This is a specification section (09 72 16) for vinyl-coated fabric wall coverings and installation in construction projects. The specification establishes requirements for materials, products, installation practices, and quality assurance for this finish work.

Products and Materials: Wall coverings must comply with Wallcovering Association standard WA W-101 and be Type II (Medium Duty) vinyl-coated fabric with a factory-applied polyvinyl-fluoride (PVF) coating of minimum 0.0125 mm thickness. The material must achieve a fungal resistance rating of zero per ASTM G21 and maintain Class A fire hazard classification. Approved manufacturers include MDC Wallcovering and Momentum Textiles with suede surface texture. Adhesives must contain volatile organic compounds (VOCs) of 50 grams per liter or less per EPA Method 24 standards and be vermin, mildew resistant, and germicidal inhibiting types recommended by the wall covering manufacturer. Installation Requirements: Contractors must maintain minimum temperatures of 16°C (60°F) for three days before work begins and throughout the curing process, provide minimum lighting of 15 candela per 0.09 square meter, and ensure continuous ventilation. Surface preparation requires testing substrate moisture content at no more than 5 percent, completion of patches and repairs, and application of cement plaster or wall/liner on masonry and concrete. Installation must follow consecutive panel ordering from fabric rolls, eliminate horizontal seams, and use double-cut seams at inside corners (minimum 50 mm from corner) and outside corners (minimum 152 mm from corner). Installer qualifications require minimum three years of documented experience in this type of work.

View the file

Other files

File Type Posted
Am 7 - Att 1 - 585-337 Prebid RFIs 061626.pdf PDF
36C77626B0016 0007.pdf PDF
36C77626B0016 0006.pdf PDF
Am 6 - Att 1 - Wage Rate 051826.pdf PDF
36C77626B0016 0005.pdf PDF
Am 5 - Att 1 - 585-337 Prebid RFIs 061526_.pdf PDF
36C77626B0016 0004.pdf PDF
Am 4 - Att 1 - Addendum 3 Documents - 2026-05-14 1.pdf PDF
36C77626B0016 0003.pdf PDF
Am 3 - ATT 7 - G004K - PHASING PLANS.pdf PDF
Am 3 - ATT 2 - 585-337 - ADD 1.pdf PDF
Am 3 - ATT 1 - 585-337 Prebid RFIs 060826.pdf PDF
Am 3 - ATT 8 - 014535-585-337 Spec.pdf PDF
Am 3 - ATT 6 - G003K PHASING PLANS.pdf PDF
Am 3 - ATT 10 - Site Plan Laydown.pdf PDF
Am 3 - ATT 5 - 585-337 - Rev phasing plan.pdf PDF
Am 3 - ATT 4 - 585-337 - ADD 3.pdf PDF
Am 3 - ATT 3 - 585-337 - ADD 2.pdf PDF
36C77626B0016 0002.pdf PDF
Amend 2 - ATT 2 - 52.222-90.pdf PDF
Amend 2 - ATT 1 - WR Determination 051326.pdf PDF
36C77626B0016 0001.pdf PDF
Amendment 1 - ATT 2 - Site Visit Agenda 585-337.pdf PDF
Amendment 1 - ATT 1 - 585-337 Site visit sign in.pdf PDF
Attachment 01 - Specifications_Iron Mountain_030526.pdf PDF
Attachment 08 - Site Visit - Iron Mountain.pdf PDF
36C77626B0016.pdf PDF
Attachment 02 - Drawings_Iron Mountain.pdf PDF
Attachment 07 - Wage Rate Determination - Iron Mountain.pdf PDF
Attachment 04 - Limitations on Subcontracting - Iron Mountain.pdf PDF
Attachment 06 - ICRA Pharamcy and Radiology 585-337 15Dec2025.pdf PDF
Attachment 03 - Brand Name Justification - Iron Mountain_redacted.pdf PDF
Attachment 05 - PCRA Pharamcy and Radiology 585-337 15Dec2025.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

01-01-21

09 72 16 - 1

SECTION 09 72 16

VINYL-COATED FABRIC WALL COVERINGS

PART 1 - GENERAL

1.1 DESCRIPTION

A. Section specifies vinyl coated fabric wall covering and installation.

1.2 RELATED WORK

A. Section 09 06 00, SCHEDULE FOR FINISHES: Color, pattern, type, direction of hanging and areas to receive wall covering.

