Amendment0003 - Attachment 29 - 550-319 Drawings Set_Part 8 Full Size.pdf
PDF 12 MB Posted
- Solicitation number
- 36C77624B0020
About this file
This document is Amendment 0003 to Attachment 29 of the 550-319 Drawings Set for Solicitation 36C77624B0020, which is a minor construction project for the Department of Veterans Affairs (VA) to construct two new green homes at the Danville VA Medical Center.
The key details are: The solicitation is for the construction of two new homes (7 and 8) at the Danville VAMC, with questions due by July 26, 2024 at 2:00 pm EDT and bids due on August 13, 2024 at 2:00 pm EDT. All questions and bids must be submitted via email to the specified VA contracting points of contact. The solicitation is being issued by the VA Technology Acquisition Center in Austin, TX, which is a civilian federal agency. No additional details about the construction requirements, pricing, set-asides, or incumbents are provided in this particular document.
View the file
Other files
Show all 40
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SA
SA
RA
SA
EA
OA
TA
FD
SD
FSD
RA
RA
EA
EA
SUPPLY DIFFUSER
RETURN GRILLE
EXHAUST GRILLE
LINEAR SLOT DIFFUSER
TS
FS
PS
SA AIR DUCT TURNING UP
SA AIR DUCT TURNING DOWN
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
AUTOMATIC AIR VENT
BALANCING VALVE
BALL VALVE
BUTTERFLY VALVE
CHECK VALVE
FLEXIBLE PIPE CONNECTION
FLOW METER (VENTURI)
FLOW SWITCH
PRESSURE SWTICH
TAMPER SWITCH
THERMOMETER
FLEXIBLE DUCT
DOUBLE CHECK VALVE ASSEMBLY
SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
OUTSIDE AIR DUCT
TRANSFER AIR DUCT
PIPING UNION
FIRE DAMPER
SMOKE DAMPER
COMBINATION FIRE/SMOKE DAMPER
PETE'S PLUG
MANUAL AIR VENT
TRIPLE DUTY VALVE
MANUAL ISOLATION VALVE
GLOBE VALVE
OS&Y (GATE) VALVE
AUTO-FLOW CONTROL VALVE
VOLUME DAMPER
PIPE ELBOW TURNING UP/TURNING DOWN
PIPE TEE TURNING UP/TURNING DOWN
HVAC LEGEND
X TAGGED NOTE DESIGNATOR
REVISION DESIGNATOR
STRAINER
PRESSURE REDUCING VALVE (STEAM, GAS, WATER, ETC.)
MOTORIZED DAMPER
RA AIR DUCT TURNING UP
RA AIR DUCT TURNING DOWN
EA AIR DUCT TURNING UP
EA AIR DUCT TURNING DOWN
EQUIPMENT TAG DESIGNATOR (BUILDING NO. - ITEM - ITEM NUMBER)
T THERMOSTAT
TEMPERATURE SENSOR
XX—XX —XX
H HUMIDISTAT
T
X
A/E ARCHITECT / ENGINEER
AAHX AIR TO AIR HEAT EXCHANGER
AAV AUTOMATIC AIR VENT
AB AIR BLENDER
ACC AIR COOLED CONDENSER
ACCH AIR COOLED CHILLER
ACCU AIR COOLED CONDENSING UNIT
ACD AUTOMATIC CONTROL DAMPER,
MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER,
TWO POSITION
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AFW AIR FOIL WHEEL (FAN)
AHU AIR-HANDLING UNIT
AMP AMPERE
AP ACCESS PANEL
APD AIR PRESSURE DROP
AQST AQUASTAT
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATION AIR
CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
AW AIR WASHER
AXF AXIAL FLOW
B BOILER
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BIW BACKWARD INCLINED WHEEL (FAN)
BMT BONE MARROW TRANSPLANT
BR BOTTOM REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
C CENTIGRADE (CELSIUS)
CAV CONSTANT AIR VOLUME
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CEILING DIFFUSER
CD-1 CONSTRUCTION DOCUMENTS (SUBMISSION1)
CD-2 CONSTRUCTION DOCUMENTS (SUBMISSION2)
CENT CENTRIFICAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFT CUBIC FEET
CFP CHEMICAL FEED PUMP
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHW CHILLER WATER
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CM CARBON MONOXIDE
CM CUBIC METER
CM/S CUBIC METER PER SECOND
CO CLEAN OUT
CO2 CARBON DIOXODE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CR CEILING REGISTER
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONSTANT VOLUME
CW COLD WATER (POTABLE)
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO
COOLING TOWER)
CWS CONDENSER WATER SUPPLY (FROM
COOLING TOWER)
D DAMPER - AUTOMATIC
Db DRY-BULB TEMPERATURE
DB DECIBELS
DCW DOMESTIC COLD WATER
DD-1 DESIGN DEVELOPMENT (SUBMISSION 1)
DD-2 DESIGN DEVELOPMENT (SUBMISSION 2)
DDC DIRECT DIGITAL CONTROLS
DEG DEGREE
DF DIFFUSER
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DIA DIAMETER
DIW DEIONIZED WATER
DP DEW POINT TEMPERATURE
DP DIFFUSER PLATE
DPA DIFFERENTIAL PRESSURE ASSEMBLY
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EC EVAPORATIVE COOLER
ECC ENGINEERING CONTROL CENTER
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EGT ENTERING GLYCOL TEMPERATURE
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
EX EXISTING
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/SDPR COMBINATION FIRE SMOKE DAMPER
FA FREE AREA
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FCW FORWARD CURVED WHEEL (FAN)
FD FLOOR DRAIN
FD FIRE DAMPER
FF FINAL FILTER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FOHX FUEL OIL HEAT EXCHANGER
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT WC FEET OF WATER COLUMN
FT-LB FOOT-POUND
FTR FIN TUBE RADIATION
FV FACE VELOCITY
GA GAUGE
GAL GALLONS
GH GRAVITY HOOD
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
H HUMIDIFER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HOOD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRP HYDRONIC RADIANT (CEILING) PANEL
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HVD HOISTWAY VENT DAMPER
HX HEAT EXCHANGER
HZ HERTZ
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICF IN-LINE CENTRIFUGAL FAN
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCH WATER COLUMN
IN WG INCH WATER GAUGE
IN-LB INCH-POUND
IPLV INTERGRATED PART LOAD VALUE
IRH INTRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
J INTENTIALLY LEFT BLANK
KG KILOGRAM
KG/HR KILOGRAM PER HOUR
kPa KILOPASCAL
KW KILOWATT
KWH KILOWATT HOUR
L LITER
L/h LITERS PER HOUR (or LITERS/HOUR) L/m LITERS PER MINUTE (or LITERS/MINUTE) L/s LITERS PER SECOND (or LITERS/SECOND)
LAT LEAVING AIR TEMPERATURE
LBS/HR POUNDS PER HOUR
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LPG LIQUEFIED PETROLEUM GAS
LPR LOW PRESSURE RETURN (STEAM CONDENSATE)
LPRC LOW PRESSURE STEAM RETURN (CLEAN)
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPS LOW PRESSURE STEAM
LPSC LOW PRESSURE STEAM (CLEAN)
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M METER, SI UNIT
M/S METERS PER SECOND (OR
METERS/SECOND)
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKE-UP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1,000 BTUH
MCA MINIMUM BRANCH CIRCUIT AMPACITY
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING VALUE
MH MANHOLE
MHP MOTOR HORSEPOWER
MIN MINIMUM
MM MILLIMETER
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING
MTD MEAN TEMPERATURE DIFFERENCE
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOWMETER
Nm NEWTON METER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC
ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPSH NET POSITIVE SUCTION HEAD
NPSHA NET POSITIVE SUCTION HEAD AVAILABLE
NPSHR NET POSITIVE SUCTION HEAD REQUIRED
NTS NOT TO SCALE
OA OUTSIDE AIR
OAD OUTDOOR AIR DAMPER
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OD OUTSIDE DIAMETER
OFM OIL FLOWMETER
OR OPERATING ROOM
UC UNDER CUT
UC UNIT COOLER
UH UNIT HEATER
U UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
P PUMP
Pa PASCAL
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT (FEET)
PD PRESSURE DROP
PEF PROPELLER (TYPE) EXHAUST FAN
PF PRE-FILTER
PG PRESSURE GAGE
PGW PROPYLENE GLYCOL-WATER (SOLUTION)
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRS PRESSURE REGULATING (VALVE) STATION
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH – ABSOLUTE
PSIG POUNDS PER SQUARE INCH – GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
R/E RETURN OR EXHAUST
RA RETURN AIR
RAD RETURN AIR DAMPER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCU RECIPROCATING CHILLER UNIT
RD REFRIGERANT DISCHARGE
RDS ROOM DATA SHEETS
REA RELIEF AIR
RELAD RELIEF AIR DAMPER
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOF TOP UNIT
RV RELIEF VALVE
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCI SPINAL CODE INJURY
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SD-1 SCHEMATIC DESIGN (SUBMISSION1)
SD-2 SCHEMATIC DESIGN (SUBMISSION2)
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SI SQUARE INCHES
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT (FEET)
SR SUPPLY AIR REGISTER
SS STAINLESS STEEL
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
ST STEAM TRAP
SUH STEAM UNIT HEATER
SV STEAM PRESSURE REDUCING VALVE
SVS STEAM VENT SILENCER
SW SOFTWATER
SWHX STEAM TO WATER HEAT EXCHANGER
T&PCV TEMPERATURE AND PRESSURE
CONTROL VALVE
TAB TESTING, ADJUSTING, BALANCE
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
UC UNDER CUT
UC UNIT COOLER
UH UNIT HEATER
U UNDERWRITERS LABORATORY
URV UPBLAST UNIT VENTILATOR
V VALVE
VAF VANE-AXIAL FAN
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED
BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
VUH VERTICAL UNIT HEATER
W WATTS
WAG WASTE ANETHESIA GAS
Wb WET-BULB (TEMPERATURE)
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCHP WATER COOLED HEAT PUMPS
WCPU WATER COOLED PACKAGED UNIT
WEF WALL EXHAUST FAN
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
YR YEAR
HVAC ABBREVIATIONS
I LL IN O IS
R
.E
SS
E J
FARBE
LICENSED
PROFESSIONAL
OF
ENGINEER
062.069980
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs \m h e a le y \D o c u m e n ts \V
IG
H
-M -R m h e a le y c m ta e g rs .c o m
.r v t
/1
/2
:3
:1
A
M
ML100
MECHANICAL LEGEND AND
GENERAL NOTESGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA ST.
