Bldg 37 2024 FM-200 Inspections.pdf

PDF 348 KB Posted

Attached to
4240--Life Safety Equipment/Systems Maintenance (VA-25-00063754)
Solicitation number
36S79725Q0005
Issued by

About this file

This document is an Annual NFPA 2001 Report of Inspection/Test for clean agent fire suppression systems conducted by Chicago Fire Protection at Hines VA Building #37 in Hines, Illinois on 2024-09-26. The inspection covered three separate clean agent systems located in different rooms: TELCO room 127 (Clean Agent 1), UPS closet room (Clean Agent 2), and Server room C1085 (Clean Agent 3). Each system was a FM-200 type with a 4.5% design concentration, manufactured by Pyro Chem or Janus, and underwent comprehensive testing of cylinders, control panels, batteries, initiating devices, and notification devices.

The inspection revealed no deficiencies across all three systems. Key details include multiple smoke detectors, manual pull stations, horn strobes, and bells in each protected area. The systems had various components such as 180-360 degree nozzle types, mechanical time delays ranging from 30-60 seconds, and consistent battery specifications (12v, 8ah). All systems passed visual inspections, equipment checks, and device functionality tests. The inspection was completed by Ezequiel Valdivia and signed off by Paul Coppola, with the systems restored to normal operation on different dates in September 2024 between 12:00 pm and 3:00 pm.

View the file

Other files

File Type Posted
Bldgs 37 38 2024 Fire Alarm Annual Inspection 9-25-24.pdf PDF
Bldg 38 2024 5-Year Internal Pipe Inspection.pdf PDF
FM-200.2pic.jpg JPG image
VA Hines SDC Bldg 37 - Hydrants.pdf PDF
36S79725Q0005 0002.docx DOCX document
FM-200.jpg JPG image
Bldg 38 2024 Fire Sprinkler Hydrant Inspections.pdf PDF
Bldg 37 2024 5-Year Internal Pipe Inspection.pdf PDF
HYdrants and water supply.docx DOCX document
Bldg 37 2024 Fire Sprinkler Hydrant Inspections 10-4-24.pdf PDF
36S79725Q0005 0001_1.docx DOCX document
36S79725Q0005 0001.docx DOCX document
36S79725Q0005_1.docx DOCX document
Service Contract Act WD 2015-5017.pdf PDF
36S79725Q0005.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Report of Inspection / Test for - Clean Agent 1

System Info

Type FM-200 Facp Location TELCO room 127 in PIV

Manufacturer Pyro Chem Model 570006

Serial Number 4BW 450 Deck to Deck 50%

Design Concentration 4.5% Nozzle Type 180

Main and Reserve No Number of Exits 2

Sub Floor Yes Normal Ambient Temp 70 F

Dimensions 364"X131"X114" Area 47684

Volume 5435976 Fan Shutdown N/A

Mechanical Time Delay 30 sec Audio Visual Signal Make Wheelock

Number of Distribution Lines 3 Pressure Switch Installed 1

Release Boxes 1 Number of Reserve Cylinders 0

Cylinder Counts

Number of Agent Cylinders 0 Number of Pilot Cylinders 1

VISUAL INSPECTION

Are manual controls unobstructed? Yes Does the system show no physical damage that would prevent operation?

Yes

Are the pressure gauges in the operable range? Yes Has the protected equipment and/or hazard remained unchanged?

N/A

Is the releasing panel powered and free of supervisory, trouble or alarm conditions?

Yes Have all of the deficiencies been corrected since last inspection?

N/A

CONTAINERS(S)

Have Container(s) (over 5 years past testing or discharged) been inspected per the CGA C-6 (section 3)?

Yes Are Container(s) Visually Inspected for Proper Support? Yes

Have Container(s) been weighed and/or pressures been recorded?

Yes Are Container(s) Free of Physical Damage? Yes

Are Container(s) weight (halocarbon) and/or pressure (inert) measurement recorded at container location?

Yes Have the clean agents not loss more than 5% (halocarbons

- weight / inert gas - pressure)?

Yes

EQUIPMENT INSPECTION

Is Piping Properly Installed and Supported? Yes Are Nozzle Deflector Plates installed Properly? Yes

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Copyright 2024 Inspect Point

Are the Flexible Hoses on the units free from visual damage?

N/A Is the Piping Network free from Visual Damage? Yes

Are the Gauges Calibrated? Yes Are All Door(s) Exiting Protected Area Self Closing? Yes

Are All Nozzles in Place and are Properly Orientated? Yes Are Door(s) Sweep(s) Seals in Place? Yes

Is Room Integrity Visually Inspected for Areas of Potential Leakage?

