22-117 ELEC_ET ADD NO-1_Rev.pdf
PDF 7 MB Posted
- Solicitation number
- 36C77624B0008
About this file
This document appears to be a set of 100% bid documents for the EHRM Infrastructure Upgrade - Data Center project at the Northern Arizona VA Health Care System in Prescott, Arizona. It includes electrical and technology plans, details, and schedules related to constructing a new data center building (Building 166) and upgrading the existing infrastructure.
The key details are:
- The project involves constructing the data center building shell and infrastructure, routing new fiber optic cabling, connecting power to the new and existing buildings, relocating existing UPS systems, and migrating the existing data center components to the new facility.
- The electrical plans show the site infrastructure, power distribution, lighting, and lightning protection systems for the new data center.
- The technology plans detail the fiber optic and Ethernet cabling routes, telecom rooms, and physical access control system for the new facility.
- The project is being procured through Solicitation 36C77624B0008, which is an opportunity for the Department of Veterans Affairs Technology Acquisition Center Austin.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
L L
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
R RELOCATE/RELOCATED
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
D DEMOLITION
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA
STANDARDS.
PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO
SUIT THE PARTICULAR INSTALLATION.
PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING
CONSTRUCTION.
ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW
TERMINALS.
MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR
FINAL CONNECTIONS.
ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD
PARTY TESTING AGENCY.
FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.
PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
MINIMUM CONDUIT SIZE TO BE USED IS 3/4". PROVIDE PULL STRING FOR ANY SPARE CONDUITS.
FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.
ALL PART NUMBERS LISTED ARE BASIS OF DESIGN REFERENCES. EQUAL PRODUCTS WILL BE CONSIDERED.
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE
EQUIPMENT CONNECTIONAS
NOTED
E
208V DUPLEX RECEPTACLE18"
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
120V SIMPLEX RECEPTACLE18" 2' X 2' RECESSED ARCHITECTURAL TROFFER
2' X 4' RECESSED ARCHITECTURAL TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT LENS TROFFER
2' LINEAR - WALL MOUNTED7'-0"
CENTER
4' LINEAR - WALL MOUNTED7'-0"
CENTER
WALL SCONCE6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
VS: VACANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
DR: DUAL RELAY
VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER
OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
4: 4 WAY
48"
CENTER
OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY - CEILING MOUNTED---
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, LOW VOLTAGE, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED---
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
OS
OS
LS
4' LINEAR STRIP - SUSPENDED---
EMERGENCY 4' LINEAR STRIP - SUSPENDED---
1. CONSTRUCT DATA CENTER BUILDING SHELL AND SUPPORTING INFRASTRUCTURE.
2. ROUTE NEW FIBER (B-SIDE) TO ALL TELECOMMUNICATIONS ROOM IN SCOPE.
3. INITIALLY, CONNECT POWER TO NORMAL AND EMERGENCY SOURCES IN BUILDING 12 IN PARALLEL WITH EXISTING NORMAL
AND EMERGENCY SOURCES FEEDING BUILDING 12 DATA CENTER. THIS WILL SERVE THE DATA CENTER HOUSE LOADS.
4. ONCE DATA CENTER IS POWERED AND B-SIDE FIBER OPTIC CABLING IS ROUTED TO ALL EXISTING TR'S AND TESTED, CONTRACTOR SHALL MOVE ONE UPS FROM THE EXISTING DATA CENTER TO THE NEW DATA CENTER, CONNECTING POWER DISTRIBUTION, WIRE MANAGEMENT AND POWER DISTRIBUTION ABOVE ALL SERVER CABINETS.
5. ONCE ALL SERVER CABINETS POWER DISTRIBUTION, WIRE MANAGEMENT AND DATA CENTER CABLING ARE IN PLACE, COORDINATE WITH VA REGIONAL OIT STAFF AND ANY VENDROS LISTED ON SERVER SCHEDULES TO MIGRATE EXISTING BUILDING 12 COMPONENTS TO NEW SERVER SPACE AND CONNECT INTO B-SIDE FIBER INFRASTRUCTURE.
6. ONCE ALL EXISTING DATA CENTER COMPONENTS ARE MOVED TO THE NEW DATA CENTER AND ARE CONENCTED TO B-SIDE FIBER, CONTRACTOR SHALL DISCONNECT ALL OIT FIBER SOURCED FROM BUILDING 12, SPLICE THE FIBER TO EXTEND TO
MDA-A LOCATION AND RE-ESTABLISH FIBER AT THAT LOCATION.
7. ONCE ALL MDA-A FIBER IS ESTABLISHED, ALL SERVER COMPONENTS SHALL BE CONNECTED TO THE A-SIDE AS WELL AS B-
SIDE.
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
5/
/2
6:
:0
PM
C :\U se rs
\w re ed \D oc um en ts
\E _2
2-
VA
P re sc ot t-E H
R M
D C
_w re ed R
G 8R
E.
rv t
E-001
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 9CNJ
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
JAV
ELECTRICAL ABBREVIATIONS LIST
ELECTRICAL SYMBOL NOTES
ELECTRICAL GENERAL NOTES
ELECTRICAL SYMBOL LEGEND LIGHTING SYMBOL LEGENDPROJECT PHASING NARRATIVE
wreed Model
Chapel Police Logistics
Student Qtrs Misc. Adm
LibraryTheater & Voluntary
Museum
AFGE
SW Ed.
0100' 100' 200' 300'
EXIST. (2) 4"∅
CONC. DUCT
BANK 8"X14"
EXIST. (4) 4"∅
CONC. DUCT BANK
12"X14"
EXIST. (1) 4"∅ CONC.
DUCT
BANK 8"X14"
EXIST. (2) 4"∅
CONC. DUCT
BANK 8"X14"
EXIST. (2) 4"∅
CONC. DUCT
BANK 8"X14"
EXIST. 3"∅
DUCT BANK
8"X14"X30"DP.
EXIST. 64"X76"
TELECOM MAINT.
HOLE
EXIST. 64"X76"
TELECOM MAINT.
HOLE
EXIST. 4"∅ CONC. DUCT
BANK 8"X14"
CHILLER
Medical Center Site Plan
WAREHOUSE
Chapel Police Logistics
Student Qtrs Misc. Adm
LibraryTheater & Voluntary
Museum
AFGE
SW Ed.
Chapel
Police & Logistics
Program Space
Misc.
Adm
Library
Theater
Museum
AFGE
SW Ed.
Adm
Dom
CLC
OIT
ED/
FAC
MH
HOSP
MH
Hmless
Prgrms
Solar Power Panels
PARKING
LOT D
PARKING
LOT B
YAVAPAI T
RAIL
W H
IPPLE PAR
KW
AY
W H
IPPLE PAR
KW
AY
O
FFIC
ER
S R
O W
OFFICERS ROW
DR. LEIB LANE
NELL CROUCH ROAD
C
OL.
