Bldg 37 2024 Fire Sprinkler Hydrant Inspections 10-4-24.pdf
PDF 733 KB Posted
- Solicitation number
- 36S79725Q0005
About this file
This document is an Annual Fire Sprinkler Inspection Report for the Hines VA Building #37 located in Hines, IL, conducted by Chicago Fire Protection on October 1, 2024. The comprehensive inspection revealed several critical deficiencies, including issues with fire hydrants, fire department connection gaskets, and valve maintenance. Specifically, the report noted that 3 out of 10 fire hydrants did not properly drain after testing, posing a potential freezing risk in winter, and all 10 fire department connections have dry-rotted or missing gaskets that need replacement.
The inspection covered multiple building systems, including 13 wet systems and 1 dry system, with detailed assessments of control valves, alarm devices, inspector's test pipes, and various risers. While most systems functioned adequately, the report highlighted several non-critical deficiencies that require 5-year inspections, such as lack of internal piping assessments, outdated gauges, and unexamined check valves. The deficiencies were categorized with varying levels of urgency, with some marked as impairments that need immediate attention to ensure the building's fire protection system remains fully operational and compliant with safety standards.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bldg 37 2024 FM-200 Inspections.pdf | ||
| Bldgs 37 38 2024 Fire Alarm Annual Inspection 9-25-24.pdf | ||
| Bldg 38 2024 5-Year Internal Pipe Inspection.pdf | ||
| FM-200.2pic.jpg | JPG image | |
| VA Hines SDC Bldg 37 - Hydrants.pdf | ||
| 36S79725Q0005 0002.docx | DOCX document | |
| FM-200.jpg | JPG image | |
| Bldg 38 2024 Fire Sprinkler Hydrant Inspections.pdf | ||
| Bldg 37 2024 5-Year Internal Pipe Inspection.pdf | ||
| HYdrants and water supply.docx | DOCX document | |
| 36S79725Q0005 0001_1.docx | DOCX document | |
| 36S79725Q0005 0001.docx | DOCX document | |
| 36S79725Q0005_1.docx | DOCX document | |
| Service Contract Act WD 2015-5017.pdf | ||
| 36S79725Q0005.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Report of Inspection / Test General Questions
W.O/JOB NUMBERS
W.O.#: 36S79724 P0015
JOB#: CFP24-
LICENSE NUMBERS
State License #: FSI0095 UA #: 1461646
CHICAGO SPRINKLER INVENTORY
# of Wet Systems in the Building: 13 # of Dry Systems in the Building: 1
# of Wet Systems Tested on Report: 13 # of Dry Systems Tested on Report: 1
SYSTEM STATUS
1. Is the system in service? Yes 2. Attach a copy of your owner information from with all questions answered and signed by the owner/representative. Required by the Chicago Fire Department in order to submit the report.
N/A
Is the building occupied? Yes Are all fire protection systems in service? Yes
Has the occupancy classification, hazard of contents, and/or storage method remained the same since the last inspection?
Yes Has the system remained in service without modification since the last inspection?
Yes
Was the system free of actuations of devices or alarms since the last inspection?
Yes
BACKFLOW
3. Are the isolation backflow valves in the open position and secured or supervised?
Yes Is relief port on RPZ device not discharging? N/A
CONTROL VALVES
4. Are the control valves with electrical supervision in correct (open or closed) position?
Yes 5. Are the control valves secured or supervised? supervised
Are the control valves supervised with seals locked or is supervision in place?
Yes Are the control valves supervised with seals accessible? N/A
6. Are the control valves accesible? Yes 7. Are the control valves free from damage or leaks? Yes
Are the control valves supervised with seals free from leaks?
N/A 8. Do the control valves have proper signage displayed? Yes
Are the control valves supervised with seals have appropriate wrenches?
N/A 9. All control valves operated through full range of motion and returned to normal position (where a fire pump test header valve is present - disregard as it will be tested during the annual fire pump test)
Yes
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Copyright 2024 Inspect Point
Are the control valves supervised with seals properly identified?
