Bldg 37 2024 Fire Sprinkler Hydrant Inspections 10-4-24.pdf

PDF 733 KB Posted

Attached to
4240--Life Safety Equipment/Systems Maintenance (VA-25-00063754)
Solicitation number
36S79725Q0005
Issued by

About this file

This document is an Annual Fire Sprinkler Inspection Report for the Hines VA Building #37 located in Hines, IL, conducted by Chicago Fire Protection on October 1, 2024. The comprehensive inspection revealed several critical deficiencies, including issues with fire hydrants, fire department connection gaskets, and valve maintenance. Specifically, the report noted that 3 out of 10 fire hydrants did not properly drain after testing, posing a potential freezing risk in winter, and all 10 fire department connections have dry-rotted or missing gaskets that need replacement.

The inspection covered multiple building systems, including 13 wet systems and 1 dry system, with detailed assessments of control valves, alarm devices, inspector's test pipes, and various risers. While most systems functioned adequately, the report highlighted several non-critical deficiencies that require 5-year inspections, such as lack of internal piping assessments, outdated gauges, and unexamined check valves. The deficiencies were categorized with varying levels of urgency, with some marked as impairments that need immediate attention to ensure the building's fire protection system remains fully operational and compliant with safety standards.

View the file

Other files

File Type Posted
Bldg 37 2024 FM-200 Inspections.pdf PDF
Bldgs 37 38 2024 Fire Alarm Annual Inspection 9-25-24.pdf PDF
Bldg 38 2024 5-Year Internal Pipe Inspection.pdf PDF
FM-200.2pic.jpg JPG image
VA Hines SDC Bldg 37 - Hydrants.pdf PDF
36S79725Q0005 0002.docx DOCX document
FM-200.jpg JPG image
Bldg 38 2024 Fire Sprinkler Hydrant Inspections.pdf PDF
Bldg 37 2024 5-Year Internal Pipe Inspection.pdf PDF
HYdrants and water supply.docx DOCX document
36S79725Q0005 0001_1.docx DOCX document
36S79725Q0005 0001.docx DOCX document
36S79725Q0005_1.docx DOCX document
Service Contract Act WD 2015-5017.pdf PDF
36S79725Q0005.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Report of Inspection / Test General Questions

W.O/JOB NUMBERS

W.O.#: 36S79724 P0015

JOB#: CFP24-

LICENSE NUMBERS

State License #: FSI0095 UA #: 1461646

CHICAGO SPRINKLER INVENTORY

# of Wet Systems in the Building: 13 # of Dry Systems in the Building: 1

# of Wet Systems Tested on Report: 13 # of Dry Systems Tested on Report: 1

SYSTEM STATUS

1. Is the system in service? Yes 2. Attach a copy of your owner information from with all questions answered and signed by the owner/representative. Required by the Chicago Fire Department in order to submit the report.

N/A

Is the building occupied? Yes Are all fire protection systems in service? Yes

Has the occupancy classification, hazard of contents, and/or storage method remained the same since the last inspection?

Yes Has the system remained in service without modification since the last inspection?

Yes

Was the system free of actuations of devices or alarms since the last inspection?

Yes

BACKFLOW

3. Are the isolation backflow valves in the open position and secured or supervised?

Yes Is relief port on RPZ device not discharging? N/A

CONTROL VALVES

4. Are the control valves with electrical supervision in correct (open or closed) position?

Yes 5. Are the control valves secured or supervised? supervised

Are the control valves supervised with seals locked or is supervision in place?

Yes Are the control valves supervised with seals accessible? N/A

6. Are the control valves accesible? Yes 7. Are the control valves free from damage or leaks? Yes

Are the control valves supervised with seals free from leaks?

N/A 8. Do the control valves have proper signage displayed? Yes

Are the control valves supervised with seals have appropriate wrenches?

N/A 9. All control valves operated through full range of motion and returned to normal position (where a fire pump test header valve is present - disregard as it will be tested during the annual fire pump test)

Yes

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Copyright 2024 Inspect Point

Are the control valves supervised with seals properly identified?