HOLM
BERG R
OAD
COL. HOLMBERG ROAD
DR. KENDALL WAY
UPPER ROAD
COL. HOLMBERG ROAD
W H
IPPLE PAR
KW
AY
EXISTING ROAD
DR. ALLEE LANE
NELL CROUCH ROAD
NELL CROUCH ROAD
OFF
IC
ER
S
ROW
UPPER ROAD
(GRAVEL)
(GRAVEL)
110111
T-5
108 107
T-6
BAS
KET
BAL
L/TE
NNI
S
HAN
DBA
LL
STOR & RRM
BLE
ACH
ERS
EXIST. (2) 4"∅
CONC. DUCT BANK
8"X14"
PARKING
PARKING
PARKIN
G LO
T O
PARKING
PARKING
PARKING
PARKING
PARKING
PARKING
LOT C
LOT A
LOT R
LOT Q
LOT T
LOT S
PARKING
LOT NPARKING
LOT P
LOT G LOT H
PARKING
LOT F
PARKING
LOT E
(RESERVED)
AUTHORIZED
VEHICLES
ONLY
LOT W
PARKING
LOT M
PARKING LOT L
PARKING
LOT K
PARKING
LOT J
PARKING
LOT U
PARKING
TO YAVAPAI COLLEGE
SITE AREA = 4,830,763 SQUARE FEET OR 110.89 ACRES
7 8
4°
EXISTING PANEL 'SES'-12, IN BASEMENT
NEW WIREWAY
NEW WIREWAY
EXISTING PANEL '115-1X-2'
BLDG 115, ROOM 100
NEW 'ATS-166'
(2) 4" C
(2) 4" C
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
5/
/2
6:
:0
PM
C :\U se rs
\w re ed \D oc um en ts
\E _2
2-
VA
P re sc ot t-E H
R M
D C
_w re ed R
G 8R
E.
rv t
ES101
ELECTRICAL SITE PLAN
2 9TT
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
JAV
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L.
H
O
LM
BE
R
G R
O
AD
Scale: 1/16" = 1'-0"1 ELECTRICAL POWER SITE PLAN
A. FOR INFORMATION ON CONDUCTORS,
CONDUITS QUANTITIES AND SIZES, SEE SINGLE
LINE DIAGRAM ON SHEET E-601.
B. NEW ELECTRICAL DUCTBANK SHALL BE
CONCRETE ENCASED.
C. ROUTING AND INFORMATION SHOWN IS BASED
ON BEST AVAILABLE INFORMATION AT TIME OF
FIELD INVESTIGATION. CONTRACTOR IS
RESPONSIBLE FOR CONDUCTING THEIR OWN
SURVEY TO CONFIRM ROUTING AND EXISTING
CONDITIONS ARE AS INDICATED.
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L.
H
O
LM
BE
R
G R
O
AD
NORTH
0 2 4 8
1 EXISTING PANEL 'SES' LOCATED IN
BASEMENT OF BLDG 12. PROVIDE NEW
BREAKER AND CONDUCTORS IN CONDUIT TO
NEW DATA CENTER ATS. SEE SHEET E-601
FOR SINGLE LINE.
2 PROVIDE WIREWAY FOR TRANSITION OF
CABLING THROUGH BLDG ENVELOPE.
CONTINUE ROUTING OF CONDUCTORS
UNDERGROUND.
3 EXISTING PANEL '115-1X-2'. PROVIDE NEW
BREAKER AND CONDUCTORS IN CONDUIT
FROM PANEL THROUGH TO NEW ATS IN NEW
DATA CENTER. SEE SHEET E-601 FOR SINGLE
LINE.
4 NEW SERVICE ENTRANCE RATED ATS
LOCATED IN NEW DATA CENTER. PROVIDE
NEW CONNECTIONS FOR EMERGENCY AND
NORMAL POWER SYSTEMS STUBBED UP AT
APPROXIMATE ATS LOCATION. COORDINATE
FINAL LOCATION OF ALL SURROUNDING
EQUIPMENT FOR STUBBED UP CONDUIT.
5 EXISTING LOCATIONS OF UPS'S TO BE
RELOCATED.
GFI
J
GFI
GFI
J
E E
E
E
EE
E
ATS
J
E
E
E
W
E
J
J
J
JA
CRAC-1 CRAC-2
FC-1
LALB
LDC-1,3
LDC-2,4,6
PANEL 'LDC'
MDP-1
CONNECT TO
BUILDING 12. SEE
ES101 AND E-601 FOR
MORE INFO.
MDP-1-5
MDP-1-6
MDP-1-1
MDP-1-2
UPS-B
ODU-2
ODU-1
CU-1
MDP-1-3
'LDC'- 9
'LDC'- 11
'LDC'- 10
'LDC'- 13
MDP-1-4
'LDC'- 12
ATS B166
CONNECT TO
BUILDING 115 ROOM 100. SEE ES101
AND E-601 FOR MORE INFO.
'LDC'- 17
'LDC'- 16,18
FUTURE
USE
IWH-104
'LDC'- 14
EDH-1
'LDC'- 19,21,23
'LDC'- 22
LDC-24 LDC-24
LDC-24
LDC-24
UPS-A
B
1.0 2.0 3.0
C
4.0
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
5/
/2
6:
:0
PM
C :\U se rs
\w re ed \D oc um en ts
\E _2
2-
VA
P re sc ot t-E H
R M
D C
_w re ed R
G 8R
E.
rv t
EP101
FIRST FLOOR POWER PLAN
3 9CNJ
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
JAV
Scale: 1/4" = 1'-0"1 FIRST FLOOR POWER PLAN
1 BUSWAY, SEE SINGLELINE AND DETAIL FOR
SIZING.
2 UPS RELOCATED FROM BASEMENT OF
BUILDING 12 WITH BATTERY CABINET
ADDITION.
3 EMERGENCY POWER OFF SWITCH. SHALL BE
A DISCONNECTING MEANS FOR POWER TO IT
EQUIPMENT AND HVAC EQUIPMENT.
4 FOR MORE INFORMATION, SEE SHEET ES101.
5 FOR MORE INFORMATION ON ROUTING, SEE
SHEET ES101.
6 PROVIDE A AND B STARLINE E-CONNECT
"U225T3C4 BUSWAY WITH PLUG UNIT
CB25E92-L620-4". PROVIDE TWO
CHATSWORTH EO-1013-C VERTICAL PDU’S
FOR RACK.
7 120V POWER CIRCUIT FOR DOOR
COMPONENTS FOR PACS.
8 POWER CIRCUIT FOR FACP.
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L.
H
O
LM
BE
R
G R
O
AD
NORTH
0 2 4 8
A.
B.
C.
D.
PROVIDE AND INSTALL ALL ELECTRICAL
DEVICES SHOWN.
SEE SINGLE-LINE DIAGRAM FOR
DISTRIBUTION COMPONENT SIZING.
ALL INFORMATION TECHNOLOGY RACKS TO
BE FITTED WITH PDUS PER DETAIL 5/E-502.
PROVIDE POWER CONECTIONS TO
MECHANICAL EQUIPMENT SHOWN. SEE
EQUIPMENT CONDUCTOR SCHEDULE ON
E-602.
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L.