SUITE 200
317.800.6388
CMTA
10411 Meeting Street
Prospect, Kentucky 40059
502.326.3085
CONSTRUCT TWO NEW GREEN
HOMES 7 & 8
1900 E. MAIN ST., DANVILLE, IL 61832
550-319
7 & 8
04/09/2020 AJM MJH
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
MECHANICAL GENERAL NOTES:
A. COORDINATE THE LOCATION OF DRAINS, THERMOSTATS, GAS
OUTLETS, ETC., WITH ALL CASEWORK EQUIPMENT,
MECHANICAL ROOM EQUIPMENT, ETC., PRIOR TO COMMENCING
INSTALLATION. WORK NOT SO COORDINATED SHALL BE
REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THE
CONTRACTOR.
B. THE CONTRACTOR SHALL EXERCISE EXTREME CARE IN THE
COURSE OF THEIR WORK SO AS TO INSURE THAT THEY DO NOT
INTERRUPT ANY EXISTING SERVICE. FOR SAFETY PURPOSES,
PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE
TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE
LOCATION, SIZE, TYPE, ETC., OF EACH UNDERGROUND OR
OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN
ACCORD WITH ALL FEDERAL, STATE AND/OR LOCAL RULES,
REGULATIONS, STANDARD AND SAFETY REQUIREMENTS.
UTILITIES SHALL BE INSTALLED IN ACCORD WITH THE
APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS.
IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL
APPLY.
C. WHERE WORK IS REQUIRED ABOVE EXISTING LAY-IN, PLASTER
OR GYPSUM BOARD CEILINGS, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR REMOVAL AND REINSTALLATION (OR
REPLACEMENT, IF DAMAGED) OF ALL CEILING OR TILE AND
GRID MEMBERS NECESSARY TO PERFORM HIS WORK. NEW
TILE AND GRID SHALL MATCH THE SURROUNDING AREAS. ALL
PATCHING WORK SHALL MATCH ADJACENT SURFACES.
D. ALL NEW WORK SHALL BE HUNG FROM STRUCTURE, NOT FROM
THE WORK OF OTHER TRADES, WHETHER EXISTING OR NEW.
E. COORDINATE ALL WORK WITH PROJECT PHASING
REQUIREMENTS.
F. PATCH, REPAIR AND PAINT (TO OWNER'S STANDARDS) OR
PROVIDE WALL COVERING FOR EXISTING WALLS, CEILINGS,
ETC., THAT ARE TO REMAIN IF DAMAGED DURING
CONSTRUCTION. REPAIRS SHALL MATCH ADJACENT
SURFACES TO THE SATISFACTION OF THE ARCHITECT AND
OWNER.
G. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS
THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT.
(CITY, COUNTY, LOCAL, FEDERAL, MUNICIPALITY, UTILITY
COMPANY, COMMONWEALTH OF KENTUCKY, ETC.)
H. CONTRACTOR SHALL BE AWARE OF UNSEEN PLUMBING, HVAC
AND ELECTRICAL WORK DURING DEMOLITION. IF ITEMS ARE
UNCOVERED DURING DEMOLITION THEN FIELD VERIFY THE USE
OF THE ITEMS AND PLAN AN ALTERNATE ROUTE TO RUN THESE
ITEMS. THEN CONTACT THE ENGINEERS TO REVIEW THE
ROUTING.
I. IF AREA OF CONSTRUCTION HAS A POST TENSION FLOOR SLAB.
CONTRACTOR SHALL USE ULTRA SOUND OR OTHER APPROVED
METHODS TO SURVEY THE EXISTING FLOOR STRUCTURE
BEFORE MAKING ANY AND ALL FLOOR PENETRATIONS.
J. WHERE FIRE PROOFING IS SPRAYED ON EXISTING STRUCTURE
ALL EXISTING CONDUITS, WATER, HYDRONIC, STEAM, CHILLED
WATER, FIRE PROTECTION LINES, MED GAS, ETC. SHALL BE
LOWERED TO BE BELOW FULL THICKNESS OF FIRE PROOFING
WITH NO INTERFERENCE.
K. ALL PENETRATIONS OF FIRE AND SMOKE RATED ASSEMBLIES
SHALL BE APPROPRIATELY FIRE STOPPED PER AN APPROVED
U.L. LISTED STANDARD. CONTRACTOR SHALL PAY PARTICULAR
ATTENTION TO INSULATED PIPING PENETRATIONS.
L. ALL WORK REQUIRING DOWNTIME OF ANY AREA IN THE
BUILDING SHALL BE SCHEDULED 2 WEEKS IN ADVANCE, AND
SHALL COMPLY WITH INTERIM LIFE SAFETY MEASURES.
M. ALL DUCTWORK, PIPING, CONDUITS, ETC. IN ROOMS WITH
CEILINGS SHALL BE ABOVE CEILING EXCEPT AS NOTED.
N. INSTALL AIR VENTS AT HIGH POINTS IN PIPING AND DRAINS IN
LOW POINTS. USE CARE TO AVOID FREEZING OF EXTERIOR
VENTS.
O. LOCATIONS OF PIPING, DUCTS AND EQUIPMENT ARE
APPROXIMATE AND SUBJECT TO MINOR ADJUSTMENTS IN THE
FIELD. DO NOT SCALE THE DRAWINGS.
P. ALL OFFSETS IN DUCTS AND PIPING ARE NOT NECESSARILY
SHOWN. PROVIDE ADDITIONAL OFFSETS WHERE NECESSARY.
Q. COORDINATE ALL HVAC WORK WITH ELECTRICAL, PLUMBING
AND OTHER TRADES TO AVOID INTERFERENCE WITH PIPING,
DUCTS, CONDUIT AND OTHER EQUIPMENT.
R. INSTALL ALL PIPING, DUCTWORK AND EQUIPMENT IN STRICT
ACCORDANCE WITH MANUFACTURER'S INSTALLATION
INSTRUCTION. IF IN CONFLICT WITH THE DESIGN INDICATED IN
CONTRACT DOCUMENTS, ADVISE THE ENGINEERS PRIOR TO
INSTALLATION FOR CLARIFICATION. PROVIDE RECOMMENDED
ACCESS AND SERVICE CLEARANCES FOR ALL EQUIPMENT.
S. SEAL AIRTIGHT AROUND ALL DUCTS AND PIPING PENETRATIONS
THROUGH WALLS, FLOORS AND ROOF. PROVIDE FIRE
STOPPING IN FIRE PARTITION.
T. SEAL ALL NEW DUCTWORK JOINTS WITH UNITED MCGILL,
IRONGRIP 6O1 OR EQUAL WATER BASED SEALANT.
U. ALL MOTOR DRIVEN EQUIPMENT SHALL BE INSTALLED WITH
FLEXIBLE CONNECTIONS TO DUCTWORK, PIPING, ETC., UNLESS
OTHERWISE NOTED.
V. THE CONTRACTOR SHALL RELOCATE OR AVOID ANY EXISTING
EQUIPMENT APPURTENANCES, ETC., THAT CONFLICT WITH
NEW WORK.
W. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN
CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE
ENGINEERS BEFORE INSTALLATION. REFER ALSO TO
ARCHITECTURAL WALL INTERIOR AND EXTERIOR WALL
ELEVATIONS, CEILING HEIGHTS AND OTHER DETAIL OF THESE
DOCUMENTS.
X. DOUBLE WIDTH TURNING VANES SHALL BE INSTALLED IN ALL
SUPPLY, RETURN, AND EXHAUST DUCTWORK ELBOWS.
TURNING VANES NOT REQUIRED FOR KITCHEN EXHAUSTS.
Y. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION
PRODUCING EQUIPMENT SHALL BE ISOLATED FROM
SURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR
STRUCTURALLY DAMAGING INSTALLATIONS SHALL BE
SATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING
CONTRACTOR'S EXPENSE. THE FINAL DECISION ON THE
SUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY
SHALL BE THAT OF THE ENGINEER.
Z. DEVIATIONS IN SIZE, CAPACITIES, FIT, FINISH, ETC. FOR
EQUIPMENT FROM THAT USED AS BASIS OF DESIGN SHALL BE
THE RESPONSIBILITY OF THE PURCHASER OF THAT
EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A
DEVIATION, WHETHER APPROVED BY THE ENGINEERS OR NOT,
SHALL BE THE RESPONSIBILITY OF THE PURCHASER.