N/A 10. Were the control valves outside Stem & Yoke valve stems lubricated?
Yes
Are the control valves with locks in correct (open or closed) position?
N/A Are the control valves with locks locked or is supervision in place?
N/A
10.1. Post Indicator Valves (PIVs) are provided with correct
wrenches?
Yes Are the control valves with locks accessible? N/A
Are the control valves with electrical supervision locked or is supervision in place?
Yes Are the control valves with locks free from any leaks? N/A
Are the control valves with electrical supervision accessible?
Yes Are the control valves with electrical supervision free from any leaks?
Yes
Are the control valves with locks have the appropriate wrenches?
N/A Are the control valves with electrical supervision have the appropriate wrenches?
N/A
Are the control valves with locks properly identified? N/A Are the control valves with electrical supervision properly identified?
Yes
Water Flow (sec.) N/A
ALARM DEVICES/RISER CHECK
11. Are the water flow alarm devices are free of damage? Yes 12. Do the water flow alarm devices operate correctly when the inspector's test valve is opened and flow observed?
Yes
13. Do the supervisory switches functions properly? Yes 14. Are there records that substantiate that the check valves have been internally inspected and verified to have been working correctly in the past (5) years?
No
15. Outside 10 inch bell(s) present and operates correctly Yes 16. Inside 6" bell present and operates correctly Yes
Are alarms and supervisory devices not damaged? Yes
INSPECTOR'S TEST PIPE (ITV)
17. Was the most remote inspector's test pipe (ITV) operated and flow witnessed in a single-story structure?
Note: Buildings under city pressure only, no fire pump
N/A 17.1 Was the test and drain operated and flow witnessed on each floor level of a multi-level structure?
N/A
FIRE DEPARTMENT CONNECTIONS
18. Are the fire department connection(s) visible and accessible?
Yes Are the FDC caps and plugs in place and undamaged? Yes
18.1. Check valve is not leaking Yes Is the FDC check valve free of leaks? Yes
18.2. Visible piping supplying the fire department
connection is undamaged
Yes Is the clapper and automatic drain valve in place and properly operating?
Yes
18.3. Piping from fire department connection to fire
department connection check valve has been hydrostatically tested at 150 psi (10 bar) for at least 2 hours
No Is the FDC identification sign(s) in place? Yes
Has the interior of the FDC been inspected for obstructions?
No 19. Do the fire department connection(s) swivels operate correctly?
Yes
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
20. Are the fire department connection(s) plugs or tamper covers in place?
Yes 21. Are the fire department connection(s) gaskets in place and not damaged?
No
Is the FDC easily accessible? Yes 22. Is the fire department connection ball drip valve functional?
Yes
23. In buildings that are not fully sprinklered (e.g. - garage only) are system Identification signs adjacent to the FDC in place and accurate?
N/A 24. In high-rise buildings with multiple zones, are zone identification signs adjacent to the FDC in place and accurate?
N/A
25. Is the fire department connection interior visibly clear of obstructions?
N/A 26. Do the fire department connection flapper(s) operates correctly?
N/A
SPRINKLERS (VISIBLE)
27. Are fire sprinklers free of damage or leaks? Yes 28. Sprinklers and concealed cover plates (if present) are free of corrosion, foreign material, or paint
N/A
29. Are fire sprinklers installed in proper orientation? Yes 30. Do all sprinklers have fluid in glass bulbs, if applicable? Yes
31. Loading - sprinklers are free of accumulated dust or grease
Yes 32. Minimum clearance maintained between sprinklers and storage
Yes
33. Sprinklers tested or replaced due to age - per appropriate testing schedule
N/A 34. Spare sprinkler heads - Proper number and type, including installation wrench
Yes
35. The inspector/tester did not find any recalled devices during the visual inspection
Yes Are visible sprinklers in the proper position: upright, pendent, sidewall?
Yes
Are visible sprinklers free of corrosion and physical damage?
