472_24059.SAA - WHV VMS Genetec Phase 2 Cameras - Drawings Part 1 of 3.pdf
PDF 3 MB Posted
- Solicitation number
- RFQ 171 260000000347 3
- Issued by
- Washtenaw County, Michigan
About this file
This is a technical drawings document for a Video Management System (VMS) Genetec Phase 2 Cameras project in Michigan, specifically related to contract 472/24059.SAA for the Whitehall Village Center Facility (WHVCF). The document constitutes Part 1 of 3 drawings and contains architectural and technical specifications for the camera installation system. The drawings provide detailed layouts and installation requirements for the Genetec Phase 2 camera system, which represents the second phase of a video surveillance infrastructure upgrade at the facility. The document establishes the physical specifications and spatial requirements necessary for bidders to understand the scope of equipment installation and integration.
The technical drawings serve as the basis for vendors to develop accurate bids for supplying and installing the specified Genetec Phase 2 camera system and related VMS infrastructure. These drawings are critical for ensuring that all bidders understand the exact installation locations, mounting requirements, cable routing, and integration points within the existing facility infrastructure. The multi-part drawing series (Part 1 of 3) indicates a comprehensive system design requiring detailed technical documentation across multiple document sections to capture all aspects of the camera placement and system architecture.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATE OF MICHIGAN
WOMEN'S HURON VALLEY CORRECTIONAL FACILITY
VMS GENETEC PHASE 2 CAMERAS
FILE NUMBER: 472/24059.SAA
SECURITY DESIGN
COMMTECH DESIGN
6585 BELDING RD. NE, SUITE B
ROCKFORD, MI 49341
(616) 863-8132
3201 BEMIS RD, YPSILANTI, MI 48197
WOMEN'S HURON VALLEY CORRECTIONAL FACILITY
SECURITY DRAWING INDEX
DRAWING LIST:
TC101 WHV SECURITY LEGENDS, DETAILS AND SCHEDULES
TC102 WHV CABLING AND SECURITY MOUNTING DETAILS
TC103 WHV CABLING AND CAMERA DETAILS
TC104 WHV SECURITY MOUNTING DETAILS
TC105 WHV NEW CAMERA ON POLE, SURGE PROTECTION & A.V. DETAILS
TC106 WHV MDOC CONDUIT STANDARDS
TC107 WHV LCD DISPLAY AND SURFACE RACEWAY DETAILS
TC108 WHV FIBER BACKBONE AND CONNECTIVITY
TC109 WHV RACK LAYOUTS
TC110 WHV RACK LAYOUTS
TC111 WHV RACK LAYOUTS
TC112 WHV RACK LAYOUTS
TC113 WHV RACK LAYOUTS
TC114 WHV RACK LAYOUTS AND FIBER DETAILS
TC115 WHV WEST ADMIN CORE DESIGN
TC116 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC117 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC118 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC119 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC120 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC121 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC122 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC123 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC124 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC125 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC126 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC127 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC128 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC129 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC130 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC131 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC132 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC133 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC134 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC135 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC136 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC137 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC138 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC139 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC140 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC141 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC142 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC143 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC144 WHV SECURITY CAMERA ONE LINE DIAGRAMS
TC145 WHV SECURITY CAMERA ONE LINE DIAGRAMS - PERIMETER
TC146 WHV SECURITY CAMERA ONE LINE DIAGRAMS - PERIMETER
TC147 WHV SECURITY CAMERA ONE LINE DIAGRAMS - PERIMETER
TC148 WHV SECURITY CAMERA ONE LINE DIAGRAMS - PERIMETER & PASS THRU DETAILS
TC300 WHV WEST ADMINISTRATION BLDG. - NEW & ADDITIONAL
TC301 WHV WEST FOOD SERVICE - NEW & ADDITIONAL
TC302 WHV WEST PRISONER SERVICES - FIRST & SECOND FLOORS - NEW & ADDITIONAL
TC303 WHV WEST PROGRAMS BLDG. - FIRST FLOOR - AREA A - NEW & ADDITIONAL
TC304 WHV WEST PROGRAMS BLDG. - FIRST FLOOR - AREA B & BASEMENT - NEW & ADDITIONAL
TC305 WHV WEST FIELD HOUSE - NEW & ADDITIONAL
TC306 WHV WEST MAINTENANCE - NEW & ADDITIONAL
TC307 WHV WEST HOUSING UNIT 1 - LOWER LEVEL - NEW & ADDITIONAL
TC308 WHV WEST HOUSING UNIT 1 - MAIN LEVEL - NEW & ADDITIONAL
TC309 WHV WEST HOUSING UNIT 2 - LOWER LEVEL - NEW & ADDITIONAL
TC310 WHV WEST HOUSING UNIT 2 - MAIN LEVEL - NEW & ADDITIONAL
TC311 WHV WEST HOUSING UNIT 3 - LOWER LEVEL - NEW & ADDITIONAL
TC312 WHV WEST HOUSING UNIT 3 - MAIN LEVEL - NEW & ADDITIONAL
TC313 WHV WEST HOUSING UNIT 4 - LOWER LEVEL - NEW & ADDITIONAL
TC314 WHV WEST HOUSING UNIT 4 - MAIN LEVEL - NEW & ADDITIONAL
TC315 WHV WEST HOUSING UNIT 5 - LOWER LEVEL - NEW & ADDITIONAL
TC316 WHV WEST HOUSING UNIT 5 - MAIN LEVEL - NEW & ADDITIONAL
TC317 WHV EAST POWER PLANT - BASEMENT & GROUND FLOORS - NEW & ADDITIONAL
TC318 WHV EAST RGC - LOWER LEVEL - NEW & ADDITIONAL
TC319 WHV EAST RGC - UPPER LEVEL & RGC MODULAR UNIT - NEW & ADDITIONAL
TC320 WHV EAST MSI BUILDING NEW & ADDITIONAL
TC321 WHV EAST ADMIN. - FIRST FLOOR AREA A - NEW & ADDITIONAL
TC322 WHV EAST ADMIN. - FIRST FLOOR AREAS B & C - NEW & ADDITIONAL
TC323 WHV EAST ADMIN. - SECOND FLOOR - NEW & ADDITIONAL
TC324A WHV EAST CALHOUN HALL - FIRST FLOOR AREAS A & B - NEW & ADDITIONAL
TC324B WHV EAST CALHOUN HALL - ATTIC AREAS A & B - NEW & ADDITIONAL
TC325A WHV EAST DICKINSON HALL - FIRST FLOOR AREAS A & B - NEW & ADDITIONAL
TC326B WHV EAST DICKINSON HALL - SECOND FLOOR A & B - NEW & ADDITIONAL
TC326C WHV EAST DICKINSON HALL - ATTIC AREAS A & B - NEW & ADDITIONAL
TC327A WHV EAST EMMETT HALL - FIRST & SECOND FLOORS - NEW & ADDITIONAL
TC327B WHV EAST EMMETT HALL - ATTIC - NEW & ADDITIONAL
TC328A WHV EAST FILMORE HALL - FIRST & SECOND FLOORS - NEW & ADDITIONAL
TC328B WHV EAST FILMORE HALL - ATTIC - NEW & ADDITIONAL
TC329A WHV EAST GLADWIN HALL - FIRST & SECOND FLOORS - NEW & ADDITIONAL
TC329B WHV EAST GLADWIN HALL - ATTIC - NEW & ADDITIONAL
TC330A WHV EAST HARRISON HALL - FIRST & SECOND FLOORS - NEW & ADDITIONAL
TC330B WHV EAST HARRISON HALL - ATTIC - NEW & ADDITIONAL
TC331 WHV EAST JENNINGS HALL - IRST & SECOND FLOORS AREA A - NEW & ADDITIONAL
TC332 WHV EAST JENNINGS HALL - FIRST FLOOR AREA B - NEW & ADDITIONAL
TC333 WHV EAST KENT HALL - FIRST FLOOR NEW & ADDITIONAL
TC334 WHV EAST KENT HALL - SECOND FLOOR NEW & ADDITIONAL
TC335 WHV WEST SIDE SITE PLAN - NEW & ADDITIONAL
TC336 WHV EAST SIDE SITE PLAN - NEW & ADDITIONAL
TC337 WHV SITE PLAN - TUNNEL LAYOUT - CAMERAS TO REMAIN
ELECTRICAL ENGINEER
MATRIX CONSULTING ENGINEERS, INC.
1601 E CESAR E. CHAVEZ AVENUE
LANSING, MI 48906
(517) 487-2511
ELECTRICAL & MECHANICAL
DRAWING INDEX
DRAWING LIST:
M-100 MECHANICAL SYMBOLS, NOTES, ABBREVIATIONS, AND SCHEDULES
M-300 PARTIAL FIRST FLOOR PLAN WEST ADMINISTRATION BLDG - MECHANICAL/PIPING DEMOLITION
M-400 PARTIAL FIRST FLOOR PLAN WEST ADMINISTRATION BLDG - MECHANICAL/PIPING NEW
E-100 WHV ELECTRICAL SYMBOLS, ABBREV & NOTES
E-200 WHV- WEST - SITE PLAN - ELECTRICAL
E-201 WHV EAST - SITE PLAN - ELECTRICAL
E-500 WEST ADMINISTRATION FLOOR PLAN - POWER
E-600 ELECTRICAL RISER DIAGRAM + PANEL SCHEDULES
E-700 ELECTRICAL ENLARGEMENTS WEST ADMINISTRATION
E-800 ELECTRICAL DETAILS
E-801 ELECTRICAL DETAILS
TITLE
C om m te ch
D es ig n
B
EL
D
IN
G R
O
AD
N E.
, S U
IT
E
B R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M a t r ix
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
472/24059.SAA
AutoCAD SHX Text file no.
AutoCAD SHX Text checked by
AutoCAD SHX Text drawn by
AutoCAD SHX Text consultant
AutoCAD SHX Text issue date
AutoCAD SHX Text acctg template.
AutoCAD SHX Text contract order no.
AutoCAD SHX Text 472WHVMaintproj
AutoCAD SHX Text consultant job no.