H
O
LM
BE
R
G R
O
AD
VS
A
1.0
B
3.0 4.0
A
2.0
C
VESTIBULE
126 SF
DATA
CENTER
1071 SF
SERVICE
YARD
898 SF
TOILET
69 SF
STORAGE
194 SF
SECURE
STORAGE
65 SF
W W W
W
W W
W
D
D
B B
C C C
CE C CE CC
CECCCEC
C C CE C C
LL5
'LDC'- 5
'LDC'- 5 'LDC'- 5
'LDC'- 5
'LDC'- 7
E1
E1
E1
E1
C
C C
C
'LDC'- 8
B
1.0 2.0 3.0
C
4.0
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
5/
/2
6:
:1
PM
C :\U se rs
\w re ed \D oc um en ts
\E _2
2-
VA
P re sc ot t-E H
R M
D C
_w re ed R
G 8R
E.
rv t
EL101
FIRST FLOOR LIGHTING PLAN
4 9CNJ
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
JAV
Scale: 1/4" = 1'-0"1 FIRST FLOOR LIGHTING PLAN
NORTH
0 2 4 8
1 208V ASTRONOMICAL TIME CLOCK BASIS OF
DESIGN INTERMATIC ET8000
2 LIGHTS IN DATA CENTER TO BE UNSWITCHED
FOR SECURITY.
3 COORDINATE LIGHT FIXTURE MOUNTING
WITH MECHANICAL TRAPEZE MOUNTING
HARDWARE.
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L.
H
O
LM
BE
R
G R
O
AD
A.
B.
a.
b.
c.
C.
D.
E.
F.
G.
PROVIDE AND INSTALL ALL ELECTRICAL
DEVICES SHOWN.
ALL 208 VOLT 20 AMP BRANCH CIRCUIT
CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG
EG IN 3/4" CONDUIT, UNLESS NOTED
OTHERWISE.
RUNS LESS THAN 300' SHALL BE
MINIMUM 2-12 AWG, 1-12 AWG EG IN
3/4" C.
RUNS BETWEEN 300'-500' SHALL BE
MINIMUM 2-10 AWG, 1-10 AWG EG IN
3/4" C.
RUNS GREATER THAN 500' SHALL BE
MINIMUM 2-8 AWG, 1-8 AWG EG IN 3/4"
C.
ALL INTERIOR UN-SWITCHED EXIT SIGNS AND
EMERGENCY LIGHTING SHALL BE CIRCUITED
FROM LIFE SAFETY EMERGENCY LIGHTING
CIRCUIT, BUT AHEAD OF ANY SWITCHING. E1
AND CE FIXTURES UNSWITCH ON DEDICATED
PNL-166-19.
CONTRACTOR SHALL VERIFY COMPATIBILITY
OF ALL LIGHTING CONTROLS WITH THE LED
DRIVERS TO BE CONTROLLED.
COORDINATE ALL TIME DELAY, AUTO DIM,
PRESET DIMMING LEVELS, SENSOR
SENSITIVITY AND OTHER CONFIGURATIONS
WITH THE VA.
SEE LUMINAIRE SCHEDULE ON SHEET E-602
FOR LIGHTING TYPES & CHARACTERISTIC
DETAILS.
FOR EXTERIOR WALL PACK FIXTURES,
COORDINATE MOUNTING HEIGHT WITH
ARCHITECTURAL ELEVATIONS.
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L.
H
O
LM
BE
R
G R
O
AD
GFI
WP
E
A
1.0
B
3.0 4.0
A
2.0
C
SERVICE
YARD BELOW
3'-0"
3'-0" 4'-0" 4'-0" 3'-0"
HIGH ROOF
LOW ROOF
4'-0"4'-0" 3'-0" 1
1 1
LDC-15
EF-1
'LDC'- 20
B
1.0 2.0 3.0
C
4.0
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
5/
/2
6:
:1
PM
C :\U se rs
\w re ed \D oc um en ts
\E _2
2-
VA
P re sc ot t-E H
R M
D C
_w re ed R
G 8R
E.
rv t
EP102
ELECTRICAL ROOF PLAN
5 9HT
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
JAV
NORTH
0 4 8 16
Scale: 1/4" = 1'-0"1 ROOFTOP POWER AND LIGHTNING PROTECTION PLAN
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L.
H
O
LM
BE
R
G R
O
AD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
CONTRACTOR SHALL PROVIDE A LIGHTNING
PROTECTION SYSTEM THAT MEETS UFC
3-600-01 AND UL AND NFPA RELATED
DOCUMENTS.
LIGHTNING PROTECTION SYSTEM SHALL
MEET UL REQUIREMENTS SUCH THAT THE
SYSTEM SHALL HAVE A MASTER LABEL
CERTIFICATE.
THE COMPLETED INSTALLATION SHALL MEET
THE REQUIREMENTS OF THE NATIONAL FIRE
PROTECTION ASSOCIATIONS’ LIGHTNING
PROTECTION CODE – 2020 (NFPA 780), IAW
UFC 3-600-01, 03 AND THE INSTALLATION
REQUIREMENTS FOR LIGHTNING
PROTECTION SYSTEMS, UL 96A’ OF
UNDERWRITERS LABORATORIES INC. THE
MASTER LABEL SHALL BE FURNISHED TO THE
OWNER UPON COMPLETION.
COPPER LIGHTNING PROTECTION SYSTEM
COMPONENTS SHALL NOT BE MOUNTED TO
ALUMINUM SURFACES UNLESS THEY ARE
ISOLATED BY ADHESIVE.
GROUNDED METAL BODIES WITHIN THE
BONDING DISTANCE DETERMINED BY NFPA
780-2020 SHALL BE BONDED TO THE SYSTEM
IN ACCORDANCE WITH CODE
REQUIREMENTS.
UNDER GROUND METALLIC PIPING ENTERING
THE BUILDING SHALL BE BONDED TO THE
NEAREST DOWN CONDUCTOR OR GROUND
ELECTRODE.
ADHESIVE USED WITH ADHESIVE AIR
TERMINAL BASES AND CONDUCTOR
FASTENERS SHALL BE COMPATIBLE WITH
ROOFING MEMBRANE – VERIFY WITH
ROOFING CONTRACTOR.
AIR TERMINALS HAVE BEEN LOCATED ON THE
ROOF TOP EQUIPMENT AS REQUIRED. IF THE
METAL THICKNESS OF AN OBJECT IS 3/16’’ OF
GREATER, AIR TERMINALS MAY BE
ELIMINATED IF THE OBJECT IS PROPERLY
CONNECTED TO THE SYSTEM.
ALL LIGHTNING PROTECTION MATERIALS
SHALL BE CLASS II.
LIGHTNING PROTECTION CONDUCTORS
SHALL BE SIZED PER NFPA 780-20.
PROVIDE LIGHTNING PROTECTION GROUND
BUS.
THE LIGHTNING PROTECTION CONTRACTOR
SHALL BOND THE ROOF’S “FALL SYSTEM” AND
ITS ASSOCIATED RAILINGS AND BASES TO
THE NEW LIGHTNING PROTECTION SYSTEM.
ALL INTERCONNECTIONS BETWEEN LPS AND
GROUND SYSTEMS TO BE 4/0 AWG COPPER
UNO.
SEE EQUIPMENT CONDUCTOR SCHEDULE
E-602 FOR MECH EQUIPMENT CONNECTORS.
