22-117 PLUMB ADD NO-1_Rev.pdf

PDF 902 KB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades - Tier 2 - Prescott, AZ (VA-24-00011412)
Solicitation number
36C77624B0008
Issued by

About this file

This document contains multiple pages of design plans and details related to a plumbing system for a federal construction project. It includes first floor plans for the drain, waste, vent, and domestic water systems, as well as details for items like roof vents, floor sinks, backflow preventers, and incoming water service.

The related federal contract opportunity is a solicitation from the Department of Veterans Affairs Technology Acquisition Center Austin for the EHRM Infrastructure Upgrades - Tier 2 project at the Northern Arizona VA Health Care System in Prescott, Arizona. The solicitation number is 36C77624B0008 and the project number is VA-24-00011412. The solicitation page is left intentionally blank.

View the file

Other files

File Type Posted
Award Notice 36C77624C0136_1 Final.docx DOCX document
Attachment ELEC-A.pdf PDF
013526 Sfty Requirements.pdf PDF
22-117 ELEC_ET ADD NO-1_Rev.pdf PDF
Prescott AZ Data Center_2024-04-26_Signed.pdf PDF
22-117 MECH ADD NO-1_Rev.pdf PDF
Amendment 5 - 36C77624B0008 0005.docx DOCX document
075423 TPO Roofing_WUFI Changes.pdf PDF
649-22-701 Pre-Bids RFI RESPONSES FINAL_5.22.2024.pdf PDF
090600 Sched of Finishes.pdf PDF
22-117-Q31-Addendum 1-20240429.pdf PDF
22-117 A-503 ADD NO-1_Rev.pdf PDF
22-117 G-001 ADD NO-1_Rev.pdf PDF
Attachment ENV-A.pdf PDF
087100 Door Hardware.pdf PDF
014500 QualityControl.pdf PDF
Amendment 4 - 36C77624B0008 0004.docx DOCX document
36C77624B0008 0003.docx DOCX document
36C77624B0008 0002.docx DOCX document
36C77624B0008 - Prebid Walk Sign-in for 3.22.2024.pdf PDF
S04 - Site Visit Meeting Minutes - IFB.doc DOC document
Amendment 1 - 36C77624B0008_1.docx DOCX document
SPECIAL NOTE - BID TAXES - AFTER FAR 52.229-3.docx DOCX document
Specs.pdf PDF
36C77624B0008_1 - Final.docx DOCX document
Drawings.pdf PDF
Attachment - Limitations on Subcontracting - Construction.docx DOCX document
DBA Wage Determination - Prescott AZ - 1.19.2024.pdf PDF
SOW.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1.0 3.0 4.02.0

A

B

C

TOILET

VESTIBULE

STORAGE

DATA

CENTER

SERVICE

YARD

CRAC-1 CRAC-2

P-401

/2

V

2" V

4" SAN

2" V

1" CO

1" CO

D

D

SECURE

STORAGE

4" SAN

FD-S

INVERT ELEVATION

AT BUILDING: 5314.8

AD-1

S D

AD-2

S D

6" SD6" CO

4" WCO

P-101

INVERT ELEVATION

AT BUILDING: 5316.76

PB CONTROL CENTER

AIR COMPRESSOR

AIR DRYER

1" D 1" D

3/4" D

1/2" D

1/2" D

4" SAN4" SAN

CRAC-2

CRAC-1

P-401

4" SAN

1" D

1" D

1" D

1" CO

1" CO

V

/2

V

2" V

FD-S

SEE CIVIL PLANS FOR CONTINUATION

AD-1

4" SAN

4" S D

3" SAN

1 1/2" SAN

4" S D

6" SD

6" CO

AD-2

SEE CIVIL PLANS FOR CONTINUATION

4" WCO

P-101

V

2" SAN

4" SAN

AIR DRYER

1" D

3/4" D

V

HU-1

WT-1

PB CONTROL

CENTER

D

1/2" D

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/2

/2

:5

:5

P

M C

U s e rs \t b u d a i\ D o c u m e n ts

\F M

P

-1

V A

P re s c o tt -E

H R

M D

C tb u d a i.

rv t

PW101

FIRST FLOOR DRAIN, WASTE, AND

VENT PLAN & SANITARY PIPE RISERS

2 6TB

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

SPG

NORTH

0 4 8 16

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L H

O L M

B E

R G

R O

A D

Scale: 1/4" = 1'-0"

FIRST FLOOR DRAIN, WASTE, AND VENT PLAN

A. SLEEVE ALL PENETRATIONS. FIRESTOP AND

SEAL WATER TIGHT.

B. UNLESS NOTED OTHERWISE, THE SIZE OF

FIXTURE CONNECTIONS SHALL BE AS LISTED

IN THE PLUMBING FIXTURE SCHEDULE.