AutoCAD SHX Text 1065_24B
AutoCAD SHX Text sheet title
AutoCAD SHX Text
VIDEO SECURITY FLOOR PLANS
AutoCAD SHX Text
VMS GENETEC PHASE 2 CAMERAS
AutoCAD SHX Text
WOMEN'S HURON VALLEY CORRECTIONAL FACILITY
AutoCAD SHX Text
YPSILANTI ,MICHIGAN
AutoCAD SHX Text Y22432
AutoCAD SHX Text
VIDEO SECURITY UPGRADES
AutoCAD SHX Text P
AutoCAD SHX Text L
AutoCAD SHX Text U
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text B
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text N
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text C
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text C
AutoCAD SHX Text U
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text I
AutoCAD SHX Text C
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text Q
AutoCAD SHX Text U
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text E
AutoCAD SHX Text I
AutoCAD SHX Text S
AutoCAD SHX Text P
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text L
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text O
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text 06/11/26
AutoCAD SHX Text
ISSUED FOR BID
AutoCAD SHX Text
CONSULTING ENGINEERS, INC
AutoCAD SHX Text
FAX: 517.487.2544
AutoCAD SHX Text
PHONE: 517.487.2511
AutoCAD SHX Text
LANSING, MI 48917
AutoCAD SHX Text
544 CHERBOURG DRIVE
AutoCAD SHX Text
MATRIX PROJECT:
AutoCAD SHX Text WEB: www.matrixceinc.com
GENERAL HVAC NOTES
1. ALL WORK SHALL CONFORM TO MICHIGAN MECHANICAL CODE,
LATEST APPLICABLE EDITION.
2. INSTALL ALL EQUIPMENT, MATERIALS, AND ACCESSORIES PER
MANUFACTURERS WRITTEN INSTRUCTIONS.
3. BOTTOM OF EQUIPMENT ON ROOF SHALL BE A MINIMUM OF 18"
ABOVE ROOF MEMBRANE. CONTRACTOR SHALL COORDINATE
ASSOCIATED ROOF CURB HEIGHT AS REQUIRED.
4. NOTIFY OWNER OF ANY PIPING OR DUCTWORK DEMOLITION
THAT MAY AFFECT NORMAL OPERATION OF OTHER AREAS.
5. FIELD VERIFY LOCATIONS OF EXISTING PIPING THAT MAY
CONFLICT WITH NEW CONSTRUCTION AND RELOCATE AS
NEEDED.
6. LOCATIONS OF THE THERMOSTATS TO BE VERIFIED IN FIELD.
7. SMOKE DETECTORS SHALL BE FURNISHED AND CONNECTED
BY ELECTRICAL CONTRACTOR, INSTALLATION BY MECHANICAL
CONTRACTOR.
8. CONTRACTOR SHALL COORDINATE ALL WORK WITH OTHER
DISCIPLINES PRIOR TO CONSTRUCTION TO AVOID CONFLICTS.
9. OFFSET PIPING TO ACCOMMODATE LARGE DUCTWORK.
10. THE CONTRACTOR SHALL FIELD VERIFY THE SIZES, LOCATION,
ELEVATIONS, AND DETAILS OF ALL EXISTING CONDITIONS THAT
MAY AFFECT THE WORK.
11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING
THE INTEGRITY OF ALL EQUIPMENT AND MATERIALS IN A "NEW"
CONDITION DURING CONSTRUCTION.
12. ALL WORK SHALL BE PERFORMED BY LICENSED
CONTRACTORS AND SUBCONTRACTORS AS REQUIRED BY LAW.
13. ALL CONDENSATE DRAIN PIPING SET @ MIN. 1% SLOPE.
14. ALL CONDENSATE DRAIN PIPING TO TERMINATE TO DRAIN VIA
AIR GAP.
15. IF THERE IS CONFLICTING INFORMATION IN THE PLANS OR
SPECIFICATIONS THE MORE STRINGENT AND GREATER COST
ITEM SHALL BE USED.
16. DRAWINGS INDICATE REQUIRED SIZES AND POINTS OF
TERMINATION OF PIPES AND DUCTS AND SUGGESTED ROUTES.
IT IS NOT INTENTION OF DRAWINGS TO INDICATE ALL
NECESSARY OFFSETS. INSTALL WORK IN MANNER TO
CONFORM TO STRUCTURE, AVOID OBSTRUCTIONS, PRESERVE
HEADROOM AND KEEP OPENINGS AND PASSAGEWAYS CLEAR.
DO NOT SCALE FROM DRAWINGS.
17. ANY INFORMATION FOUND ON THE DRAWINGS AND NOT IN THE
SPECIFICATIONS, OR FOUND IN SPECIFICATIONS AND NOT IN
THE DRAWINGS, SHALL BE CONSTRUED AS TO BE INCLUDED IN
BOTH THE SPECIFICATIONS AND THE DRAWINGS. ANY
CONFLICT BETWEEN THE PLANS AND THE SPECIFICATIONS
WILL BE INTERPRETED BY THE ARCHITECT. IN THE EVENT OF
CONFLICT, FOR THE PURPOSE OF BIDDING, THE CONTRACTOR
SHALL PRESUME THE MOST EXPENSIVE COMBINATION OF
QUALITY AND QUANTITY OF WORK SHALL PREVAIL.
18. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS,
REVISIONS, AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE
STATUTES, ORDINANCES, CODES OR REGULATIONS OF
FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING
JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
19. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY
OSHA, UNDERWRITERS, LABORATORIES, AMERICAN CODES,
ASA, ASHRAE, ARI, NEC, STATE FIRE INSURANCE REGULATION
BODY, NFPA OR OTHERS, THESE STANDARDS SHALL BE
FOLLOWED WHETHER OR NOT INDICATED ON THE DRAWING
AND SPECIFICATIONS.
20. DUCT/PIPING LAYOUT IS SCHEMATIC. EXACT LOCATION OF
DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH
BUILDING STRUCTURE, EQUIPMENT FURNISHED,
ARCHITECTURAL DRAWINGS, AND ALL OTHER TRADES PRIOR
TO INSTALLATION. ANY CONTRACTOR INSTALLING WORK
WITHOUT PRIOR COORDINATION SHALL RELOCATE HIS WORK
AT HIS EXPENSE TO ALLOW PROPER INSTALLATION OF ANY
AND ALL TRADES WORK.
21. UNLESS OTHERWISE NOTED, ALL DUCT/PIPING SHALL BE
CONCEALED WHEREVER POSSIBLE. PROVIDE CHROME
ESCUTCHEON OR ALUMINUM DUCT COLLAR AT EACH
PENETRATION OF A FINISHED SURFACE.
22. DUCT/PIPING SHALL NOT BE RUN ABOVE ELECTRICAL GEAR IN
THE SERVICE SPACE REQUIRED BY THE NATIONAL ELECTRICAL
CODE.
23. ANY ADDITIONAL LOW VOLTAGE CONTROL WIRING THAT IS
REQUIRED SHALL BE PROVIDED BY THE HVAC CONTRACTOR.
CONTROL WIRING SHALL BE RUN IN CONDUIT IF REQUIRED BY
LOCAL CODES OR THE SPECIFICATIONS. POWER SHALL BE
PROVIDED BY THE ELECTRICAL CONTRACTOR.
24. PROVIDE TRAP FOR CONDENSATION DRAIN LINES.
25. PROVIDE VIBRATION ISOLATION AT EACH CONNECTION TO A
MOTORIZED PIECE OF EQUIPMENT BY THE HVAC
CONTRACTOR.
26. MOUNT THERMOSTAT/SENSORS AT 48" AFF UNLESS NOTED
OTHERWISE.
27. THE HVAC CONTRACTOR SHALL CLOSELY COORDINATE AIR
DEVICE AND DUCTWORK LOCATIONS WITH REFLECTED CEILING
PLANS.
21. ALL FASTENERS USED IN AREAS EXPOSED TO INMATES SHALL
USE TAMPERPROOF SCREWS.
22. CONTRACTOR TO ATTEND A 6 MONTH AND AN 11 MONTH POST
CONSTRUCTION MEETING WITH THE ENGINEER AND OWNER
TO REVIEW AND FIX ISSUES DURING THE WARRANTY PERIOD.
23. CONTRACTOR TO TRACK AND PROVIDE PAPERWORK TO
OWNER OF THE AMOUNT OF MATERIAL BEING RECYCLED
THROUGHOUT THE PROJECT.
24. CONTRACTOR TO PATCH EXISTING ROOF AS REQUIRED TO
MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN EXISTING
WARRANTIES WHERE DEMOLITION AND/OR NEW WORK IS
COMPLETED.
25. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING
WALLS/CEILINGS AS REQUIRED TO MATCH EXISTING WHERE
DEMOLITION AND/OR NEW WORK IS COMPLETED.
26. CONTRACTOR TO NOTIFY THE FACILITY AT LEAST 1 DAY IN
ADVANCE FOR ANY HOT WORK TO ALLOW THE OWNER TO
DISABLE THE FIRE ALARM.
27. CONTRACTOR TO REFER TO ALL ELECTRICAL CONSTRUCTION
DOCUMENTS AND DIVISION 26 SPECIFICATIONS FOR CONTROL
WIRING RACEWAYS. ALL CONTROL WIRING RACEWAYS ARE TO
MEET MDOC REQUIREMENTS.
28. CONTRACTOR TO CONNECT ALL NEW EQUIPMENT TO THE
EXISTING BASS DDC CONTROL SYSTEM. CONTRACTOR TO
PROVIDE ALL REQUIRED CONTROLS, CONTROL WIRING, AND
EQUIPMENT/ACCESSORIES NEEDED TO CONNECT NEW
EQUIPMENT TO THE EXISTING BASS DDC CONTROL PANEL AND
INTEGRATE THE NEW EQUIPMENT ONTO THE EXISTING
FRONT-END GRAPHICS.
29. CONTRACTOR TO PROVIDE AND INSTALL NEW CEILING TILES
(SAME MAKE/MODEL AS THE EXISTING CEILING TILES) AS
REQUIRED TO ENSURE A COMPLETED LAY-IN CEILING SYSTEM
AFTER ALL DEMOLITION/NEW WORK IS COMPETED.