B. Section 09 72 31, POLYPROPYLENE FABRIC WALL COVERING: Textile wall coverings.

1.3 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Samples:

1. Each type and pattern as specified in Section 09 06 00, SCHEDULE FOR

FINISHES.

2. Size: Full width of mill run not less than 450 mm (18 inches) in length.

C. Manufacturer's Certificates:

1. Compliance with WA W-101.

2. Wall covering manufacturer's approval of adhesive.

D. Manufacturer's Literature and Data:

1. Wall covering primer and adhesive.

2. Installation instructions.

3. Maintenance instructions, including recommended materials and methods for maintaining wall covering with precautions in use of cleaning material.

E. Tests: Substrate moisture.

1.4 QUALITY ASSURANCE

A. Installer Qualifications: Company specializing in performing work of type specified, with minimum 3 years of documented experience.

1.5 DELIVERY, STORAGE AND HANDLING

A. Deliver in original unopened containers bearing the manufacturer's name, brand name, and product designation.

B. Store in accordance with manufacturer's instructions.

C. Handle to prevent damage to material.

D. Do not store roll goods on end.

09 72 16 - 2

1.6 APPLICABLE PUBLICATIONS

A. Publications listed below form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only.

B. ASTM International (ASTM):

E84-20..................Surface Burning Characteristics of Building

Materials

G21-15..................Determining Resistance of Synthetic Polymeric

Materials to Fungi

C. Code of Federal Regulation (CFR):

40 CFR 59(2016) Subpart D..... National Volatile Organic Compound

Emission Standards for Architectural Coatings

D. Wallcovering Association (WA):

W-101-17................Quality Standard Polymer Coated Fabric

Wallcoverings

PART 2 - PRODUCTS

2.1 VINYL COATED FABRIC WALL COVERING

A. Comply with WA W-101.

B. Fungi Resistance: ASTM G21, rating of zero (0).

C. Factory-applied clear delustered polyvinyl-fluoride (PVF) coating:

1. Minimum 0.0125 mm (1/2 mil) thickness.

2. Do not include PVF coating weight in minimum total weight.

3. Fire hazard classification with PVF coating: Class A unless specified otherwise.

D. Type II (Medium Duty).

E. Digital Wall covering – Type WC1: Fabric-backed vinyl roll stock

1. Surface texture: Suede

2. Manufacturers:

a. MDC Wallcovering: www.mdcwall.com

b. Momentum Textiles: www.momentumtextilesandwalls.com

c. Refer to 09 06 00 Schedule of Finishes for additional information.

2.2 PRIMER AND ADHESIVE

A. Adhesive shall have a VOC content of 50 gram/liter or less when calculated according to 40 CFR 59, (EPA Method 24).

B. Vermin, mildew resistant and germicidal inhibiting type recommended by wall covering manufacturer for use on substrate to receive wall covering.

http://www.momentumtextilesand/

09 72 16 - 3

PART 3 - EXECUTION

3.1 JOB CONDITIONS

A. Temperatures:

1. Do not perform work until surfaces and materials have been maintained at minimum of 16 degrees C (60 degrees F) for three (3) days before work begins.

2. Maintain minimum temperatures of 16 degrees C (60 degrees F) until adhesives are dried or cured.

B. Lighting:

1. Do not proceed unless a minimum lighting level of 15 candela per

0.09 square meter (15 candela per square foot) is provided.

2. Measure light level at mid-height of wall.

C. Ventilation: Provide continuous ventilation as required to rid the spaces in which the wall coverings are being installed of volatile compounds given off by the wall coverings, sealers and adhesives and as recommended by the product manufacturer for full drying or curing.

D. Protect other surfaces from damage resulting from installation of wall coverings. Provide drop cloths, shields and protective equipment to prevent primers, adhesives or wall covering from fouling adjacent surfaces and in particular, storage and preparation areas.

