22-117 PLUMB ADD NO-1_Rev.pdf
PDF 902 KB Posted
- Solicitation number
- 36C77624B0008
About this file
This document contains multiple pages of design plans and details related to a plumbing system for a federal construction project. It includes first floor plans for the drain, waste, vent, and domestic water systems, as well as details for items like roof vents, floor sinks, backflow preventers, and incoming water service.
The related federal contract opportunity is a solicitation from the Department of Veterans Affairs Technology Acquisition Center Austin for the EHRM Infrastructure Upgrades - Tier 2 project at the Northern Arizona VA Health Care System in Prescott, Arizona. The solicitation number is 36C77624B0008 and the project number is VA-24-00011412. The solicitation page is left intentionally blank.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1.0 3.0 4.02.0
A
B
C
TOILET
VESTIBULE
STORAGE
DATA
CENTER
SERVICE
YARD
CRAC-1 CRAC-2
P-401
/2
V
2" V
4" SAN
2" V
1" CO
1" CO
D
D
SECURE
STORAGE
4" SAN
FD-S
INVERT ELEVATION
AT BUILDING: 5314.8
AD-1
S D
AD-2
S D
6" SD6" CO
4" WCO
P-101
INVERT ELEVATION
AT BUILDING: 5316.76
PB CONTROL CENTER
AIR COMPRESSOR
AIR DRYER
1" D 1" D
3/4" D
1/2" D
1/2" D
4" SAN4" SAN
CRAC-2
CRAC-1
P-401
4" SAN
1" D
1" D
1" D
1" CO
1" CO
V
/2
V
2" V
FD-S
SEE CIVIL PLANS FOR CONTINUATION
AD-1
4" SAN
4" S D
3" SAN
1 1/2" SAN
4" S D
6" SD
6" CO
AD-2
SEE CIVIL PLANS FOR CONTINUATION
4" WCO
P-101
V
2" SAN
4" SAN
AIR DRYER
1" D
3/4" D
V
HU-1
WT-1
PB CONTROL
CENTER
D
1/2" D
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:5
:5
P
M C
U s e rs \t b u d a i\ D o c u m e n ts
\F M
P
-1
V A
P re s c o tt -E
H R
M D
C tb u d a i.
rv t
PW101
FIRST FLOOR DRAIN, WASTE, AND
VENT PLAN & SANITARY PIPE RISERS
2 6TB
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
SPG
NORTH
0 4 8 16
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L H
O L M
B E
R G
R O
A D
Scale: 1/4" = 1'-0"
FIRST FLOOR DRAIN, WASTE, AND VENT PLAN
A. SLEEVE ALL PENETRATIONS. FIRESTOP AND
SEAL WATER TIGHT.
B. UNLESS NOTED OTHERWISE, THE SIZE OF
FIXTURE CONNECTIONS SHALL BE AS LISTED
IN THE PLUMBING FIXTURE SCHEDULE.
C. PROVIDE THERMOSTATIC MIXING VALVE AT
EACH LAVATORY. SET TEMPERATURE AT 110°F.
D. SANITARY PIPING ARE BELOW THE FLOOR
UNLESS OTHERWISE NOTED.
1 2" VENT PIPE UP TO VTR.
2 NEW 4" SANITARY MAIN INTO BUILDING
UNDERSLAB. CONNECT TO EXISTING SANITARY
SEWER LINE. SEE CIVIL PLANS FOR
CONTINUATION.
3 INSTALL 3" AIR GAP FITTING IN 3" SANITARY
PIPING FOR CONDENSATE DRAIN.
4 ROUTE 1" COOPER PIPE CONDENSATE DRAIN
PUMPED WITH BUILT-IN IN CRAC UNIT PUMP TO
3" SINK DRAIN.
5 PROVIDE DRIP PAN UNDER PIPE. SEE DETAIL
7/P-501 FOR MORE INFORMATION.
6 FLOOR SINK TO HAVE TRAP PRIMER. SEE
DETAIL 2/P-502 FOR MORE INFORMATION.