N/A 10. Were the control valves outside Stem & Yoke valve stems lubricated?

Yes

Are the control valves with locks in correct (open or closed) position?

N/A Are the control valves with locks locked or is supervision in place?

N/A

10.1. Post Indicator Valves (PIVs) are provided with correct

wrenches?

Yes Are the control valves with locks accessible? N/A

Are the control valves with electrical supervision locked or is supervision in place?

Yes Are the control valves with locks free from any leaks? N/A

Are the control valves with electrical supervision accessible?

Yes Are the control valves with electrical supervision free from any leaks?

Yes

Are the control valves with locks have the appropriate wrenches?

N/A Are the control valves with electrical supervision have the appropriate wrenches?

N/A

Are the control valves with locks properly identified? N/A Are the control valves with electrical supervision properly identified?

Yes

Water Flow (sec.) N/A

ALARM DEVICES/RISER CHECK

11. Are the water flow alarm devices are free of damage? Yes 12. Do the water flow alarm devices operate correctly when the inspector's test valve is opened and flow observed?

Yes

13. Do the supervisory switches functions properly? Yes 14. Are there records that substantiate that the check valves have been internally inspected and verified to have been working correctly in the past (5) years?

No

15. Outside 10 inch bell(s) present and operates correctly Yes 16. Inside 6" bell present and operates correctly Yes

Are alarms and supervisory devices not damaged? Yes

INSPECTOR'S TEST PIPE (ITV)

17. Was the most remote inspector's test pipe (ITV) operated and flow witnessed in a single-story structure?

Note: Buildings under city pressure only, no fire pump

N/A 17.1 Was the test and drain operated and flow witnessed on each floor level of a multi-level structure?

N/A

FIRE DEPARTMENT CONNECTIONS

18. Are the fire department connection(s) visible and accessible?

Yes Are the FDC caps and plugs in place and undamaged? Yes

18.1. Check valve is not leaking Yes Is the FDC check valve free of leaks? Yes

18.2. Visible piping supplying the fire department

connection is undamaged

Yes Is the clapper and automatic drain valve in place and properly operating?

Yes

18.3. Piping from fire department connection to fire

department connection check valve has been hydrostatically tested at 150 psi (10 bar) for at least 2 hours

No Is the FDC identification sign(s) in place? Yes

Has the interior of the FDC been inspected for obstructions?

No 19. Do the fire department connection(s) swivels operate correctly?

Yes

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

20. Are the fire department connection(s) plugs or tamper covers in place?

Yes 21. Are the fire department connection(s) gaskets in place and not damaged?

No

Is the FDC easily accessible? Yes 22. Is the fire department connection ball drip valve functional?

Yes

23. In buildings that are not fully sprinklered (e.g. - garage only) are system Identification signs adjacent to the FDC in place and accurate?

N/A 24. In high-rise buildings with multiple zones, are zone identification signs adjacent to the FDC in place and accurate?

N/A

25. Is the fire department connection interior visibly clear of obstructions?

N/A 26. Do the fire department connection flapper(s) operates correctly?

N/A

SPRINKLERS (VISIBLE)

27. Are fire sprinklers free of damage or leaks? Yes 28. Sprinklers and concealed cover plates (if present) are free of corrosion, foreign material, or paint

N/A

29. Are fire sprinklers installed in proper orientation? Yes 30. Do all sprinklers have fluid in glass bulbs, if applicable? Yes

31. Loading - sprinklers are free of accumulated dust or grease

Yes 32. Minimum clearance maintained between sprinklers and storage

Yes

33. Sprinklers tested or replaced due to age - per appropriate testing schedule

N/A 34. Spare sprinkler heads - Proper number and type, including installation wrench

Yes

35. The inspector/tester did not find any recalled devices during the visual inspection

Yes Are visible sprinklers in the proper position: upright, pendent, sidewall?

Yes

Are visible sprinklers free of corrosion and physical damage?