MECHANICAL SYMBOLS LEGEND
HVAC PIPING SYMBOLSHVAC PIPING
HVAC DUCTWORK
F/S
F/S s s
TEMPERATURE CONTROL SYMBOLS
MISCELLANEOUS NOTES
HVAC DUCTWORK SYMBOLS HVAC DUCTWORK & DIFFUSER TAGS HVAC PIPING VALVES
MECHANICAL ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AC AIR COMPRESSOR
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
A.T.C. ARCHITECTURAL TRADES CONTRACTOR
B BOILER
B.A.S. BUILDING AUTOMATION SYSTEM
CAF COMBUSTION AIR FAN
CC COOLING COIL
CFM CUBIC FEET PER MINUTE
CHLR CHILLER
CHP CONSOLE HEAT PUMP
CONV CONVECTOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
CWP CHILLED WATER PUMP
DB DRY BULB
DFU DUCT FURNACE
DIA DIAMETER
DN DOWN
DPR DAMPER
DS DUCT SILENCER
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
E.T.C. ELECTRICAL TRADES CONTRACTOR
EVR EVAPORATOR
EWT ENTERING WATER TEMPERATURE
EXH EXHAUST
EXIST EXISTING
FF FINISH FLOOR
FPM FEET PER MINUTE
FT FEET
FTR FINNED TUBE RADIATION
FU FURNACE
GAL GALLON
GFRH GAS FIRED RADIANT HEATER
GR GRILLE
H HUMIDIFIER
HC HEATING COIL
HD HEAD (FT)
HP HORSE POWER
HHP HORIZONTAL HEAT PUMP
HTG HEATING
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWP HEATING WATER PUMP
HX HEAT EXCHANGER
ID INSIDE DIAMETER
I.E. INVERT ELEVATION
IAH INTAKE HOOD
LAT LEAVING AIR TEMPERATURE
LH LATENT HEAT (MBH)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH BTU PER HOUR (THOUSAND)
MIN MINIMUM
M.T.C. MECHANICAL TRADES CONTRACTOR
N.C. NOISE CRITERIA
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NTS NOT TO SCALE
P PUMP
PCR PUMPED CONDENSATE RETURN
PD PRESSURE DROP
RCP RADIANT CEILING PANEL
REQ'D REQUIRED
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RLH RELIEF HOOD
RTU ROOF TOP UNIT
SD SUPPLY DIFFUSER
SF SUPPLY FAN
SG SUPPLY GRILLE
SH SENSIBLE HEAT (MBH)
SM SHEET METAL
SQ. FT. SQUARE FEET
SST SATURATED SUCTION TEMPERATURE
STR STRAINER
TC TOTAL COOLING (MBH)
TCL TEMPERATURE CONTROL
T&P TEMPERATURE & PRESSURE RELIEF VALVE
TYP TYPICAL
UH UNIT HEATER
VAV VARIABLE AIR VOLUME BOX
VRH VARIABLE AIR VOLUME REHEAT BOX
FPVAV FAN POWERED VARIABLE AIR VOLUME BOX
V.F.D VARIABLE FREQUENCY DRIVE
ZD ZONE DAMPER
X-SA EXISTING ITEM (EXISTING SUPPLY AIR DUCT)
ITEM
EXISTING
CHILLED WATER SUPPLY
CHILLED WATER RETURN
CONDENSATE DRAIN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
COOLING TOWER WATER SUPPLY
COOLING TOWER WATER RETURN
DIRECT EXPANSION
HEAT PUMP WATER SUPPLY
HEAT PUMP WATER RETURN
HEATING WATER SUPPLY
HEATING WATER RETURN
SUCTION (REFRIGERANT)
LIQUID (REFRIGERANT)
SUCTION (DIRECT EXPANSION)
LIQUID (DIRECT EXPANSION)
LOW PRESSURE STEAM (0-20 LBS.)
MEDIUM PRESSURE STEAM (21-75 LBS.)
HIGH PRESSURE STEAM (76 LBS. & ABV.)
STEAM CONDENSATE (GRAVITY)
PUMPED STEAM CONDENSATE
STEAM CONDENSATE BOILER FEED
GATE VALVE
GAS COCK
CHECK VALVE
BALANCE COCK
CIRCUIT SETTER
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
GLOBE VALVE
BALL VALVE
SOLENOID VALVE
EXPANSION VALVE WITH
THERMOSTATIC BULB
PLUG VALVE
BUTTERFLY VALVE
RELIEF VALVE
HOSE & DRAIN END VALVE
PRESSURE RELIEF VALVE
PRESSURE REDUCING VALVE
TRIPLE DUTY VALVE
GAS PRESSURE REGULATOR
STRAINER (BLOW-OFF)
FLOW DIRECTION
PIPING DROP
PIPING RISE
INLINE PIPING DROP
INLINE PIPING RISE
PIPING TEE
PIPING ELBOW
THERMOMETER
PUMP
UNION
PIPE ANCHOR
PIPE GUIDE
BACK FLOW PREVENTER
PIPE CAP
PIPE BREAK
THERMOMETER WELL
EXPANSION LOOP
EXPANSION COMPENSATOR
FLOAT & THERMOSTATIC STEAM TRAP
INVERTED BUCKET STEAM TRAP
THERMOSTAT
PROGRAMMABLE THERMOSTAT
THERMOSTAT (W/ NIGHT SETBACK)
ROOM SENSOR
HUMIDISTAT
PRESSURE GAUGE
DAMPER (ELECTRIC OPERATION)
DAMPER (PNEUMATIC OPERATION)
DAMPER BLADES
SUPPLY AIR DUCT
EXIST SUPPLY AIR DUCT
RETURN AIR DUCT
EXIST RETURN AIR DUCT
OUTSIDE AIR DUCT
EXIST OUTSIDE AIR DUCT
EXHAUST AIR DUCT
EXIST EXHAUST AIR DUCT
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
OUTSIDE AIR DUCT RISER (AS NOTED)
EXHAUST AIR DUCT
INSULATED DUCTWORK (AS NOTED)
SUPPLY AIR DIFFUSER (SQUARE)
SUPPLY AIR DIFFUSER (INLINE)
TURNING VANES
SURFACE MTD. GRILLE
SUPPLY AIR DIFFUSER (ROUND)
90° TEE W/45° APPROACH
CONICAL TAKE-OFF
CONICAL TAKE-OFF W/ DAMPER
BALANCE DAMPER
RETURN AIR DUCT BOOT
ECCENTRIC REDUCER
CONCENTRIC REDUCER
VERTICAL FIRE DAMPER
EXISTING VERTICAL FIRE DAMPER
HORIZONTAL FIRE DAMPER
EXISTING HORIZONTAL FIRE DAMPER
VERTICAL SMOKE DAMPER
HORIZONTAL SMOKE DAMPER
VERTICAL FIRE / SMOKE DAMPER
HORIZONTAL FIRE / SMOKE DAMPER
DUCT SMOKE DETECTOR, INSTALLED BY M.T.C.,
PROVIDED & WIRED BY E.T.C.
UNIT HEATER
CEILING EXHAUST FAN
ROOF MOUNTED EXHAUST FAN
DEMOLITION
POINT OF CONNECTION BETWEEN NEW AND
EXISTING
POINT OF EXISTING TO REMAIN AND EXISTING
TO BE REMOVED
INDICATES PLAN NOTE
INDICATES DEMOLITION NOTE
DETAIL BUBBLE
DETAIL NUMBER
PAGE LOCATION INDICATES
DIRECTION OF DETAIL SECTION
X
X
XX
XXXX
XX
XXXX
SA
OA
X-OA
X-EA
EA
X-SA
X-RA
RA
SCP
SC
DXS
DXL
HR
CR
CD
CS
DX
CTR
HPR
HS
HPS
CTS
CWR
CWS
S
L
LPS
MPS
HPS
SC (BF)
TAG CFM
NECK REMARKS
SIZE
BT
FT
SD-1 250
8"ø ---
P
H
S
T
T P
T N
M
M
SD
1. EXISTING EQUIPMENT LAYOUT IS SCHEMATIC. EXACT LOCATION OF EXISTING
DUCT/PIPING AND EQUIPMENT SHALL BE COORDINATED WITH BUILDING
STRUCTURE, EQUIPMENT FURNISHED, ARCHITECTURAL DRAWINGS AND ALL
OTHER TRADES PRIOR TO DEMOLITION.
2. PERFORM WORK IN ACCORDANCE WITH THE LATEST EDITIONS, REVISIONS,
AMENDMENTS, OR SUPPLEMENTS OF APPLICABLE STATUTES, ORDINANCES,
CODES OR REGULATIONS OF FEDERAL, STATE, AND LOCAL AUTHORITIES
HAVING JURISDICTION IN EFFECT ON THE DATE BIDS ARE RECEIVED.
3. WHERE APPROVED STANDARDS HAVE BEEN ESTABLISHED BY OSHA,
UNDERWRITERS LABORATORIES, AMERICAN CODES, ASA, ASHRAE, ARI, NEC,
STATE FIRE INSURANCE REGULATION BODY, NFPA OR OTHERS. THESE
STANDARDS SHALL BE FOLLOWED WHETHER OR NOT INDICATED ON THE
DRAWING AND SPECIFICATIONS.
4. COORDINATE CUTTING AND PATCHING WITH GENERAL CONTRACTOR.
5. ALL BOLD DASHED LINES INDICATE ITEMS TO BE REMOVED UNLESS NOTED BY
KEYNOTE. ALL OTHER EXISTING SYSTEMS SHOWN FOR REFERENCE ONLY.
6. PATCH AND REPAIR ALL FLOOR AND WALL SURFACES LEFT DAMAGED OR
INCOMPLETE FROM REMOVAL OF EXISTING PARTITIONS, MILLWORK,
CASEWORK, OR OTHER FIXED ACCESSORIES AND EQUIPMENT WITH
MATERIALS TO MATCH EXISTING, AS ACCEPTABLE TO THE OWNER.
7. NOTATIONS ARE MADE IN VARIOUS PLACES ON THE DRAWINGS TO CALL
ATTENTION TO DEMOLITION WHICH IS REQUIRED. HOWEVER, THESE
DRAWINGS ARE NOT INTENDED TO SHOW EACH AND EVERY ITEM TO BE
REMOVED. CONTRACTOR SHALL REMOVE ALL MATERIALS RELATED TO THEIR
RESPECTIVE TRADES AS REQUIRED TO PERMIT THE CONSTRUCTION OF THE
NEW WORK AS SHOWN.
8. THE GENERAL CONTRACTOR SHALL COORDINATE THE EXTENT OF THE
REQUIRED DEMOLITION OF THE EXISTING BUILDING AS REQUIRED TO
FACILITATE THE CONSTRUCTION OF THE PROJECT AS SHOWN AS PART OF
THIS WORK.
9. ALL DEMOLITION SHALL BE APPROVED BY THE OWNER/TENANT PRIOR TO
COMMENCEMENT AND SHALL BE PERFORMED UNDER REQUIREMENTS AND
APPROVAL OF THE LOCAL CODE JURISDICTIONS.
10. PROTECT ALL EXISTING WORK WHICH IS TO REMAIN AND RESTORE IN AN
APPROVED MANNER ANY SUCH WORK WHICH BECOMES DAMAGED.
11. RUBBISH AND DEBRIS RESULTING FROM THE WORK SHALL BE REMOVED
IMMEDIATELY FROM THE SITE IN A SAFE AND LEGAL MANNER BY THE
CONTRACTOR.
12. DEMOLITION CONTRACTOR SHALL BE RESPONSIBLE TO CONTACT BUILDING
REPRESENTATIVE TO CLARIFY ANY ITEMS NOT SHOWN ON THESE
DOCUMENTS OR SHOWN NOT MATCHING FIELD CONDITIONS.