Yes Is there proper clearance below the sprinklers? Yes
Is there liquid in all visible glass bulb sprinklers? Yes Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?
N/A
Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?
N/A Dry-type sprinklers replaced or successfully sample tested within last 10 years?
N/A
Have sprinklers subject to harsh environments been replaced or successfully sample tested in the last 5 years?
N/A Are there spare sprinklers and a sprinkler wrench? Yes
HANGERS/SEISMIC BRACING
36. Are visible hangers/seismic bracing in good condition and not damaged or loose?
Yes
DRY SPRINKLER SYSTEMS
37. Did dry pipe test pass NFPA 25 requirements? Yes 38. Were the dry pipe system low points drained in accordance with NFPA 25 and the system restored to service?
Yes
PIPES AND FITTINGS (VISIBLE)
37. Are all visible pipes and fittings in good condition with no external corrosion?
Yes 38. Are the visible pipes and valves free of mechanical damage or leaks?
Yes
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
39. Is visible piping in correct alignment? Yes 40. Are the visible pipes free of external loads? Yes
41. Is all wet piping protected from freezing temperatures? Yes 42. Was an assessment of the internal condition of piping was conducted (every 5 years)?
No
42.1. Was an obstruction investigation conducted if
warranted by internal assessment inspection?
N/A Are visible hangers/seismic bracing in good condition and not damaged or loose?
Yes
MAIN DRAIN TEST
43. Are the main drain test results within 10% from the previous annual test? (document static and residual pressure on the submitted test report)?
Yes 43.1a. Main drain test - if the sole purpose is through a backflow preventer or pressure reducing valve. Static PSI
43.1b. Maind drain test - if the sole purpose is through a backflow preventer or pressure reducing valve. Residual
PSI ____
GAUGES
44. Are all gauges in good operating condition? Yes 45. Gauges - normal water pressure maintained ____PSI? 65
46. Are all gauges tested or replaced every 5 years? No Are all check valves externally inspected, operating properly, and are in good condition?
No
Are the gauges on system showing normal water supply pressure?
Yes Are Pressure reducing valves in good condition including no handwheels broken?
N/A
Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed?
Yes Do valve supervisory switches indicate movement? Yes
The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed?
Yes Are the gauges on system operable and in good working condition?
Yes
Are Pressure reducing valves (sprinkler system) in open position and not leaking?
N/A Are Pressure reducing valves (sprinkler system) with downstream pressure per the design?
N/A
All control valves operated through full range and returned to normal position?
Yes
UNCOMMON WET PIPE SYSTEM TYPES
47. Are there any Non-Freezing System (not to exceed 20 sprinklers)
N/A 47.1. Has the antifreeze solution been tested? N/A
48. Are there any Foam System(s)? (If any of the following systems are present - please provide a full inspection and submit a separate test report to the appropriate equipment profile)
N/A 49. Are there any dry pipe sprinkler systems? N/A
50. Are there any pre-action systems, individual report per system?
Yes 51. Are there any Deluge System(s)? N/A
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
INSPECTION/TESTING CONCLUSION
52. Is the system free of impairments? No 53. Notifications have been made to the monitoring entity, building management, and AHJ as necessary?
Yes
54. Has the system been restored to normal operation? Yes
5 YEAR
Are all check valve parts operating properly and are in good condition?
N/A Have strainers, filters, restricted orifices and diaphragm chambers on valves and trim passed internal inspection?
No
Have gauges been checked by a calibrated gauge or replaced?
No Have alarm valves and associated strainers, filters, and restricted orifices pass an internal inspection?
N/A
Deficiency Notes
List any deficiency repairs to be done: N/A
Signature
55. Signature of Technician N/A 56. Signature of building representative N/A
57. Attach signatures (Optional) N/A
WATERFLOWS
Did all water flows operate correctly? Yes
ALARMS
Is the alarm valve free from physical damage? N/A Is the trim in correct (open or closed) position? N/A
Is there no leakage in the retarding chamber or drains? Yes
VALVE AREA
Are valve enclosures maintaining a minimum of 40 degrees F?