AA. VALVES, BALANCING DAMPERS OR ANY
MECHANICAL/ELECTRICAL ITEM REQUIRING ACCESS SHALL NOT
BE LOCATED ABOVE A HARD CEILING. IF THIS IS NOT POSSIBLE,
THEN AN APPROPRIATELY SIZED ACCESS DOOR SHALL BE
PLACED UNDER THE ITEM TO ALLOW EASY MAINTENANCE AND
ADJUSTMENT. ADDITIONALLY ALL SUCH ITEMS SHALL NOT BE
LOCATED AN UNREASONABLE DISTANCE ABOVE THE CEILINGS.
IN GENERAL ALL SUCH ITEMS UNLESS INDICATED OTHERWISE
SHALL BE MOUNTED SIX TO TWELVE INCHES ABOVE THE
CEILING. IF IN DOUBT, CONTACT ENGINEER PRIOR TO
INSTALLING.
BB. ALL MANHOLES, VAULTS AND SIMILAR UNDERGROUND
STRUCTURES SHALL HAVE THE TOP ELEVATION SET FLUSH
WITH FINISHED GRADE UNLESS SPECIFICALLY NOTED
OTHERWISE.
CC. WHEN RUNNING ANY TYPE OF PIPING BELOW A FOOTER, OR IN
THE ZONE OF INFLUENCE THE PIPING SHALL BE BACKFILLED
WITH CEMENTITIOUS FLOWABLE FILL PER SPECIFICATIONS.
WHENEVER POSSIBLE, LOCATE PIPING OUTSIDE OF THE ZONE
OF INFLUENCE. THE ZONE OF INFLUENCE IS THE AREA UNDER
THE FOOTER WITHIN A 45 DEGREE ANGLE PROJECTING DOWN
FROM THE BOTTOM EDGE OF THE FOOTER OF ALL SIDES OF
THE FOOTER. ADDITIONALLY, GREASE TRAPS, MANHOLES,
VAULTS AND OTHER UNDERGROUND STRUCTURES SHALL BE
HELD AWAY FROM BUILDING WALLS FAR ENOUGH TO BE
OUTSIDE OF THE ZONE OF INFLUENCE.
DD. WORK IN CONFINED AREAS SHALL BE IN ACCORDANCE WITH
THE OWNER'S SAFETY POLICY REQUIREMENTS.
EE. THE DOCUMENTS COMPLY WITH 2006 IMC, 2007 KBC, AND 2009
IECC.
FF. THE DOCUMENTS COMPLY WITH 2006 IMC, 2007 KBC, AND
ASHRAE 90.1-2007.
Revisions: Date:
R E
F
OVEN
R E
F
DW
DN
AA.2
B B.2 D E F G H J
C
2.5
C.6
9.6
C.7C.5
7.1
9.1
H.6E.5D.5
STORAGE
Unoccupied
Unoccupied
GARAGE
CLOSET
23A
CLOSET
22A
KITCHEN
CORRIDOR / STORM SHELTER
MEDICATION
EQUIP. STORAGE
CLEAN LINEN
TOILET
27B
STAFF LOUNGE
SOILED HOLDING
JANITOR
LAUNDRY
OFFICE
HOUSEKEEPING
DEN
BATH
16B
VESTIBULE
BATH
17B
BEDROOM
BEDROOM
VESTIBULE
LIVING ROOM
DINING
KITCHEN
PATIO
BATHROOM
23B
CLOSET
21A
BATHROOM
20B
BEDROOM
BATHROOM
11B
BEDROOM
BATHROOM
12B
BEDROOM
CLOSET
13A
BEDROOM
BATHROOM
13B
BEDROOM
BEDROOM
BATHROOM
21B
BATHROOM
14B
CORRIDOR
TOILET
BATHROOM
22B
BEDROOM
BARIATRIC
S-2
R-3
"x
O
A
"x
E A
"x
E A
12"x10" EA
STORAGE
M8
R-3
R-3
E-2A
E-2A
R-2A
E-2A
E-2A
E-2A
E-2A
E-2A
E-2A
E-2A
E-2A
CLEAN SUPPLY
"x
O A
"x
E
A
"x
O
A
S-6
S-7
S-6
S-6
"x
O
A
S-2A
S-2A
S-2A
S-2A
S-2A
S-2A
S-2
S-2A
S-2A
S-2A
S-2A
E-3
"x
E
A
E-2A
135—FCU—16
135—FCU—17
S-6
S-6
R-3
S-6
S-7
R-3
R-3
S-7
S-6
R-2A
R-2A
S-6
S-6
R-2A
R-2A
R-2A
R-3
S-2
R-2
S-2
S-2
S-5
S-2
S-2
R-5
S-2
135—FCU—23
135—FCU—22
135—FCU—21
135—FCU—20
135—FCU—14
135—FCU—13
135—FCU—12
10"x10" RA
"x
R
A
135—FCU—19B
135—FCU—11
R-7
E-5
M4
M5
135—CUH—1
135—CUH—2
135—CUH—3
"x
E A
E-6
S-3
S-3
10"x10" OA
SPA
19B
BATH
19A
"x
S A
FOR WORK IN THIS
AREA REFER TO
ENLARGED PLAN
ON SHEET MH102.
S-1A
135—RCP—10
135—RCP—11
135—RCP—12
135—RCP—13
135—RCP—14
135—RCP—16135—RCP—17
135—RCP—19B
135—RCP—20
135—RCP—21
135—RCP—22
135—RCP—23
135—RCP—6D
135—RCP—6C
135—RCP—6B135—RCP—6A
CORRIDOR
CORRIDOR
CORRIDOR
S-6
S-7
S-1A
S-2
R-2
R-3
135—BCU—2
"x
O A
"x
O
A
"x
E
A
"x
O
A
"x
O A
"x
O
A
"x
S A
10"x12" RA
"x
O A
"x
E
A
12"x8" SA8"x8" SA
"x
S A
12"x10" RA
"x
S A
S-1
S-1
S-1
S-1
S-5
S-5
S-5
"x
E
A
M2
M22
M7
M7
M7
M24
M24
M24
M1
135—RCP—7A
135—RCP—7B
"x
R
A
"x
S
A
10"x12" RA
B E
LO
W
A B
O V
E
135—CUH—4
GENERAL NOTES - MECHANICAL:
A. FLOOR PLAN FOR BUILDING 135 IS SHOWN. FLOOR PLAN APPLIES TO
BUILDINGS 134 AND 135.
I LL IN O IS
R
.E
SS
E J
FARBE
LICENSED
PROFESSIONAL
OF
ENGINEER
062.069980
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs \m h e a le y \D o c u m e n ts \V
IG
H
-M -R m h e a le y c m ta e g rs .c o m
.r v t
/1
/2
:3
:5
A
M
MH101
FIRST FLOOR PLAN - AIR
DISTRIBUTIONGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA ST.
SUITE 200
317.800.6388
CMTA
10411 Meeting Street
Prospect, Kentucky 40059
502.326.3085
CONSTRUCT TWO NEW GREEN
HOMES 7 & 8
1900 E. MAIN ST., DANVILLE, IL 61832
550-319
7 & 8
04/09/2020 AJM MJH
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
1/8" = 1'-0"
FIRST FLOOR PLAN - AIR DISTRIBUTION
TAGGED NOTES
M1 40x12 OA AND 34x12 EA DUCTS UP TO MECHANICAL ROOM.
REFER TO SHEET MH103 FOR CONTINUATION.
M2 12x8 AND 8x8 SA DUCTS UP TO MECHANICAL ROOM. REFER TO
SHEET MH103 FOR CONTINUATION.
M4 6x6 EA DUCT UP TO MECHANICAL ROOM. REFER TO SHEET
MH102 FOR CONTINUATION.
M5 10x10 EA DUCT UP TO EF-3. REFER TO SHEET MH104 FOR
CONTINUATION.
M7 DUCT DOWN IN CHASE TO LOW GRILLE. BOTTOM OF GRILLE 6"
A.F.F.
M22 12x10 RA DUCT UP TO MECHANICAL ROOM. REFER TO SHEET
MH103 FOR CONTINUATION.
M24 MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES
(TYPICAL).