GENERAL DEMOLITION NOTES
9"x15.25" POLYCARBONATE
ROOF MOUNTING PADS
12 GA. HOT DIPPED
GALVANIZED STRUT
12 GA. HOT DIPPED
GALVANIZED STRUT NOTES:
1. ROOF MOUNTED EQUIPMENT STAND BASED ON
MIRO-HD(R) OR APPROVED EQUIVALENT.
2. CONTRACTOR TO COORDINATE WITH SIZE OF HEAT
PUMP PRIOR TO ORDERING EQUIPMENT STAND TO
ENSURE PROPER FITMENT.
3. CONTRACTOR TO MOUNT HEAT PUMP TO ADJUSTABLE
FRAME RAILS WITH TAMPERPROOF CORROSION
RESISTANT HARDWARE.
4. CONTRACTOR TO ENSURE THE BOTTOM OF THE HEAT
PUMP IS AT LEAST 18" ABOVE THE ROOF.
1 ROOF MOUNTED HEAT PUMP STAND DETAIL
SCALE: NTS
2 INSULATION HANGER DETAIL
SCALE: NTS
14 GAUGE ZINC
COATED SHEET
STEEL SADDLE, AT
LEAST 12" LONG
PIPE
INSULATION
THERMAL HANGERS
SHIELD INSERTS
(360-DEG)
C om m te ch
D es ig n
472/24059.SAA
file no.
checked by drawn by consultant issue date acctg template.
contract order no.
consultant job no.
sheet title
Y22432
C O
U R
TL
AN
D S
T.
, S
U
IT
E
R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M a t r ix
06/11/26 ISSUED FOR BID
1065_24B
472/24059.SAA
472WHVMaintproj
Y22432
VIDEO SECURITY
UPGRADES
M-100
MECHANICAL SYMBOLS,
NOTES, ABBREVIATIONS,
AND SCHEDULES
CAT
DBP
T
X-SD ---
X-SD ---
X-SD ---
X-RG ---
24x24 ---
X-RG ---
24x12 ---
X-AC
X-CU
(ON ROOF)
X-AC
X-RG ---
24x24 ---
M
M
X-AC-4
X-AC-3
X-SA
X-SA
X-SA
X-SA
X-SA
X-SAX-SA
X-SAX-SA
X-SA
X-SA
X-SA
X-CU-3
(ON ROOF)
X-CU-4
(ON ROOF)
X-SD ---
X-SD ---
X-RA
X-AC
X-CU
(ON ROOF)
X-AC
X-CU
(ON ROOF)
X-AC
X-AC-4
X-AC-3
X-CU-3
(ON ROOF)
X-CU-4
(ON ROOF)
X-CU
(ON ROOF)
X-CD PUMP
X-CD PUMP
X-
CD
X-CD X-CD
X-CD
X-CD
X-CD
X-
CD
X-CW X-CW
X-
CW
X-
CW
X-
CW
X-CW
X-
CWX-
DX
X-
DX
X-DX
X-DX
X-DX
X-DX
X-FD
X-CD
X-
CD
X-
DX
X-
DX
X-
CD
X-
DX
X-
DX
X-CD
1 1
MECHANICAL DEMOLITION NOTES
DISCONNECT, REMOVE, AND DEMO EXISTING WALL MOUNTED AC UNIT, ROOF MOUNTED
CONDENSING UNIT, CONDENSING UNIT SUPPORTS, THERMOSTAT, CONTROLS,
CONTROLS WIRING, DX PIPING, CONDENSATE PIPING, VALVES, FITTINGS, AND ALL
ASSOCIATED ACCESSORIES IN THEIR ENTIRETY. CONTRACTOR TO PATCH, PRIME, AND
PAINTED EXISTING WALL AS REQUIRED WHERE THE WALL MOUNTED AC UNIT AND
THERMOSTAT ARE REMOVED TO MATCH EXISTING. CONTRACTOR TO MODIFY AND REUSE
THE EXISTING DX PIPING ROOF PENETRATIONS AS REQUIRED TO INSTALL NEW DX PIPING
SHOWN ON THE NEW DRAWINGS. CONTRACTOR TO PATCH ROOF AS REQUIRED TO
MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN ANY ROOF WARRANTIES.
EXISTING AC UNIT, CONTROLS, CONTROL WIRING, CONDENSATE PUMP, DX PIPING,
CONDENSATE PIPING, AND ALL ASSOCIATED ACCESSORIES TO REMAIN.
EXISTING ROOF MOUNTED CONDENSING UNITS, CONTROLS, CONTROL WIRING, DX
PIPING, AND ALL ASSOCIATED ACCESSORIES TO REMAIN.
DISCONNECT, REMOVE, AND DEMO EXISTING CONDENSATE PIPING, AND ALL
ASSOCIATED ACCESSORIES TO THE EXTENTS SHOWN. MODIFY EXISTING PIPING AS
REQUIRED TO INSTALL NEW CHECK VALVE SHOWN ON NEW DRAWINGS.
GENERAL DEMOLITION NOTES
1. CONTRACTOR TO REMOVE AND RE-INSTALL EXISTING CEILING GRID AND CEILING TILES
AS REQUIRED TO COMPLETE THEIR WORK. THE CONTRACTOR IS RESPONSIBLE FOR THE
REPLACEMENT OF BROKEN/DAMAGED CEILING TILES.
2. CONTRACTOR TO PATCH, PRIME, AND PAINT WALLS AS REQUIRED TO MATCH EXISTING
ONCE ALL DEMOLITION/NEW WORK IS COMPLETE.
3. ALL EXISTING EQUIPMENT, DUCTWORK, GRILLES/DIFFUSERS, CONTROLS, AND ALL
ASSOCIATED ACCESSORIES ARE TO REMAIN UNLESS OTHERWISE NOTED.
4. ALL EXISTING EQUIPMENT, PIPING, CONTROLS, AND ALL ASSOCIATED ACCESSORIES ARE
TO REMAIN UNLESS OTHERWISE NOTED.
5. CONTRACTOR TO PATCH EXISTING ROOF AS REQUIRED TO MATCH EXISTING, SEAL
WATERTIGHT, AND MAINTAIN EXISTING ROOF WARRANTIES ONCE ALL DEMOLITION/NEW
WORK IS COMPLETE.
C om m te ch
D es ig n
472/24059.SAA
file no.
checked by drawn by consultant issue date acctg template.
contract order no.
consultant job no.
sheet title
Y22432
C O
U R
TL
AN
D S
T.
, S
U
IT
E
R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M a t r ix
06/11/26 ISSUED FOR BID
1065_24B
472/24059.SAA
472WHVMaintproj
Y22432
VIDEO SECURITY
UPGRADES
M-300
PARTIAL FIRST FLOOR PLAN - WEST
ADMINISTRATION BUILDING -
MECHANICAL/PIPING DEMOLITION
N PARTIAL FIRST FLOOR PLAN - WEST ADMINISTRATION - MECHANICAL DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10
N PARTIAL FIRST FLOOR PLAN - WEST ADMINISTRATION - PIPING DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10
6/10/2026CD SET
X-SD ---
X-SD ---
X-SD ---
X-RG ---
24x24 ---
X-RG ---
24x12 ---
X-AC
X-RG ---
24x24 ---
M
M
X-AC-4
X-AC-3
X-SA
X-SA
X-SA
X-SA
X-SA
X-SAX-SA
X-SAX-SA
X-SA
X-SA
X-SA
X-CU-3
(ON ROOF)
X-CU-4
(ON ROOF)
X-SD ---
X-SD ---
X-RA
X-CU
(ON ROOF)
T
AC-7
HP-7
(ON ROOF)
AC-7
AC-5
CU-5
(ON ROOF)
RG-1 ---
24x24 ---
RG-1 ---
24x24 ---
RG-1 ---
24x24 ---
3 3
RG-1 ---
24x24 ---
AC-6
CU-6
(ON ROOF)
RG-1 ---
24x24 ---
RG-1 ---
24x24 ---
8 10
X-AC
X-AC-4
X-AC-3
X-CU-3
(ON ROOF)
X-CU-4
(ON ROOF)
X-CU
(ON ROOF)
AC-7
HP-7
(ON ROOF)
AC-5
CU-5
(ON ROOF)
AC-6
CU-6
(ON ROOF)
DX DX
PIPE
SUPPORTS
CD
CD
3/4"
3/4"
3/4" 3/4" CD
DN TO X-FD
CD PUMP
3/4"
CO
3/4"
PIPE
SUPPORTS
DX DX
CO
CD
CO
X-AC
X-AC-4
X-AC-3
X-CU-3
(ON ROOF)
X-CU-4
(ON ROOF)
X-CU
(ON ROOF)
X-CD PUMP
X-CD PUMP
X-
CD
X-CD X-CD
X-CD
X-CD
X-CD
X-
CD
X-CW X-CW
X-
CW
X-
CW
X-
CW
X-CW
X-
CWX-
DX
X-
DX
X-DX
X-DX
X-DX
X-DX
X-FD
X-CD
X-
CD
X-
DX
X-
DX
X-
CD
CD
CO
CD PUMP
CD
3/4"
3/4"5
BFP
3/4" CW DN
BFP
DX DX
PIPE
SUPPORTS
GENERAL MECHANICAL NOTES
1. CONTRACTOR TO PATCH, PRIME, AND PAINT EXISTING WALLS AS NEEDED TO
MATCH EXISTING WHERE DEMOLITION AND/OR NEW WORK IS COMPLETED. IF
MODIFICATIONS ARE MADE TO RATED WALLS, CONTRACTOR TO ENSURE
WALLS ARE PATCHED TO MATCH EXISTING AND MAINTAIN THE EXISTING
RATING.
2. CONTRACTOR IS TO REMOVE AND SALVAGE EXISTING CEILING TILES AS
REQUIRED TO INSTALL NEW RETURN GRILLES IN THE LOCATION SHOWN.
CONTRACTOR TO COORDINATE THE LOCATION OF THE NEW RETURN GRILLES
WITH THE EXISTING LIGHTS AND CEILING MOUNTED DEVICES. CONTRACTOR
TO UTILIZE SALVAGED CEILING TILES TO FILL CEILING GRID WHERE CEILING
TILES ARE CURRENTLY MISSING. CONTRACTOR TO PROVIDE ADDITIONAL
CEILING TILES (SAME COLOR/MODEL AS THE EXISTING) AS REQUIRED TO
ENSURE THAT THE ENTIRE CEILING GRID SYSTEM IS FILLED ONCE ALL
DEMOLITION/NEW WORK IS COMPETED.