Yes Are gauges on non-supervised systems in good condition and showing normal water and air pressure?
Yes
Have manual activation devices passed test? Yes
PREACTION VALVES
For freezer systems, gauge near compressor reading the same as gauge near the preaction valve?
N/A Are preaction and deluge valves free from physical damage?
Yes
Are the electrical components in service? Yes Are trim valves in appropriate (open or closed) position? Yes
Is there no leakage in the valve seat? Yes Are gauges on supervised systems indicate that normal pressure is being maintained?
Yes
Is the sign in place for the correct location and number of auxiliary drains?
N/A Is the priming level correct and has the low air pressure signal passed it's test?
Yes
Has the quick opening device passed the test? N/A Have automatic air maintenance devices passed test? N/A
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
ALARMS
Have low temperature alarms passed test? N/A
PREACTION TRIP TEST
Has preaction system passed partial flow trip test?
(performed in years when full flow test is not conducted)
Yes
MAINTENANCE
Have auxiliary drains been opened? N/A Have low points been drained before freezing weather? N/A
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Report of Inspection / Test for Asset - Building 37
OWNER SECTION
Is the private fire service main in service? Yes Has it remained in service since the last inspection? Yes
Are systems supplied by the main free of actuations of devices or alarms since the last inspection?
Yes
INSPECTION
Are control valves in correct (open or closed) position? N/A Are control valves properly sealed, locked, or supervised? N/A
Are control valves accessible and free from external leaks ? N/A Are control valves provided with appropriate wrenches? N/A
Are control valves properly identified ? N/A Are backflow preventers accessible and are isolation valves open?
N/A
Are backflow preventers sealed, locked, or supervised? N/A Is the relief port or RPZ not discharging? N/A
Are hose/hydrant houses accessible? N/A Are hose/hydrant houses fully equipped? N/A
Are hose/hydrant houses free from physical damage? N/A Are monitor nozzles free of leaks, damage and corrosion? N/A
Are hydrants accessible and operating wrench available? N/A Are hydrant outlets lubricated? Yes
Are hydrants free from leaks and cracks? Yes Are hydrant threads in good condition? Yes
Are hydrant operating nut in good condition? Yes Are dry barrel hydrants free from ice or water in barrel? No
Are mainline strainers free from plugging and corrosion N/A Is exposed piping free from leaks, physical damage and corrosion?
Yes
Is exposed piping properly restrained? N/A
TESTING
Do valve supervisory devices indicate movement? N/A Do monitor nozzles move through full range? N/A
Have monitor nozzles flowed an acceptable amount of water?
N/A Have hydrants flowed until clear (at least 1 minute)? Yes
Have dry barrel hydrants drain in at least one hour? No Have dry barrel hydrants which require pumping been identified?
N/A
Have all control valves been operated through full range and returned to normal position?
N/A Have backflow devices passed forward flow test? N/A
Are post indicator valves opened until spring or torsion is felt in rod, then closed back one quarter turn?
Yes
MAINTENANCE
Have mainline strainers been cleaned? N/A Are hydrants free of ice, snow, and damage? N/A
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Have adjusted, repaired, reconditioned or replaced components had the associated tests and/or inspections required by Table 7.5.1 of NFPA-25 been performed?
N/A Are hydrant caps, stems, plugs, and threads lubricated? Yes
Are monitor nozzles lubricated? N/A Have operating stem of all OS&Y valves been lubricated, completely closed, and reopened?