GRD RUNOUT SCHEDULE
SYMBOL DUCT INLET
E-1 6"Ø
E-1A 6"Ø
E-2 8"Ø
E-2A 8"Ø
E-3 10"Ø
E-5 6x6
E-6 12x6
R-1 6"Ø
R-1A 6"Ø
R-2 8"Ø
R-2A 8"Ø
R-3 10"Ø
R-4 12"Ø
R-5 14"Ø
R-6 12x10
R-7 12x12
S-1 6"Ø
S-1A 6"Ø
S-2 8"Ø
S-2A 8"Ø
S-3 10"Ø
S-4 12"Ø
S-5 6"Ø
S-6 8"Ø
S-7 10"Ø
S-8 8x6
S-9 12x6
F
OVEN
R E
F
DW
D E F G
2.5
E.5D.5
CORRIDOR / STORM SHELTER
MEDICATION
EQUIP. STORAGE
CLEAN LINEN
TOILET
27B
STAFF LOUNGE
27SOILED HOLDING
JANITOR
LAUNDRY
OFFICE
HOUSEKEEPING
KITCHEN
CORRIDOR
TOILET
BATHROOM
22B
S-2
"x
O
A
"x
O A
18"x10" EA
"x
E A
"x
E A
"x
S A
E-1A
E-1A
E-2
125E-1
S-2
R-4
S-2
S-1
E-2
R-1
S-1
S-2
S-1
S-1
E-1
CLEAN SUPPLY
R-3
"x
E
A
"x
O
A
S-1
R-2
S-2
S-1
S-1
S-1
S-1
S-2
S-2
S-2
S-2
R-1A
R-5
16"x8" SA
R-3
R-2
S-2
R-1
10"x10" SA
10"x10" SA
S-4
135—FCU—45
135—FCU—34
135—FCU—29
135—FCU—8
10"x10" RA
"x
R
A
S-1A
135—KH—1
"x
R
A
"x
S
A10"x10" RA
12"x10" EA
S-9
S-9
M3
M5
S-9
16"x10" SA
S-3
10"x10" OA
S-1
"x
S
A
135—BCU—1
"x
S A
"x
S
A
M21
"x
E
A
"x
R
A
MECHANICAL CLOSET
M11
MECHANICAL CLOSET
M12
"x
R
A
"x
R
A
"x
O A
"x
E
A
"x
O
A
"x
S A
"x
O
A
"x
O
A
"x
O A
"x
O
A
"ø
S A
10"x10" SA
20"x10" OA
12"x10" EA
10"x12" RA
"x
O A
135—EDH—1
S-9
30"x10" OA
16"x10" RA
"x
S
A
12"x10" OA
"x
R
A
M24
M24
M24
135—FCU—7135—FCU—10
E-2
M27
135—FCU—27
135—FCU—44
"x
R
A
10"x10" SA
10"x10" EA
"x
E
A
R-2
16"x8" EA
"x
E A
M32
GENERAL NOTES - MECHANICAL:
A. FLOOR PLAN FOR BUILDING 135 IS SHOWN. FLOOR PLAN APPLIES TO
BUILDINGS 134 AND 135.
I LL IN O IS
R
.E
SS
E J
FARBE
LICENSED
PROFESSIONAL
OF
ENGINEER
062.069980
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs \m h e a le y \D o c u m e n ts \V
IG
H
-M -R m h e a le y c m ta e g rs .c o m
.r v t
/1
/2
:3
:5
A
M
MH102
ENLARGED FIRST FLOOR PLAN -
AIR DISTRIBUTIONGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA ST.
SUITE 200
317.800.6388
CMTA
10411 Meeting Street
Prospect, Kentucky 40059
502.326.3085
CONSTRUCT TWO NEW GREEN
HOMES 7 & 8
1900 E. MAIN ST., DANVILLE, IL 61832
550-319
7 & 8
04/09/2020 AJM MJH
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
1/4" = 1'-0"
ENLARGED FIRST FLOOR PLAN - AIR
DISTRIBUTION
TAGGED NOTES
M3 10x10 EA DUCT UP TO EF-2. REFER TO SHEET MH103 FOR
CONTINUATION.
M5 10x10 EA DUCT UP TO EF-3. REFER TO SHEET MH104 FOR
CONTINUATION.
M21 8"ø DRYER VENT UP THROUGH ROOF. REFER TO SHEET MI200
FOR TERMINATION DETAIL.
M24 MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES
(TYPICAL).
M27 CONNECT KITCHEN EXHAUST DUCT TO KITCHEN HOOD.
TRANSITION TO SIZE OF EQUIPMENT OPENING AS
NECESSARY.
M32 PROVIDE 2 HOUR FIRE WRAP ON KITCHEN HOOD EXHAUST
DUCTWORK.
GRD RUNOUT SCHEDULE
SYMBOL DUCT INLET
E-1 6"Ø
E-1A 6"Ø
E-2 8"Ø
E-2A 8"Ø
E-3 10"Ø
E-5 6x6
E-6 12x6
R-1 6"Ø
R-1A 6"Ø
R-2 8"Ø
R-2A 8"Ø
R-3 10"Ø
R-4 12"Ø
R-5 14"Ø
R-6 12x10
R-7 12x12
S-1 6"Ø
S-1A 6"Ø
S-2 8"Ø
S-2A 8"Ø
S-3 10"Ø
S-4 12"Ø
S-5 6"Ø
S-6 8"Ø
S-7 10"Ø
S-8 8x6
S-9 12x6
D E
C C.6
9.6
E.5D.5
135—FCU—6
135—FCU—M21
"x
E
A
34"x12" EA
S-8
S-9
M15
M16
M14
MH103
M9
L-1
24"x20" OA
L-2
"x
S
A
135—H—1
"x
O
A
8"x6" SA
M23
M17
M24
M18
M8
M13 6"x6" EAM25
M26
1" LPS
M8
M8
IT
M22
MECHANICAL PENTHOUSE
M21
135—OA—1
M30
M31
R-6
135—FCU—M22
12"x6" SA
R-6
T
T
S-8
"x
S
A
86"x68" EA
PLENUM - 24" DEEPM33
M34
FD
FD
FD
FD
FD
GENERAL NOTES - MECHANICAL:
A. FLOOR PLAN FOR BUILDING 135 IS SHOWN. FLOOR PLAN APPLIES TO
BUILDINGS 134 AND 135.
D EC C.6 D.5
30"x40" OA
30"x40" OA
24"x24" EA
12"x34" EA
M19
M9
M18
M20
M28
M35
500-OA-1 LEGEND
1. EXHAUST FAN SECTION
2. FILTER SECTION
3. ENERGY RECOVERY WHEEL
4. FILTER SECTION
5. FACE AND BYPASS DAMPER
6. DX COOLING COIL
7. ACCESS SETION
8. SUPPLAY FAN SECTION
9. GAS-FIRED HEATING SECTION
10. ACCESS SECTION
11. HUMIDIFIER SECTION
12. DISCHARGE PLENUM
1 3 4
6 8 10 12
2 5 7 9 11
I LL IN O IS
R
.E
SS
E J
FARBE
LICENSED
PROFESSIONAL
OF
ENGINEER
062.069980
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs \m h e a le y \D o c u m e n ts \V
IG
H
-M -R m h e a le y c m ta e g rs .c o m
.r v t
/1
/2
:3
:5
A
M
MH103
ENLARGED MECHANICAL ROOM
PLANGUIDON DESIGN, INC.
1221 N. PENNSYLVANIA ST.
SUITE 200
317.800.6388
CMTA
10411 Meeting Street
Prospect, Kentucky 40059
502.326.3085
CONSTRUCT TWO NEW GREEN
HOMES 7 & 8
1900 E. MAIN ST., DANVILLE, IL 61832
550-319
7 & 8
04/09/2020 AJM MJH
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
1/4" = 1'-0"
ENLARGED MECHANICAL ROOM PLAN
TAGGED NOTES
M8 VRF REFRIGERANT PIPING. REFER TO PIPING SCHEMATIC ON
SHEET MI203 FOR SIZING. (TYPICAL)
M9 SIZE REFRIGERANT PIPING PER MANUFACTURER'S
RECOMMENDATIONS.
M13 6x6 EA DUCT UP TO EF-1. REFER TO SHEET MH104 FOR
CONTINUATION.
M14 6x6 EA DUCT DOWN TO OXYGEN STORAGE ROOM. REFER TO
SHEET MH101 FOR CONTINUATION.
M15 34x12 EA DUCT DOWN IN ATTIC SPACE. REFER TO SHEET
MH101 FOR CONTINUATION.
M16 40x12 OA DUCT DOWN IN ATTIC SPACE. REFER TO SHEET
MH101 FOR CONTINUATION.
M17 12x10 RA DUCT DOWN. REFER TO SHEET MH101 FOR
CONTINUATION.
M18 REFRIGERANT PIPING DOWN. REFER TO SHEET MP101 FOR
CONTINUATION.
M19 NATURAL GAS PIPING. REFER TO PLUMBING DRAWINGS.
M20 DOMESTIC HOT WATER PIPING. REFER TO PLUMBING
DRAWINGS.
M23 12x8 AND 8x8 SA DUCTS DOWN. REFER TO SHEET MH101 FOR
CONTINUATION.
M24 MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES
(TYPICAL).
M25 REFRIGERANT PIPING UP TO ACCU-1 ON ROOF. REFER TO
SHEET MH104 FOR CONTINUATION.
M26 REFRIGERANT PIPING UP TO ACCU-2 ON ROOF. REFER TO
SHEET MH104 FOR CONTINUATION.
M28 PROVIDE 6" THICK CONCRETE PAD UNDER UNIT.
M30 LOUVER SHALL BE USED TO REMOVE OA UNIT FOR
REPAIR/REPLACEMENT IF NECESSARY.
M31 DDC CONTROL PANEL
M33 SLOPE PLENUM BACK TO LOUVER
M34 PROVIDE UNISTRUT ASSEMBLY FOR MOUNTING OF
HUMIDIFIER.
M35 COORDINATE PIPE ROUTING TO ENSURE ADEQUATE ACCESS
TO UNIT.
1/4" = 1'-0"
MECHANICAL ROOM SECTION VIEW
1/4" = 1'-0"
DEDICATED OUTSIDE AIR UNIT SECTION
VIEW
AA.2
B B.2 D E F G H J
C
2.5
C.6
9.6
C.7C.5
7.1
9.1
H.6E.5D.5
135—EF—1
135—EF—2
135—EF—3
135—ACCU—1135—ACCU—2
M36
RD M29
135—EF—4
135—EF—5 135—EF—6
135—EF—7
M38M38M38
M38
GENERAL NOTES - MECHANICAL:
A. FLOOR PLAN FOR BUILDING 135 IS SHOWN. FLOOR PLAN APPLIES TO
BUILDINGS 134 AND 135.