7 HUMIDIFIER WATER TREATMENT CABINET.
REFER TO MECHANICAL. RUN 1/4" DRAIN TO
FLOOR SINK AND DISCHARGE THROUGH
APPROVED AIR GAP.
8 HUMIDIFIER UNIT. REFER TO MECHANICAL.
9 NEW 6" STORM PIPE INTO BUILDING
UNDERSLAB. CONNECT TO EXISTING STORM
LINE. SEE CIVIL PLANS FOR CONTINUATION.
Scale: No Scale
SANITARY PIPE RISERS
2" VTR
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L H
O L M
B E
R G
R O
A D
1 ADDENDUM #1 4/29/2024
1.0 3.0 4.02.0
A
B
C
TOILET
VESTIBULE
101 STORAGE
DATA
CENTER
SERVICE
YARD
CRAC-1 CRAC-2
P-401
IWH-104
1-BF-2
1-BF-1
/2
D
C W
SECURE
STORAGE
WHA-A6
1/2" FD-S
3/4"
1 1/4"2"
P-101 1/2" DCW
PB CONTROL CENTER
AIR COMPRESSOR
AIR DRYER
1/2"1/2" DCW
1/2" RO
1/2" RO
CRAC-1
CRAC-2
/2
D
C W
1-BF-1
1-BF-2
IWH-104
1/2" DHW
P-401
FD-S
METER
WHA-A
WATER PRESSURE
REDUCING VALVE
HOT BOX
SEE CIVIL PLANS FOR
CONTINUATION
1/2"
2"
1 1/4"
P-101
1/2" DCW
HU-1
WT-1
AIR DRYER
PB CONTROL CENTER
/2
R
O
1/2" DCW
1/2" RO
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:5
:5
P
M C
U s e rs \t b u d a i\ D o c u m e n ts
\F M
P
-1
V A
P re s c o tt -E
H R
M D
C tb u d a i.
rv t
PP101
FIRST FLOOR DOMESTIC WATER PLAN
& DOMESTIC WATER PIPE RISERS
3 6TB
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
SPG
NORTH
0 4 8 16
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L H
O L M
B E
R G
R O
A D
Scale: 1/4" = 1'-0"
FIRST FLOOR DOMESTIC WATER PLAN
1 HUMIDIFIER UNIT. REFER TO MECHANICAL.
CONNECT WITH 1/2" RO WATER FROM WATER
TREATMENT CABINET.
2 NEW 3" DCW MAIN INTO BUILDING UNDERSLAB.
CONNECT TO EXISTING DOMESTIC COLD
WATER LINE. SEE CIVIL PLANS FOR
CONTINUATION.
3 HUMIDIFIER WATER TREATMENT CABINET.
REFER TO MECHANICAL. CONNECT WITH 1/2"
DOMESTIC COLD WATER. RUN 1/2" RO WATER
TO HUMIDIFIER.
4 ACCESS PANEL FOR TRAP PRIMER LOCATED 6'
AFF.
5 SEE INCOMING DOMESTIC WATER SERVICE
DIAGRAM 04/P-502 FOR MORE INFORMATION.
6 PROVIDE HEATED HOT BOX, FIBERGLASS
FLIPTOP ENCLOSURE FOR BACKFLOW
PREVENTERS.
A. SLEEVE ALL PENETRATIONS. FIRESTOP AND
SEAL WATER TIGHT.
B. UNLESS NOTED OTHERWISE, THE SIZE OF
FIXTURE CONNECTIONS SHALL BE AS LISTED IN
THE PLUMBING FIXTURE SCHEDULE.
C. PROVIDE ISOLATION BALL VALVES AT EACH
BRANCH TO FIXTURE. LOCATE AS CLOSE TO
MAIN AS POSSIBLE.
D. PROVIDE WATER HAMMER ARRESTOR AT ALL
QUICK CLOSING VALVES. SEE DETAIL 5/P-501
FOR SCHEDULE.