3. CONTRACTOR IS TO REMOVE, SALVAGE, AND RE-INSTALL EXISTING CEILING
GRID AND CEILING TILES AS REQUIRED TO COMPLETE THEIR WORK.
CONTRACTOR IS RESPONSIBLE FOR REPLACING DAMAGED/BROKEN CEILING
TILES.
4. ALL NEW CONTROL WIRING, RACEWAYS, AND ALL ASSOCIATED ACCESSORIES
TO BE CONCEALED IN WALLS OR ABOVE CEILING SPACE. CONTRACTOR TO
CUT, PATCH, PRIME, AND PAINT WALLS AS NEEDED TO INSTALL CONCEALED
WIRING TO MATCH EXISTING.
5. INSTALL ALL NEW EQUIPMENT PER THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS. ENSURE ALL MANUFACTURER REQUIRED CLEARANCES ARE
MAINTAINED.
6. CONTRACTOR TO CONNECT ALL NEW EQUIPMENT TO THE EXISTING BASS DDC
CONTROL SYSTEM. CONTRACTOR TO PROVIDE ALL REQUIRED CONTROLS,
CONTROL WIRING, AND EQUIPMENT/ACCESSORIES NEEDED TO CONNECT
NEW EQUIPMENT TO THE EXISTING BASS DDC CONTROL PANEL AND
INTEGRATE THE NEW EQUIPMENT ONTO THE EXISTING FRONT-END GRAPHICS.
7. CONTRACTOR TO PATCH ALL ROOF PENETRATIONS/MODIFICATIONS AS
REQUIRED TO MATCH EXISTING, SEAL WATER TIGHT, AND MAINTAIN ANY
EXISTING ROOF WARRANTIES.
8. INSTALL 0.020" THICK ALUMINUM, STUCCO EMBOSSED JACKET AROUND ALL
EXPOSED, ROOF ROUTED REFRIGERANT PIPING.
MECHANICAL KEY NOTES
INSTALL NEW FLOOR MOUNTED AC UNIT, ROOF MOUNTED CONDENSING UNIT,
SUPPORTS, CONTROLS, CONTROL WIRING, FIELD INSTALLED CONDENSATE PUMP,
DX PIPING, CONDENSATE PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED
ACCESSORIES IN LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS. CONTRACTOR TO CONNECT NEW AC UNIT AND CONDENSING UNIT
TO THE EXISTING CONTROLS BASS DDC CONTROL PANEL. CONTRACTOR TO
PROVIDE AND INSTALL ALL REQUIRED CONTROLS AND CONTROLS
DEVICES/ACCESSORIES TO INTEGRATE THE NEW AC UNIT AND CONDENSING UNIT
ONTO THE EXISTING FRONT-END GRAPHICS. NEW ROOF MOUNTED CONDENSING
UNIT TO BE INSTALLED ON MANUFACTURER PROVIDED 36" TALL CONDENSER
LEGS.
INSTALL NEW WALL MOUNTED AC UNIT, ROOF MOUNTED HEAT PUMP, HANGERS,
SUPPORTS, THERMOSTAT, CONTROLS, CONTROL WIRING, DX PIPING,
CONDENSATE PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED ACCESSORIES IN
THE LOCATION SHOWN PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
CONTRACTOR TO CONNECT NEW WALL MOUNTED AC UNIT AND ROOF MOUNTED
HEAT PUMP TO EXISTING BASS DDC CONTROL PANEL. CONTRACTOR TO PROVIDE
AND INSTALL ALL REQUIRED CONTROLS AND CONTROLS DEVICES/ACCESSORIES
TO INTEGRATE THE NEW AC UNIT AND HEAT PUMP ONTO THE EXISTING
FRONT-END GRAPHICS. NEW ROOF MOUNTED HEAT PUMP TO BE INSTALLED ON
NEW CONTRACTOR PROVIDED ELEVATED EQUIPMENT STAND.
INSTALL NEW RETURN AIR GRILLE AND ALL ASSOCIATED ACCESSORIES IN THE
LOCATION SHOWN. CONTRACTOR TO COORDINATE THE LOCATION OF THE NEW
RETURN GRILLES WITH THE EXISTING LIGHTS AND CEILING MOUNTED DEVICES.
CONTRACTOR TO MODIFY EXISTING AC UNIT AND CONDENSING UNIT CONTROLS
AS REQUIRED TO OPERATE PER THE SEQUENCE OF OPERATIONS WITH THE
ADDITION OF AC-5/CU-5 & AC-6/CU-6 SERVING THE CAMERA ROOM SPACE.
CONTRACTOR TO PROVIDE ALL REQUIRED CONTROLS, CONTROL WIRING, AND ALL
ASSOCIATED ACCESSORIES AS NEEDED TO HAVE UNIT OPERATE PER THE
SEQUENCE OF OPERATIONS.
INSTALL NEW CONDENSATE PIPING, VALVES, FITTINGS, AND ALL ASSOCIATED
ACCESSORIES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
CONTRACTOR TO MAKE NEW ABOVE CEILING WALL PENETRATIONS AS REQUIRED
TO ROUTE NEW CONDENSATE PIPING. CONTRACTOR TO PATCH , PRIME, AND
PAINT EXISTING WALL AS REQUIRED TO MATCH EXISTING. CONTRACTOR TO
CONNECT NEW CONDENSATE PIPING TO EXISTING PIPING IN THE LOCATION
SHOWN. CONTRACTOR TO MODIFY EXISTING PIPING AS REQUIRED FOR NEW
CONNECTION.
SUPPORT REFRIGERANT PIPING ON ROOF WITH PIPE SUPPORTS BASED ON MIRO
#5-RAH-7 OR APPROVED EQUIVALENT. SPACE PIPING SUPPORTS PER
MANUFACTURER'S RECOMMENDATIONS. INSTALL PIPE SUPPORT PAD OR
MANUFACTURER APPROVED EQUIVALENT.
INSTALL NEW DOMESTIC COLD WATER PIPING, VALVES, FITTINGS, AND ALL
ASSOCIATED ACCESSORIES PER THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS. CONTRACTOR TO CONNECT NEW DOMESTIC COLD WATER PIPING
TO EXISTING PIPING IN THE LOCATION SHOWN. CONTRACTOR TO MODIFY
EXISTING PIPING AS REQUIRED FOR NEW CONNECTION.
INSTALL NEW DOUBLE DEFLECTION SUPPLY AIR DIFFUSER (TITUS 272RL OR
APPROVED EQUAL) ON FRONT/BOTTOM DISCHARGE OF THE AC UNIT. OPENING
FOR NEW SUPPLY AIR DIFFUSER IS APPROXIMATELY 26.75" WIDE x 10.75" TALL.
INSTALL NEW DX PIPING, HANGER, SUPPORTS, AND ALL ASSOCIATED
ACCESSORIES PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. ROUTE
NEW DX PIPING THROUGH NEW/EXISTING ROOF PENETRATIONS AND THROUGH
NEW CURB AND ROOF BOOT. PATCH ROOF PENETRATIONS TO MATCH EXISTING,
SEAL WATER TIGHT, AND MAINTAIN ANY EXISTING ROOF WARRANTIES.
INSTALL NEW NEW FLOOR MOUNTED AC UNIT AS CLOSE AS POSSIBLE TO X-AC-4
WHILE MAINTAINING ALL MANUFACTURER REQUIRED CLEARANCES.
C om m te ch
D es ig n
472/24059.SAA
file no.
checked by drawn by consultant issue date acctg template.
contract order no.
consultant job no.
sheet title
Y22432
C O
U R
TL
AN
D S
T.
, S
U
IT
E
R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M a t r ix
06/11/26 ISSUED FOR BID
1065_24B
472/24059.SAA
472WHVMaintproj
Y22432
VIDEO SECURITY
UPGRADES
M-400
PARTIAL FIRST FLOOR PLAN -
WEST ADMINISTRATION BUILDING
- MECHANICAL/PIPING NEW
N PARTIAL FIRST FLOOR PLAN - WEST ADMINISTRATION - MECHANICAL NEW
SCALE: 1/4" = 1'-0"
0 1 5 10
N PARTIAL FIRST FLOOR PLAN - WEST ADMINISTRATION - PIPING NEW
SCALE: 1/4" = 1'-0"
0 1 5 10
X
X
X
TVSS
VFD
TRANSIENT VOLTAGE SURGE SUPPRESSION
VARIABLE FREQUENCY DRIVEDUPLEX RECEPTACLE
DOCK LIGHT FIXTURE
TELEPHONE / DATA OUTLET
ADDENDUM NOTE
PLAN NOTE
DEMOLITION NOTE
THREE PHASE MOTOR
ELECTRICAL SYMBOLS LEGEND
J
SINGLE RECEPTACLE (120 VOLT)
EMERGENCY RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR BOX
SURFACE FLOOR BOX
SPECIAL EQUIPMENT RECEPTACLE
TELEPHONE OUTLET
DATA OUTLET
POWER POLE
JUNCTION BOX
WALL JUNCTION BOX
PULL (JUNCTION) BOX
UNDERFLOOR JUNCTION BOX
OUTLETS
LIGHT FIXTURE
STRIP FIXTURE
IN-GRADE LIGHT FIXTURE
SPOTLIGHT (number of heads shown) EXIT SIGN (face & direction as shown)
WALL MOUNT LIGHT FIXTURE
CEILING LIGHT FIXTURE
TRACK & FIXTURE
STREET TYPE POLE FIXTURE
POLE MOUNTED LIGHT FIXTURE
EXTERIOR WALL MOUNT LIGHT FIXTURE
WALLPACK LIGHT FIXTURE
SPECIAL PURPOSE LIGHT FIXTURE
HIGH BAY LIGHT FIXTURE
EMERGENCY EGRESS LIGHT FIXTURE
(number of heads shown)
EMERGENCY LIGHT FIXTURE
FIXTURES
SWITCHES
SINGLE-POLE SWITCH
DIMMER SWITCH
TIME SWITCH
KEY SWITCH
MANUAL MOTOR SWITCH
THERMAL OVERLOAD SWITCH
SWITCH WITH PILOT LIGHT
FOUR-WAY SWITCH
THREE-WAY SWITCH
CIRCUITRY and RACEWAYS
UNDERFLOOR DUCT
BUS DUCT
PLUGMOLD AS SPECIFIED
WIREMOLD AS SPECIFIED
FLEXIBLE PIGTAILS/CONNECTIONS
"CONDUIT RUN CONTINUES" INDICATION
END OF CONDUIT RUN, CAP AND STAKE
END OF CONDUIT RUN
HOME RUN (with circuit numbers)
CONDUIT STUB DOWN
CONDUIT STUB UP
CONDUIT INSTALLED
CONDUIT INSTALLED
MECHANICAL
ELECTRIC WATER HEATER
ELECTRIC UNIT HEATER
PIPE TRACE HEATER
RESISTANCE HEATER, KW SHOWN
SINGLE PHASE MOTOR
SERVICE and EQUIPMENT
THERMOSTAT
CAPACITOR
ENCLOSED CIRCUIT BREAKER
TRANSFER SWITCH
WIREWAY
GROUND CONNECTION PER N.E.C.