N/A
Report of Inspection / Test for Asset - Hydrant #1
Fire Hydrant Information
Hydrant ID #1
Description Good
Location Door #34
Report of Inspection / Test for Asset - Hydrant #2
Fire Hydrant Information
Hydrant ID #2
Description Filled with water, did not drain after flow
Location Door #32
Static Hydrant Description 14 1/2 turns
Report of Inspection / Test for Asset - Hydrant #3
Fire Hydrant Information
Hydrant ID #3
Description Empty when opened, did not drain after flow , no gasket in 5" cap
Location Door 30
Static Hydrant Description 14 1/2 turns
Report of Inspection / Test for Asset - Hydrant #4
Fire Hydrant Information
Hydrant ID #4
Description Empty when opened, did not drain
Location Door #28
Static Hydrant Description 14 1/2 turns
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Report of Inspection / Test for Asset - Hydrant #5
Fire Hydrant Information
Hydrant ID #5
Description Empty when opened, drained very slowly
Location Across road from Door #23
Static Hydrant Description 18 turns to close, very tight
Report of Inspection / Test for Asset - Hydrant #6
Fire Hydrant Information
Hydrant ID #6
Description Empty when opened, opened after 2 turns, spun 30 something times with no increase in flow
Location Door #18
Static Hydrant Description 4 1/2 turns to close
Report of Inspection / Test for Asset - Hydrant #7
Fire Hydrant Information
Hydrant ID #7
Description Bagged, valve will not turn, also didn't turn last 2 yrs
Location Across road at corner of building between Doors #15 & 16
Report of Inspection / Test for Asset - Hydrant #8
Fire Hydrant Information
Hydrant ID #8
Description Empty, no gasket on 5" cap, drained
Location By generators by Door #14
Static Hydrant Description 9 1/2 turns
Report of Inspection / Test for Asset - Hydrant #9
Fire Hydrant Information
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Hydrant ID #9
Description Empty when opened, drained
Location Door #38
Static Hydrant Description 18 1/2 turns
Report of Inspection / Test for Asset - Hydrant #10
Fire Hydrant Information
Hydrant ID #10
Description Empty when opened, drained
Location Between Doors #35 & 36
Static Hydrant Description 18 1/2 turns
MAIN DRAIN FLOW TESTS
System Initial Static Residual Static Seconds to Return to
Initial Static
Flow Observed?
Did waterflow alarm operate?
Building #38 Wet Riser 1 65 60 65 N/A Yes Yes
Riser #1 80 60 65 N/A Yes Yes
Riser #2 65 60 65 N/A Yes Yes
Riser #3 65 60 65 N/A Yes Yes
Riser #4 65 55 65 N/A Yes Yes
Riser #5 65 55 65 N/A Yes Yes
Riser #6 70 65 65 N/A Yes Yes
Riser #7 65 60 65 N/A Yes Yes
Riser #8 70 60 65 N/A Yes Yes
Riser #8 B 70 60 65 N/A Yes Yes
Riser #9 65 60 65 N/A Yes Yes
Riser #10 65 60 65 N/A Yes Yes
Riser #11 65 60 65 N/A Yes Yes
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
INSPECTORS TEST CONNECTION
System Location Description Time to
Alarm (seconds)
Reported? Smooth Orifice
Easily Accessible
Signs? Pass?