1 DOWN CONDUCTOR TO GROUND ROD. SEE
DETAIL 5/E-501.
2 PROVIDE NEW CONVENIENCE OUTLET FOR
MECHANICAL EQUIPMENT.
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L.
H
O
LM
BE
R
G R
O
AD
ROOF
COPPER CONDUCTOR
CONNECT TO PERIMETER
CONDUCTOR
THRU-ROOF ROD
#SNHB-95D
ROOF FLASHING PROVIDED
BY THE ROOFING
CONTRACTOR
BRASS CONNECTOR
COPPER CONDUCTOR
#CCHB-28-14
THRU-ROOF ROD
SEAL PVC CONDUIT WITH
SILICONE SEALANT TO
PREVENT INGRESS OF
WATER
THRU-ROOF ROD
#SNHB-950
ROOF CONDUCTOR
CCHB-28-14
PROPER ROOF FLASHING
(FURNISHED AND
INSTALLED BY THE
ROOFING CONTRACTOR)
DOWN CONDUCTOR IN 1" PVC
CONDUIT (ALL CONDUIT SHALL
BE FURNISHED, INSTALLED,
WEATHERPROOFED, AND
MAINTAINED FREE FROM
OBSTRUCTIONS BY THE
ELECTRICAL CONTRACTOR)
INTERMEDIATE-LEVEL POTENTIAL
EQUALIZATION LOOP #CCHB-28-14
NOTE: ALL DOWN CONDUCTORS AND
OTHER GROUNDED MEDIA SHALL BE
INTERCONNECTED WITH THE
INTERMEDIATE LEVEL LOOP.
ALL JUNCTION BOXES SHALL
BE PROVIDED BY THE ELEC.
CONTR. (TYP.)
COLUMN/EXTERIOR WALL
BARE COPPER
CONUCTOR CCHB-28-14
FLOOR SLAB
GROUND ROD
CONNECTOR
#CGHB-57D
3/4" X 10'-0' COPPERWELD
GROUND ROD #CGHB-107GR
GROUND LOOP
BY OTHERS
12"
24" MIN.
24" MIN.
AIR TERMINAL
NOTES:
1. SEE PLATE E-001 FOR LEGEND.
2. ALL SPLICES BELOW GRADE SHALL BE THE
EXOTHERMIC
WELD TYPE.
3. AIR TERMINALS SHALL EXTEND NO LESS THAN 24
INCHES
ABOVE THE ROOF.
4. ALL METAL EQUIPMENT ON THE ROOF SHALL BE
BONDED
TO THE LIGHTNING PROTECTION SYSTEM.
5. THRU ROOF FLASHING SHALL BE COPPER WITH 8 INCH
ROUND BASE AND VERTICAL TUBE WITH NEOPRENE
SEAL.
FLASHING SHALL BE THE PRODUCT OF THE
MANUFACTURER
OF THE LIGHTNING PROTECTION SYSTEM. A MEMBRANE
FLASHING SHALL BE PROVIDED OVER THE THRU ROOF
FLASHING.
MAIN CONDUCTOR
CLIP CABLE SUPPORT
SEALING WASHER
2' -0
M
IN
FINISHED GRADE
TOP OF GROUND ROD, 24" BELOW FINAL
GRADE
GROUND ROD SHALL NOT BE ANGLED MORE
THAN 30° FROM VERTICAL WHERE
POSSIBLE.
EXOTHERMIC WELD CONNECTION
TREATED WITH TWO (2) COATS COLD
GALVANIZED PAINT
3/4" DIAMETER COPPER CLAD STEEL GROUND
ROD 10' LONG. AT LEAST 8' OF GROUND ROD
IN
CONTACT WITH SOIL
30° MAX
Typical adhesive parapet air terminal placement.
LIGHTNING PROTECTION
GROUND BUS
COPPER GROUND BAR PER
MANUFACTURER STANDARDS
NEMA 3R ENCLOSURE
MOUNTED TO EXTERIOR OF
BUILDING PER MANUFACTURER
STANDARDS
TELEPHONE GROUNDING CONDUCTOR
CATV GROUNDING CONDUCTOR
LIGHTNING PROTECTION DOWN CONDUCTOR
GROUNDING ELECTRODE CONDUCTOR
WALL
UNISTRUT-
MOUNTED
TO WALL
UNISTRUT
SPRING
CLIP
ELECTRICAL
PANEL
P1000 STEEL
UNISTRUT
MOUNTED TO
WALL
UNISTRUT MOUNTED PANEL
BOLT
ELECTRICAL
PANEL
CONDUIT FITTING
JUNCTION BOX
(SIZE AS
REQUIRED)
PROVIDE PROPER
SUPPORT FOR
JUCTIONBOX PER NEC
314.23
JUNCTION BOX, TYP
(SIZE AS REQUIRED)
MAXIMUM 6' -
FLEXIBLE METAL
CONDUIT
1.
2.
GENERAL NOTE:
COORDINATE FINAL ELECTRICAL CONNECTIONS FOR MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR.
PERFORM FINAL TERMINATIONS IN MECHANICAL EQUIPMENT PER MANUFACTURER'S INSTRUCTIONS.
MECHANICAL
EQUIPMENT
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
5/
/2
6:
:1
PM
C :\U se rs
\w re ed \D oc um en ts
\E _2
2-
VA
P re sc ot t-E H
R M
D C
_w re ed R
G 8R
E.
rv t
E-501
ELECTRICAL DETAILS
6 9HT
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
JAV
Scale: No Scale1
LIGHTING PROTECTION THOUGH ROOF PENETRATION
DETAIL
Scale: No Scale4 LIGHTNING PROTECTION AIR TERMINAL
Scale: No Scale5 GROUND ROD DETAIL
Scale: No Scale3 LIGHTNING PROTECTION AIR PARAPET
Scale: 1 1/2" = 1'-0"2 LIGHTNING PROTECTION GROUND BUS
Scale: No Scale6 UNISTRUT PANEL MOUNTING
Scale: No Scale7 MECHANICAL EQUIPMENT ELECTRICAL CONNECTION
2X4 LED LIGHT PANEL
OR 1X4 LED FIXTURES
ALL FIXTURES MOUNTED
BELOW MECH EQUIPMENT
AT SAME HEIGHT AFF.
CONCRETE CEILING
3/4"C
CONCRETE CEILING ANCHORS
CEILING MOUNTED
METAL BOX
3/4"C
PENDANT MOUNT
FIXTURE
CEILING HANGER WIRE
ARCHITECTURAL
CEILING GRID
HANGER WIRE AND MOUNTING
CHANNEL ATTACHED TO
STRUCTURE. REFER TO
SPECIFICATION SECTION 26 51 00
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
ARCHITECTURAL
CEILING GRID
ACOUSTICAL CEILING
TILE, TYP.
ARCHITECTURAL
CEILING GRID
1/4" SCREW
JUNCTION BOX
LOCKING SQUARE
WASHER & NUT
FIXTURE WHIP FROM JUNCTION
BOX (6' [1829MM] LONG MAX)
1.
