Bldg 37 2024 FM-200 Inspections.pdf
PDF 348 KB Posted
- Solicitation number
- 36S79725Q0005
About this file
This document is an Annual NFPA 2001 Report of Inspection/Test for clean agent fire suppression systems conducted by Chicago Fire Protection at Hines VA Building #37 in Hines, Illinois on 2024-09-26. The inspection covered three separate clean agent systems located in different rooms: TELCO room 127 (Clean Agent 1), UPS closet room (Clean Agent 2), and Server room C1085 (Clean Agent 3). Each system was a FM-200 type with a 4.5% design concentration, manufactured by Pyro Chem or Janus, and underwent comprehensive testing of cylinders, control panels, batteries, initiating devices, and notification devices.
The inspection revealed no deficiencies across all three systems. Key details include multiple smoke detectors, manual pull stations, horn strobes, and bells in each protected area. The systems had various components such as 180-360 degree nozzle types, mechanical time delays ranging from 30-60 seconds, and consistent battery specifications (12v, 8ah). All systems passed visual inspections, equipment checks, and device functionality tests. The inspection was completed by Ezequiel Valdivia and signed off by Paul Coppola, with the systems restored to normal operation on different dates in September 2024 between 12:00 pm and 3:00 pm.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bldgs 37 38 2024 Fire Alarm Annual Inspection 9-25-24.pdf | ||
| Bldg 38 2024 5-Year Internal Pipe Inspection.pdf | ||
| FM-200.2pic.jpg | JPG image | |
| VA Hines SDC Bldg 37 - Hydrants.pdf | ||
| 36S79725Q0005 0002.docx | DOCX document | |
| FM-200.jpg | JPG image | |
| Bldg 38 2024 Fire Sprinkler Hydrant Inspections.pdf | ||
| Bldg 37 2024 5-Year Internal Pipe Inspection.pdf | ||
| HYdrants and water supply.docx | DOCX document | |
| Bldg 37 2024 Fire Sprinkler Hydrant Inspections 10-4-24.pdf | ||
| 36S79725Q0005 0001_1.docx | DOCX document | |
| 36S79725Q0005 0001.docx | DOCX document | |
| 36S79725Q0005_1.docx | DOCX document | |
| Service Contract Act WD 2015-5017.pdf | ||
| 36S79725Q0005.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Report of Inspection / Test for - Clean Agent 1
System Info
Type FM-200 Facp Location TELCO room 127 in PIV
Manufacturer Pyro Chem Model 570006
Serial Number 4BW 450 Deck to Deck 50%
Design Concentration 4.5% Nozzle Type 180
Main and Reserve No Number of Exits 2
Sub Floor Yes Normal Ambient Temp 70 F
Dimensions 364"X131"X114" Area 47684
Volume 5435976 Fan Shutdown N/A
Mechanical Time Delay 30 sec Audio Visual Signal Make Wheelock
Number of Distribution Lines 3 Pressure Switch Installed 1
Release Boxes 1 Number of Reserve Cylinders 0
Cylinder Counts
Number of Agent Cylinders 0 Number of Pilot Cylinders 1
VISUAL INSPECTION
Are manual controls unobstructed? Yes Does the system show no physical damage that would prevent operation?
Yes
Are the pressure gauges in the operable range? Yes Has the protected equipment and/or hazard remained unchanged?
N/A
Is the releasing panel powered and free of supervisory, trouble or alarm conditions?
Yes Have all of the deficiencies been corrected since last inspection?
N/A
CONTAINERS(S)
Have Container(s) (over 5 years past testing or discharged) been inspected per the CGA C-6 (section 3)?
Yes Are Container(s) Visually Inspected for Proper Support? Yes
Have Container(s) been weighed and/or pressures been recorded?
Yes Are Container(s) Free of Physical Damage? Yes
Are Container(s) weight (halocarbon) and/or pressure (inert) measurement recorded at container location?
Yes Have the clean agents not loss more than 5% (halocarbons
- weight / inert gas - pressure)?
Yes
EQUIPMENT INSPECTION
Is Piping Properly Installed and Supported? Yes Are Nozzle Deflector Plates installed Properly? Yes
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Copyright 2024 Inspect Point
Are the Flexible Hoses on the units free from visual damage?
N/A Is the Piping Network free from Visual Damage? Yes
Are the Gauges Calibrated? Yes Are All Door(s) Exiting Protected Area Self Closing? Yes
Are All Nozzles in Place and are Properly Orientated? Yes Are Door(s) Sweep(s) Seals in Place? Yes
Is Room Integrity Visually Inspected for Areas of Potential Leakage?
