4_Technical_Exhibit_145027-26-0030.pdf
PDF 751 KB Posted
- Solicitation number
- 1305M326Q0317
About this file
This document is a technical exhibit containing a Hangar 32 electrical inspection report and single-line power diagrams for a federal facility. The inspection was conducted by McKinstry Co. and documents the electrical infrastructure conditions across two hangars (32 and 33) with detailed equipment listings, identified code violations, and recommended corrective actions.
The inspection identifies 42 pieces of electrical equipment including switchboards, panels, transformers, disconnects, and fuses across multiple locations within Building 32. Key findings include numerous code violations requiring repair or replacement, such as undersized conductors, improper lug ratings, missing safety seals, and non-compliant wire colors. The report designates equipment for removal, repair, or replacement, with several items flagged as "very old" requiring full replacement. Major work items are organized into contract line items (CLINs 001-006), including a new generator connection with manual transfer switch (MTS) as optional work (CLIN 006). Notable equipment to be removed includes Panel K (CLIN 001), multiple old disconnects and fuses (CLIN 002), and panels in the abandoned upper floor of the south lean-to. The single-line diagrams show the distribution network fed from 75-80 KVA transformers at 480V/3Ø stepping down to 120/208V and 277V systems. The technical exhibit references E6.01 designation and includes comprehensive power routing schematics showing panel interconnections, transformer feeds, and planned scope modifications during the PMEL Power Project.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HANGAR 32 SINGLE-LINE DIAGRAM - POWER
HANGAR 33 SINGLE-LINE DIAGRAM - POWER
PANEL
OLD LTG
MLO
PANEL
D
800A
MOB
PANEL
LAB VAN
MLO
PANEL
II
100A
MCB
PANEL
JJ
(PNL J)
100A
MCB
PANEL
F3
277V
MLO
PANEL
CB-1
100A
MCB
PANEL
AA
(PNL B)
225A
208V/3Ø
MCB
PANEL
A
100A 480V/3Ø
MCB
PANEL
AB
MML
FREEZER
60A
PANEL
Z
200A 120/208V
MCB
PANEL
Y
200A 120/208V
MCB
PANEL
CB-2
480V/3Ø
MCB
PANEL
C-1Ø
MLO
PANEL
C-3Ø
MLO
PANEL
225A 120/208V
MCB
PANEL
D
125A
MLO
PANEL
F2
150A
MCB
PANEL
F
400A 480V/3Ø
MCB
PANEL
F1
100A
MLO
PANEL
B-1Ø
MLO
PANEL
B-3Ø
MLO
PANEL
HH
100A
MLO
PANEL
GG
100A
MCB
SW CORNER
HANGAR BAY
SW CORNER
HANGAR BAY
LAW
ENFORCEMENT
WALK-IN
FREEZER
NE
HANGAR BAY
NORTH LEAN-TO
RM 1109
NORTH LEAN-TO
RM 1109
NORTH LEAN-TO
RM 1109
PANEL
F4
NW
HANGAR BAY
2ND FLOOR
SOUTH LEAN-TO
HALLWAY
J BOX @
MID
HANGAR
S
WIND
TUNNEL
60 A
T-WP
15 KVA
WINCH
PANEL
100 A
PANEL
DD
225A
NE
HANGAR BAY
REMOVE
NEW ROUTING TO PANEL HH
REMOVE
TO BE REPLACED
DURING PMEL POWER PROJECT
1ST FLOOR
SE STAIRWELL
S WALL
HANGAR BAY
S WALL
HANGAR BAY
NOS
WALK-IN
FREEZER
/ COOLER
PMEL
LAB VAN
2ND FLOOR NE
STAIRWALL
2ND FLOOR NW
STAIRWALL
WALK-IN
FREEZER
TO BE REMOVED
DURING PMEL PROJECT
MID HANGAR
NEW SCOPE DURING
PMEL POWER PROJECT
PANEL
F2A
WITH
MTS
GENERATOR
CONNECTION
GUARD