GENERAL NOTE:
INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING
INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING
HARDWARE.
INTEGRATED UPS LINE UP WITH TWO (2) BATTERY CABINETS,
MAINTENANCE BYPASS CABINET AND OUTPUT DISTRIBUTION.
(RELOCATED)
UPS A
70KVA,
MODULAR
208V-3PH
INPUT
208Y/120V-3PH
OUTPUT
BUSWAY
POWER FEED
UNIT, TYP.
BUSWAY, WITH
TAPS AND DROP
CORDS FOR
CABINETS, TYP.
(3) #2, #4 GND
IN 2-1/2" C
BUSWAY 1-B
BUSWAY 1-A
(NEW)
PANEL
LA
225A
208Y/120
V-3PH
(4) 4/0, #2 GND IN
2-1/2"C (4) 3/0, #4 GND IN
2-1/2"C
(NEW)
PANEL
LB
225A
208Y/120
V-3PH
BUSWAY
POWER FEED
UNIT, TYP. BUSWAY, WITH
TAPS AND DROP
CORDS FOR
CABINETS, TYP.
BUSWAY 2-B
BUSWAY 2-A
(4) 3/0, #4 GND IN
2-1/2"C
(RELOCATED)
UPS B
70KVA,
MODULAR
208V-3PH
INPUT
208Y/120V-3P
H OUTPUT
PANEL
MDP-1
400A
208Y/120
V-3PH
ATS-B166
(4) 4/0, #2 GND IN
2-1/2"C
FINISHED FLOOR
3 4
RACK 1
CIRCUIT A FIBER LOOP
REMOTE BUILDINGS
FINISHED FLOOR
3 4
RACK 2
CIRCUIT B FIBER LOOP
REMOTE BUILDINGS
7'
0"7'
6"
9'
0"
8'
3.
6"
"12
RETURN AIR DUCT
FLOOR TO ENCLOSURE TOP
FLOOR TO BOTTOM OF CABLE TRAY
FLOOR TO BOTTOM OF BUSWAY
FLOOR TO BOTTOM OF RETURN DUCT
FLOOR TO TOP OF RETURN DUCT
FLOOR TO SLAB ABOVE
NO SUSPENDED CEILING
MINIMUM 12' REQUIRED
RECOMMENDED 16'
WIRE MESH
CABLE TRAY
POWER FEED UNIT WITH
CURRENT MONITOR TO
SUPPORT EACH ROW
VERTICAL EXAUST DUCT
208V 3 PHASE POWER BUSBAR
HINGED FIBER CHANNEL PATHWAY
BUSWAY TAP - PROVIDE
(12) 20A DISCONNECTS PER
BUSWAY. SPACING OF
DISCONNECT CONNECTION
POINTS TO BE MAX 30"
REAR VIEW
BUSWAY
FIBER CABLE TRAY WITH
1'' BEND RADIUS CONTROL
VERTICAL TEE OR TRUMPET
UTP CABLE TRAY
WITH DROP OUT KIT
RETURN AIR DUCT TO CRACS
SIZED TO SUPPORT HEAT REJECTION
IN ACCORDANCE WITH COMPUTATIONAL
FLUID DYNAMICS (CFD) ANALYSIS (3W X 2.5H)
VERTICAL EXHAUST DUCT
ENCLOSURE
SIDE VIEW
POWER BUSWAY TAP WITH SINGLE
BREAKER 3' DROP CORD (WITH
STRAIN RELIEF) WITH L21-20R TO
CONNECT TO RACK PDU
VERTICAL PDUs
VERTICAL PDUs VERTICAL PDUs
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
5/
/2
6:
:2
PM
C :\U se rs
\w re ed \D oc um en ts
\E _2
2-
VA
P re sc ot t-E H
R M
D C
_w re ed R
G 8R
E.
rv t
E-502
ELECTRICAL DETAILS
7 9HT
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
JAV
Scale: 1" = 1'-0"1 PENDENT MOUNTED FIXTURES (FOR OPTIONS 2&3)
Scale: N.T.S.2 EXIT SIGN MOUNTING - LAY-IN CEILING
Scale: 3/16" = 1'-0"3 NEW MCR RISER DIAGRAMS
1.
2.
3.
4.
5.
6.
DETAIL NOTES:
144 PORT FIBER OPTIC ANGLED PATCH PANEL WITH
COUPLERS.
HORIZONTAL WIRE MANAGMENT (1U).
TR CHANNEL RACK 30" DEEP.
6"W X 10"D VERTICAL WIRE MANAGEMENT WITH DOORS, IF
RACKS ARE GANGABLE THEN PROVIDE ONLY ONE VERTICAL
WIRE MANAGEMENT BETWEEN THEM.
RACK, WIRE MANAGEMENT, AND RACK MOUNTED
EQUIPMENT SHALL BE WHITE IN COLOR.
1.
2.
3.
4.
5.
6.
DETAIL NOTES:
144 PORT FIBER OPTIC ANGLED PATCH PANEL WITH
COUPLERS.
HORIZONTAL WIRE MANAGMENT (1U).
TR CHANNEL RACK 30" DEEP.
6"W X 10"D VERTICAL WIRE MANAGEMENT WITH DOORS, IF
RACKS ARE GANGABLE THEN PROVIDE ONLY ONE VERTICAL
WIRE MANAGEMENT BETWEEN THEM.
RACK, WIRE MANAGEMENT, AND RACK MOUNTED
EQUIPMENT SHALL BE WHITE IN COLOR.
Scale: No Scale5 FIBER OPTIC DISTRIBUTION CABINET MDA-1
Scale: No Scale6 FIBER OPTIC DISTRIBUTION CABINET MDA-2 Scale: N.T.S.4 POWER MECH RACK ELEVATION
200A 208/120V
PANELBOARD
'LDC'
200A 200A 200A 225A
30A30A
70kVA
208/120V INPUT
208/120V OUTPUT
UPS-A
(RELOCATED) 225A
225A 208/120V
3-PHASE 4-WIRE
LA
400A 208/120V
3-PHASE 4-WIRE
MDP-1
200A
CRAC-1
26 TON
225A 225A
CRAC-2
26 TON
CONDENSER
'ODU-2'
CONDENSER
'ODU-1'
BLDG 12
BASEMENT
225A
70kVA
208/120V INPUT
208/120V OUTPUT
UPS-B
(RELOCATED)
225A
225A 208/120V
3-PHASE 4-WIRE
LB
225A 225A
225A BUSWAY
ROW 1
225A BUSWAY
ROW 2
225A BUSWAY
ROW 3
225A BUSWAY
ROW 4
SPACE SPACE SPACE
SPACE SPACE SPACE
400A
ATS B166
3-PHASE
400A
800A 208/120V
EXISTING
PANELBOARD
'115-1X-2'
400A
800A 208/120V
EXISTING
PANELBOARD
'SES-12'
400A
BLDG 115
ROOM 100
200NG
225NG
225NG
400G
400G 400G
225NG
225NG
CIRCUIT BREAKER
GENERATOR
CONTACTOR
FUSED SWITCH
MOTOR
SURGE PROTECTION DEVICE
SYMBOL DESCRIPTION
METER
DIGITAL POWER METER
ELECTRONIC OVERLOAD
FUSE
GROUND
TRANSFER SWITCH
DPM
G
M
SPD
100A4G
SWITCH
TRANSFORMER
UTILITY LINE SERVICE DROP
ELECTRICAL PANEL
NOTE: PANEL SHOWN HERE IS MAIN LUGS
ONLY. MCB PANEL IS INDICATED BY
REPLACING MLO SYMBOL WITH CIRCUIT
BREAKER SYMBOL. ADDITIONAL PANEL
INFORMATION INDICATED BELOW SYMBOL.