Yes

INSPECTION INFORMATION

System Restored To Normal Operation Time: 12:00pm System Restored To Normal Operation Date: 9/26/24

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

CYLINDERS

Location Manufacturer Serial Number

Size Last Tested At Condition Net Weight/ Agent

Full Weight/ Cylinder

Pressure Ambient Temp.

Tare Weight

Is Liquid Liquid Level Reading

Pass/Fail

TELCO room 127 in

PIV

Pyro Chem

4BW

Good 105# 216.5# 360 psi 70F 108# No Pass

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Address Location Device Type Factory Setting

Measured Setting

Visual Functional Pass/Fail

W room W item Smoke Detector Yes Yes Pass

W room E item Smoke Detector Yes Yes Pass

E room W item Smoke Detector Yes Yes Pass

E room W item under floor

Smoke Detector Yes Yes Pass

E room E item Smoke Detector Yes Yes Pass

E room E item under floor

Smoke Detector Yes Yes Pass

Above panel Manual Pull Station Yes Yes Pass

Above panel Bell Yes Yes Pass

Above panel Horn Strobe Yes Yes Pass

Outside PIV office Horn Strobe Yes Yes Pass

Outside TELCO room

Horn Strobe Yes Yes Pass

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Control Panel and Battery Readings

Location: In PIV

Manufacturer: Pyro Chem

Model: PCR-100

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 100%

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

Yes 12 v 8 ah

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12 v 8 ah

Second Battery

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

100%

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Yes 12v 8ah

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12v 8ah

Comments

Report of Inspection / Test for - clean_agent 2

System Info

Type FM-200 Facp Location UPS closet room C1060B

Manufacturer Janus Model 18525

Deck to Deck Yes Design Concentration 4.5%

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Nozzle Type 180 Main and Reserve No

Number of Exits 2 Sub Floor No

Normal Ambient Temp 70 F Mechanical Time Delay 60 sec

Audio Visual Signal Make Potter Number of Distribution Lines 2

Pressure Switch Installed 1 Release Boxes 2

Number of Reserve Cylinders 0

Cylinder Counts

Number of Agent Cylinders 0 Number of Pilot Cylinders 1

VISUAL INSPECTION

Are manual controls unobstructed? Yes Is the releasing panel powered and free of supervisory, trouble or alarm conditions?

Yes

Has the protected equipment and/or hazard remained unchanged?

N/A Have all of the deficiencies been corrected since last inspection?

N/A

Are the pressure gauges in the operable range? Yes Does the system show no physical damage that would prevent operation?

Yes

CONTAINERS(S)

Are Container(s) Free of Physical Damage? Yes Have the clean agents not loss more than 5% (halocarbons

- weight / inert gas - pressure)?

Yes

Have Container(s) (over 5 years past testing or discharged) been inspected per the CGA C-6 (section 3)?

N/A Have Container(s) been weighed and/or pressures been recorded?

Yes

Are Container(s) Visually Inspected for Proper Support? N/A Are Container(s) weight (halocarbon) and/or pressure (inert) measurement recorded at container location?

Yes

EQUIPMENT INSPECTION

Are All Nozzles in Place and are Properly Orientated? Yes Is Piping Properly Installed and Supported? Yes

Are Nozzle Deflector Plates installed Properly? Yes Are the Gauges Calibrated? Yes

Are All Door(s) Exiting Protected Area Self Closing? Yes Is Room Integrity Visually Inspected for Areas of Potential Leakage?

Yes

Are Door(s) Sweep(s) Seals in Place? Yes Is the Piping Network free from Visual Damage? Yes

Are the Flexible Hoses on the units free from visual damage?

N/A

INSPECTION INFORMATION

System Restored To Normal Operation Date: 9/26/24 System Restored To Normal Operation Time: 1:00pm

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Number

Size Last Tested At Condition Net Weight/ Agent

Full Weight/ Cylinder

Pressure Ambient Temp.

Tare Weight

Is Liquid Liquid Level Reading

Pass/Fail

In room C1060B UUPS closet

Janus /Manches ter

AA945

Good 181# 365.4# 360psi 70F 177.6

Yes 32" Pass

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Setting

Measured Setting

Visual Functional Pass/Fail

By cylinder Bell Yes Yes Pass

Above panel Smoke Detector Yes Yes Pass

Above the cylinder Smoke Detector Yes Yes Pass

By the bell Horn Strobe Yes Yes Pass

Outside room Horn Strobe Yes Yes Pass

Below panel Manual Pull Station Yes Yes Pass

In actuator Tamper Switch Yes Yes Pass

Cerberus room C1060A

Manual Pull Station Yes Yes Pass

Room C1060A Horn Strobe Yes Yes Pass

Room C1060A Horn Strobe Yes Yes Pass

Room C1060A Bell Yes Yes Pass

Outside room C1060A

Horn Strobe Yes Yes Pass

Room C1060A Smoke Detector Yes Yes Pass

Room C1060A Smoke Detector Yes Yes Pass

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Location: UPS closet room C1060B

