Paint Chip Survey - Alexandria Cemetery EH217092 10-6-21.pdf
PDF 395 KB Posted
- Attached to
- Y1AZ--825CM3013 Alexandria NC Roads and Restroom
- Solicitation number
- 36C78623B0010
About this file
This document contains the results of a lead-containing paint inspection report for the maintenance building at Alexandria National Cemetery in Pineville, Louisiana. Terracon Consultants conducted limited lead paint sampling at five locations on the building in preparation for planned renovations. Samples were taken from various building components and substrates and analyzed by EMSL Analytical, with results ranging from less than 1% to 4.1% lead by dry weight. The related federal contract opportunity is solicitation number 36C78623B0010 for renovations to the maintenance facility and roads at Alexandria National Cemetery, issued by the Department of Veterans Affairs National Cemetery Administration. Work will include renovations to address the lead-containing paint identified in the inspection report.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C78623B0010 0003.docx | DOCX document | |
| 01 45 00 Quality Control Revised 4-12-2023.pdf | ||
| 01 35 26 Safety Requirements - Revised 4-12-2023.pdf | ||
| 36C78623B0010 0002.docx | DOCX document | |
| 36C78623B0010 0001.docx | DOCX document | |
| LIQUIDATED DAMAGES FORMULATION.docx | DOCX document | |
| Asbestos Survey - Alexandria Cemetery EH217091 9-24-21.pdf | ||
| Limitations on Subcontracting Certificate for 825CM3013 Renovate Maintenance Facility _ Roads.docx | DOCX document | |
| 36C78623B0010_1.docx | DOCX document | |
| IFB Lump Sum Division Spreadsheet.xlsx | XLSX spreadsheet | |
| Specifications for 825CM3013 Renovate Maintenance Facility _ Roads.zip | ZIP file | |
| Drawings 1 of 2 for 825CM3013 Renovate Maintenance Facility _ Roads.pdf | ||
| RFI Form.docx | DOCX document | |
| Drawings 2 of 2 for 825CM3013 Renovate Maintenance Facility _ Roads.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Terracon Consultants, Inc. 2822 O’Neal Lane, Bui ld ing B Baton Rouge, Louisiana 70816
P (225) 239 2636 terracon.com
October 6, 2021
Vali Cooper International 126 Terra Bella Boulevard, Suite B
Covington, LA 70433
Attn: Mr. Taqi Muhammad P: (504) 378-7399 E: Taqi@valiint.com
Re: Lead-Containing Paint Inspection Report Alexandria National Cemetery - Maintenance Building 209 East Shamrock Street Pineville, LA 71360 Terracon Project No. EH217092
Dear Mr. Muhammad:
Terracon Consultants, Inc. (Terracon) conducted limited lead paint sampling at the subject property located at 209 East Shamrock Street in Pineville, Louisiana on September 20, 2021.
The sampling was conducted in general accordance with Terracon’s Proposal Number
PEH217092 dated May 21, 2021. Terracon understands that this survey was requested due to the planned renovation of the maintenance building.
Project Information
Limited lead paint chip sampling was performed on September 20, 2021, by Mr. Lem Dial, a
Terracon professional under the direction of Jeremiah Garms, an LDEQ Lead Risk Assessor
(AI#: 140570). Our scope of services included the collection of bulk paint chip samples of suspect lead-containing paint prior to the planned renovations of the Alexandria National Cemetery
Maintenance Building. The disturbance of lead-containing paints as it relates to this project is regulated by the Occupational Safety and Health Administration (OSHA) for employee exposure.
Findings
Terracon’s Lead Risk Assessor identified five potential combinations of building component, substrate, and paint color where lead-containing paint could be present. As a result, five paint bulk chips were collected from various building components and were submitted under chain of custody to EMSL Analytical, Inc. of Cinnaminson, New Jersey for total lead analysis by EPA method (SW 846 3050B/7000B - Flame AAS). EMSL Analytical, Inc. is accredited by the
Louisiana Environmental Laboratory Accreditation Program (LELAP; Certification No. 01950). The results of the sample analysis ranged from less than (<)0.0080% to 0.65% lead by weight (wt).