WIRE TAG INDICATING FEEDER SIZE. SEE FEEDER
SCHEDULE.
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
5/
/2
6:
:2
PM
C :\U se rs
\w re ed \D oc um en ts
\E _2
2-
VA
P re sc ot t-E H
R M
D C
_w re ed R
G 8R
E.
rv t
E-601
SINGLE LINE DIAGRAM
8 9CNJ
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
JAV
Scale: No Scale1 SINGLE LINE DIAGRAM
ELECTRICAL SYMBOL LEGEND
10. INDICATED FEEDERS ARE SIZED LARGER TO PREVENT EXCESSIVE VOLTAGE DROP. IF THE
INSTALLED CONDUIT TYPE AND CONDUCTOR TYPE ARE DIFFERENT THAN THE INDICATED
TYPES, RE-EVALUATE CONDUCTOR AND CONDUIT SIZE FOR VOLTAGE DROP AND RESIZE IF
REQUIRED. EVALUATE VOLTAGE DROP AT THE FARTHEST OUTLET OF POWER, HEATING AND
LIGHTING LOADS, OR COMBINATIONS OF SUCH LOADS. SIZE CONDUCTORS FOR FEEDERS TO
PREVENT A VOLTAGE DROP EXCEEDING 2 PERCENT. SIZE CONDUCTORS FOR BRANCH
CIRCUITS TO PREVENT A VOLTAGE DROP EXCEEDING 3 PERCENT. THE MAXIMUM TOTAL
VOLTAGE DROP ACROSS BOTH FEEDERS AND BRANCH CIRCUITS IN SERIES TO THE FARTHEST
OUTLET SHALL NOT EXCEED 5 PERCENT.
9. INDICATED FEEDERS SHALL USE COPPER CONDUCTORS.
8. INDICATED FEEDER CONDUCTORS ARE SIZED BASED ON THE NEUTRAL CONDUCTOR BEING
COUNTED AS A CURRENT CARRYING CONDUCTOR.
7. INDICATED FEEDERS SHALL HAVE RACEWAYS SIZED BASED ON SCHEDULE 40 PVC CONDUIT.
USE OF OTHER CONDUIT TYPES SHALL REQUIRE RESIZING OF CONDUIT.
6. INDICATED FEEDERS SHALL BE FOR SINGLE MOTOR BRANCH CIRCUITS. FEEDERS SERVING
MOTOR CIRCUITS EQUIPPED WITH ADJUSTABLE SPEED DRIVES SHALL BE PROVIDED WITH
STRANDED CONDUCTORS
5. EACH CONDUIT COMPRISING INDICATED FEEDERS SHALL HAVE A FULL SIZE EQUIPMENT
GROUND CONDUCTOR BASED ON THE TRIP RATING OF THE FEEDER OVERCURRENT
PROTECTIVE DEVICE. PROVIDE PROPERLY SIZED TERMINATIONS.
4. INDICATED FEEDERS SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR AND AN ISOLATED
EQUIPMENT GROUNDING CONDUCTOR. PROVIDE PROPERLY SIZED TERMINATIONS..
3. DUE TO HARMONIC CURRENTS CARRIED BY THE NEUTRAL, THE NEUTRAL OF THE INDICATED
FEEDER SHALL CONSIST OF TWO CONDUCTORS IN EACH RACEWAY TERMINATED TO THE SAME
LUGS, AND HAS COMPOSITE AMPACITY THAT IS 200% OF THE AMPACITY OF THE INDIVIDUAL
PHASE CONDUCTORS. THE FEEDER SIZES ARE BASED ON 75 DEGREE CENTIGRADE
TEMPERATURE RATINGS FOR THE CONDUCTORS AND THE TERMINATIONS.
2. INDICATED FEEDERS SHALL HAVE AN EQUIPMENT BONDING JUMPER. PROVIDE PROPERLY
SIZED TERMINATIONS.
1. AMPACITIES USED IN THIS FEEDER SCHEDULE ARE BASED ON MAXIMUM 60 DEGREE
CENTIGRADE FOR WIRE AND TERMINATIONS FOR SIZES #14 TO #1, AND MAXIMUM 75 DEGREE
CENTIGRADE FOR WIRE AND TERMINATIONS FOR SIZES #1/0 AND LARGER. UNLESS NOTED
OTHERWISE, CONDUIT IS SIZED BASED ON TYPE EMT CONDUIT. USE OF OTHER CONDUIT
TYPES REQUIRES RESIZING OF CONDUIT.
REMARKS:
FEEDER SCHEDULE
TAG CONDUIT & CONDUCTORS REMARKS
200NG 3-3/0 AWG, 1-3/0 AWG NEU, 1-6 AWG EG, IN 2-1/2" C
225NG 3-4/0 AWG, 1-4/0 AWG NEU, 1-4 AWG EG, IN 2-1/2" C
400G 3-600 KCMIL, 1-1/0 AWG EG, IN 4" C
EQUIPMENT CONDUCTOR SCHEDULE
TAG DESCRIPTION VOLTS PHASE LOAD MOCP CONDUCTORS NEUTRAL GROUND CONDUIT DISCONNECT TYPE CRAC-1 AIR CONDITIONING UNIT 208V 3 42.9 kVA 200A 3 3/0 AWG 3/0 AWG 4 AWG 2" DISCONNECT SWITCH
CRAC-2 AIR CONDITIONING UNIT 208V 3 42.9 kVA 200A 3 3/0 AWG 3/0 AWG 4 AWG 2" DISCONNECT SWITCH
ODU-1 CONDENSER 208V 3 3.062 KVA 30A 3 10 AWG 10 AWG 10 AWG 3/4" DISCONNECT SWITCH
ODU-2 CONDENSER 208V 3 3.062 KVA 30A 3 10 AWG 10 AWG 10 AWG 3/4" DISCONNECT SWITCH
EF-1 EXHAUST FAN 120V 1 0.5 kVA 20A 1 12 AWG 12 AWG 12 AWG 3/4" MOTOR RATED SWITCH
EDH-1 SPLIT SYSTEM HEAT PUMP 208V 3 4.96 kVA 20A 3 12 AWG 12 AWG 12 AWG 3/4" MOTOR RATED SWITCH
FC-1 ELECTRICAL DUCT MOUNTED HEATER 208V 3 0.260 kVA 20A 1 12 AWG 12 AWG 12 AWG 3/4" MOTOR RATED SWITCH
HU-1 HEATER UNIT 120V 1 0.5 kVA 20A 1 12 AWG 12 AWG 12 AWG 3/4" MOTOR RATED SWITCH
CU-1 CONDENSING UNIT 208V 1 5.0 kVA 20A 1 12 AWG 12 AWG 12 AWG 3/4" 15A NF DISCONNECT SWITCH
Engineers Architects Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
NOT FOR
CONSTRUCTION
NOT FOR
CONSTRUCTION
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
5/
/2
6:
:2
PM
C :\U se rs
\w re ed \D oc um en ts
\E _2
2-
VA
P re sc ot t-E H
R M
D C
_w re ed R
G 8R
E.
rv t
E-602
ELECTRICAL SCHEDULES
9 9CNJ
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
JAV
2. (*) NUMBER INDICATES BREAKER TYPE: 1 = AFCI, 2 = CLASS A 5mA GFCI, 3 = 30mA GFPE, 4 = SHUNT TRIP ACTIVATED, 5 = PANELBOARD FEEDER SERVING UNIT SHALL BE LOCKABLE USING A PADLOCK, IN ACCORDANCE WITH OSHA LOCK-OUT-TAG RULES, 6 = LSI, 7 = LSIG.