Manufacturer: Janus

Model: JFS-C1

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120 100%

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

12v 8ah

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12v 8ah

Second Battery

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

100%

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

12v 8ah

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12v 8ah

Comments

Report of Inspection / Test for - clean_agent 3

System Info

Type FM-200 Facp Location Server room C1085

Manufacturer Pyro Chem Model 570006

Ceiling Type Ceiling tile Deck to Deck No

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Design Concentration 4.5% Nozzle Type 360

Main and Reserve No Number of Exits 2

Sub Floor No Normal Ambient Temp 70

Fan Shutdown Yes Mechanical Time Delay 30 sec

Audio Visual Signal Make Hochiki Installed Date 2024-05-05

Number of Distribution Lines 1 Pressure Switch Installed 1

Release Boxes 1 Number of Reserve Cylinders 0

Cylinder Counts

Number of Agent Cylinders 0 Number of Pilot Cylinders 1

VISUAL INSPECTION

Are manual controls unobstructed? Yes Has the protected equipment and/or hazard remained unchanged?

N/A

Have all of the deficiencies been corrected since last inspection?

Yes Are the pressure gauges in the operable range? Yes

Is the releasing panel powered and free of supervisory, trouble or alarm conditions?

Yes Does the system show no physical damage that would prevent operation?

Yes

CONTAINERS(S)

Have the clean agents not loss more than 5% (halocarbons

- weight / inert gas - pressure)?

Yes Are Container(s) weight (halocarbon) and/or pressure (inert) measurement recorded at container location?

Yes

Have Container(s) been weighed and/or pressures been recorded?

Yes Are Container(s) Free of Physical Damage? Yes

Are Container(s) Visually Inspected for Proper Support? Yes Have Container(s) (over 5 years past testing or discharged) been inspected per the CGA C-6 (section 3)?

N/A

EQUIPMENT INSPECTION

Is the Piping Network free from Visual Damage? Yes Are the Gauges Calibrated? Yes

Is Room Integrity Visually Inspected for Areas of Potential Leakage?

Yes Are Nozzle Deflector Plates installed Properly? Yes

Are All Door(s) Exiting Protected Area Self Closing? Yes Are All Nozzles in Place and are Properly Orientated? Yes

Are Door(s) Sweep(s) Seals in Place? Yes Is Piping Properly Installed and Supported? Yes

Are the Flexible Hoses on the units free from visual damage?

N/A

INSPECTION INFORMATION

System Restored To Normal Operation Date: 9/25/24 System Restored To Normal Operation Time: 3:00pm

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Number

Size Last Tested At Condition Net Weight/ Agent

Full Weight/ Cylinder

Pressure Ambient Temp.

Tare Weight

Is Liquid Liquid Level Reading

Pass/Fail

Server room Pyro Chem

57000

Good 98# 208.5# 360psi 70F 107.5

No Pass

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Setting

Measured Setting

Visual Functional Pass/Fail

By cylinder Manual Pull Station Yes Yes Pass

Above cylinder Bell Yes Yes Pass

Above cylinder Smoke Detector Yes Yes Pass

Further end of the room

Smoke Detector Yes Yes Pass

Inside by double door

Horn Strobe Yes Yes Pass

Outside by double doors

Horn Strobe Yes Yes Pass

Above cylinder Strobe Yes Yes Pass

Outside by entrance door

Strobe Yes Yes Pass

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Location: Server room C1085

Manufacturer: Auto pulse

Model: 542R

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

120v 100%

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

Ground Fault

12v 8ah

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12v 8ah

Second Battery

AC Power Supply Volts

AC

DC Power Supply Volts

DC

Load Test % Battery w/Charger Battery w/Out Charger

100%

Battery Date AC Loss Causes Trouble

DC Loss Causes Trouble

Battery Voltage & AH Rating

12v 8ah

Battery Voltage AH Rating

Battery Voltage AH Rating w/Charger

Battery Voltage AH Rating w/Out Charger

Battery Voltage & AH Rating Under Load

12v 8ah

Comments

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Deficiencies - Clean Agent 1

None

Deficiencies - clean_agent 2

None

Deficiencies - clean_agent 3

None

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Inspector Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

Ezequiel Valdivia 2024-09-26

Client Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Client Name Signature Date Completed

Paul Coppola 2024-09-26

Report of Inspection / Test Annual NFPA 2001

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Conducted by: Ezequiel Valdivia

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com