I LL IN O IS
R
.E
SS
E J
FARBE
LICENSED
PROFESSIONAL
OF
ENGINEER
062.069980
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs \m h e a le y \D o c u m e n ts \V
IG
H
-M -R m h e a le y c m ta e g rs .c o m
.r v t
/1
/2
:3
:5
A
M
MH104
ROOF PLAN - MECHANICAL
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA ST.
SUITE 200
317.800.6388
CMTA
10411 Meeting Street
Prospect, Kentucky 40059
502.326.3085
CONSTRUCT TWO NEW GREEN
HOMES 7 & 8
1900 E. MAIN ST., DANVILLE, IL 61832
550-319
7 & 8
04/09/2020 AJM MJH
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
1/8" = 1'-0"
ROOF PLAN - MECHANICAL
TAGGED NOTES
M29 ROOF HATCH
M36 REFER TO DRYER VENT DETAIL ON SHEET MI200.
M38 ATTIC VENTILATION FAN. PROVIDE WITH
TEMPERATURE/HUMIDITY SENSOR LOCATED IN DRAFTSTOP
ZONE SERVED BY THIS FAN. REFER TO ARCHITECTURAL
PLANS FOR DRAFTSTOP ZONE LOCATIONS. CONFIRM EXACT
SENSOR LOCATION WITH VA IN THE FIELD.
F
OVEN
R E
F
DW
AA.2
B B.2 D E F G H J
C
2.5
C.6
9.6
C.7C.5
7.1
9.1
H.6E.5D.5
STORAGE
GARAGE
CLOSET
23A
CLOSET
22A
SPA
19B
CLEAN SUPPLY
CORRIDOR / STORM SHELTER
MEDICATION
EQUIP. STORAGE
CLEAN LINEN
TOILET
27B
STAFF LOUNGE
SOILED HOLDING
JANITOR
LAUNDRY
OFFICE
HOUSEKEEPING
DEN
BEDROOM
CLOSET
17A
CLOSET
16A
BATH
16B
VESTIBULE
BATH
17B
BEDROOM
BEDROOM
VESTIBULE
CORRIDOR
LIVING ROOM
DINING
KITCHEN
PATIO
BATHROOM
23B
CLOSET
21A
CLOSET
20A
BATHROOM
20B
BEDROOM
BATHROOM
11B
BEDROOM
BATHROOM
12B
BEDROOM
BEDROOM
BATHROOM
13B
BEDROOM
BEDROOM
BATHROOM
21B
BATH
19A
SCREENED PORCH
BATHROOM
14B
CORRIDOR
TOILET
BATHROOM
22B
BEDROOM
BARIATRIC
135—FCU—45
135—FCU—34
135—FCU—27
135—FCU—44
135—FCU—8
135—FCU—29
135—FCU—20
135—FCU—19B
135—FCU—17 135—FCU—16
135—FCU—14
135—FCU—13
135—FCU—12
135—FCU—11
135—FCU—23
135—FCU—22
135—FCU—21
135—BCU—1
135—FCU—10
135—FCU—7
M8
M8
M8
M8
M8
M8
M8
M8
M10
M10
M11
1" CD
1" CD
C D
C D
1" CD
135—BCU—2
T
T
T
T
T
H
T
T
T
T
T
TT
T
T
T
T
T
T
T
T
T
CORRIDOR
CORRIDOR
PANTRY
M37
M37
M6
GENERAL NOTES - MECHANICAL:
A. FLOOR PLAN FOR BUILDING 135 IS SHOWN. FLOOR PLAN APPLIES TO
BUILDINGS 134 AND 135.
I LL IN O IS
R
.E
SS
E J
FARBE
LICENSED
PROFESSIONAL
OF
ENGINEER
062.069980
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs \m h e a le y \D o c u m e n ts \V
IG
H
-M -R m h e a le y c m ta e g rs .c o m
.r v t
/1
/2
:3
:1
A
M
MP101
FIRST FLOOR PLAN - HYDRONICS
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA ST.
SUITE 200
317.800.6388
CMTA
10411 Meeting Street
Prospect, Kentucky 40059
502.326.3085
CONSTRUCT TWO NEW GREEN
HOMES 7 & 8
1900 E. MAIN ST., DANVILLE, IL 61832
550-319
7 & 8
04/09/2020 AJM MJH
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
1/8" = 1'-0"
FIRST FLOOR PLAN - HYDRONICS
TAGGED NOTES
M6 REFRIGERANT PIPING UP TO MECHANICAL ROOM. REFER TO
SHEET MH103 FOR CONTINUATION.
M8 VRF REFRIGERANT PIPING. REFER TO PIPING SCHEMATIC ON
SHEET MI203 FOR SIZING. (TYPICAL)
M10 ROUTE CONDENSATE TO NEAREST FLOOR DRAIN.
M11 ROUTE CONDENSATE TO MOP SINK.
M37 ROUTE 3/4" CONDENSATE DRAIN FROM VERTICAL FAN COIL
UNITS TO FLOOR DRAIN IN MECHANICAL ROOM.
NTS
EXHAUST OR RETURN BRANCH DUCTWORK
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR
FLOW
PROVIDE VOLUME DAMPER
AT EACH BRANCH DUCT
1/4W OR 4" [100mm] MIN.
BRANCH DUCT
VD
AIR
FLOW
W
NTS
FLEXIBLE DUCT CONNECTIONS
ROUND FLEXIBLE CONNECTION
RECTANGULAR FLEXIBLE CONNECTION
FLANGED CONNECTION ON
FAN SIDE
WASHER 1-1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED.
6" [150mm] NOMINAL WITH MATERIAL TAUT
FLEXIBLE
MATERIAL AS
SPECIFIED
1"x1/8" [25x3mm] DRAW BAND
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
5/16" [8mm] FLANGE
DUCT
SHEET METAL SCREWS ON
12" [300mm] CENTERS
RIVET ON 4" [100mm]
CENTERS
SHEET METAL
AS
SPECIFIED FOR
DUCTWORK.
1"x1/8" [25x3mm] BAND IRON
BOLT ON 4" [100mm] CENTERS
1" [25mm] FLANGE & HEMALTERNATE
POSITION OF
BOLT 1 1/2" [40mm] POCKET
SLIP
DUCT
SHEET METAL
AS
SPECIFIED FOR
DUCTWORK.
[15mm] [15mm] [40mm]
1 1/2" [40mm] MIN. TO 3" [75mm] MAX. INSTALLED.
6" [150mm] NOMINAL WITH MATERIAL TAUT
FLANGED CONNECTION
ON FAN SIDE
WASHER
FLEXIBLE MATERIAL
AS
SPECIFIED
1/2" 1/2"1 1/2"
NTS
NOTE:
1.
2.
3.
SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED LAG BOLTS NOT OVER 12" [300mm]
ON CENTER.
SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH RUST RESISTANT BOLTS.
RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER, THEN THROUGH
VENTILATOR ELECTRICAL CONDUIT GUIDE.
POWER ROOF VENTILATOR
GRAVITY BACKDRAFT DAMPER
RIGID CONDUIT TO
ACCOMMODATE
ELECTRICAL WIRES
SEE NOTE 2
PREFABRICATED
ROOF CURB
WOOD NAILING
STRIP
ELECTRICAL CONDUIT
GUIDE
MOTOR HOUSING
DUCT
TRANSITION DUCT TO FULL
SIZE OF DAMPER SUPPLIED
WITH ROOF VENTILATOR
ROOF
SEE NOTE 2
SEE NOTE 1
CURB CAP
NTS
ROUND DUCT HANGERS
2500 [1133]
1320 [598]
420 [190]ONE 1 [25] x 18 GA STRAP36 [900]
TWO 1/2 [13]∅ RODS
TWO 3/8 [10]∅. RODS
ONE 1 [25] x 16 GA STRAP
84 [2100]
60 [1500]
50 [1250] 700 [317]
ONE 1 [25] x 22 GA STRAP
QUANTITY/SIZEMAX. DUCT ∅
26 [650]
HANGER STRAPS OR RODS
MAX. LOAD
LBS. [kg]
260 [119]
MAX.
144 [3600]
IN. [mm]
SPACING
IN. [mm] IN. [mm]
144 [3600]
144 [3600]
144 [3600]
144 [3600]
NOTE:
TABULATED DATA FROM SMACNA ALLOWS FOR
DUCT REINFORCING AND INSULATION, BUT NO
EXTERNAL LOAD.
BAND
OVER 50"
[1250mm]∅
HANGER RODS
50" [1250mm]Ø
& UNDER
LOAD RATED
FASTENERS
BAND OF SAME
SIZE AS HANGER
STRAP
NTS
VOLUME DAMPER DETAIL
SECTIONSIDE ELEVATION
STIFFEN BLADE
AS REQUIRED
DUCT
1/2" [15mm] ROUND
ROD PIN
INSULATION
STAND-OFF
HANDLE WITH
LOCKING
QUADRANT
INSIDE END BEARING
OUTSIDE END BEARING
1/8" [6mm]
CLEARANCE ALL
AROUND
DAMPER BLADE
INSULATION SEE
SPECIFICATION
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
NOTE:
1.
2.
FULL SIZE TRANSITION
FROM UNIT OPENING TO SA
DUCT SIZE SHOWN ON
FLOOR PLANS. PROVIDE A
FLEXIBLE DUCT
CONNECTION AT UNIT
OPENING.
MAINTAIN ALL
MANUFACTURER
RECOMMENDED
SERVICE
CLEARANCES.