Yes Is there proper clearance below the sprinklers? Yes

Is there liquid in all visible glass bulb sprinklers? Yes Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?

N/A

Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?

N/A Dry-type sprinklers replaced or successfully sample tested within last 10 years?

N/A

Have sprinklers subject to harsh environments been replaced or successfully sample tested in the last 5 years?

N/A Are there spare sprinklers and a sprinkler wrench? Yes

HANGERS/SEISMIC BRACING

36. Are visible hangers/seismic bracing in good condition and not damaged or loose?

Yes

DRY SPRINKLER SYSTEMS

37. Did dry pipe test pass NFPA 25 requirements? Yes 38. Were the dry pipe system low points drained in accordance with NFPA 25 and the system restored to service?

Yes

PIPES AND FITTINGS (VISIBLE)

37. Are all visible pipes and fittings in good condition with no external corrosion?

Yes 38. Are the visible pipes and valves free of mechanical damage or leaks?

Yes

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

39. Is visible piping in correct alignment? Yes 40. Are the visible pipes free of external loads? Yes

41. Is all wet piping protected from freezing temperatures? Yes 42. Was an assessment of the internal condition of piping was conducted (every 5 years)?

No

42.1. Was an obstruction investigation conducted if

warranted by internal assessment inspection?

N/A Are visible hangers/seismic bracing in good condition and not damaged or loose?

Yes

MAIN DRAIN TEST

43. Are the main drain test results within 10% from the previous annual test? (document static and residual pressure on the submitted test report)?

Yes 43.1a. Main drain test - if the sole purpose is through a backflow preventer or pressure reducing valve. Static PSI

43.1b. Maind drain test - if the sole purpose is through a backflow preventer or pressure reducing valve. Residual

PSI ____

GAUGES

44. Are all gauges in good operating condition? Yes 45. Gauges - normal water pressure maintained ____PSI? 65

46. Are all gauges tested or replaced every 5 years? No Are all check valves externally inspected, operating properly, and are in good condition?

No

Are the gauges on system showing normal water supply pressure?

Yes Are Pressure reducing valves in good condition including no handwheels broken?

N/A

Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes Do valve supervisory switches indicate movement? Yes

The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes Are the gauges on system operable and in good working condition?

Yes

Are Pressure reducing valves (sprinkler system) in open position and not leaking?

N/A Are Pressure reducing valves (sprinkler system) with downstream pressure per the design?

N/A

All control valves operated through full range and returned to normal position?

Yes

UNCOMMON WET PIPE SYSTEM TYPES

47. Are there any Non-Freezing System (not to exceed 20 sprinklers)

N/A 47.1. Has the antifreeze solution been tested? N/A

48. Are there any Foam System(s)? (If any of the following systems are present - please provide a full inspection and submit a separate test report to the appropriate equipment profile)

N/A 49. Are there any dry pipe sprinkler systems? N/A

50. Are there any pre-action systems, individual report per system?

Yes 51. Are there any Deluge System(s)? N/A

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

INSPECTION/TESTING CONCLUSION

52. Is the system free of impairments? No 53. Notifications have been made to the monitoring entity, building management, and AHJ as necessary?

Yes

54. Has the system been restored to normal operation? Yes

5 YEAR

Are all check valve parts operating properly and are in good condition?

N/A Have strainers, filters, restricted orifices and diaphragm chambers on valves and trim passed internal inspection?

No

Have gauges been checked by a calibrated gauge or replaced?

No Have alarm valves and associated strainers, filters, and restricted orifices pass an internal inspection?

N/A

Deficiency Notes

List any deficiency repairs to be done: N/A

Signature

55. Signature of Technician N/A 56. Signature of building representative N/A

57. Attach signatures (Optional) N/A

WATERFLOWS

Did all water flows operate correctly? Yes

ALARMS

Is the alarm valve free from physical damage? N/A Is the trim in correct (open or closed) position? N/A

Is there no leakage in the retarding chamber or drains? Yes

VALVE AREA

Are valve enclosures maintaining a minimum of 40 degrees F?