TELEPHONE TERMINAL BOARD
GENERATOR, KW SHOWN
CURRENT TRANSFORMERS
UTILITY METER, AS REQUIRED
WEATHERHEAD
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
COMB. STARTER
MAGNETIC STARTER
DISCONNECT SWITCH
TRANSFORMER
CONTROL
xxVA connection by x/C) IRRIGATION CONTROLLER (120 volt
LIGHTING CONTACTOR
CONTROL TRANSFORMER
buttons indicated) PUSHBUTTON STATION (number of TIME CLOCK (24 hour U.O.N.)
PHOTOCELL (voltage as required)
HUMIDISTAT
DESIGNATIONS
(by E.C.)
(by others)
TT
G
WW
PC
CT
TS
T
H
TC
IC
T
1,3
OR
PM
WM
BD
UFD
F S
J
J
D
WH
PP
J
SWITCH STYLE OCCUPANCY SENSOROC
DIGITAL TIME SWITCH
POWER PACK
DUAL TECHNOLOGY SENSOR - 360° - 500 SQ FT
DUAL TECHNOLOGY SENSOR - 360° - 1000 SQ FT
ULTRASONIC SENSOR - 360° - 2 CIRCUIT
OCCUPANCY SENSOR / PHOTOCELL
WALL MOUNT DUAL TECHNOLOGY SENSOR
OS5
OS4
T
OS2
OS3
OS1
PP
CEILING MOUNTED WIFI
DIGITAL EQUIPMENT METER, AS REQUIRED
POLE
PUMP
PANEL
P
PNL
PVC
PRV-
P-
PB
POLY VINYL CLORIDE
POWER ROOF VENTILATOR
PULL BOX
GENERAL CONTRACTOR
GROUND
HUMIDIFIERH-
GND
GFI
GC
GROUND FAULT INTERUPTER
ABBREVIATIONS LEGEND
POWER
SWITCH
RECEPT
SF-
SWBD
TCC
SPEC
SW
RGC
RTU-
PWR
VOLTS
WATTS
UF
V
W
UL
VL
UNO
UH-
TS
TYP
TR
ROOF TOP UNIT
RECEPTACLE
SWITCHBOARD
UNDER FLOOR
SPECIFICATIONS
RIGID GALVANIZED STEEL CONDUIT
UNLESS NOTED OTHERWISE
UNDERWRITERS' LABORATORIES, INC.
TAMPER PROOF RECEPTACLE
TAMPER PROOF SWITCH
TEMPERATURE CONTROL CONTRACTOR
VERIFY LOCATION WITH OWNER
TYPICAL
UNIT HEATER
SUPPLY FAN
WITH
WITHOUT
W/
XFMR
W/O
WP
TRANSFORMER
WEATHER PROOF
HOUR
LIGHT
JUNCTION BOX
LIGHT CONTROL
ISOLATED GROUND
HORSEPOWER
MINIMUM
MOUNT
MAKE-UP AIR UNIT
MOTOR CONTROL CENTER
MAIN LUG ONLY
MOUNTED
MOUNTING
MAXIMUM
LIGHTING
LT FLEX
MTD
MUAU-
MTG
MLO
MIN
MT
MC
MAX
MCC
LTG
IG
LC
LT
IMC
JB
HR
HVAC
HOA
HP
NORMALLY CLOSED
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NIGHT LIGHTNL
NTS
NO
NIC
NC
HAND-OFF-AUTO SELECTOR SWITCH
HEATING/VENTILATING/AIR CONDITIONING
INTERMEDIATE METAL CONDUIT
LIQUID TIGHT FLEXIBLE METAL CONDUIT
MECHANICAL CONTRACTOR
HID HIGH INTENSITY DISCHARGE
A
AC
AFF
ACU-
AHJ
AHU-
AS
B-
BC
AIC
ATS
BLDG
CHLR-
CND (C)
CKT BKR
CKT
CUH-
CU-
DISC
DFU-
EF-
EC
DWH-
EBB-
DWG
CT-
EXIST (E)
EWC
FLEX
FLA
FLR
FSES
FLUOR
EMT
ABOVE FINISHED FLOOR
AIR CONDITIONING UNIT
AMPS
ABOVE COUNTER
AIR HANDLING UNIT
AUTOMATIC TRANSFER SWITCH
AMPS INTERUPTING CAPACITY
AUTHORITY HAVING JURISDICTION
ABOVE SHELF
BOILER
BUILDING
BELOW COUNTER
CHILLER
DOMESTIC WATER HEATER
CABINET UNIT HEATER
CIRCUIT
CIRCUIT BREAKER
CONDUIT
CONDENSING UNIT
COOLING TOWER
DUCT FURNACE
DRAWING
DISCONNECT
FOOD SERVICE EQUIP. SUPPLIER
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRIC BASEBOARD
ELECTRICAL METALLIC TUBING
EXISTING
EXHAUST FAN
FLOOR
FLUORESCENT
FLEXIBLE CONDUIT
FULL LOAD AMPS
EM EMERGENCY
F/S FIRE/SMOKE
FU- FURNACE
GENERAL ELECTRICAL NOTES
SOUND and SIGNAL
SSCP
COCCTV
SECURITY SYSTEM CONTROL PANEL
CAMERA
DATA RACK
RACK MOUNTED UPS
BRACKET MOUNTED UPS
POLE
PLUG STRIP (PDU)
P
C
DR
RUPS
BUPS
1. ALL NON-FIRE RATED WALLS ARE TO BE PATCHED WITH LIKE MATERIAL TO MAINTAIN
ORIGINAL RATING.
2. ALL WALL AND FLOOR PENETRATIONS THROUGH FIRE RATED WALLS ARE TO BE
SEALED WITH FIRE CAULK TO MAINTAIN ORIGINAL RATING.
3. ALL CONDUITS SHALL BE FIELD ROUTED ALONG EXISTING PIPING AND STRUCTURAL
STEEL.
4. CONTRACTORS SHALL VISIT THE PROJECT SITE DURING PRE-BID WALK THROUGH TO
DETERMINE THE EXACT EXTENT OF THE WORK REQUIRED BEFORE BIDDING THE
PROJECT.
5. REMOVE ALL EXISTING EXPOSED CONDUIT, WIRE, AND EQUIPMENT NOT TO BE
RE-USED WHERE WORK IS BEING DONE EXCEPT ITEMS NOTED OTHERWISE.
6. WHERE BUILDING SURFACES ARE DAMAGED BY THE REMOVAL OF OLD WORK,
SURFACES SHALL BE PATCHED AND PAINTED TO MATCH ADJACENT.
7. EXISTING WORK WHICH IS PRESENTLY CONCEALED, WHICH WILL REMAIN CONCEALED,
AND DOES NOT INTERFERE WITH ANY NEW WORK OF ANY TRADE NEED NOT BE
REMOVED. HOWEVER, ALL CONDUIT SHALL BE CAPPED BELOW FINISH SURFACE AND
THEN PATCHED AND PAINTED TO MATCH, OR AS NOTED.
8. EXISTING OPENINGS, WHICH ARE TO BE REUSED, SHALL BE MODIFIED OR ENLARGED
TO SUIT THE NEW SYSTEMS AS REQUIRED. PROVIDE ALL REQUIRED CUTTING AND
PATCHING.
9. CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING THE EXISTING WALLS TO
MATCH THE ADJACENT SURFACES BEHIND ALL SURFACE MOUNTED EQUIPMENT.
10. CONTRACTOR SHALL FIELD VERIFY ALL EQUIPMENT AND LOADS PRIOR TO INSTALLING
SERVICE TO EQUIPMENT.
11. DRAWINGS ARE BASED ON EXISTING RECORD DOCUMENTS AND CASUAL FIELD
OBSERVATION PERFORMED ON AUGUST 16, 2024. REPORT ANY DISCREPANCIES TO
ENGINEER FOR CLARIFICATION.
12. MINIMUM RACEWAY SIZE; 3/4" TRADE SIZE. ALL FLEXIBLE CONDUIT RACEWAYS SHALL
BE LIQUID TITE, MAXIMUM 36" LENGTH. REFER TO SPECIFICATION 260533 - RACEWAY
AND BOXES FOR ELECTRICAL SYSTEMS.
13. ALL CONDUIT ABOVE 10 FOOT SHALL MEET THE FOLLOWING REQUIREMENTS:
13.1. STRAP DISTANCE: 5 FEET.
13.2. FASTENERS: 2 HOLE
13.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED- GRC.
13.4. FITTINGS: COMPRESSION.
13.5. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES.
14. ALL CONDUIT 10 FOOT AND BELOW SHALL MEET THE FOLLOWING REQUIREMENTS:
14.1. STRAP DISTANCE: 3 FEET.
14.2. FASTENERS: 2 HOLE WITH SECURITY SCREWS.
14.3. CONDUIT: INTERIOR EMT, EXTERIOR EXPOSED/ CONCEALED - GRC.
14.4. FITTINGS: COMPRESSION.
14.5. BELL BOXES: FS TYPE.
14.6. NO KNOCKOUTS.
14.7. SECURE CONDUIT WITHIN 12 INCHES OF BOXES AND ENCLOSURES
15. ALL EXPOSED WIRING SHALL BE IN CONDUIT. OPEN LOW VOLTAGE WIRING ABOVE
CEILINGS IS ACCEPTABLE.
15.1. ALL EXPOSED WIRING ABOVE CEILINGS SHALL BE INSTALLED WITH J-HOOKS. DO
NOT CONNECT TO EXISTING CEILING TIE WIRES.
16. CONDUITS AND WIRES SHALL BE INSTALLED STRAIGHT, LEVEL, AND SHALL BE
PARALLEL OR PERPENDICULAR TO THE BUILDING LINES.
17. CONTRACTOR SHALL VERIFY ALL VOLTAGES BEFORE CONNECTING ANY EQUIPMENT.
18. ALL LOCATIONS WHERE THE WALLS CAN NOT BE FISHED SHALL BE SURFACE
MOUNTED CONDUIT FOLLOWING NOTES 12 THROUGH 14 ABOVE.