RETURN DUCT; REFER
TO FLOOR PLANS FOR
SIZES
PROVIDE AND INSTALL A FULL SIZE
EQUIPMENT STAND TO ELEVATE UNIT FOR
BOTTOM RETURN AIR DUCT CONNECTION.
STAND SHALL BE A MINIMUM OF 18" TALL.
CLEAN-LINE FLAT BANK FILTER
RACK, WITH HINGED ACCESS
DOOR. FILTER RACK SHALL BE
16 GAUGE ALUMINIZED STEEL.
24X12-2"
UNIT CONDENSATE LINE
CONNECTION; SPILL CONDENSATE TO
NEAREST FLOOR DRAIN. PROVIDE
WITH P-TRAP PER MANUFACTURER'S
RECOMMENDATIONS.
REFRIGERANT BRANCH LINE
CONNECTIONS FROM MAIN WITH
ISOLATION VAVLES. REFER TO
FLOOR PLANS FOR CONTINUATION
OF PIPING.
NTS
VERTICAL FAN COIL UNIT INSTALLATION DETAIL
X
FAN COIL UNIT DETAIL TAG NOTES:
1. HORIZONTAL VRF UNIT. DO NOT BLOCK ACCESS PANEL FOR UNIT WITH ANY PIPING,
CONDUIT, ETC.
2. PROVIDE FLEXIBLE CANVAS CONNECTIONS AT UNIT CONNECTION. TRANSITION
DUCTWORK TO UNIT OPENING AS NEEDED.
3. INSTALL REFRIGERANT PIPING PER MANUFACTURER'S RECOMMENDATION.
4. INSTALL CONDENSATE PIPING PER MANUFACTURER'S RECOMMENDATION.
5. SUPPLY AIR DUCTWORK. REFER TO DRAWINGS FOR DUCT SIZE.
6. PROVIDE UNI-STRUT BETWEEN BEAMS FOR HORIZONTAL PROPER SUPPORT OF
VRF INSTALLATION.
7. PROVIDE SECONDARY DRAIN PAN.
R F
RF
RF
CD
NTS
HORIZONTAL FAN COIL UNIT INSTALLATION DETAIL
CD
18"
FINISHED ROOF
FLASH EXHAUST AIR DUCT
ACCORDING TO ROOF
MANUFACTURER'S
RECOMMENDATIONS
12"
12"
EA DUCT (REFER TO
FLOOR PLAN FOR SIZE)
PAINT DUCTWORK WITH
EPOXY WEATHER
COATING. MATCH COLOR
WITH ADJACENT ROOF.
PROVIDE ALUMINUM BIRD SCREEN
SEAL ROOF PENETRATION
WATERTIGHT
NTS
DRYER VENT/ROOF PENETRATION DETAIL
I LL IN O IS
R
.E
SS
E J
FARBE
LICENSED
PROFESSIONAL
OF
ENGINEER
062.069980
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs \m h e a le y \D o c u m e n ts \V
IG
H
-M -R m h e a le y c m ta e g rs .c o m
.r v t
/1
/2
:3
:5
A
M
MI200
MECHANICAL DETAILS
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA ST.
SUITE 200
317.800.6388
CMTA
10411 Meeting Street
Prospect, Kentucky 40059
502.326.3085
CONSTRUCT TWO NEW GREEN
HOMES 7 & 8
1900 E. MAIN ST., DANVILLE, IL 61832
550-319
7 & 8
04/09/2020 AJM MJH
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
1/2'' DOMESTIC COLD WATER
1/2'' CW
V
KOOLER
DRANE
DRANE KOOLER 2
WAY CONTROL
VALVE, TYP.
AHU
STEEL PIPE PER SPECIFICATIONS
ATMOSPHERIC STEAM TO AHU. PIPE
PER MANUFACTURER'S
INSTRUCTIONS.
PITCH 1/8''
PER FT.
TEMPERED WATER
SPILL TO F.D.
MECH. RM
FLOOR
CONCRETE CURB AREA
STEAM HEADER
CONDENSATE HEADER
SUPPORT HUMIDIFER GRID
AS RECOMMENDED BY
MANUFACTURER.
DISPERSION TUBE SPACE AS
RECOMMENDED BY
MANUFACTURER FOR SCHEDULED
CAPACITY AND REQUIRED
ABSORPTION DISTANCE.
LONG RADIUS 90. TYP.
CONNECT TO DOMESTIC WATER
HUMIDIFIER
HUMIDIFIER PIPING SCHEMATIC
NTS
SPILL TO F.D.
TYPICAL INSULATED CURB OPENING,
THYCURB TC-1, OR EQUAL. CURB SHALL BE
18'' TALL.
SPACE ALLOWED FOR ROOFING
MATERIAL UNDER PORTAL
CONVENIENCE OUTLET (CAULK ALL
PENETRATIONS)
13X13 PORTAL TO BE
16 GAUGE ALUMINUM
CONSTRUCTION
UNISTRUT BACKING CHANNEL
INSIDE
WELDED CORNERS
(MICRO SEALED)
FASTENERS
(TYPICAL)
REMOVABLE WATERTIGHT
COVER.
GLUE 1/2" ARMAFLEX INSULATION TO THE
INSIDE OF THE PORTAL.
1" LIP
ROOF PRODUCTS, INC. MODEL
RPPC-90 OR APPROVED EQUAL.
HOLE SAW PIPE PENETRATIONS
ACCOUNT FOR INSULATION IF
APPLICABLE. CAULK OPENING AFTER
CONDUIT INSTALLATION.
SUPPORT PIPE WITH UNISTRUT
ATTACHED TO ROOF CURB WITH
HYDRAZORB CLAMPS.
* GALVANIZED STEEL IS NOT
ACCEPTABLE.
PIPE CHASE / ROOF CURB DETAIL
NTS
AIR HANDLING UNIT DRAIN TRAP DETAIL
NTS
DRAW THRU
BLOW THRU
2" [50mm]
PLUS X
1" [25mm]
MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE SAME SIZE AS THE
NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L OR TYPE M
UNLESS
NOTE BELOW IS MET
PITCH DOWN
TOWARD
DRAIN
CLEAN OUT
FLOOR SINK
DRAIN PAN
NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA
AND IS INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS
ARE TO BE CONNECTED.
[2 5m m
DIELECTRIC
FITTING
A B1
REFER TO THE PIPING
PORTAL DETAIL ON THIS
DRAWING FOR CONTINUATION
THYBAR TEMS-1 EQUIPMENT RAILS
OR APPROVED EQUAL, RAILS
SHALL BE 10'' TALL. COORDINATE
ROOF CUT AND PATCH WITH
GENERAL CONTRACTOR.
FASTEN TO THE RAILS WITH
LAG BOLTS. SEAL
PENETRATION WITH SILICON
FASTEN RAILS TO
STRUCTURE BELOW.
RAILS ARE TO BE FULL
LENGTH OF UNIT PLUS LENGTH
REQUIRED TO SPAN ROOF
STRUCTURE BELOW.
ROOF MOUNTED CONDENSING UNIT DETAIL
NTS
NTS
FIRE DAMPER INSTALLATION
SECTION THRU
NOTE:
1.
2.
3.
4.
5.
6.
A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION IS SIMILAR.
FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS
AND GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE
INSTALLED IN THE PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.
GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO
DAMPER FRAME AND TO PERIMETER ANGLES.
PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm], 14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON
ALL 4 SIDES.
BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN
SMACNA. ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE
LINK OR LINKS.
PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL
OPEN SPACE WITH ROCK WOOL FIRESTOP FIBER.
ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS
AND MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH
CONCRETE CURB AROUND OPENING FOR DUCT.
SLEEVE, NOTE 2
DUCT
CONNECTION
NOTE 4
DAMPER,
NOTE 1
DAMPER COLLAR
EXTENSION INTEGRAL
PART OF SLEEVE
SLEEVE, NOTE 2
NOTE 6FIRE BARRIER
PARTITION OR CHASE
TYPICAL
DUCT
INSULATION
PERIMETER ANGLE, NOTE 3
(NOTE FASTENED TO
PARTITION)
ACCESS
PANEL
NOTE 5
[2 m m
I LL IN O IS
R
.E
SS
E J
FARBE
LICENSED
PROFESSIONAL
OF
ENGINEER
062.069980
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs \m h e a le y \D o c u m e n ts \V
IG
H
-M -R m h e a le y c m ta e g rs .c o m
.r v t
/1
/2
:3
:0
A
M
MI201
MECHANICAL DETAILS
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA ST.
SUITE 200
317.800.6388
CMTA
10411 Meeting Street
Prospect, Kentucky 40059
502.326.3085
CONSTRUCT TWO NEW GREEN
HOMES 7 & 8
1900 E. MAIN ST., DANVILLE, IL 61832
550-319
7 & 8
04/09/2020 AJM MJH
100% CONSTRUCTION
DOCUMENTS
VRF FAN COIL UNIT CONTROLS
NTS
RA
RR
RS
LEV
FAN
SST
HS
T-1
ROOM TEMPERATURE SENSOR WITH SPACE ADJUSTABLE WALL
MOUNTED
48" [1200mm] AFF.