SHACK
PANEL
2ND FLOOR SE
STAIRWALL
2ND FLOOR SW
STAIRWALL
SW CORNER
HANGAR BAY
SE CORNER
HANGAR BAY
REMOVE
REMOVE
1ST FLOOR
NE STAIRWELL
1ST FLOOR
SW STAIRWELL
1ST FLOOR
SE STAIRWELL
OLD
PANEL
#651
#654
EMPTY
PANEL
1ST FLOOR
NE STAIRWELL
#648
#648
#649
#652 #653
#647 #646 #645
#644
#643
#641 #642
#660
#661
#662
#663
PAINT
BOOTH
#664
#666
#667 #665#668
#669 #670
#671
#677
#672
#675#674
#678
#673
#676
PANEL
D
PANEL
P2
REMOVE
1ST FLOOR
SW STAIRWELL
EMPTY
PANEL
#679 #680
#681#682
EMPTY
PANEL
#682
PANEL NOT FOUND
HANGAR 32 ELECTRICAL INSPECTION - MCKINSTRY CO
LOCATION "ID
TAG #"
EQUIPMENT DESCRIPTION RECOMMENDED
ACTION
McK REMARKS NOAA REMARKS FOR ADDITIONAL CLIN WORK
Bldg. 32 NW Corner/Room 112
641 Switchboard 800A Fused – 480V
3PH, 4W
NONE
Bldg. 32 NW Corner/Room 112
642 Switchboard 800A Fused – 480V, 3PH, 4W
NONE
Bldg. 32 NW Corner/Room 109
643 PNL-F 400A Main Breaker,480V, 3PH, 4W
NONE (5)K.O. Seals needed - Very Old, Remove/Replace
Replacing in PMEL Power Project
Bldg. 32 NW Corner/Room 109
644 PNL-F1 Main Lug 100A, 480V, 3PH, 4W
NONE
Bldg. 32 NW Corner/Room 109
645 45 KVA Transformer 480V?208V
NONE
Bldg. 32 NW Corner/Room 109
646 Disconnect S-2 , 150A, 208V, 3PH Feeds PNL-F2
NONE Very Old, Remove/Replace Remove
Bldg. 32 NW Corner/Room 109
PNL-F2 150A Main Breaker, 208V, 3PH, 4W NONE
"K.O. seals needed, 3”,1”,3/4”, ½” CKT-26,28,30 has 2wires per, wrong size wire for 100A 3-pole"
Repair
Bldg. 32 - NE Corner 648 "PNL-DD Main Lug 120/208V, 3PH, 4W
Fed from 75KVA Transformer"
NONE Panel does not have main breaker or disconnecting means. Needs ½” K.O. seal
Repair as part of new MTS for generator connection
Bldg. 32 - NE Corner 649 Disconnect T-32NL 100A
480V, 3PH, 3W NONE
"Disconnect is not fused, missing bushing on line side, missing mounting screws to hold to wall. Fed from?"
Repair as part of new MTS for generator connection
Bldg. 32 - NE Corner 650 75 KVA Transformer NONE
Bldg. 32 - NE Corner 651 PNL-D 125A 120/208V, 3PH, 4W NONE Main lugs used to splice #2 and #6 STR copper conductors.
Fed from?
Remove
Bldg. 32 - NE Stair – 2nd Floor
652 PNL-HH 100A 120/208V 3W Low Grade Fault "CKT-18 To be monitored – Plan new inspection within 90 days Dan Krigsvold removed hot breaker(#18), Re-terminated wire to ckt-20"
Review for repair
Bldg. 32 - NE Stair – 2nd Floor
653 PNL-GG 100A 120/208V 3W NONE
Bldg. 32 - NE Stair – 2nd Floor
150A Breaker Feeds Security Fed from Panel D (splice box) NONE
Very old – Plexiglass cover Remove/Replace - Wrong size wire
Remove
Bldg. 32 – Center - West 655 PNL-K 225A 3PH, 4W NONE Old – Remove/Replace Many code violations
Removed in BiB Demo
Bldg. 32 – Center - West 656 75 KVA Transformer T-2 480V?208V
NONE Removed in BiB Demo
Bldg. 32 – South of Center
657 60A Disconnect 480V, 3PH (Rope Strength Tester)
NONE "Code Violations – wire size too small (2)#10 wires on each lug of load side"
Repair
Bldg. 32 – South of Center
658 Disconnect 60A 480V, 3PH NONE
"Code Violations-#12AWG Doubled up w/#6AWG on Line side lugs.