19. ALL WALLS THAT ARE ACCESSIBLE SHALL BE FISHED AND DEVICE CUT INTO WALL.
20. ALL EXTERIOR CONCEALED CONDUIT UNDERGROUND SHALL BE RNC, TYPE
EPC-40-PVC. ALL EXTERIOR ABOVE GROUND CONDUIT SHALL BE GRC.
21. ALL ELECTRICAL OUTAGES SHALL NOT LAST OVER 2-HOURS. PORTABLE GENERATORS
SHALL BE USED TO REPLACE ANY ELECTRICAL SERVICE EXCEEDING THAT DURATION.
22. WHEN RELOCATING ANY ELECTRICAL DEVICE, CONTRACTOR SHALL COMPLETE THE
RELOCATION IN ONE DAY AND VERIFY THAT ALL DEVICES RELOCATED ARE WORKING
PROPERLY PRIOR TO LEAVING THE SITE.
23. CONTRACTOR SHALL PROVIDE AND INSTALL ALL REQUIRED COMPONENTS,
RACEWAYS, WIRE, AND HARDWARE, AS INDICATED ON DRAWINGS.
24. ALL WORK DONE WITHOUT APPROVED SHOP DRAWINGS IS AT CONTRACTORS RISK.
25. CONTRACTOR SHALL CONTACT COMMTECH FOR SPECIFICATIONS FOR CAT6 AND
OTHER LOW VOLTAGE REQUIREMENTS.
26. CONTRACTOR SHALL NOTIFY PSC OF ANY EXISTING INSTALLATIONS NOT MEETING
THESE STANDARDS PRIOR TO STARTING WORK IN THE AREA.
27. THESE DRAWINGS HAVE BEEN SUBMITTED AND APPROVED BY LOCAL AUTHORITIES
HAVING JURISDICTION. ANY COMMENTS THAT WERE PROVIDED BY THE LOCAL
AUTHORITIES HAVING JURISDICTION HAVE BEEN ADDRESSED, AND THE DRAWINGS
MODIFIED ACCORDINGLY. BECAUSE OF THIS, RESPONSIBILITY OF ANY ISSUES THAT
ARISE UPON FINAL INSPECTION SHALL NOT FALL UPON MATRIX CONSULTING
ENGINEERS.
DESCRIPTION AND COMMENTSTYPE MANUFACTURER CATALOG NO.
NEW LIGHT POLE SCHEDULE
D560-70OA140-145-GV-HH-SFBC-AB
WISCONSIN LIGHTING LAB
OR APPROVED EQUAL14
14' TAPERED STEEP POLE WITH BASE, 2"X4" HAND HOLE AT 18" FROM THE BASE TO
HAND HOLE, ANCHOR BOLTS PER MANUFACUTRURE RECOMMENDATIONS.
60KVA UPS- EQUIPMENT SPECIFICATION
60KVA UNINTERRUPTIBLE POWER SUPPLY (UPS) EATON 93PM
PROVIDE UNINTERRUPTIBLE POWER SUPPLY (UPS). UPS SHALL BE
VERTIV APM2 60KVA RATED, HIGH EFFICIENCY, DOUBLE CONVERSION,
CONTINUOUS DUTY, ON-LINE TYPE. INPUT VOLTAGE OF 208VAC, 60HZ,
3-PHASE 4-WIRE PLUS GROUND. OUTPUT VOLTAGE OF 208VAC, 60HZ,
3-PHASE 4-WIRE PLUS GROUND. 65 KAIC RATED. CONTINUOUS DUTY
STATIC BYPASS SWITCH, BACKLIT LCD CONTROL PANEL. INCLUDE FRONT
ACCESS, INDOOR RATED IP-20 ENCLOSURE. 13MIN LITHIUM ION
BATTERIES.
INCLUDE SYSTEM STARTUP SERVICES, USER TRAINING, AND THREE YEAR ON SITE
WARRANTY SERVICE FOR PARTS AND LABOR.
VS-RTSA-25-70-7-LAB-GV-DB-PC
WISCONSIN LIGHTING LAB
OR APPROVED EQUAL25
25' TAPERED STEEL POLE WITH 11" BASE, 2-3/8" TENON, 3"X5" HAND HOLE AT 14"-18",
6"-7" BOTTOM DIAMETER, 3"-4" TOP DIAMETER, 7 GAGE, 55,000 PSI, A153
GALVANIZEDHARDWARE, ANCHOR BOLTS ARE EXISTING TO REUSED, FESTOON
OPENING AT 22', DARK BRONZE FINISH. CONTRACTOR TO FIELD VERIFY ORIENTATION.
E-100
DRK
JFS
ELECTRICAL
SYMBOLS, ABBREV.,
& NOTES
C om m te ch
D es ig n
472/24059.SAA
file no.
checked by drawn by consultant issue date acctg template.
contract order no.
consultant job no.
sheet title
Y22432
C O
U R
TL
AN
D S
T.
, S
U
IT
E
R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M a t r ix
06/11/26 ISSUED FOR BID
1065_24B
472/24059.SAA
472WHVMaintproj
Y22432
VIDEO SECURITY
UPGRADES
C
C
C
C
C
C C
C C
CC
C C
C
C
C
C
C C
C
C
C
C
C C
C
C
C
C C
C
C
C
C
C
C
C
C C
C
C
C
C
CC
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C C
C
C
C
C
C
C
C
C
C C
C
C
C
C C
CC
C
C
C
C
C
C
C
C
C C
C
C C
CC
C
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P P
PP
P
P
P
P
P
P
P
P
P P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P P
P
P
P
PP
P
P
P P
PPPP
P
P
P
P
P
P
P
P
P
P
C
P
P
P
P C
CAB-001
CAB-002
CA
B-
CA
B-
CAB-005
CAB-006
CAB-007
CAB-008
CAB-017
CAB-018
2 2
C
C
C
C
C2
C
C
C
C 2
C
C
C
CC
C
C
C
C1C 2
C
C2
C
P C
C
C
C
C
C
C
(1) 1" CONDUIT
(1) 1" CONDUIT
C
C
C
C
C2
C
P
P
ELECTRICAL KEY NOTES
REMOVE EXISTING LOW VOLTAGE SURGE PROTECTION
DEVICES. PROVIDE AND INSTALL NEW LOW VOLTAGE SURGE
PROTECTION DEVICES FOR CAMERAS ON POLE. RE-USE
EXISTING JUNCTION BOX. PULL EXISTING CAT 6 CABLE BACK
TO CBAINET AND RE-PULL EXISTING UN-SHIELDED CAT 6
CABLE WITH #10 GND. REPLACE EXISTING SHIELDED CAT 6
WITH UN-SHIELDED AS REQUIRED. TEST AND RE-TERMINATE
LOW VOLTAGE CABLES. ALL POLES ARE EXISTING TO REMAIN
UNLESS OTHERWISE SPECIFIED. REFER TO SHEET E-800
DETAIL 3.
PROVIDE AND INSTALL NEW SURGE PROTECTION DEVICE IN
COMMUNICATIONS ROOM FOR CAMERAS. REFER TO SHEET
E-800 DETAIL 2.
REMOVE EXISTING LINE AND LOW VOLTAGE SURGE
PROTECTION DEVICES. PROVIDE AND INSTALL NEW LINE AND
LOW VOLTAGE SURGE PROTECTION DEVICES (RAYCAP
G29-00-394-OTL-PROTEC-T1-40 AND RAYCAP NJ2010B) IN
PERIMETER CABINET. REFER TO SHEET E-800 DETAIL 1 FOR
COMMUNICATIONS CONNECTIVITY. PROVIDE AND INSTALL
NEW SURGE PROTECTION DEVICE IN ADMIN DATA RACK FOR
FIRST AND LAST CABINETS. PROVIDE AND INSTALL #10 GND
IN 3/4" CONDUIT FOR CAMERA POLE GROUNDING.
CONTRACTOR TO PROVIDE AND INSTALL ANCHOR BOLTS.
PROVIDE AND INSTALL NEW POLE AND BASE FOR NEW 360
DEGREE SALLY PORT DRIVE CAMERA. REFER TO SHEET E-801
DETAILS 4&5 AND POLE SCHEDULE ON SHEET E-100.
PROVIDE (1) 1" CONDUIT TO CAB-018 FOR LOW VOLTAGE AND
GROUND CABLES. REFER TO LOW VOLTAGE DRAWINGS FOR
LOW VOLTAGE CABLE INFORMATION.
PROVIDE AND INSTALL NEW CONCRETE BASE AND POLE FOR
NEW CAMERA. REFER TO SHEET E-100 FOR POLE SCHEDULE.
CONTRACTOR TO PROVIDE AND INSTALL ANCHOR BOLTS.
DIRECTIONAL BORE AND HYDRO-EXCAVATE CONDUITS FOR
LOW VOLTAGE PATHWAYS. REFER TO SPEC 023200 - HYDRO
EXCAVATION. REFER TO LOW VOLTAGE DRAWINGS FOR
CABLE TYPES AND QUANTITIES.
EXISTING DEVICES TO BE REMOVES. REMOVE ASSOCIATED
CONDUIT AND WIRE BACK TO SOURCE.
E-200
DRK
JFS
ELECTRICAL
FLOOR PLAN
NEW POWER
N ELECTRICAL - WEST SITE PLAN - POWER
SCALE: 1" = 60'-0"
400 10 20 80 150
WEST SITE PLAN
ELECTRICAL
C om m te ch
D es ig n
472/24059.SAA
file no.
checked by drawn by consultant issue date acctg template.
contract order no.
consultant job no.
sheet title
Y22432
C O
U R
TL
AN
D S
T.
, S
U
IT
E
R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M a t r ix
06/11/26 ISSUED FOR BID
1065_24B
472/24059.SAA
472WHVMaintproj
Y22432
ELECTRICAL KEY NOTES
REMOVE EXISTING LOW VOLTAGE SURGE PROTECTION
DEVICES. PROVIDE AND INSTALL NEW LOW VOLTAGE SURGE
PROTECTION DEVICES FOR CAMERAS ON POLE. RE-USE
EXISTING JUNCTION BOX. PULL EXISTING CAT 6 CABLE BACK
TO CBAINET AND RE-PULL EXISTING UN-SHIELDED CAT 6
CABLE WITH #10 GND. REPLACE EXISTING SHIELDED CAT 6
WITH UN-SHIELDED AS REQUIRED. TEST AND RE-TERMINATE
LOW VOLTAGE CABLES. ALL POLES ARE EXISTING TO REMAIN
UNLESS OTHERWISE SPECIFIED. REFER TO SHEET E-800
DETAIL 3.
PROVIDE AND INSTALL NEW SURGE PROTECTION DEVICE IN
COMMUNICATIONS ROOM FOR CAMERAS. REFER TO SHEET
E-800 DETAIL 2.