Yes Are gauges on non-supervised systems in good condition and showing normal water and air pressure?

Yes

Have manual activation devices passed test? Yes

PREACTION VALVES

For freezer systems, gauge near compressor reading the same as gauge near the preaction valve?

N/A Are preaction and deluge valves free from physical damage?

Yes

Are the electrical components in service? Yes Are trim valves in appropriate (open or closed) position? Yes

Is there no leakage in the valve seat? Yes Are gauges on supervised systems indicate that normal pressure is being maintained?

Yes

Is the sign in place for the correct location and number of auxiliary drains?

N/A Is the priming level correct and has the low air pressure signal passed it's test?

Yes

Has the quick opening device passed the test? N/A Have automatic air maintenance devices passed test? N/A

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

ALARMS

Have low temperature alarms passed test? N/A

PREACTION TRIP TEST

Has preaction system passed partial flow trip test?

(performed in years when full flow test is not conducted)

Yes

MAINTENANCE

Have auxiliary drains been opened? N/A Have low points been drained before freezing weather? N/A

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Report of Inspection / Test for Asset - Building 37

OWNER SECTION

Is the private fire service main in service? Yes Has it remained in service since the last inspection? Yes

Are systems supplied by the main free of actuations of devices or alarms since the last inspection?

Yes

INSPECTION

Are control valves in correct (open or closed) position? N/A Are control valves properly sealed, locked, or supervised? N/A

Are control valves accessible and free from external leaks ? N/A Are control valves provided with appropriate wrenches? N/A

Are control valves properly identified ? N/A Are backflow preventers accessible and are isolation valves open?

N/A

Are backflow preventers sealed, locked, or supervised? N/A Is the relief port or RPZ not discharging? N/A

Are hose/hydrant houses accessible? N/A Are hose/hydrant houses fully equipped? N/A

Are hose/hydrant houses free from physical damage? N/A Are monitor nozzles free of leaks, damage and corrosion? N/A

Are hydrants accessible and operating wrench available? N/A Are hydrant outlets lubricated? Yes

Are hydrants free from leaks and cracks? Yes Are hydrant threads in good condition? Yes

Are hydrant operating nut in good condition? Yes Are dry barrel hydrants free from ice or water in barrel? No

Are mainline strainers free from plugging and corrosion N/A Is exposed piping free from leaks, physical damage and corrosion?

Yes

Is exposed piping properly restrained? N/A

TESTING

Do valve supervisory devices indicate movement? N/A Do monitor nozzles move through full range? N/A

Have monitor nozzles flowed an acceptable amount of water?

N/A Have hydrants flowed until clear (at least 1 minute)? Yes

Have dry barrel hydrants drain in at least one hour? No Have dry barrel hydrants which require pumping been identified?

N/A

Have all control valves been operated through full range and returned to normal position?

N/A Have backflow devices passed forward flow test? N/A

Are post indicator valves opened until spring or torsion is felt in rod, then closed back one quarter turn?

Yes

MAINTENANCE

Have mainline strainers been cleaned? N/A Are hydrants free of ice, snow, and damage? N/A

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Have adjusted, repaired, reconditioned or replaced components had the associated tests and/or inspections required by Table 7.5.1 of NFPA-25 been performed?

N/A Are hydrant caps, stems, plugs, and threads lubricated? Yes

Are monitor nozzles lubricated? N/A Have operating stem of all OS&Y valves been lubricated, completely closed, and reopened?

N/A

Report of Inspection / Test for Asset - Hydrant #1

Fire Hydrant Information

Hydrant ID #1

Description Good

Location Door #34

Report of Inspection / Test for Asset - Hydrant #2

Fire Hydrant Information

Hydrant ID #2

Description Filled with water, did not drain after flow

Location Door #32

Static Hydrant Description 14 1/2 turns

Report of Inspection / Test for Asset - Hydrant #3

Fire Hydrant Information

Hydrant ID #3

Description Empty when opened, did not drain after flow , no gasket in 5" cap

Location Door 30

Static Hydrant Description 14 1/2 turns

Report of Inspection / Test for Asset - Hydrant #4

Fire Hydrant Information

Hydrant ID #4

Description Empty when opened, did not drain

Location Door #28

Static Hydrant Description 14 1/2 turns

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Report of Inspection / Test for Asset - Hydrant #5

Fire Hydrant Information

Hydrant ID #5

Description Empty when opened, drained very slowly

Location Across road from Door #23

Static Hydrant Description 18 turns to close, very tight

Report of Inspection / Test for Asset - Hydrant #6

Fire Hydrant Information

Hydrant ID #6

Description Empty when opened, opened after 2 turns, spun 30 something times with no increase in flow

Location Door #18

Static Hydrant Description 4 1/2 turns to close

Report of Inspection / Test for Asset - Hydrant #7

Fire Hydrant Information

Hydrant ID #7

Description Bagged, valve will not turn, also didn't turn last 2 yrs

Location Across road at corner of building between Doors #15 & 16

Report of Inspection / Test for Asset - Hydrant #8

Fire Hydrant Information

Hydrant ID #8

Description Empty, no gasket on 5" cap, drained

Location By generators by Door #14

Static Hydrant Description 9 1/2 turns

Report of Inspection / Test for Asset - Hydrant #9

Fire Hydrant Information

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Hydrant ID #9

Description Empty when opened, drained

Location Door #38

Static Hydrant Description 18 1/2 turns

Report of Inspection / Test for Asset - Hydrant #10

Fire Hydrant Information

Hydrant ID #10

Description Empty when opened, drained

Location Between Doors #35 & 36

Static Hydrant Description 18 1/2 turns

MAIN DRAIN FLOW TESTS

System Initial Static Residual Static Seconds to Return to

Initial Static

Flow Observed?

Did waterflow alarm operate?

Building #38 Wet Riser 1 65 60 65 N/A Yes Yes

Riser #1 80 60 65 N/A Yes Yes

Riser #2 65 60 65 N/A Yes Yes

Riser #3 65 60 65 N/A Yes Yes

Riser #4 65 55 65 N/A Yes Yes

Riser #5 65 55 65 N/A Yes Yes

Riser #6 70 65 65 N/A Yes Yes

Riser #7 65 60 65 N/A Yes Yes

Riser #8 70 60 65 N/A Yes Yes

Riser #8 B 70 60 65 N/A Yes Yes

Riser #9 65 60 65 N/A Yes Yes

Riser #10 65 60 65 N/A Yes Yes

Riser #11 65 60 65 N/A Yes Yes

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

INSPECTORS TEST CONNECTION

System Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

Building #38 Wet Riser 1

South west wall Test & Drain Yes Yes Yes

VALVES

System Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

# of Turn s

Riser #11 Good CMOP behind offices

OS&Y 4 " Monitored Yes Yes Yes Yes Yes

Riser #4 Good In Cold Storage/Records Room

OS&Y 4 " Monitored Yes Yes Yes Yes Yes

Riser #5 Good At riser #4 OS&Y 4 " Monitored Yes Yes Yes Yes Yes

Computer Room

Good At riser #1 Butterfly 4 " Monitored Yes Yes Yes Yes N/A

Riser #2 Good In closet in Room

OS&Y 8 " Monitored Yes Yes Yes Yes Yes

Riser #6 Good Dock OS&Y 8 " Monitored Yes Yes Yes Yes Yes

Riser #8 B CMOP At riser #8 Butterfly 2-1/2 " Monitored Yes Yes Yes Yes N/A

Building #38 Wet Riser 1

Backflow Valve 1

North Wall OS&Y 4 " Monitored Yes Yes Yes Yes Yes

Riser #7 Good Dock OS&Y 8 " Monitored Yes Yes Yes Yes Yes

Riser #1 Riser #1 OS&Y 8 " Monitored Yes Yes Yes Yes Yes

Riser #1 Outside Between doors 34 & 35

Post Indicator 8 " Padlock Yes Yes Yes Yes N/A

Riser #9 Good Room 155B OS&Y 8 " Monitored Yes Yes Yes Yes Yes

Riser #3 Good Operations-Forklift charging area

OS&Y 8 " Monitored Yes Yes Yes Yes Yes

Riser #8 Good Janitors Closet C1014

OS&Y 8 " Monitored Yes Yes Yes Yes Yes

Riser #10 Good Room behind Server Room

OS&Y 8 " Monitored Yes Yes Yes Yes Yes

Riser #1 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes Yes N/A N/A

Building #38 Wet Riser 1

Backflow Valve 2

North wall OS&Y 4 " Monitored Yes Yes Yes Yes Yes

Riser #9 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

VALVES

System Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

# of Turn s

Riser #2 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Riser #10 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Riser #11 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Riser #3 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Riser #8 B Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Riser #4 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Riser #6 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Computer Room

Good At riser #1 Dry Pipe Valve 4 " Not Applicable N/A Yes Yes N/A N/A

Riser #7 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Riser #8 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Riser #2 Outside door #38 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A

Riser #9 FDC At valve Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Building #38 Wet Riser 1

FDC At valve approximately 15' off ground

Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Riser #1 FDC At valve Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Riser #2 FDC At valve Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Riser #3 FDC At valve Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Riser #4 FDC At valve Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Riser #6 FDC At valve Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Riser #7 FDC At valve Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Riser #8 FDC At valve Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Riser #10 FDC At valve Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

VALVES

System Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

# of Turn s

Riser #11 FDC At valve Fdc Check Valve

4 " Not Applicable N/A Yes N/A N/A N/A

Riser #3 By generators Outside door #14

Post Indicator 8 " Padlock Yes Yes Yes Yes N/A

Riser #4/5 Outside door #16 Post Indicator 8 " Padlock Yes Yes Yes No N/A

Riser #8 Good At riser #8 Butterfly 8 " Monitored Yes Yes Yes Yes N/A

Riser #6 Outside door #18 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A

Riser #8 Good At valve Riser Check Valve

8 " Not Applicable N/A Yes N/A N/A N/A

Riser #7 Outside Door #18 &

Post Indicator 8 " Padlock Yes Yes Yes Yes N/A

Riser #8 & 8 B

Outside door #27 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A

Riser #9 Outside door #29 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A

Riser #10 Outside door 33 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A

Riser #11 Outside door #21 Post Indicator 8 " Padlock Yes Yes Yes Yes N/A

DRAIN VALVES

System Description Location Drain Aux Drain Drained Water Flow Observed

Building #38 Wet Riser 1 Main Drain At valve Ball Valve N/A Yes

Riser #1 Main Drain At valve Globe Valve N/A Yes

Computer Room Main Drain At valve Angle Valve N/A Yes

Riser #2 Main Drain At valve Ball Valve N/A Yes

Riser #3 Main Drain At valve Ball Valve N/A Yes

Riser #4 Main Drain At valve Ball Valve N/A Yes

Riser #5 Main Drain At valve Ball Valve N/A Yes

Riser #6 Main Drain At valve Ball Valve N/A Yes

Riser #7 Main Drain At valve Ball Valve N/A Yes

Riser #8 Main Drain At valve Ball Valve N/A Yes

Riser #8 B Main Drain At valve Ball Valve N/A Yes

Riser #9 Main Drain At valve Ball Valve N/A Yes

Riser #10 Main Drain At valve Ball Valve N/A Yes

Riser #11 Main Drain At valve Ball Valve N/A Yes

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Questions with Photos and Notes

Computer Room - Seconds to return to initial static

Notes:

Static 75 psi Residual S/T Return 65 psi Air Pressure 28 psi Low Air 16 psi

Visit Photos

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Deficiencies - General Questions

Deficiency #1

14. Are there records that substantiate that the check valves have been internally inspected and verified to have been working correctly in the past (5) years?: No Status: Non Critical

Notes: 5 yr inspection is scheduled

Deficiency #2

21. Are the fire department connection(s) gaskets in place and not damaged?: No Status: Impairment

Notes: All (10) FDC's have dry rotted or missing gaskets. Need to be replaced

Deficiency #3

18.3. Piping from fire department connection to fire department connection check valve has been hydrostatically tested at 150 psi (10 bar) for at least 2 hours: No Status: Non Critical

Notes: 5 yr inspection is scheduled

Deficiency #4

46. Are all gauges tested or replaced every 5 years?: No Status: Non Critical

Notes: Approximately 30 water gauges are over 5 yrs old, 5 yr inspection is scheduled

Deficiency #5

42. Was an assessment of the internal condition of piping was conducted (every 5 years)?: No Status: Non Critical

Notes: 5 yr inspection is scheduled

Deficiency #6

52. Is the system free of impairments?: No Status: Impairment

Notes: (1) fire hydrant will not open, (3) fire hydrants did not drain, potential freezing risk in winter

Deficiency #7

Has the interior of the FDC been inspected for obstructions?: No Status: Non Critical

Notes: 5 yr inspection is scheduled

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Deficiency #8

Are all check valves externally inspected, operating properly, and are in good condition?: No Status: Non Critical

Notes: 5 yr inspection is scheduled

Deficiency #9

Have gauges been checked by a calibrated gauge or replaced?: No Status: Non Critical

Notes: Some gauges are from 2014. 5yr inspection is scheduled

Deficiency #10

Have strainers, filters, restricted orifices and diaphragm chambers on valves and trim passed internal inspection?: No Status: Non Critical

Notes: 5 yr inspection is scheduled

Deficiencies - General Wet System Questions

None

Deficiencies - General Preaction System Questions

None

Deficiencies - Building #38 Wet Riser 1

None

Deficiencies - Riser #1

None

Deficiencies - Computer Room

None

Deficiencies - Riser #2

None

Deficiencies - Riser #3

None

Deficiencies - Riser #4

None

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Deficiencies - Riser #5

None

Deficiencies - Riser #6

None

Deficiencies - Riser #7

None

Deficiencies - Riser #8

None

Deficiencies - Riser #8 B

None

Deficiencies - Riser #9

None

Deficiencies - Riser #10

None

Deficiencies - Riser #11

None

Deficiencies - Building 37

Deficiency #11

Are dry barrel hydrants free from ice or water in barrel?: No Status: Impairment

Notes: Hydrants #2, #3 & #4 were filled with water when caps opened, did not drain after flow test. Potential for freezing in winter.

Deficiency #12

Have dry barrel hydrants drain in at least one hour?: No Status: Impairment

Notes: Hydrants #2, #3 & #4 were filled with water when caps opened, did not drain after flow test. Potential for freezing in winter.

Deficiencies - Hydrant #1

None

Deficiencies - Hydrant #2

None

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Deficiencies - Hydrant #3

None

Deficiencies - Hydrant #4

None

Deficiencies - Hydrant #5

None

Deficiencies - Hydrant #6

None

Deficiencies - Hydrant #7

None

Deficiencies - Hydrant #8

None

Deficiencies - Hydrant #9

None

Deficiencies - Hydrant #10

None

Deficiencies - Inspectors Test Connection

None

Deficiencies - Valves

Deficiency #13

Location: Outside door #16 Valve Type: Post Indicator Size: 8 Description: Riser #4/5 Exercised?: No Status: Non Critical

Notes: Could not operate PIV, housing spins, is disconnected from portion that goes underground

Deficiencies - Drain Valves

None

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02

Chicago Fire Protection 10355 S Kedzie Ave Chicago IL 60655 7733663477 margaret@chicagofireprotect.com

Inspector Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

Jeff Franco 2024-09-30

Client Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Client Name Signature Date Completed

Paul Coppola 2024-09-27

Report of Inspection / Test Annual Fire Sprinkler Inspection

2024-10-01 Property Hines VA Building #37 S 1st Ave Hines IL Print Date: 2024-10-02