Bldg 38 2024 5-Year Internal Pipe Inspection.pdf

PDF 219 KB Posted

Attached to
4240--Life Safety Equipment/Systems Maintenance (VA-25-00063754)
Solicitation number
36S79725Q0005
Issued by

About this file

This document is a Five Years Fire Sprinkler Inspection Report for Building #38, located at S 1st Ave in Hines, IL, conducted by Chicago Fire Protection on 2024-10-07. The comprehensive inspection covered multiple aspects of the fire sprinkler system, including internal pipe inspection, check valves, and riser systems. Key findings indicate that the internal pipes in multiple areas of the garage were free of debris, with the main pipe size being 4" and branch-line size 1 1/4", located at the south end of the building. The check valve by door P3 was found to be approximately 20' off the ground and passed all operational checks, including correct movement and good condition.

The inspection report shows no deficiencies were identified in the general questions, wet system questions, riser, internal pipe, or internal check valves sections. The next five-year internal pipe inspection is scheduled for 10/4/29. Both the inspector (Jeff Franco) and the client (Paul Coppola) signed the document on 2024-10-04, confirming that all equipment was left in operational condition upon completion of the inspection. The report includes photographic documentation of the internal check valve and pipe inspection, providing visual evidence of the system's condition.

View the file

Other files

File Type Posted
Bldg 37 2024 FM-200 Inspections.pdf PDF
Bldgs 37 38 2024 Fire Alarm Annual Inspection 9-25-24.pdf PDF
FM-200.2pic.jpg JPG image
VA Hines SDC Bldg 37 - Hydrants.pdf PDF
36S79725Q0005 0002.docx DOCX document
FM-200.jpg JPG image
Bldg 38 2024 Fire Sprinkler Hydrant Inspections.pdf PDF
Bldg 37 2024 5-Year Internal Pipe Inspection.pdf PDF
HYdrants and water supply.docx DOCX document
Bldg 37 2024 Fire Sprinkler Hydrant Inspections 10-4-24.pdf PDF
36S79725Q0005 0001_1.docx DOCX document
36S79725Q0005 0001.docx DOCX document
36S79725Q0005_1.docx DOCX document
Service Contract Act WD 2015-5017.pdf PDF
36S79725Q0005.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Report of Inspection / Test General Questions

W.O/JOB NUMBERS

Job Number CFP24-

Work Order Number 36S79724 P0015

LICENSE NUMBERS

License Number FSI0095, #1461658

ALARM DEVICES/RISER CHECK

11.2. Alarm valve interior including strainers, filters, and

restriction orifices (every five years)

N/A Alarm valve interior including strainers, filters, and restriction orifices (every five years)

N/A

SPRINKLERS (VISIBLE)

Test sprinklers in harsh or corrosive environment every 5 years or replace

N/A Test extra high temp sprinklers (325 degrees and up) every 5 years

N/A

Test sprinklers that are more than 75 years old N/A

PIPES AND FITTINGS (VISIBLE)

Has an internal investigation of the pipe been performed in the last 5 years? (If no, conduct investigation)

Yes

5 YEAR

Have the check valves been internally inspected? Yes Interior Inspection of external reset dry or pre-action valve. N/A

Have pressure reducing valves passed full flow test? N/A Flow test all wet and dry standpipes. N/A

Did the FDC piping pass the hydrostatic test? Yes Hydrostatic test manual dry standpipes. N/A

Has an internal pipe inspection been performed? Yes Test Sprinklers in harsh or corrosive environments. N/A

Have sprinklers above high temperature been tested? (325 degrees and up)

N/A Have backflow preventers been internally inspected to verify all components are in good condition, operate correctly and move freely?

N/A

Report of Inspection / Test Five Years Fire Sprinkler Inspection

2024-10-07 Property Building #38 S 1st Ave Hines IL 60141 Print Date: 2024-10-07

Conducted by: Jeff Franco

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Copyright 2024 Inspect Point

Report of Inspection / Test for System - Riser #1

INTERNAL PIPE INSPECTION

Date of last 5-year internal pipe inspection? 10/4/24 Date of next 5-year internal pipe inspection? 10/4/29

Main Size? 4" Branch-Line Size? 1 1/4"

Branch line location? south end of building

Internal pipe free of debris? Yes

If yes Size of lift needed? piping is approximat ely 25' high at peak of roof

Report of Inspection / Test Five Years Fire Sprinkler Inspection

2024-10-07 Property Building #38 S 1st Ave Hines IL 60141 Print Date: 2024-10-07

Conducted by: Jeff Franco

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Internal Pipe Five Year

Location Description Size Free of Debris

Pass Inspection

Next Five Year

Notes

Multiple areas of garage Head, line, main 1/2", 1 1/4", 4"

Yes Yes 10/4/24

Internal Check Valve Five Year

Location Description Size Manufacturer Operates Correctly

Moves Freely

Good Condition

Pass Inspection?

Notes

By door P3 FDC 4" Yes Yes Yes Yes Check valve is approximately 20' off ground need lift to access

Report of Inspection / Test Five Years Fire Sprinkler Inspection

2024-10-07 Property Building #38 S 1st Ave Hines IL 60141 Print Date: 2024-10-07

Conducted by: Jeff Franco

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Questions with Photos and Notes

Internal Check Valve - FDC By door P3

Notes:

Check valve is approximately 20' off ground need lift to access

Internal Pipe Inspection - Head, line, main Multiple areas of garage

Notes:

Report of Inspection / Test Five Years Fire Sprinkler Inspection

2024-10-07 Property Building #38 S 1st Ave Hines IL 60141 Print Date: 2024-10-07

Conducted by: Jeff Franco

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Report of Inspection / Test Five Years Fire Sprinkler Inspection

2024-10-07 Property Building #38 S 1st Ave Hines IL 60141 Print Date: 2024-10-07

Conducted by: Jeff Franco

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Deficiencies - General Questions

None

Deficiencies - General Wet System Questions

None

Deficiencies - Riser #1

None

Deficiencies - Internal Pipe

None

Deficiencies - Internal Check Valves

None

Report of Inspection / Test Five Years Fire Sprinkler Inspection

2024-10-07 Property Building #38 S 1st Ave Hines IL 60141 Print Date: 2024-10-07

Conducted by: Jeff Franco

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Inspector Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

Jeff Franco 2024-10-04

Client Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Client Name Signature Date Completed

Paul Coppola 2024-10-04

Report of Inspection / Test Five Years Fire Sprinkler Inspection

2024-10-07 Property Building #38 S 1st Ave Hines IL 60141 Print Date: 2024-10-07

Conducted by: Jeff Franco

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

File details come from the government source that posted it. Updated .