1. ALL BREAKERS ARE STANDARD UNLESS OTHERWISE NOTED
NOTES:
LIGHTING (EXTERIOR) 0.28 kVA 125.00% 0.35 kVA LIGHTING (GENERAL) 0.95 kVA 125.00% 1.19 kVA TOTAL DEMAND CURRENT: 339 A SPEC 113.59 kVA 103.36% 117.40 kVA TOTAL CONNECTED CURRENT: 328 A RECEPTACLES (GENERAL) 3.06 kVA 100.00% 3.06 kVA TOTAL DEMAND: 122.12 kVA Power 0.80 kVA 100.00% 0.80 kVA TOTAL CONNECTED LOAD: 118.04 kVA Other 0.00 kVA 0.00% 0.00 kVA Load Classification Connected Load Demand Factor Demand Load PANEL TOTALS
TOTAL AMPS: 332 A 329 A 324 A
TOTAL CONNECTED LOAD: 39.76 kVA 39.38 kVA 38.89 kVA
7 LDC 400 A 20 A 3 17.85 kVA 17.43 kVA 16.94 kVA 6 CRAC UNIT 2 400 A 200 A 3 0.00 kVA 0.00 kVA 0.00 kVA 5 CRAC UNIT 1 400 A 200 A 3 14.29 kVA 14.29 kVA 14.29 kVA 4 UPS2 400 A 225 A 3 0.00 kVA 0.00 kVA 0.00 kVA 3 UPS1 400 A 225 A 3 7.81 kVA 7.81 kVA 7.81 kVA 2 ODU-2 400 A 30 A 3 0.00 kVA 0.00 kVA 0.00 kVA 1 ODU-1 400 A 30 A 3 1.02 kVA 1.02 kVA 1.02 kVA
ITEM NO. IDENTIFICATION BREAKER
FRAME
BREAKER
TRIP
TYPE
(*) POLE A B C REMARKS
MAIN: 400 A MCB BUSSING: SEE SPEC MCB 100% RATED (Y/N): N
RATED AMPERAGE: 400 A ISOLATED GROUND BUS (Y/N): N MCB SHUNT TRIP (Y/N): Y
PHASE / WIRE: 3Ø / 4W OPD INTERRUPTING RATING (SYM): MCB GROUND FAULT PROTECTION (Y/N): N
VOLTAGE: 208 SCC RATING (SYM): MOUNTING:
MDP-1
2. (*) NUMBER INDICATES BREAKER TYPE: 1 = AFCI, 2 = CLASS A 5mA GFCI, 3 = 30mA GFPE, 4 = SHUNT TRIP ACTIVATED, 5 = PANELBOARD FEEDER SERVING UNIT SHALL BE LOCKABLE USING A PADLOCK, IN ACCORDANCE WITH OSHA LOCK-OUT-TAG RULES, 6 = LSI, 7 = LSIG.
1. ALL BREAKERS ARE STANDARD UNLESS OTHERWISE NOTED
NOTES:
TOTAL DEMAND CURRENT: 97 A
TOTAL CONNECTED CURRENT: 97 A
TOTAL DEMAND: 34.98 kVA SPEC 34.98 kVA 100.00% 34.98 kVA TOTAL CONNECTED LOAD: 34.98 kVA Other 0.00 kVA 0.00% 0.00 kVA Load Classification Connected Load Demand Factor Demand Load PANEL TOTALS
TOTAL AMPS: 97 A 97 A 97 A
TOTAL CONNECTED LOAD: 11.66 kVA 11.66 kVA 11.66 kVA
2 BUSWAY 400 A 225 A 3 5.83 kVA 5.83 kVA 5.83 kVA 1 BUSWAY 400 A 225 A 3 5.83 kVA 5.83 kVA 5.83 kVA
ITEM NO. IDENTIFICATION BREAKER
FRAME
BREAKER
TRIP
TYPE
(*) POLE A B C REMARKS
MAIN: 225 A MCB BUSSING: SEE SPEC MCB 100% RATED (Y/N): N
RATED AMPERAGE: 225 A ISOLATED GROUND BUS (Y/N): N MCB SHUNT TRIP (Y/N): N
PHASE / WIRE: 3Ø / 4W OPD INTERRUPTING RATING (SYM): MCB GROUND FAULT PROTECTION (Y/N): N
VOLTAGE: 208Y/120 V SCC RATING (SYM): MOUNTING: SURFACE
LA
2. (*) NUMBER INDICATES BREAKER TYPE: 1 = AFCI, 2 = CLASS A 5mA GFCI, 3 = 30mA GFPE, 4 = SHUNT TRIP ACTIVATED, 5 = PANELBOARD FEEDER SERVING UNIT SHALL BE LOCKABLE USING A PADLOCK, IN ACCORDANCE WITH OSHA LOCK-OUT-TAG RULES, 6 = LSI, 7 = LSIG.