The following table provides a summary of the results. The laboratory analytical report is included as Appendix A and selective photographs are presented in Appendix B.
Limited Paint Sampling Results 209 East Shamrock Street ■ Pineville, Louisiana October 6, 2021 ■ Terracon Project EH217092
Responsive ■ Resourceful ■ Reliable 2
Table 1 – Summary of Lead Content in Paint
Sample Number Component Substrate Color Lead
Concentration
200 - 01 Interior Wall Concrete Grey <0.032% wt
200 - 02 Exterior Wall / Gutters Wood / Metal White 0.65 % wt
200 – 03 Interior Wall Sheetrock Cream <0.0080% wt
200 – 04 Interior Wall Brick White 0.017 % wt
200 – 05 Wall/Ceiling Plaster Cream <0.0080% wt
The results indicate that lead was detected in the white paint on the exterior wood walls & white gutters of the building and the white paint on the interior brick walls. These areas should be considered for abatement or stabilization. The analytical report is presented as Appendix A.
The Occupational Safety and Health Administration (OSHA) regulates lead in construction work in any concentration because it may be possible to generate significant airborne lead concentrations when performing certain work on materials containing lead.
Recommendations
Any detectable level of lead presents a potential source of exposure with regard to the OSHA
Lead in Construction Standard (29 CFR 1926.62). OSHA defines lead-containing paint as a paint that contains lead, regardless of the concentration.
Therefore, Terracon recommends that maintenance personnel and any potential contractors be made aware of the findings of this limited lead-containing paint survey. Maintenance personnel and contractors should follow the requirements of the OSHA Lead in Construction standard when disturbing lead-containing components. The full OSHA lead standard should be referenced for compliance.
All occupational exposure to lead occurring during construction work, including maintenance activities, painting, alteration and repairs is subject to the OSHA Lead Exposure in Construction standard. Construction work covered by 29 CFR 1926.62 includes any repair or renovation activities or other activities that disturb in-place lead-containing materials, but does not include routine cleaning and repainting where there is insignificant damage, wear, or corrosion of existing lead-containing coatings or substrates. Employers must assure that no employee will be exposed to lead at concentrations greater than 50 micrograms per cubic meter averaged over an eight-hour period without adequate protection.
The landfill selected to receive the waste stream should be contacted to determine specific disposal requirements prior to transportation.
Responsive ■ Resourceful ■ Reliable 3
General Comments
Limited lead paint sampling activities were conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions and recommendations expressed in this report are based on conditions observed during limited sampling event. This letter report has been prepared on behalf of and exclusively for use and reliance by the Client. This report is not a bidding document. Contractors or consultants reviewing this limited sampling report must draw their own conclusions regarding further investigation or remediation deemed necessary.
Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information, which may have been used in the preparation of this report. No warranty, express or implied is made.
The above overview is not intended to be inclusive of all potentially pertinent regulatory information. The relevant EPA and OSHA standards should be consulted prior to undertaking activities involving the demolition, renovation, or maintenance of surfaces coated with lead-based paints. Limited lead-based paint sampling is not intended to serve as a comprehensive building lead-based paint survey, comprehensive inspection, or comprehensive assessment for the presence of lead-based paint on all or most of the building systems.
Terracon appreciates the opportunity to provide this service to Vali Cooper International. If you have any questions regarding this sampling report, please contact the undersigned at (225) 239-
2636.
Sincerely, Prepared By: Reviewed By:
Jeremiah Garms Rush Bowers, CIH, CSP
LDEQ Lead Risk Assessor (AI#: 140570) Senior Industrial Hygiene Consultant
Attachments:
Exhibit 1 – Sample Locations Diagram
Appendix A – Laboratory Analytical Reports
Appendix B – Certifications
THIS DIAGRAM IS FOR GENERAL LOCATION ONLY, AND IS NOT INTENDED FOR CONSTRUCTION PURPOSES
LEGEND
NOT TO SCALE
Drawn By:
Checked By:
Approved By:
Project Mngr:
File No.
Date:
Scale:
Project No.
Consulting Engineers and Scientists
EXHIBITSAMPLE LOCATION DIAGRAM
LBP SURVEY
ALEXANDRIA NATIONAL CEMETERY
200 EAST SHAMROCK STREET
PINEVILLE, LOUISIANA
JG
SEG
MRF/JG
LN
EH217092
AS SHOWN
ASEH217092-1
SEPTEMBER 2021 2822 O'Neal Lane, Building B Baton Rouge, LA 70816
(225) 344-6052 (225) 344-6346
SAMPLE LOCATION
RESTROOM STORAGE
EQUIPMENT
STORAGE
OFFICE
BATHROOM
STORAGE
200-04
200-03
200-05
200-02
200-01
SHOWER
AutoCAD SHX Text N
Responsive ■ Resourceful ■ Reliable 4
APPENDIX A
Client Sample Description ConcentrationLab ID Analyzed Weight Lead
Collected
EMSL Analytical, Inc.
200 Route 130 North, Cinnaminson, NJ 08077 Phone/Fax: (856) 303-2500 / (856) 786-5974 http://www.EMSL.com cinnaminsonleadlab@emsl.com
Attn: Lem Dial Terracon Consultants 524 Elmwood Park Blvd.
Ste. 170 New Orleans, LA 70123
Received: 9/23/2021 11:15 AM
EH217092
Fax:
Phone: (504) 818-3638
Project:
9/20/2021Collected:
Test Report: Lead in Paint Chips by Flame AAS (SW 846 3050B/7000B)*
202107248 CustomerID: TCNL25 CustomerPO: EH217091 ProjectID:
EMSL Order:
0.0619 Site: grey on interior concrete
202107248-0001200-01 <0.032 % wt9/23/2021 g9/20/2021
0.2504 Site: white exterior wood
202107248-0002200-02 0.65 % wt9/23/2021 g9/20/2021
0.2602 Site: cream interior drywall
202107248-0003200-03 <0.0080 % wt9/23/2021 g9/20/2021
0.2553 Site: white interor brick walls
202107248-0004200-04 0.017 % wt9/23/2021 g9/20/2021
0.2538 Site: cream interior plaster walls / ceilings
202107248-0005200-05 <0.0080 % wt9/23/2021 g9/20/2021
Phillip Worby, Lead Laboratory Manager or other approved signatory
Test Report ChmSnglePrm/nQC-7.32.3 Printed: 9/23/2021 4:35:40 PM
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.
Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.008% wt based on the minimum sample weight per our SOP. "<" (less than) result signifies the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. Definitions of modifications are available upon request.
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NELAP Certifications: NJ 03036, NY 10872, PA 68-00367, AIHA-LAP, LLC ELLAP 100194, A2LA 2845.01
Initial report from 09/23/2021 16:35:40 http://www.EMSL.com mailto:cinnaminsonleadlab@emsl.com
Responsive ■ Resourceful ■ Reliable 5
APPENDIX B
STATE OF LOUISIANA
DEPARTMENT OF ENVIRONMENTAL QUALITY
certifies that
Jeremiah A Garms
Has complied with all requirements of the Louisiana Department of Environmental Quality and is authorized to perform the duties of
Lead Risk Assessor
Accreditation No. MR140570 AI No. 140570
Date of Issuance April 30, 2021 Expiration March 3, 2022
Failure to comply with all applicable provisions of La. R.S. 2025.E. (1)(a) and La. R.S. 2025.F. (2)(a) may result in civil and/or criminal enforcement actions by the State.
Public Participation & Permit Support Division
Office of Environmental Services
| Lead Risk Assessor LDEQ Jeremiah A Garms 140570 |
| LBP DIagram |
| Sheets and Views |
| Model |
202107248_002 LBP Lab Report
| 2021-10-06T16:45:01-0500 | |
| Nunez, Lucio |
| 2021-10-06T17:04:41-0500 | |
| Whitting, Steve E |
File details come from the government source that posted it. Updated .