Yes
INSPECTION INFORMATION
System Restored To Normal Operation Time: 12:00pm System Restored To Normal Operation Date: 9/26/24
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
CYLINDERS
Location Manufacturer Serial Number
Size Last Tested At Condition Net Weight/ Agent
Full Weight/ Cylinder
Pressure Ambient Temp.
Tare Weight
Is Liquid Liquid Level Reading
Pass/Fail
TELCO room 127 in
PIV
Pyro Chem
4BW
Good 105# 216.5# 360 psi 70F 108# No Pass
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS
Address Location Device Type Factory Setting
Measured Setting
Visual Functional Pass/Fail
W room W item Smoke Detector Yes Yes Pass
W room E item Smoke Detector Yes Yes Pass
E room W item Smoke Detector Yes Yes Pass
E room W item under floor
Smoke Detector Yes Yes Pass
E room E item Smoke Detector Yes Yes Pass
E room E item under floor
Smoke Detector Yes Yes Pass
Above panel Manual Pull Station Yes Yes Pass
Above panel Bell Yes Yes Pass
Above panel Horn Strobe Yes Yes Pass
Outside PIV office Horn Strobe Yes Yes Pass
Outside TELCO room
Horn Strobe Yes Yes Pass
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Control Panel and Battery Readings
Location: In PIV
Manufacturer: Pyro Chem
Model: PCR-100
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 100%
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
Yes 12 v 8 ah
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12 v 8 ah
Second Battery
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
100%
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Yes 12v 8ah
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12v 8ah
Comments
Report of Inspection / Test for - clean_agent 2
System Info
Type FM-200 Facp Location UPS closet room C1060B
Manufacturer Janus Model 18525
Deck to Deck Yes Design Concentration 4.5%
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Nozzle Type 180 Main and Reserve No
Number of Exits 2 Sub Floor No
Normal Ambient Temp 70 F Mechanical Time Delay 60 sec
Audio Visual Signal Make Potter Number of Distribution Lines 2
Pressure Switch Installed 1 Release Boxes 2
Number of Reserve Cylinders 0
Cylinder Counts
Number of Agent Cylinders 0 Number of Pilot Cylinders 1
VISUAL INSPECTION
Are manual controls unobstructed? Yes Is the releasing panel powered and free of supervisory, trouble or alarm conditions?
Yes
Has the protected equipment and/or hazard remained unchanged?
N/A Have all of the deficiencies been corrected since last inspection?
N/A
Are the pressure gauges in the operable range? Yes Does the system show no physical damage that would prevent operation?
Yes
CONTAINERS(S)
Are Container(s) Free of Physical Damage? Yes Have the clean agents not loss more than 5% (halocarbons
- weight / inert gas - pressure)?
Yes
Have Container(s) (over 5 years past testing or discharged) been inspected per the CGA C-6 (section 3)?
N/A Have Container(s) been weighed and/or pressures been recorded?
Yes
Are Container(s) Visually Inspected for Proper Support? N/A Are Container(s) weight (halocarbon) and/or pressure (inert) measurement recorded at container location?
Yes
EQUIPMENT INSPECTION
Are All Nozzles in Place and are Properly Orientated? Yes Is Piping Properly Installed and Supported? Yes
Are Nozzle Deflector Plates installed Properly? Yes Are the Gauges Calibrated? Yes
Are All Door(s) Exiting Protected Area Self Closing? Yes Is Room Integrity Visually Inspected for Areas of Potential Leakage?
Yes
Are Door(s) Sweep(s) Seals in Place? Yes Is the Piping Network free from Visual Damage? Yes
Are the Flexible Hoses on the units free from visual damage?
N/A
INSPECTION INFORMATION
System Restored To Normal Operation Date: 9/26/24 System Restored To Normal Operation Time: 1:00pm
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Number
Size Last Tested At Condition Net Weight/ Agent
Full Weight/ Cylinder
Pressure Ambient Temp.