REMOVE EXISTING LINE AND LOW VOLTAGE SURGE
PROTECTION DEVICES. PROVIDE AND INSTALL NEW LINE AND
LOW VOLTAGE SURGE PROTECTION DEVICES (RAYCAP
G29-00-394-OTL-PROTEC-T1-40 AND RAYCAP NJ2010B) IN
PERIMETER CABINET. REFER TO SHEET E-800 DETAIL 1 FOR
COMMUNICATIONS CONNECTIVITY. PROVIDE AND INSTALL
NEW SURGE PROTECTION DEVICE IN ADMIN DATA RACK FOR
FIRST AND LAST CABINETS. PROVIDE AND INSTALL #10 GND
IN 3/4" CONDUIT FOR CAMERA POLE GROUNDING.
CONTRACTOR TO PROVIDE AND INSTALL ANCHOR BOLTS.
PROVIDE AND INSTALL NEW POLE AND BASE FOR NEW 360
DEGREE SALLY PORT DRIVE CAMERA. REFER TO SHEET E-801
DETAILS 4&5 AND POLE SCHEDULE ON SHEET E-100.
PROVIDE (1) 1" CONDUIT TO CAB-018 FOR LOW VOLTAGE AND
GROUND CABLES. REFER TO LOW VOLTAGE DRAWINGS FOR
LOW VOLTAGE CABLE INFORMATION.
PROVIDE AND INSTALL NEW CONCRETE BASE AND POLE FOR
NEW CAMERA. REFER TO SHEET E-100 FOR POLE SCHEDULE.
CONTRACTOR TO PROVIDE AND INSTALL ANCHOR BOLTS.
DIRECTIONAL BORE AND HYDRO-EXCAVATE CONDUITS FOR
LOW VOLTAGE PATHWAYS. REFER TO SPEC 023200 - HYDRO
EXCAVATION. REFER TO LOW VOLTAGE DRAWINGS FOR
CABLE TYPES AND QUANTITIES.
C
C
C
C
C
C C
C
C
C
C
CCCCC
CCC
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C C
C C C
C
C C
C
C
C C C
CCCC
C C
C
C
C C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
C
CCC
C
C C
C
C
C
C C
C
C
CC
C
CC
C
C
C
C
C
C
C
C
C C
C
C
C
C
C
C
C C
C
C
C
P
P
P
P
P
P
PPPPPPPPPPPP
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P P
P
P
P
P
P
P P P
P
P P P P
P
P
P P P
P
P
P
P
P
P
P
P
P
P
P
P
PPPP
P P P P
P
P
P
P
P
P
P
P
P
P P
P P
P
P
P
P
P
P
P
P
P
PPPPP
PP
P
P P
P
P
P
P
P
P
P
P
P
P
P
P C
P
C
P
P
P
PP
P
CAB-008
CA
B-
CAB-010 CAB-011
CA
B-
CA
B-
CA
B-
CA
B-
CAB-016
CAB-017
1 1
2 2 2 2
3 3
C
C
CCCC
C
CCCC
C
C
C
C C
C
C
C
C
C
C
C
C
C
C C 2 2
C
C 2
C2
C
P
C2
C
C2
P
C
C
C
C
C
C
C
C
C
E-201
JFS
ELECTRICAL
SITE PLAN
N ELECTRICAL - EAST SITE PLAN - POWER
SCALE: 1" = 60'-0"
400 10 20 80 150
DRK
EAST SITE PLAN
ELECTRICAL
C om m te ch
D es ig n
472/24059.SAA
file no.
checked by drawn by consultant issue date acctg template.
contract order no.
consultant job no.
sheet title
Y22432
C O
U R
TL
AN
D S
T.
, S
U
IT
E
R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M a t r ix
06/11/26 ISSUED FOR BID
1065_24B
472/24059.SAA
472WHVMaintproj
Y22432
DEPUTY
WARDEN
OFFICE
TOILET
DEPUTY
WARDEN
SECRETARY
CLOSET
DEPUTY SUITE
CONFERENCE
ROOM
INSPECTOR
OFFICE
CLOSET
CLOSET
CLOSET
CLOSET
DEPUTY
SUITE
CORRIDOR
MENTAL
HEALTH
NORTH
CORR.
MENTAL
HEALTH
NORTH
CORR.
MENTAL
HEALTH
NORTH
CORR.
MENTAL
HEALTH
NORTH
CORR.
MENTAL
HEALTH
STAFF
TOILET
MENTAL
HEALTH
PRISONER
TOILET MENTAL
HEALTH
OFFICER
DESK
MENTAL
HEALTH
STAFF
TOILET
MENTAL
HEALTH
STAFF
TOILETMENTAL
HEALTH
WEST
CORR.
MENTAL
HEALTH
EAST
CORR.
FIRE
ALARM
PANEL
MED LINE
VEST.
SHIFT COMMAND
TOILET
CONTROL
CENTER
VEST.
CONTROL
CENTER
STAFF
TOILET W. LOBBY
MENS
TOILET
W. LOBBY
WOMENS
TOILET
W. LOBBY
WOMENS
TOILET
CONTROL CENTER
SOUTH CORRIDOR
WEST VISITING/
GATE PASSAGE
WEST GATE
BUBBLE
WEST
GATE
PRISONER
SHAKE DOWN
ARSENAL
VEST.
RECORDS
MENS
STAFF
TOILET
RECORDS
WOMENS
STAFF
TOILET
RECORDS
RESTROOM
PASSAGE
ARSENAL
RESTROOM
MAIN LOBBY
OFFICERS DESK
W. ADMIN
MAIN LOBBY
MAIN LOBBY
VISITOR WAITING MAIN LOBBY
VESTIBULE
STAFF
LUNCH
ROOM
LOBBY PORTER
CLOSET
RECORDS SOUTH
CORRIDOR
WORD
PROCESSING
WARDENS
TOILET
SWITCHGEAR/
ELECTRICAL
ROOM
BASEMENT
STAIR
WEAPONS
DISPENSING
DEPATMENTAL
SPECIALIST
OFFICE
CENTER
RECORDS
CORRIDOR
RECORDS
EAST
CORRIDOR
RECORDS
CAUSTIC EAST
ENTRY
VEST.
NORTH RECORDS
CORRIDOR
DEPUTY WARDEN
SUITE STORAGE
DEPARTMENTAL
TECHNICIAN
OFFICE
DEPUTY SUITE
COPY ROOM
PHONE
ROOM
INTEVIEW
ROOM 1697
CRITICAL TOOL
STORAGE
RUM OFFICE
H.I. OFFICE
GROUP ROOM
D
GROUP ROOM
C
GROUP ROOM
B
TELEMED
OFFICE
MENTAL HEALTH
SUPERVISER OFFICE
CLOSET
STORAGE
STORAGE
PORTER
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
MEETING
ROOM
OFFICE
OFFICE
OFFICE
PASSAGE
OFFICE
GROUP ROOM
#2
GROUP ROOM
#3
MED. STORAGE
MED. ROOM
GROUP ROOM
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
OFFICE
CLOSET
ELECTRICAL/
STORAGE
STORAGE
CAPT.
OFFICE
CLOSET
CAMERA ROOM
MONITOR
ROOM
SHIFT
COMMAND
VIDEO
RM. 1
VIDEO
RM. 2
NON-CONTACT
VISIT
CONTROL
CENTER
CONFERENCE
ROOM
IT ROOM
ARSENAL
A111B
RECORDS
COPY
ROOM
A111
RECORD
SUPERVISER
OFFICE
A113
WARDENS CONFRENCE
ROOM
A107
WARDENS
OFFICE
A105B
ADMINISTRATIVE
ASST. OFFICE
A110
RECORD
OFFICE
A18
TRANSPORTATION
OFFICE
A19
CONFERENCE
ROOM
A120
TRANSPORTATION
LOCKER RM
A121
IT/STORAGE
A122
STORAGE
A123
RECORD OFFICE
FILE ROOM
STORAGE
WEST VISITING
ROOM
STORAGE
INTERVIEW
A105C
VEST.
CAUSTIC
A108
WARDENS
SECRATARY
A125
RM
DTMB
OFFICE
A112 I.T.
STORAGE
ARSENAL
ARSENAL
STORAGE
UPS-7
E-700
EXISTING 1000A
DOUBLE ENDED
SWITCHGEAR
NEW 1000A
CAMLOCK
CABINET
400A ATS
E-500
JJD
JFS
N WEST ADMINISTRATION BLDG - FLOOR PLAN - POWER
SCALE: 1/8" = 1'-0"
0 1 5 10 20
WEST ADMINISTRATION
FLOOR PLAN
POWER
C om m te ch
D es ig n
472/24059.SAA
file no.
checked by drawn by consultant issue date acctg template.
contract order no.
consultant job no.
sheet title
Y22432
C O
U R
TL
AN
D S
T.
, S
U
IT
E
R
O C
KF
O
R D
, M
IC
H
IG
AN
W W
W .C
O M
M
TE
C H
D
ES
IG
N
.C O
M
D
EP
A R
TM
EN
T O
F
TE
C H
N O
LO
G
Y , M
A N
A G
EM
EN
T A
N D
B U
D G
ET
ST
A
TE
O
F M
IC
H
IG
A
N
A D
A M
P . L
A C
H , R
A , D
IR
EC
TO
R
ST
A
TE
F
A C
IL
IT
IE
S
A D
M
IN
IS
TR
A
TI
O N
D
ES
IG
N
A N
D C
O N
ST
R
U C
TI
O
N D
IV
IS
IO
N
M a t r ix
06/11/26 ISSUED FOR BID
1065_24B
472/24059.SAA
472WHVMaintproj
Y22432
PANEL
EXISTING
LP-J
100A, 3P100A, 3P200A, 3P
PANEL
EXISTING
LP-EM
300A, 3P400A, 3P
PANEL
EXISTING
LP-A
WEST ADMIN. SWITCHGEAR - 1600A RATED 120/208VAC,
3Ø, 4W
200A, 3P
400A OPEN
TRANSITION
AUTOMATIC
TRANSFER
SWITCH
PANEL
NEW
K 120/208V 3Ø, 4W
400A, MLO
60KVA UPS
PANEL
NEW
UPS-B
120/208V 3Ø, 4W
225A, MLO
EXISTING TRANSFORMER
300KVA, 208Y/120V, 3Ø, 4W
FROM EAST ADMIN.
BUILDING SWITCHGEAR
EXISTING TRANSFORMER
300KVA, 208Y/120V, 3Ø, 4W
FROM MAIN 4800V
SWITCHGEAR
PANEL
EXISTING
XRAY
EATON UPS
PANEL
EX…