T
PC
FILTER
24/7 CONSTANT VOLUME FAN COIL SEQUENCE OF OPERATION
FAN COIL UNIT SHALL OPERATE 24/7. FAN SHALL RUN CONTINUOUSLY. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL BE GENERATED IN THE EVENT THE UNIT FAILS TO RUN. THE ADJUSTABLE ROOM TEMP SET POINT WILL BE 70°-75° WITH 0.5° HEATING/COOLING OFFSETS. THE UNIT SHALL MODULATE ITS INTERNAL LINEAR EXPANSION VALVE (LEV) TO MAINTAIN THE TEMPERATURE SET POINT VIA THE INDOOR UNIT'S INTERNAL CONTROLS. ROOM TEMPERATURE SETPOINT SHALL BE ADJUSTABLE FROM THE BAS. UPON FALL IN ROOM TEMPERATURE 3°F BELOW SET POINT THE ELECTRIC RADIANT CEILING PANEL SHALL
OPERATE TO PROVIDE SUPPLEMENTAL HEAT.
TT
CS
COOLING/HEATING COIL
RA
RR
RS
LEV
FAN
SST
HS
T-1
ROOM TEMPERATURE SENSOR WITH
SPACE ADJUSTABLE WALL MOUNTED
48" [1200mm] AFF.
T
PC
FILTER
TT
CS
COOLING/HEATING COIL
TT
ELECTRIC DUT HEATER
H-1H
MEDICATION ROOM FAN COIL SEQUENCE OF OPERATION
FAN COIL UNIT SHALL OPERATE CONTINUOUSLY. FAN SHALL RUN CONTINUOUSLY. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL BE GENERATED IN THE EVENT THE UNIT FAILS TO RUN. THE ADJUSTABLE ROOM TEMP SET POINT WILL BE 70°-75° WITH 0.5° HEATING/COOLING OFFSETS. THE UNIT SHALL MODULATE ITS INTERNAL LINEAR EXPANSION VALVE (LEV) TO MAINTAIN THE TEMPERATURE SET POINT VIA THE INDOOR UNIT'S INTERNAL CONTROLS. ROOM OCCUPANT WILL HAVE ABILITY OF ADJUSTING ROOM TEMPERATURE BETWEEN 70°-75°. IF THE ROOM HUMIDITY EXCEEDS 55% AND THE ROOM TEMPERATURE IS SATISFIED, THEN THE UNIT SHALL ENTER DEHUMIDIFICATION MODE. IN DEHUMIDIFICATION MODE THE UNIT SHALL OPERATE IN FULL COOLING AND THE ELECTRIC DUCT HEATER SHALL MODULATE TO MAINTAIN A LEAVING AIR TEMPERATURE EQUAL TO ROOM TEMPERATURE.
SCHEDULED CONSTANT VOLUME FAN COIL SEQUENCE OF OPERATION
FAN COIL SHALL OPERATE ON A SCHEDULE AS SET BY ECC. SCHEDULE SHALL BE ADJUSTABLE BY ECC.
OCCUPIED MODE:
FAN SHALL RUN CONTINUOSULY. FAN STATUS SHALL BE MONITORED AND AN ALARM MESSAGE SHALL BE GENERATED IN THE EVENT THE UNIT FAILS TO RUN. THE ADJUSTABLE ROOM TEMP SET POINT WILL BE 70°-75° WITH 0.5° HEATING/COOLING OFFSETS. THE UNIT SHALL MODULATE ITS INTERNAL LINEAR EXPANSION VALVE (LEV) TO MAINTAIN THE TEMPERATURE SET POINT VIA THE INDOOR UNIT'S INTERNAL
CONTROLS. ROOM TEMPERATURE SETPOINT SHALL BE ADJUSTABLE FROM THE BAS.
UNOCCUPIED MODE:
FAN SHALL ONLY RUN WHEN THE ROOM THERMOSTAT REQUIRES HEATING OR COOLING. THE ADJUSTABLE ROOM TEMP SET POINT WILL BE 65°-81° WITH 0.5° HEATING/COOLING OFFSETS. THE UNIT SHALL MODULATE ITS INTERNAL LINEAR EXPANSION VALVE (LEV) TO MAINTAIN THE TEMPERATURE SET POINT VIA THE INDOOR UNIT'S INTERNAL CONTROLS. ROOM TEMPERATURE SETPOINT SHALL BE ADJUSTABLE FROM THE BAS.
VARIABLE VOLUME FAN COIL SEQUENCE OF OPERATION
FAN COIL UNIT SHALL OPERATE AS REQUIRED TO MAINTAIN SPACE TEMPERATURE. FAN SHALL ONLY RUN WHEN THE ROOM THERMOSTAT REQUIRES HEATING OR COOLING. THE ADJUSTABLE ROOM TEMP SET POINT WILL BE 70°-75° WITH 0.5° HEATING/COOLING OFFSETS. THE UNIT SHALL MODULATE ITS INTERNAL LINEAR EXPANSION VALVE (LEV) TO MAINTAIN THE TEMPERATURE SET POINT VIA THE INDOOR UNIT'S
INTERNAL CONTROLS. ROOM TEMPERATURE SETPOINT SHALL BE ADJUSTABLE FROM THE BAS.
NTS
DEDICATED OUTSIDE AIR SYSTEM AIR HANDLING UNIT CONTROL DIAGRAM
EXHAUST AIR
D-2
P R
E
F
IL
T E
R
OUTSIDE
AIR
D-1
C O
IL
C
O O
LI
N
G
LOCATE SENSOR
OUTSIDE UNDER
SHIELD
V-1
RF
RF
EXHAUST FAN
RETURN
AIR
A F
M D
SUPPLY AIR TO
TERMINAL UNIT
TT
TT TT
FT
A F
T E
R
F
IL
T E
R
TT
HS
IT
VSMC
HSVSMC
4 6
SD
CURRENT
TRANSMITTER
FOR FAN
STATUS
,TYP.
PSH
SMOKE
DETECTOR
VARIABLE SPEED MOTOR
CONTROLLER, TYP.
ZC
ZC
PDS PDS
SST
PSL
IT
SST
SD
SD
SD
SPSTSL
TSL-1
NO
ECC
ECC
PRESSURE SWITCH LOW
TO DISABLE RETURN FAN WHEN
SMOKE DAMPER IN RETURN DUCT
CLOSES
PRESSURE SWITCH HIGH
TO DISABLE FAN WHEN
HIGH
PRESSURE LIMIT SETPOINT
IS REACHED
TT
MT
A F
M D
FT
F
IL
T E
R
PDS
MT
AT
CO2
C O
IL
H
E A
T
IN
G
NG
V-2
E N
E R
G Y
R E
C O
V E
R Y
W H
E E
L
TT
MT
PDS
HS
IT
VSMC
VARIABLE SPEED MOTOR
CONTROLLER, TYP.
SST
ECC
HT
HHL
2C
ELECTRIC STEAM HUMIDIFIER
SUPPLY FAN
TT
ZC
D-3
ALARM
PROCESSING
D U
TY
C
YC
LE
FU
N
C
TI
O N
SC
H
ED
U
LE
S
TA
R
T/
ST
O P
HUMIDITY HIGH LIMIT
EXHAUST FAN VSMC ALARM
SUPPLY FAN VSMC ALARM
EXHAUST FAN STATUS
STATIC PRESSURE HIGH LIMIT
SUPPLY AIR FLOW (CFM)
RETURN LOW PRESSURE
ST
AT
U S
SYSTEM
AL
AR
M
P R
IO
R
IT
Y
/A D
D -A
LT
E
R N
A T E
N O
EL
EC
TR
IC
D
EV
IC
E
SP
EE
D C
O M
M
AN
D
PO
IN
T
ID
DISCHARGE STATIC PRESSURE
DISCHARGE AIR HUMIDITY
DISCHARGE AIR TEMPERATURE
OUTSIDE AIR TEMPERATURE DOWNSTREAM OF ERW
EXHAUST AIR TEMPERATURE
COOLING COIL TEMPERATURE
SYSTEM COMPONENT:
RETURN AIR FLOW (CFM)
RETURN AIR TEMPERATURE
-- O
PE
N /C
LO
SE
ST
AR
T/
ST
O P
-- VA
LV
E
PO
SI
TI
O N
D
AM
PE
R
P O
SI
TI
O N
JOB: 550-319
DEDICATED OUSTIDE AIR
SYSTEM AIR HANDLER
7 & 8
SYSTEM:
BUILDING:
LEGEND
POINT
BINARY
TE
M
PE
R
AT
U
R E
(T I)
Lo ca l A la rm P an el
M as te r A la rm
P an el
Ar ea
A la rm P an el
H
IG
H S
TA
TI
C P
R
ES
SU
R
E
H
IG
H H
U M
ID
IT
Y
PR
ES
SU
R
E
--LO
W
T
EM
PE
R
AT
U
R E
PE
R
C
EN
T
PR
ES
SU
R
E
PO
SI
TI
O N
FL
O
W
H
IG
H L
IM
IT
LO
W
L
IM
IT
SYSTEM INPUTS
ANA- BINARY ANALOG
SP
AC
E
TE
M P.