Tare Weight
Is Liquid Liquid Level Reading
Pass/Fail
In room C1060B UUPS closet
Janus /Manches ter
AA945
Good 181# 365.4# 360psi 70F 177.6
Yes 32" Pass
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Setting
Measured Setting
Visual Functional Pass/Fail
By cylinder Bell Yes Yes Pass
Above panel Smoke Detector Yes Yes Pass
Above the cylinder Smoke Detector Yes Yes Pass
By the bell Horn Strobe Yes Yes Pass
Outside room Horn Strobe Yes Yes Pass
Below panel Manual Pull Station Yes Yes Pass
In actuator Tamper Switch Yes Yes Pass
Cerberus room C1060A
Manual Pull Station Yes Yes Pass
Room C1060A Horn Strobe Yes Yes Pass
Room C1060A Horn Strobe Yes Yes Pass
Room C1060A Bell Yes Yes Pass
Outside room C1060A
Horn Strobe Yes Yes Pass
Room C1060A Smoke Detector Yes Yes Pass
Room C1060A Smoke Detector Yes Yes Pass
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Location: UPS closet room C1060B
Manufacturer: Janus
Model: JFS-C1
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120 100%
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
12v 8ah
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12v 8ah
Second Battery
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
100%
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
12v 8ah
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12v 8ah
Comments
Report of Inspection / Test for - clean_agent 3
System Info
Type FM-200 Facp Location Server room C1085
Manufacturer Pyro Chem Model 570006
Ceiling Type Ceiling tile Deck to Deck No
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Design Concentration 4.5% Nozzle Type 360
Main and Reserve No Number of Exits 2
Sub Floor No Normal Ambient Temp 70
Fan Shutdown Yes Mechanical Time Delay 30 sec
Audio Visual Signal Make Hochiki Installed Date 2024-05-05
Number of Distribution Lines 1 Pressure Switch Installed 1
Release Boxes 1 Number of Reserve Cylinders 0
Cylinder Counts
Number of Agent Cylinders 0 Number of Pilot Cylinders 1
VISUAL INSPECTION
Are manual controls unobstructed? Yes Has the protected equipment and/or hazard remained unchanged?
N/A
Have all of the deficiencies been corrected since last inspection?
Yes Are the pressure gauges in the operable range? Yes
Is the releasing panel powered and free of supervisory, trouble or alarm conditions?
Yes Does the system show no physical damage that would prevent operation?
Yes
CONTAINERS(S)
Have the clean agents not loss more than 5% (halocarbons
- weight / inert gas - pressure)?
Yes Are Container(s) weight (halocarbon) and/or pressure (inert) measurement recorded at container location?
Yes
Have Container(s) been weighed and/or pressures been recorded?
Yes Are Container(s) Free of Physical Damage? Yes
Are Container(s) Visually Inspected for Proper Support? Yes Have Container(s) (over 5 years past testing or discharged) been inspected per the CGA C-6 (section 3)?
N/A
EQUIPMENT INSPECTION
Is the Piping Network free from Visual Damage? Yes Are the Gauges Calibrated? Yes
Is Room Integrity Visually Inspected for Areas of Potential Leakage?
Yes Are Nozzle Deflector Plates installed Properly? Yes
Are All Door(s) Exiting Protected Area Self Closing? Yes Are All Nozzles in Place and are Properly Orientated? Yes
Are Door(s) Sweep(s) Seals in Place? Yes Is Piping Properly Installed and Supported? Yes
Are the Flexible Hoses on the units free from visual damage?
N/A
INSPECTION INFORMATION
System Restored To Normal Operation Date: 9/25/24 System Restored To Normal Operation Time: 3:00pm
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Number
Size Last Tested At Condition Net Weight/ Agent
Full Weight/ Cylinder
Pressure Ambient Temp.
Tare Weight
Is Liquid Liquid Level Reading
Pass/Fail
Server room Pyro Chem
57000
Good 98# 208.5# 360psi 70F 107.5
No Pass
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Setting
Measured Setting
Visual Functional Pass/Fail
By cylinder Manual Pull Station Yes Yes Pass
Above cylinder Bell Yes Yes Pass
Above cylinder Smoke Detector Yes Yes Pass
Further end of the room
Smoke Detector Yes Yes Pass
Inside by double door
Horn Strobe Yes Yes Pass
Outside by double doors
Horn Strobe Yes Yes Pass
Above cylinder Strobe Yes Yes Pass
Outside by entrance door
Strobe Yes Yes Pass
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Location: Server room C1085
Manufacturer: Auto pulse
Model: 542R
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
120v 100%
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
Ground Fault
12v 8ah
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12v 8ah
Second Battery
AC Power Supply Volts
AC
DC Power Supply Volts
DC
Load Test % Battery w/Charger Battery w/Out Charger
100%
Battery Date AC Loss Causes Trouble
DC Loss Causes Trouble
Battery Voltage & AH Rating
12v 8ah
Battery Voltage AH Rating
Battery Voltage AH Rating w/Charger
Battery Voltage AH Rating w/Out Charger
Battery Voltage & AH Rating Under Load
12v 8ah
Comments
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Deficiencies - Clean Agent 1
None
Deficiencies - clean_agent 2
None
Deficiencies - clean_agent 3
None
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
Ezequiel Valdivia 2024-09-26
Client Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Client Name Signature Date Completed
Paul Coppola 2024-09-26
Report of Inspection / Test Annual NFPA 2001
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Conducted by: Ezequiel Valdivia
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
File details come from the government source that posted it. Updated .