E. Store flammable rubbish, waste, cloths and materials which may constitute a fire hazard, in closed metal containers. Daily remove and properly dispose of flammable wastes from the site.

3.2 SURFACE CONDITION AND PREPARATION

A. Inspect surfaces to receive wall coverings to assure that:

1. Patches and repairs to substrates are completed.

2. Surfaces are clean, smooth and prime painted.

3. Masonry and concrete walls are to have flush joints. Coat these walls with cement plaster or wall/liner as substrate preparation.

B. Surfaces to receive wall covering are to be dry. Test moisture content of plaster, concrete, and masonry walls with an electric moisture meter. The moisture content is not permitted to be more than 5 percent.

Submit test results.

C. Do not proceed until discovered defects have been corrected by other trades and surfaces are ready to receive wall covering.

09 72 16 - 4

D. Carefully remove electrical outlet and switch plates, mechanical diffusers, escutcheons, registers, surface hardware, fittings and fastenings, prior to starting work and store items for reinstallation.

3.3 APPLICATION OF ADHESIVE

A. Mix and apply adhesives in accordance with manufacturer's directions.

B. Prevent adhesive from getting on face of wall covering.

C. Apply adhesive to wall covering back.

3.4 INSTALLATION

A. Use wall covering of same batch or run in each area. Use fabric rolls in consecutive numerical sequence of manufacture.

B. Install material completely adhered, smooth, clean, without wrinkles, air pockets, gaps or overlaps.

C. Extend wall covering continuous behind non-built-in casework and other items which are not bolted to the walls.

D. Install wall covering before installation of resilient base. Extend wall covering not more than 6 mm (1/4 inch) below top of resilient base.

E. Install wall covering panels consecutively in order in which they are cut from the roll including filling spaces above or below windows, doors, or similar penetrations.

F. Do not install horizontal seams.

G. Except on match patterns, hang fabric by reversing alternate strips, except as recommended by the manufacturer.

H. Cutting:

1. Cut on a work table with a straight edge.

2. Joints or seams that are not cut clean are unacceptable.

3. Trim additional selvage to achieve a color and pattern match at seams. Overlapped seams are not allowed.

4. Do not double cut seams on wall unless specified.

5. If double cutting on the wall is necessary, place a three inch strip of Type I wall covering under pasted edge.

a. Do not cut into wall surface.

b. After cutting, remove strip and excess adhesive from seam before proceeding to next seam.

c. Smooth down seam in adhesive for tight bond and joint.

I. Trim strip-matched patterns which are not factory pre-trimmed.

J. Inside Corners:

09 72 16 - 5

1. Wrap wall covering around corners.

2. Do not seam within 50 mm (2 inches) of inside corners.

3. Double cut seams.

K. Outside Corners:

1. Wrap wall covering around corners.

2. Do not seam within 152 mm (6 inches) of outside corners.

3. Double cut seams.

3.5 CLEANING AND INSTALLING TEMPORARY REMOVED ITEMS

A. Remove adhesive from wall covering as work proceeds.

B. Remove adhesives where spilled, splashed or splattered on wall coverings or adjacent surfaces in a manner not to damage surface from which it is removed.

C. Upon completion of work, leave wall covering free of dirt or soil.

D. Remove all debris associated with wall covering installation.

E. Reinstall previously removed electrical outlet and switch plates, mechanical diffusers, escutcheons, registers, surface hardware, fittings and fastenings.

- - - E N D - - -

SECTION 09 72 16 VINYL-COATED FABRIC WALL COVERINGS
PART 1 - GENERAL
1.1 DESCRIPTION
1.2 RELATED WORK
1.3 SUBMITTALS
1.4 QUALITY ASSURANCE
1.5 DELIVERY, STORAGE AND HANDLING
1.6 APPLICABLE PUBLICATIONS
PART 2 - PRODUCTS
2.1 VINYL COATED FABRIC WALL COVERING
2.2 PRIMER AND ADHESIVE
PART 3 - EXECUTION
3.1 JOB CONDITIONS
3.2 SURFACE CONDITION AND PREPARATION
3.3 APPLICATION OF ADHESIVE
3.4 INSTALLATION