C O
N
TR
O L
--ST
AT
IC
P
R
ES
SU
R
E R
ES
ET
--D
EM
AN
D
L
IM
IT
IN
G
TE
M
PE
R
AT
U
R E
R
ES
ET
TE
M
PE
R
AT
U
R E
O
VE
R R
ID
E
EN
TH
AL
PY
E C
O N
O M
IZ
ER
TE
M
PE
R
AT
U
R E
EC
O
N O
M
IZ
ER
FA
IL
U R
E M
O D
E
P R
E S
S U
R E
/V O
LU
M
E C
O N
T R
O L
REMARKS
FU
LL
C O
M M
U N
IC
AT
IO
N
SYSTEM SOFTWARE/CONTROL
APPLICATION/FUNCTION
PAGE:
RETURN AIR HUMIDITY
SUPPLY FAN STATUS
OUTSIDE AIR LOW LIMIT
RETURN FAN START/STOP
COOLING VALVE V-1
HEATING VALVE V-2
EXHAUST AIR DAMPER
SUPPLY FAN VSMC
OUTSIDE AIR DAMPER
EXHAUST FAN VSMC
ST
AT
IC
P
R
ES
SU
R
E
C
AR
BO
N
M O
N O
XI
D
E
H U
M
ID
IT
Y
VA
C
U U
M
ENERGY RECOVERY WHEEL START/STOP
SUPPLY FAN START/STOP
AI-1
AI-2
AI-3
AI-4
AI-5
AI-6
AI-7
AI-8
AI-9
AI-10
TR
EN
D
IN
G
OUTSIDE AIR TEMPERATURE AI-11
BI-1
BI-2
BI-3
BI-4
BI-5
BI-6
BI-7
BI-8
AO-1
AO-2
AO-4
AO-5
AO-7
AO-8
BO-1
BO-2
BO-3
FULL COMMUNICATION
FULL COMMUNICATION
AB
BR
EV
IA
TI
O
N
RAT
RAH
RAF
EAT
OAT-2
CCT
DAT
DASP
DAH
SAF
OAT-1
RLP
EF-STS
SF-STS
TSL-1
SPS-2
HHL
SF-ALA
RF-ALA
RF-SPD
SF-SPD
OAD
EAD
HTG-V2
CLG-V1
RF-SST
SF-SST
ERW-SST
NTS
AIR HANDLING UNIT
POINTS LIST FOR DEDICATED OUTSIDE AIR SYSTEM
OUTPUTS
LOG
ENERGY RECOVERY WHEEL (ERW) VSMC ALARM BI-9 ERW-ALA
ENERGY RECOVERY WHEEL VSMC AO-3 FULL COMMUNICATIONERW-SPD
FACE AND BYPASS DAMPER AO-6 FBD
HUMIDIFIER START/STOP BO-4 HUM-SST
HUMIDIFIER STATUS BI-10 HUM-STS
EF-1 START/STOP BO-5 EF1-SST
EF-2 START/STOP BO-6 EF2-SST
EF-3 START/STOP BO-7 EF3-SST
EF-4 START/STOP BO-8 EF4-SST
EF-5 START/STOP BO-9 EF5-SST
EF-6 START/STOP BO-10 EF6-SST
EF-7 START/STOP BO-11 EF7-SST
EF-4 ATTIC AIR TEMPERATURE AI-12 AAT-4
EF-5 ATTIC AIR TEMPERATURE AI-14 AAT-5
EF-4 ATTIC AIR HUMIDITY AI-13 AAH-4
EF-5 ATTIC AIR HUMIDITY AI-15 AAH-5
EF-6 ATTIC AIR TEMPERATURE AI-16 AAT-6
EF-6 ATTIC AIR HUMIDITY AI-17 AAH-6
EF-7 ATTIC AIR TEMPERATURE AI-18 AAT-7
EF-7 ATTIC AIR HUMIDITY AI-19 AAH-7
SEQUENCE OF OPERATION FOR DEDICATED OUTSIDE AIR SYSTEM AIR HANDLING UNIT
1. GENERAL
1.1
2. TEMPERATURE CONTROL
2.1
2.2
2.3
2.4
3. AIR FLOW CONTROL
3.1
3.2
3.3
4. HUMIDITY CONTROL
4.1
5. AUTOMATIC SHUTDOWN/RESTART
6.1
6.2
7. EMERGENCY CONSTANT SPEED OPERATION
7.1
THE SYSTEM WILL BE PLACED INTO A MODE OF OPERATION BASED UPON THE FOLLOWING ADJUSTABLE TEMPERATURE
SCHEDULE:
OUTSIDE AIR TEMPERATURE MODE OF OPERATION
65°F OR GREATER (ADJ.) COOLING MODE
BETWEEN 55°F AND 65°F (ADJ.) ECONOMIZER MODE
55°F OR LESS (ADJ.) HEATING MODE
UPON FAILURE OF THE VSMC, THE SUPPLY AND EXHAUST FANS SHALL BE STARTED/STOPPED MANUALLY AT THE DIGITAL
CONTROL PANEL OR THE ECC THROUGH THE BY-PASS STARTER. FANS SHALL THEN BE OPERATED AT CONSTANT SPEED.
WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTOR, SD, THE SUPPLY AND EXHAUST FANS SHALL SHUT "OFF" AND
AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM.
THE ANCILIARY EXHAUST FANS SERVING AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN. SUPPLY AND EXHAUST
FANS SHALL RESTART WHEN FIRE ALARM CIRCUIT IS RESET.
IF THE RETURN AIR HUMIDITY SENSOR H-1 MEASURES HUMIDITY ABOVE 60% RH (ADJ.), THEN THE UNIT SHALL OPERATE IN COOLING MODE REGARDLESS OF OUTSIDE AIR TEMPERATURE. ONCE H-1 READS BELOW 55% RH (ADJ.), THE SYSTEM SHALL
RETURN TO NORMAL OPERATION.
IN COOLING MODE THE ENERGY RECOVERY WHEEL SHALL BE ON. THE DX COOLING COIL SHALL MODULATE TO MAINTAIN A 55°F LEAVING AIR TEMPERATURE. THE FACE AND BYPASS DAMPERS SHALL MODULATE TO MAINTAIN A UNIT DISCHARGE AIR
TEMPERATURE OF 63°F.
IN HEATING MODE THE ENERGY RECOVERY WHEEL SHALL BE ON. THE GAS FIRED HEATING SECTION SHALL MODULATE TO
MAINTAIN A UNIT DISCHARGE AIR TEMPERATURE OF 70°F.
ENERGY RECOVERY WHEEL: IF THE OUTSIDE AIR TEMPERATURE IS BETWEEN 60°F (ADJ) AND 65°F (ADJ), THEN THE ENERGY
RECOVERY WHEEL SHALL BE OFF AND THE WHEEL BYPASS DAMPERS SHALL BE OPEN.
UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE ECC. H-O-A SWITCH SHALL BE KEPT IN THE "AUTO" POSITION.
"HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE. WHEN THE UNIT IS "OFF" D-1, D-2, SHALL BE FULLY
CLOSED. WHEN THE UNIT IS "ON" D-1, D-2, SD-1 AND SD-2 SHALL BE FULLY OPEN.
1.2 THE MAJOR COMPONENTS OF THE SYSTEM ARE A SUPPLY FAN, EXHAUST FAN, TOTAL ENERGY RECOVERY WHEEL, DX
COOLING COIL, AND GAS HEAT SECTION.
THE SUPPLY AIR FLOW SHALL BE CONTROLLED BY THE DIGITAL CONTROL PANEL MODULATING THE SUPPLY FAN SPEED MOTOR CONTROLLER TO MAINTAIN 1.0" [25mm] OF DUCT STATIC PRESSURE (FIELD ADJUSTABLE), SENSED BY SPS-1.
COORDINATE WITH BALANCE CONTRACTOR.
THE DIGITAL CONTROL PANEL, USING TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS, SHALL RESET THE EXHAUST AIR FAN VSMC TO MAINTAIN A CONSTANT AIR FLOW DIFFERENCE BETWEEN THE SUPPLY AIR AND THE RETURN AIR EQUAL TO
10% OF THE SUPPLY AIR FLOW.
USING HIGH PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN DISCHARGE, SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 3" [75mm] OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 DOES EXCEED 3" [75mm] THE SUPPLY AIR FAN SHALL STOP. SPS-2 SHALL BE HARDWIRED TO THE SUPPLY FAN VSMC AND UNIT SHALL BE SHUTDOWN IN HAND,AUTO OR BYPASS MODE. SPS-2 WILL REQUIRE MANUAL RESET AT THE DEVICE.
4.2 RETURN AIR HUMIDITY SHALL BE MAINTAINED AT SETPOINT OF 35% RH (ADJ) BY MODULATING ELECTRIC HUMIDIFIER TO
MAINTAIN THE DESIRED HUMIDITY.
8. ANCILIARY EXHAUST FANS
8.1 ANCILIARY EXHAUST FANS, EF-1, EF-2, AND EF-3, SHALL RUN CONTINOUSLY 24/7.
8.2 ATTIC VENTILATION EXHAUST FANS, EF-4, EF-5, EF-6, AND EF-7, SHALL OPERATE BASED ON TEMPERATURE/HUMIDITY SENSORS LOCATED IN THE DRAFTSTOP ZONE SERVED BY THE ASSOCIATED FAN. THE FAN SHALL OPERATE WHEN THE
RELATIVE HUMIDITY EXCEEDS 60% (ADJ.) OR THE TEMPERATURE EXCEEDS 90°F (ADJ.).
I LL IN O IS
R
.E
SS
E J
FARBE
LICENSED
PROFESSIONAL
OF
ENGINEER
062.069980
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs \m h e a le y \D o c u m e n ts \V
IG
H
-M -R m h e a le y c m ta e g rs .c o m
.r v t
/1
/2
:3
:0
A
M
MI202
CONTROL SCHEMATICS
GUIDON DESIGN, INC.
1221 N. PENNSYLVANIA ST.
SUITE 200
317.800.6388
CMTA
10411 Meeting Street
Prospect, Kentucky 40059
502.326.3085
CONSTRUCT TWO NEW GREEN
HOMES 7 & 8
1900 E. MAIN ST., DANVILLE, IL 61832
550-319
7 & 8
04/09/2020 AJM MJH
100% CONSTRUCTION
DOCUMEN…