C. PROVIDE THERMOSTATIC MIXING VALVE AT

EACH LAVATORY. SET TEMPERATURE AT 110°F.

D. SANITARY PIPING ARE BELOW THE FLOOR

UNLESS OTHERWISE NOTED.

1 2" VENT PIPE UP TO VTR.

2 NEW 4" SANITARY MAIN INTO BUILDING

UNDERSLAB. CONNECT TO EXISTING SANITARY

SEWER LINE. SEE CIVIL PLANS FOR

CONTINUATION.

3 INSTALL 3" AIR GAP FITTING IN 3" SANITARY

PIPING FOR CONDENSATE DRAIN.

4 ROUTE 1" COOPER PIPE CONDENSATE DRAIN

PUMPED WITH BUILT-IN IN CRAC UNIT PUMP TO

3" SINK DRAIN.

5 PROVIDE DRIP PAN UNDER PIPE. SEE DETAIL

7/P-501 FOR MORE INFORMATION.

6 FLOOR SINK TO HAVE TRAP PRIMER. SEE

DETAIL 2/P-502 FOR MORE INFORMATION.

7 HUMIDIFIER WATER TREATMENT CABINET.

REFER TO MECHANICAL. RUN 1/4" DRAIN TO

FLOOR SINK AND DISCHARGE THROUGH

APPROVED AIR GAP.

8 HUMIDIFIER UNIT. REFER TO MECHANICAL.

9 NEW 6" STORM PIPE INTO BUILDING

UNDERSLAB. CONNECT TO EXISTING STORM

LINE. SEE CIVIL PLANS FOR CONTINUATION.

Scale: No Scale

SANITARY PIPE RISERS

2" VTR

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L H

O L M

B E

R G

R O

A D

1 ADDENDUM #1 4/29/2024

1.0 3.0 4.02.0

A

B

C

TOILET

VESTIBULE

101 STORAGE

DATA

CENTER

SERVICE

YARD

CRAC-1 CRAC-2

P-401

IWH-104

1-BF-2

1-BF-1

/2

D

C W

SECURE

STORAGE

WHA-A6

1/2" FD-S

3/4"

1 1/4"2"

P-101 1/2" DCW

PB CONTROL CENTER

AIR COMPRESSOR

AIR DRYER

1/2"1/2" DCW

1/2" RO

1/2" RO

CRAC-1

CRAC-2

/2

D

C W

1-BF-1

1-BF-2

IWH-104

1/2" DHW

P-401

FD-S

METER

WHA-A

WATER PRESSURE

REDUCING VALVE

HOT BOX

SEE CIVIL PLANS FOR

CONTINUATION

1/2"

2"

1 1/4"

P-101

1/2" DCW

HU-1

WT-1

AIR DRYER

PB CONTROL CENTER

/2

R

O

1/2" DCW

1/2" RO

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

/2

/2

:5

:5

P

M C

U s e rs \t b u d a i\ D o c u m e n ts

\F M

P

-1

V A

P re s c o tt -E

H R

M D

C tb u d a i.

rv t

PP101

FIRST FLOOR DOMESTIC WATER PLAN

& DOMESTIC WATER PIPE RISERS

3 6TB

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

SPG

NORTH

0 4 8 16

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L H

O L M

B E

R G

R O

A D

Scale: 1/4" = 1'-0"

FIRST FLOOR DOMESTIC WATER PLAN

1 HUMIDIFIER UNIT. REFER TO MECHANICAL.

CONNECT WITH 1/2" RO WATER FROM WATER

TREATMENT CABINET.

2 NEW 3" DCW MAIN INTO BUILDING UNDERSLAB.

CONNECT TO EXISTING DOMESTIC COLD

WATER LINE. SEE CIVIL PLANS FOR

CONTINUATION.

3 HUMIDIFIER WATER TREATMENT CABINET.

REFER TO MECHANICAL. CONNECT WITH 1/2"

DOMESTIC COLD WATER. RUN 1/2" RO WATER

TO HUMIDIFIER.

4 ACCESS PANEL FOR TRAP PRIMER LOCATED 6'

AFF.

5 SEE INCOMING DOMESTIC WATER SERVICE

DIAGRAM 04/P-502 FOR MORE INFORMATION.

6 PROVIDE HEATED HOT BOX, FIBERGLASS

FLIPTOP ENCLOSURE FOR BACKFLOW

PREVENTERS.

A. SLEEVE ALL PENETRATIONS. FIRESTOP AND

SEAL WATER TIGHT.

B. UNLESS NOTED OTHERWISE, THE SIZE OF

FIXTURE CONNECTIONS SHALL BE AS LISTED IN

THE PLUMBING FIXTURE SCHEDULE.