Building #38 Wet Riser 1
South west wall Test & Drain Yes Yes Yes
VALVES
System Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
# of Turn s
Riser #11 Good CMOP behind offices
OS&Y 4 " Monitored Yes Yes Yes Yes Yes
Riser #4 Good In Cold Storage/Records Room
OS&Y 4 " Monitored Yes Yes Yes Yes Yes
Riser #5 Good At riser #4 OS&Y 4 " Monitored Yes Yes Yes Yes Yes
Computer Room
Good At riser #1 Butterfly 4 " Monitored Yes Yes Yes Yes N/A
Riser #2 Good In closet in Room
OS&Y 8 " Monitored Yes Yes Yes Yes Yes
Riser #6 Good Dock OS&Y 8 " Monitored Yes Yes Yes Yes Yes
Riser #8 B CMOP At riser #8 Butterfly 2-1/2 " Monitored Yes Yes Yes Yes N/A
Building #38 Wet Riser 1
Backflow Valve 1
North Wall OS&Y 4 " Monitored Yes Yes Yes Yes Yes
Riser #7 Good Dock OS&Y 8 " Monitored Yes Yes Yes Yes Yes
Riser #1 Riser #1 OS&Y 8 " Monitored Yes Yes Yes Yes Yes
Riser #1 Outside Between doors 34 & 35
Post Indicator 8 " Padlock Yes Yes Yes Yes N/A
Riser #9 Good Room 155B OS&Y 8 " Monitored Yes Yes Yes Yes Yes
Riser #3 Good Operations-Forklift charging area
OS&Y 8 " Monitored Yes Yes Yes Yes Yes
Riser #8 Good Janitors Closet C1014
OS&Y 8 " Monitored Yes Yes Yes Yes Yes
Riser #10 Good Room behind Server Room
OS&Y 8 " Monitored Yes Yes Yes Yes Yes
Riser #1 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes Yes N/A N/A
Building #38 Wet Riser 1
Backflow Valve 2
North wall OS&Y 4 " Monitored Yes Yes Yes Yes Yes
Riser #9 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
VALVES
System Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
# of Turn s
Riser #2 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Riser #10 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Riser #11 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Riser #3 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Riser #8 B Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Riser #4 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Riser #6 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Computer Room
Good At riser #1 Dry Pipe Valve 4 " Not Applicable N/A Yes Yes N/A N/A
Riser #7 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Riser #8 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Riser #2 Outside door #38 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A
Riser #9 FDC At valve Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Building #38 Wet Riser 1
FDC At valve approximately 15' off ground
Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Riser #1 FDC At valve Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Riser #2 FDC At valve Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Riser #3 FDC At valve Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Riser #4 FDC At valve Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Riser #6 FDC At valve Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Riser #7 FDC At valve Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Riser #8 FDC At valve Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Riser #10 FDC At valve Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
VALVES
System Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
# of Turn s
Riser #11 FDC At valve Fdc Check Valve
4 " Not Applicable N/A Yes N/A N/A N/A
Riser #3 By generators Outside door #14
Post Indicator 8 " Padlock Yes Yes Yes Yes N/A
Riser #4/5 Outside door #16 Post Indicator 8 " Padlock Yes Yes Yes No N/A
Riser #8 Good At riser #8 Butterfly 8 " Monitored Yes Yes Yes Yes N/A
Riser #6 Outside door #18 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A
Riser #8 Good At valve Riser Check Valve
8 " Not Applicable N/A Yes N/A N/A N/A
Riser #7 Outside Door #18 &
Post Indicator 8 " Padlock Yes Yes Yes Yes N/A
Riser #8 & 8 B
Outside door #27 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A
Riser #9 Outside door #29 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A
Riser #10 Outside door 33 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A
Riser #11 Outside door #21 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A
DRAIN VALVES
System Description Location Drain Aux Drain Drained Water Flow Observed
Building #38 Wet Riser 1 Main Drain At valve Ball Valve N/A Yes
Riser #1 Main Drain At valve Globe Valve N/A Yes
Computer Room Main Drain At valve Angle Valve N/A Yes
Riser #2 Main Drain At valve Ball Valve N/A Yes
Riser #3 Main Drain At valve Ball Valve N/A Yes
Riser #4 Main Drain At valve Ball Valve N/A Yes
Riser #5 Main Drain At valve Ball Valve N/A Yes
Riser #6 Main Drain At valve Ball Valve N/A Yes
Riser #7 Main Drain At valve Ball Valve N/A Yes
