND

VIDEO

RM. 1

VIDEO

RM. 2

NON-CONTACT

VISIT

CONTROL

CENTER

CONFERENCE

ROOM

IT ROOM

ARSENAL

A111B

RECORDS

COPY

ROOM

A111

RECORD

SUPERVISER

OFFICE

A113

WARDENS CONFRENCE

ROOM

A107

WARDENS

OFFICE

A105B

ADMINISTRATIVE

ASST. OFFICE

A110

RECORD

OFFICE

A18

TRANSPORTATION

OFFICE

A19

CONFERENCE

ROOM

A120

TRANSPORTATION

LOCKER RM

A121

IT/STORAGE

A122

STORAGE

A123

RECORD OFFICE

FILE ROOM

STORAGE

WEST VISITING

ROOM

STORAGE

INTERVIEW

A105C

VEST.

CAUSTIC

A108

WARDENS

SECRATARY

A125

MAIL

RM

DTMB

OFFICE

A112 I.T.

STORAGE

ARSENAL

ARSENAL

STORAGE

UPS-7

E-700

EXISTING 1000A

DOUBLE ENDED

SWITCHGEAR

NEW 1000A

CAMLOCK

CABINET

400A ATS

E-500

JJD

JFS

N WEST ADMINISTRATION BLDG - FLOOR PLAN - POWER

SCALE: 1/8" = 1'-0"

0 1 5 10 20

WEST ADMINISTRATION

FLOOR PLAN

POWER

C om m te ch

D es ig n

472/24059.SAA

file no.

checked by drawn by consultant issue date acctg template.

contract order no.

consultant job no.

sheet title

Y22432

C O

U R

TL

AN

D S

T.

, S

U

IT

E

R

O C

KF

O

R D

, M

IC

H

IG

AN

W W

W .C

O M

M

TE

C H

D

ES

IG

N

.C O

M

D

EP

A R

TM

EN

T O

F

TE

C H

N O

LO

G

Y , M

A N

A G

EM

EN

T A

N D

B U

D G

ET

ST

A

TE

O

F M

IC

H

IG

A

N

A D

A M

P . L

A C

H , R

A , D

IR

EC

TO

R

ST

A

TE

F

A C

IL

IT

IE

S

A D

M

IN

IS

TR

A

TI

O N

D

ES

IG

N

A N

D C

O N

ST

R

U C

TI

O

N D

IV

IS

IO

N

M a t r ix

06/11/26 ISSUED FOR BID

1065_24B

472/24059.SAA

472WHVMaintproj

Y22432

PANEL

EXISTING

LP-J

100A, 3P100A, 3P200A, 3P

PANEL

EXISTING

LP-EM

300A, 3P400A, 3P

PANEL

EXISTING

LP-A

WEST ADMIN. SWITCHGEAR - 1600A RATED 120/208VAC,

3Ø, 4W

200A, 3P

400A OPEN

TRANSITION

AUTOMATIC

TRANSFER

SWITCH

PANEL

NEW

K 120/208V 3Ø, 4W

400A, MLO

60KVA UPS

PANEL

NEW

UPS-B

120/208V 3Ø, 4W

225A, MLO

EXISTING TRANSFORMER

300KVA, 208Y/120V, 3Ø, 4W

FROM EAST ADMIN.

BUILDING SWITCHGEAR

EXISTING TRANSFORMER

300KVA, 208Y/120V, 3Ø, 4W

FROM MAIN 4800V

SWITCHGEAR

PANEL

EXISTING

XRAY

EATON UPS

PANEL

EX…

This is the start of the file's text. The full file is on GovTribe.