Scale: No Scale
DOMESTIC WATER PIPE RISERS
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L H
O L M
B E
R G
R O
A D
1 ADDENDUM #1 4/29/2024
PLUMBING VENT STACK
SEALANT
DRAWBAND
INSTALL SEALANT
BETWEEN PIPE AND
PREFABRICATED
MEMBRANE FLASHING
PREFABRICATED
MEMBRANE FLASHING
SEALANT (IF REQUIRED
BY THE SPECIFIC
SYSTEM)
ROOF MEMBRANE
THERMAL
INSULATION
ROOF STRUCTURE
NOTES:
1. VENT STACKS AND OTHER PIPES SHALL HAVE A MINIMUM OF 12 INCHES OF
CLEARANCE ON ALL SIDES FROM WALLS, CURBS, AND OTHER PROJECTIONS TO
FACILITATE PROPER FLASHING.
FROM COLD
WATER MAIN
TRAP PRIMER
VALVE LOCATED
INSIDE WALL CAVITY
PROVIDE LOCKABLE
ACCESS DOOR
12''x18''
DISTRIBUTION UNIT FOR
MULTIPLE INSTALLATIONS
WALL
VENT PIPING
LOCATED IN WALL
FINISHED FLOOR
COPPER PIPING PASSING THRU
CONCRETE SLAB SHALL BE PROTECTED
BY A PROTECTIVE SHEATING OR
WRAPPING TO PREVENT CORROSION
TO THE COPPER
PROVIDE TRAP PRIMER
CONNECTION ADAPTER SO
THAT TRAP PRIMER LINES
CAN BE ROUTED BELOW
SLAB OR IN FLOOR BELOW
CEILING SPACE FROM
VALVE TO DRAIN
FLOOR DRAIN OR FLOOR SINK
NOTES:
1. SEE FLOOR PLANS FOR DRAIN LOCATIONS.
2. SEE ARCHITECTURAL DRAWINGS FOR TRAP
PRIMERS ACCESS PANEL LOCATION.
WASTE PIPE
TO MAIN
CODE ALLOWED DISTANCE
NO MORE THAN
" PLAN
WALL
REDUCED PRESSURE
PRINCIPLE BACKFLOW
PREVENTER WITH GATE
VALVES (TYP OF 2)
AIR GAP
FITTING (TYP)
WATER LINE
FROM METER
(SEE 4/P-502)
DRAIN PIPE TO
BE 2X LINE SIZE.
ROUTE TO
EXTERIOR OF
ENCLOSURE
(TYP.)
PIPE SUPPORT
12" MIN.
ELEVATION
M A
X
COLD WATER TO
SYSTEM
WATER PRESSURE
REDUCING VALVE
PRESSURE GAUGE
HEATED FIBERGLASS
ENCLOSURE
CONCRETE PAD
TO BACKFLOW
PREVENTERS
(SEE 3/P-502)
GATE VALVE (TYP.)
REDUCER (TYP.)
METER
FLANGE RODS, CLAMPS, BOLTS,
WASHERS SHALL BE MADE OF
STEEL
ROD
3" INCOMING WATER
SERVICE
GRADE
1' - 0"
2'-0"x2'-0" SQUARE
WASH
AROUND
DRAIN
AREA DRAIN
CONC SOG
W A
S H
"T
SEALANT
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:5
:5
P
M C
U s e rs \t b u d a i\ D o c u m e n ts
\F M
P
-1
V A
P re s c o tt -E
H R
M D
C tb u d a i.
rv t
P-502
PLUMBING DETAILS
6 6TB
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
SPG
Scale: No Scale
ROOF VENT DETAIL
Scale: No Scale
FLOOR SINK & TRAP PRIMER DETAIL
Scale: No Scale
BACKFLOW PREVENTERS PIPING DIAGRAM
Scale: No Scale
INCOMING DOMESTIC WATER SERVICE DIAGRAM
Scale: No Scale
AREA DRAIN DETAIL
1 ADDENDUM #1 4/29/2024
| Sheets |
| PW101 - FIRST FLOOR DRAIN, WASTE, AND VENT PLAN & SANITARY PIPE RISERS |
| PP101 - FIRST FLOOR DOMESTIC WATER PLAN & DOMESTIC WATER PIPE RISERS |
| P-502 - PLUMBING DETAILS |
File details come from the government source that posted it. Updated .