Riser #8 Main Drain At valve Ball Valve N/A Yes
Riser #8 B Main Drain At valve Ball Valve N/A Yes
Riser #9 Main Drain At valve Ball Valve N/A Yes
Riser #10 Main Drain At valve Ball Valve N/A Yes
Riser #11 Main Drain At valve Ball Valve N/A Yes
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Questions with Photos and Notes
Computer Room - Seconds to return to initial static
Notes:
Static 75 psi Residual S/T Return 65 psi Air Pressure 28 psi Low Air 16 psi
Visit Photos
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Deficiencies - General Questions
Deficiency #1
14. Are there records that substantiate that the check valves have been internally inspected and verified to have been working correctly in the past (5) years?: No Status: Non Critical
Notes: 5 yr inspection is scheduled
Deficiency #2
21. Are the fire department connection(s) gaskets in place and not damaged?: No Status: Impairment
Notes: All (10) FDC's have dry rotted or missing gaskets. Need to be replaced
Deficiency #3
18.3. Piping from fire department connection to fire department connection check valve has been hydrostatically tested at 150 psi (10 bar) for at least 2 hours: No Status: Non Critical
Notes: 5 yr inspection is scheduled
Deficiency #4
46. Are all gauges tested or replaced every 5 years?: No Status: Non Critical
Notes: Approximately 30 water gauges are over 5 yrs old, 5 yr inspection is scheduled
Deficiency #5
42. Was an assessment of the internal condition of piping was conducted (every 5 years)?: No Status: Non Critical
Notes: 5 yr inspection is scheduled
Deficiency #6
52. Is the system free of impairments?: No Status: Impairment
Notes: (1) fire hydrant will not open, (3) fire hydrants did not drain, potential freezing risk in winter
Deficiency #7
Has the interior of the FDC been inspected for obstructions?: No Status: Non Critical
Notes: 5 yr inspection is scheduled
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Deficiency #8
Are all check valves externally inspected, operating properly, and are in good condition?: No Status: Non Critical
Notes: 5 yr inspection is scheduled
Deficiency #9
Have gauges been checked by a calibrated gauge or replaced?: No Status: Non Critical
Notes: Some gauges are from 2014. 5yr inspection is scheduled
Deficiency #10
Have strainers, filters, restricted orifices and diaphragm chambers on valves and trim passed internal inspection?: No Status: Non Critical
Notes: 5 yr inspection is scheduled
Deficiencies - General Wet System Questions
None
Deficiencies - General Preaction System Questions
None
Deficiencies - Building #38 Wet Riser 1
None
Deficiencies - Riser #1
None
Deficiencies - Computer Room
None
Deficiencies - Riser #2
None
Deficiencies - Riser #3
None
Deficiencies - Riser #4
None
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Deficiencies - Riser #5
None
Deficiencies - Riser #6
None
Deficiencies - Riser #7
None
Deficiencies - Riser #8
None
Deficiencies - Riser #8 B
None
Deficiencies - Riser #9
None
Deficiencies - Riser #10
None
Deficiencies - Riser #11
None
Deficiencies - Building 37
Deficiency #11
Are dry barrel hydrants free from ice or water in barrel?: No Status: Impairment
Notes: Hydrants #2, #3 & #4 were filled with water when caps opened, did not drain after flow test. Potential for freezing in winter.
Deficiency #12
Have dry barrel hydrants drain in at least one hour?: No Status: Impairment
Notes: Hydrants #2, #3 & #4 were filled with water when caps opened, did not drain after flow test. Potential for freezing in winter.
Deficiencies - Hydrant #1
None
Deficiencies - Hydrant #2
None
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Deficiencies - Hydrant #3
None
Deficiencies - Hydrant #4
None
Deficiencies - Hydrant #5
None
Deficiencies - Hydrant #6
None
Deficiencies - Hydrant #7
None
Deficiencies - Hydrant #8
None
Deficiencies - Hydrant #9
None
Deficiencies - Hydrant #10
None
Deficiencies - Inspectors Test Connection
None
Deficiencies - Valves
Deficiency #13
Location: Outside door #16 Valve Type: Post Indicator Size: 8 Description: Riser #4/5 Exercised?: No Status: Non Critical
Notes: Could not operate PIV, housing spins, is disconnected from portion that goes underground
Deficiencies - Drain Valves
None
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
Jeff Franco 2024-09-30
Client Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Client Name Signature Date Completed
Paul Coppola 2024-09-27
Report of Inspection / Test Annual Fire Sprinkler Inspection
2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02
Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com