Remove/Replace"
Repair
Bldg. 32 – South of Center
659 Disconnect 30A 480V, 3PH NONE Code Violations- 250V fuses, Remove/Replace – Very old
Repair
Bldg. 32 – South of Center – West wall
660 "100A PNL, 120/208V, 3PH, 4W
(new Sq D PNL fed from 30KVA
XFMR)"
NONE
Bldg. 32 – South of Center – West wall
661 30 KVA Transformer 480V?120/208V
NONE
Bldg. 32 - SE (Brown Structure)
662 "PNL- AB 125A 120/208V 3PH,
4W, Main Lug (new Sq D QO PNL)"
NONE Code Violation- needs correct lug (#4-#14AWG) for ground.
Repair
HANGAR 32 ELECTRICAL INSPECTION - MCKINSTRY CO
LOCATION "ID
TAG #"
EQUIPMENT DESCRIPTION RECOMMENDED
ACTION
McK REMARKS NOAA REMARKS FOR ADDITIONAL CLIN WORK
Bldg. 32 - SE 663 PNL-CB1 100A, 208V, 4W, Main Breaker
NONE Relocate for proper access
Bldg. 32 - SE 664 Disconnect S-5 125A Fused, 208V, 3PH, NONE
"Code Violation-Line side lugs not rated for (2)#2AWG, Load side not rated for #6 and #2AWG- Very old – Remove/Replace"
Remove / Replace if needed
Bldg. 32 – SE Stair Room 132C
665 PNL-C 3PH, Sub to P2 NONE Very old, Remove/Replace Remove - unclear if this has lighting circuits
Bldg. 32 – SE Stair Room 132C
666 FU-2 (2)100A Fuses 208V NONE Very old, Remove/Replace Remove
Bldg.32 667 Light Panel C Single Phase Bottom Right
NONE Very old, Remove/De-Energized
Remove - unclear if this has lighting circuits
Bldg.32 668 Panel Top Right (8)Glass Fuses 120/208V
NONE Very old, Remove/Replace Remove
Bldg.32 669 PNL-Z 200A, 120/208V, 3PH, 4W, Main Breaker
NONE
Bldg.32 670 PNL-Y 200A, 120/208V, 3PH, 4W, Main Breaker
NONE
Bldg. 671 75 KVA Transformer TT1 NONE
Bldg.32 672 PNL#5 225A, 120/208V NONE
Bldg.32 673 75 KVA Transformer #5 480?208V
NONE
Bldg.32 - South Wall - West
674 "PNL-AA 225A, 120/208V, 3PH,
4W, Main Breaker"
NONE
Bldg.32 - South Wall - West
675 PNL-A 100A 277/480V, 3PH,
4W, Main Breaker
NONE "Code Violation- Line side main breaker (2)#4AWG on each lug"
Repair
Bldg.32 - South Wall - West
676 75 KVA Transformer T-1 480?208V
NONE Top of transformer damaged
Bldg.32 - South Wall - West
677 "PNL-CB2 400A, 277/480V,
3PH, 4W,
Main Breaker"
NONE
Bldg.32 SW Room 149D 678 PNL-FU-1 (2)150A Fuses 120/208V
NONE Very old, Remove/Replace Remove
Bldg.32 SW Room 149D 679 PNL-D NONE Very old - Remove – De-Energized
Remove
Bldg.32 SW Room 149D 680 PNL-P2 NONE Very old - Remove – De-Energized
Remove
Bldg.32 - SW - Stair – 2nd floor
681 PNL-JJ 100A 1PH, 3W,
120/208V, Main Breaker
NONE Splices in panel Investigate for repair
Bldg.32-South-2nd floor-Hall/Center
682 PNL-F3 100A 277/480V, 3PH,
4W, Main Lugs
NONE "Code Violation- 480V PNL w/ 120/208V colors(Blk,Rd,Blu)"
Change marking on panel to conform with code.
#659
MULTIPLE
DISCONNECTS
#658 #657
UPPER FLOOR OF SOUTH LEAN-TO
IS ABANDONED. NO REQUIREMENT
TO RESTORE POWER TO THESE PANELS
New
MTS
GENERATOR
CONNECTION
CLIN 003
CLIN 004
CLIN 6 OPTIONAL
CLIN 001
CLIN 001
CLIN 003
CLIN 002
CLIN 002
CLIN 002
CLIN 002
CLIN 004
CLIN 004
CLIN 004
REPLACE
CLIN 005
CLIN 005
E6.01
TECHNICAL EXHIBIT #4
File details come from the government source that posted it. Updated .