C. PROVIDE ISOLATION BALL VALVES AT EACH

BRANCH TO FIXTURE. LOCATE AS CLOSE TO

MAIN AS POSSIBLE.

D. PROVIDE WATER HAMMER ARRESTOR AT ALL

QUICK CLOSING VALVES. SEE DETAIL 5/P-501

FOR SCHEDULE.

Scale: No Scale

DOMESTIC WATER PIPE RISERS

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L H

O L M

B E

R G

R O

A D

1 ADDENDUM #1 4/29/2024

PLUMBING VENT STACK

SEALANT

DRAWBAND

INSTALL SEALANT

BETWEEN PIPE AND

PREFABRICATED

MEMBRANE FLASHING

PREFABRICATED

MEMBRANE FLASHING

SEALANT (IF REQUIRED

BY THE SPECIFIC

SYSTEM)

ROOF MEMBRANE

THERMAL

INSULATION

ROOF STRUCTURE

NOTES:

1. VENT STACKS AND OTHER PIPES SHALL HAVE A MINIMUM OF 12 INCHES OF

CLEARANCE ON ALL SIDES FROM WALLS, CURBS, AND OTHER PROJECTIONS TO

FACILITATE PROPER FLASHING.

FROM COLD

WATER MAIN

TRAP PRIMER

VALVE LOCATED

INSIDE WALL CAVITY

PROVIDE LOCKABLE

ACCESS DOOR

12''x18''

DISTRIBUTION UNIT FOR

MULTIPLE INSTALLATIONS

WALL

VENT PIPING

LOCATED IN WALL

FINISHED FLOOR

COPPER PIPING PASSING THRU

CONCRETE SLAB SHALL BE PROTECTED

BY A PROTECTIVE SHEATING OR

WRAPPING TO PREVENT CORROSION

TO THE COPPER

PROVIDE TRAP PRIMER

CONNECTION ADAPTER SO

THAT TRAP PRIMER LINES

CAN BE ROUTED BELOW

SLAB OR IN FLOOR BELOW

CEILING SPACE FROM

VALVE TO DRAIN

FLOOR DRAIN OR FLOOR SINK

NOTES:

1. SEE FLOOR PLANS FOR DRAIN LOCATIONS.

2. SEE ARCHITECTURAL DRAWINGS FOR TRAP

PRIMERS ACCESS PANEL LOCATION.

WASTE PIPE

TO MAIN

CODE ALLOWED DISTANCE

NO MORE THAN

" PLAN

WALL

REDUCED PRESSURE

PRINCIPLE BACKFLOW

PREVENTER WITH GATE

VALVES (TYP OF 2)

AIR GAP

FITTING (TYP)

WATER LINE

FROM METER

(SEE 4/P-502)

DRAIN PIPE TO

BE 2X LINE SIZE.

ROUTE TO

EXTERIOR OF

ENCLOSURE

(TYP.)

PIPE SUPPORT

12" MIN.

ELEVATION

M A

X

COLD WATER TO

SYSTEM

WATER PRESSURE

REDUCING VALVE

PRESSURE GAUGE

HEATED FIBERGLASS

ENCLOSURE

CONCRETE PAD

TO BACKFLOW

PREVENTERS

(SEE 3/P-502)

GATE VALVE (TYP.)

REDUCER (TYP.)

METER

FLANGE RODS, CLAMPS, BOLTS,

WASHERS SHALL BE MADE OF

STEEL

ROD

3" INCOMING WATER

SERVICE

GRADE

1' - 0"

2'-0"x2'-0" SQUARE

WASH

AROUND

DRAIN

AREA DRAIN

CONC SOG

W A

S H

"T

SEALANT

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/2

/2

:5

:5

P

M C

U s e rs \t b u d a i\ D o c u m e n ts

\F M

P

-1

V A

P re s c o tt -E

H R

M D

C tb u d a i.

rv t

P-502

PLUMBING DETAILS

6 6TB

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

SPG

Scale: No Scale

ROOF VENT DETAIL

Scale: No Scale

FLOOR SINK & TRAP PRIMER DETAIL

Scale: No Scale

BACKFLOW PREVENTERS PIPING DIAGRAM

Scale: No Scale

INCOMING DOMESTIC WATER SERVICE DIAGRAM

Scale: No Scale

AREA DRAIN DETAIL

1 ADDENDUM #1 4/29/2024

Sheets
PW101 - FIRST FLOOR DRAIN, WASTE, AND VENT PLAN & SANITARY PIPE RISERS
PP101 - FIRST FLOOR DOMESTIC WATER PLAN & DOMESTIC WATER PIPE RISERS
P-502 - PLUMBING DETAILS