1. ALL BREAKERS ARE STANDARD UNLESS OTHERWISE NOTED
NOTES:
TOTAL DEMAND CURRENT: 97 A
TOTAL CONNECTED CURRENT: 97 A
TOTAL DEMAND: 34.98 kVA SPEC 34.98 kVA 100.00% 34.98 kVA TOTAL CONNECTED LOAD: 34.98 kVA Other 0.00 kVA 0.00% 0.00 kVA Load Classification Connected Load Demand Factor Demand Load PANEL TOTALS
TOTAL AMPS: 97 A 97 A 97 A
TOTAL CONNECTED LOAD: 11.66 kVA 11.66 kVA 11.66 kVA
2 BUSWAY 400 A 225 A 3 5.83 kVA 5.83 kVA 5.83 kVA 1 BUSWAY 400 A 225 A 3 5.83 kVA 5.83 kVA 5.83 kVA
ITEM NO. IDENTIFICATION BREAKER
FRAME
BREAKER
TRIP
TYPE
(*) POLE A B C REMARKS
MAIN: 225 A MCB BUSSING: SEE SPEC MCB 100% RATED (Y/N): N
RATED AMPERAGE: 225 A ISOLATED GROUND BUS (Y/N): N MCB SHUNT TRIP (Y/N): N
PHASE / WIRE: 3Ø / 4W OPD INTERRUPTING RATING (SYM): MCB GROUND FAULT PROTECTION (Y/N): N
VOLTAGE: 208Y/120 V SCC RATING (SYM): MOUNTING: SURFACE
LB
Notes:
LIGHTING (EXTERIOR) 0.28 kVA 125.00% 0.35 kVA LIGHTING (GENERAL) 0.95 kVA 125.00% 1.19 kVA Total Est. Demand: 146 A SPEC 48.05 kVA 100.00% 48.05 kVA Total Conn.: 145 A Power 0.80 kVA 100.00% 0.80 kVA Total Est. Demand: 52.47 kVA RECEPTACLES (GENERAL) 3.06 kVA 100.00% 3.06 kVA Total Conn. Load: 52.22 kVA Other 0.00 kVA 0.00% 0.00 kVA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 149 A 146 A 141 A Total Load: 17.85 kVA 17.43 kVA 16.94 kVA
41 42 39 40 37 38 35 36 33 34 31 32 29 30 27 28 25 26
23 4.80 0.80 1 20 A POWER FOR PACS DOOR CONTROL 24
21 4.80 0.60 1 20 A POWER FOR FACP 22
EDH-1 20 A 3
4.80 0.00 1 20 A EF-1 20
17 FUTURE 20 A 1 0.00 10.40 18
15 RECEPTACLES (GENERAL) 20 A 1 0.18 10.40
2 20 A IWH-104 WATER HEATER
13 RECEPTACLES (GENERAL) 20 A 1 0.36 12.00 1 20 A HU-1 14
11 RECEPTACLES (GENERAL) 20 A 1 0.72 0.24 1 20 A WT-1 12
9 RECEPTACLES (GENERAL) 20 A 1 1.08 0.72 1 20 A RECEPTACLES (GENERAL) 10
7 LIGHTING (GENERAL) 20 A 1 0.65 0.28 1 20 A LIGHTING (EXTERIOR) 8
5 LIGHTING (GENERAL) 20 A 1 0.31 0.00 6
3 0.00 0.00 4
FC-1 20 A 2
0.00 0.00
3 20 A CU-1
CKT Circuit Description Trip Poles A B C A B C
Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 200 A Mounting: SURFACE Wires: 4 Mains Rating: 200 A
Supply From: MDP-1 Phases: 3 Mains Type: MAIN CB Location: DATA CENTER 102 Volts: 120/208 A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: LDC
GENERAL NOTES:
A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL.
CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE PART NUMBERS.
B. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
C. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH THE LIGHT FIXTURE SHOP
DRAWINGS, FOR A COMPLETE REVIEW.
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING LAMP DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER
B 2' X 4' LENSED TROFFER; RECESSED
GRID
LED; 4800
LUMENS;
80 CRI;
3500K
0-10V DIMMABLE TO
5% DRIVER
120.00 V 50 W - -
C 4' LINEAR LED STRIPLIGHT WITH FROSTED
LENS
CHANNEL
AND ROD
MOUNTED
LED; 4,585
LUMENS;
80 CRI;
4000K
ELECTRONIC LED
DRIVER
120.00 V 34 W LITHONIA ZL1N L48 5000LM FST MVOLT 40K 80CRI
CE 4' LINEAR LED STRIPLIGHT WITH FROSTED
LENS WITH BATTERY BACKUP
CHANNEL
AND ROD
MOUNTED
LED; 4,585
LUMENS;
80 CRI;
4000K
ELECTRONIC LED
DRIVER
120.00 V 34 W LITHONIA ZL1N L48 5000LM FST MVOLT 40K 80CRI
D 6" DIAMETER DIMMABLE LED WIDE
DISTRIBUTION DOWNLIGHT
RECESSED
GRID
LED; 2000
LUMENS;
3500K; 80
CRI
0-10V DIMMABLE TO
10% LED DRIVER
120.00 V 20 W GOTHAM EVO6 35/20 AR MWD LD MVOLT GZ10
E1 CONTEMPORARY LED SINGLE FACED EXIT
SIGN WITH BLACK POWDER PAINT ALUMINUM
HOUSING, BRUSHED ALUMINUM FACE, RED
LETTERS, AND CHEVRON ARROWS AS
SHOWN ON PLANS. INCLUDES BATTERY
BACKUP.
UNIVERSAL LED RED --- 120.00 V 5 W LITHONIA LES 1 R 120/277 EL-N
LL5 4' LINEAR SURFACE MOUNTED EXTREME
ENVIRONMENT LED ELEVATOR PIT LIGHT;
WITH RIBBED FROSTED ACRYLIC LENS;
ENCLOSED AND GASKETED; WET LOCATION
SURFACE
WALL
LED; 4,250
LUMENS;
80 CRI;
4000K
ELECTRONIC LED
DRIVER
120.00 V 33 W COLUMBIA LIGHTING LXEM4-40LW-RFA-EU
W EXTERIOR WALL PACK; DARK BRONZE FINISH
CONTROLLED BY ASTRO TIMER CONTROL
SURFACE
WALL
LED; 3400
LUMENS;
80 CRI;
3500K
ELECTRONIC LED
DRIVER
120.00 V 40 W LITHONIA DSWX1-10C-1000-40K-T3S-MVOLT-E20WC
TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - N-4 PR UTP
TELCO OUTLET - N-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"
48"
ELECTRONIC LOCKING MECHANISM
DOOR CONTACT
REQUEST FOR EXIT SENSOR
CARD READER
(K - KEYPAD, DUAL AUTHENTICATION)48"CR
ES
DC
RX
48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)
WIRELESS ACCESS POINT - N-4 PR UTP
WALL PHONEW
IC INTERCOM WITH CAMERA
IC INTERCOM MASTER WITH PUSH TO RELEASE DOORM
N
TV OUTLET WALL MOUNTED
48"
54"
DESK
CCTV DOME CAMERA FIXED
CCTV DOME CAMERA PAN/TILT/ZOOM
FOUR POST OIT EQUIPMENT RACK
OIT EQUIPMENT CABINET
MATV EQUIPMENT CABINET
CCTV EQUIPMENT CABINET
MATV
CCTV
BASKET CABLE TRAY
N
N
FLOOR BOX FOR DATA
AS NOTED
DOOR
DOOR
ABOVE
DOOR
6' TO TOP
FLOOR
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
ELECTRONIC PANIC HARDWAREEP
DO DOOR OPERATOR
GROUND BUS
CEILING
DOOR
DOOR
FLOOR
FLOOR
FLOOR
ABOVE
CEILING
18"
4'x8'x3/4" FIRE RATED TTB8"
88" MOTION DETECTORMD
FLOOR TWO POST OIT EQUIPMENT RACK
CEILING MOUNTED SPEAKERSCEILING
WALL MOUNTED SPEAKERS96"
S
S
SECURE WIRELESS ACCESS POINT - N-4 PR UTP
N
CEILING
S
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
(N - QUANTITY)
CEILING
CEILING
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
CCTV MULTISENSOR DOME CAMERA CEILING
MS
TECHNOLOGY GENERAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS,…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .