22-117 ELEC_ET ADD NO-1_Rev.pdf

PDF 7 MB Posted

Attached to
Y1DA--EHRM Infrastructure Upgrades - Tier 2 - Prescott, AZ (VA-24-00011412)
Solicitation number
36C77624B0008
Issued by

About this file

This document appears to be a set of 100% bid documents for the EHRM Infrastructure Upgrade - Data Center project at the Northern Arizona VA Health Care System in Prescott, Arizona. It includes electrical and technology plans, details, and schedules related to constructing a new data center building (Building 166) and upgrading the existing infrastructure.

The key details are:

  • The project involves constructing the data center building shell and infrastructure, routing new fiber optic cabling, connecting power to the new and existing buildings, relocating existing UPS systems, and migrating the existing data center components to the new facility.
  • The electrical plans show the site infrastructure, power distribution, lighting, and lightning protection systems for the new data center.
  • The technology plans detail the fiber optic and Ethernet cabling routes, telecom rooms, and physical access control system for the new facility.
  • The project is being procured through Solicitation 36C77624B0008, which is an opportunity for the Department of Veterans Affairs Technology Acquisition Center Austin.

View the file

Other files

File Type Posted
Award Notice 36C77624C0136_1 Final.docx DOCX document
Attachment ELEC-A.pdf PDF
013526 Sfty Requirements.pdf PDF
Prescott AZ Data Center_2024-04-26_Signed.pdf PDF
22-117 MECH ADD NO-1_Rev.pdf PDF
Amendment 5 - 36C77624B0008 0005.docx DOCX document
075423 TPO Roofing_WUFI Changes.pdf PDF
649-22-701 Pre-Bids RFI RESPONSES FINAL_5.22.2024.pdf PDF
090600 Sched of Finishes.pdf PDF
22-117-Q31-Addendum 1-20240429.pdf PDF
22-117 A-503 ADD NO-1_Rev.pdf PDF
22-117 G-001 ADD NO-1_Rev.pdf PDF
Attachment ENV-A.pdf PDF
22-117 PLUMB ADD NO-1_Rev.pdf PDF
087100 Door Hardware.pdf PDF
014500 QualityControl.pdf PDF
Amendment 4 - 36C77624B0008 0004.docx DOCX document
36C77624B0008 0003.docx DOCX document
36C77624B0008 0002.docx DOCX document
36C77624B0008 - Prebid Walk Sign-in for 3.22.2024.pdf PDF
S04 - Site Visit Meeting Minutes - IFB.doc DOC document
Amendment 1 - 36C77624B0008_1.docx DOCX document
SPECIAL NOTE - BID TAXES - AFTER FAR 52.229-3.docx DOCX document
Specs.pdf PDF
36C77624B0008_1 - Final.docx DOCX document
Drawings.pdf PDF
Attachment - Limitations on Subcontracting - Construction.docx DOCX document
DBA Wage Determination - Prescott AZ - 1.19.2024.pdf PDF
SOW.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

L L

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BIPHENYL

PC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

R RELOCATE/RELOCATED

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

2W TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCT CORRELATED COLOR TEMPERATURE

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICER

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

D DEMOLITION

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FU FUSE

FUDS FUSED SAFETY DISCONNECT

SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

MSBD MAIN SWITCHBOARD

MT MOUNT

A1 b

E1 c d

T1

'LPN'

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA

STANDARDS.

PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING

CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL

ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.

VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO

SUIT THE PARTICULAR INSTALLATION.

PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING

CONSTRUCTION.

ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.

MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT

MANUFACTURER'S SPECIFICATIONS.

CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW

TERMINALS.

MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR

FINAL CONNECTIONS.

ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD

PARTY TESTING AGENCY.

FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.

PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE

PROVIDED.

COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

MINIMUM CONDUIT SIZE TO BE USED IS 3/4". PROVIDE PULL STRING FOR ANY SPARE CONDUITS.

FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.

ALL PART NUMBERS LISTED ARE BASIS OF DESIGN REFERENCES. EQUAL PRODUCTS WILL BE CONSIDERED.

120V DUPLEX RECEPTACLE

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

SPECIAL RECEPTACLE

EQUIPMENT CONNECTIONAS

NOTED

E

208V DUPLEX RECEPTACLE18"

18"

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

CLNG

J

J

J

JUNCTION BOX, CEILING MOUNTED, PURPOSE AS

NOTED

JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS

NOTED

120V SIMPLEX RECEPTACLE18" 2' X 2' RECESSED ARCHITECTURAL TROFFER

2' X 4' RECESSED ARCHITECTURAL TROFFER

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 4' RECESSED FLAT LENS TROFFER

2' LINEAR - WALL MOUNTED7'-0"

CENTER

4' LINEAR - WALL MOUNTED7'-0"

CENTER

WALL SCONCE6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

VS: VACANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

DR: DUAL RELAY

VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER

OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

4: 4 WAY

48"

CENTER

OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY - CEILING MOUNTED---

--- LOW VOLTAGE LIGHTING CONTROL DEVICE

OCCUPANCY SENSOR, LOW VOLTAGE, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

RC

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED---

--- LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

RCD

OS

OS

LS

4' LINEAR STRIP - SUSPENDED---

EMERGENCY 4' LINEAR STRIP - SUSPENDED---

1. CONSTRUCT DATA CENTER BUILDING SHELL AND SUPPORTING INFRASTRUCTURE.

2. ROUTE NEW FIBER (B-SIDE) TO ALL TELECOMMUNICATIONS ROOM IN SCOPE.

3. INITIALLY, CONNECT POWER TO NORMAL AND EMERGENCY SOURCES IN BUILDING 12 IN PARALLEL WITH EXISTING NORMAL

AND EMERGENCY SOURCES FEEDING BUILDING 12 DATA CENTER. THIS WILL SERVE THE DATA CENTER HOUSE LOADS.

4. ONCE DATA CENTER IS POWERED AND B-SIDE FIBER OPTIC CABLING IS ROUTED TO ALL EXISTING TR'S AND TESTED, CONTRACTOR SHALL MOVE ONE UPS FROM THE EXISTING DATA CENTER TO THE NEW DATA CENTER, CONNECTING POWER DISTRIBUTION, WIRE MANAGEMENT AND POWER DISTRIBUTION ABOVE ALL SERVER CABINETS.

5. ONCE ALL SERVER CABINETS POWER DISTRIBUTION, WIRE MANAGEMENT AND DATA CENTER CABLING ARE IN PLACE, COORDINATE WITH VA REGIONAL OIT STAFF AND ANY VENDROS LISTED ON SERVER SCHEDULES TO MIGRATE EXISTING BUILDING 12 COMPONENTS TO NEW SERVER SPACE AND CONNECT INTO B-SIDE FIBER INFRASTRUCTURE.

6. ONCE ALL EXISTING DATA CENTER COMPONENTS ARE MOVED TO THE NEW DATA CENTER AND ARE CONENCTED TO B-SIDE FIBER, CONTRACTOR SHALL DISCONNECT ALL OIT FIBER SOURCED FROM BUILDING 12, SPLICE THE FIBER TO EXTEND TO

MDA-A LOCATION AND RE-ESTABLISH FIBER AT THAT LOCATION.

7. ONCE ALL MDA-A FIBER IS ESTABLISHED, ALL SERVER COMPONENTS SHALL BE CONNECTED TO THE A-SIDE AS WELL AS B-

SIDE.

Engineers Architects Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

NOT FOR

CONSTRUCTION

NOT FOR

CONSTRUCTION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

5/

/2

6:

:0

PM

C :\U se rs

\w re ed \D oc um en ts

\E _2

2-

VA

P re sc ot t-E H

R M

D C

_w re ed R

G 8R

E.

rv t

E-001

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 9CNJ

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

JAV

ELECTRICAL ABBREVIATIONS LIST

ELECTRICAL SYMBOL NOTES

ELECTRICAL GENERAL NOTES

ELECTRICAL SYMBOL LEGEND LIGHTING SYMBOL LEGENDPROJECT PHASING NARRATIVE

wreed Model

Chapel Police Logistics

Student Qtrs Misc. Adm

LibraryTheater & Voluntary

Museum

AFGE

SW Ed.

0100' 100' 200' 300'

EXIST. (2) 4"∅

CONC. DUCT

BANK 8"X14"

EXIST. (4) 4"∅

CONC. DUCT BANK

12"X14"

EXIST. (1) 4"∅ CONC.

DUCT

BANK 8"X14"

EXIST. (2) 4"∅

CONC. DUCT

BANK 8"X14"

EXIST. (2) 4"∅

CONC. DUCT

BANK 8"X14"

EXIST. 3"∅

DUCT BANK

8"X14"X30"DP.

EXIST. 64"X76"

TELECOM MAINT.

HOLE

EXIST. 64"X76"

TELECOM MAINT.

HOLE

EXIST. 4"∅ CONC. DUCT

BANK 8"X14"

CHILLER

Medical Center Site Plan

WAREHOUSE

Chapel Police Logistics

Student Qtrs Misc. Adm

LibraryTheater & Voluntary

Museum

AFGE

SW Ed.

Chapel

Police & Logistics

Program Space

Misc.

Adm

Library

Theater

Museum

AFGE

SW Ed.

Adm

Dom

CLC

OIT

ED/

FAC

MH

HOSP

MH

Hmless

Prgrms

Solar Power Panels

PARKING

LOT D

PARKING

LOT B

YAVAPAI T

RAIL

W H

IPPLE PAR

KW

AY

W H

IPPLE PAR

KW

AY

O

FFIC

ER

S R

O W

OFFICERS ROW

DR. LEIB LANE

NELL CROUCH ROAD

C

OL.

HOLM

BERG R

OAD

COL. HOLMBERG ROAD

DR. KENDALL WAY

UPPER ROAD

COL. HOLMBERG ROAD

W H

IPPLE PAR

KW

AY

EXISTING ROAD

DR. ALLEE LANE

NELL CROUCH ROAD

NELL CROUCH ROAD

OFF

IC

ER

S

ROW

UPPER ROAD

(GRAVEL)

(GRAVEL)

110111

T-5

108 107

T-6

BAS

KET

BAL

L/TE

NNI

S

HAN

DBA

LL

STOR & RRM

BLE

ACH

ERS

EXIST. (2) 4"∅

CONC. DUCT BANK

8"X14"

PARKING

PARKING

PARKIN

G LO

T O

PARKING

PARKING

PARKING

PARKING

PARKING

PARKING

LOT C

LOT A

LOT R

LOT Q

LOT T

LOT S

PARKING

LOT NPARKING

LOT P

LOT G LOT H

PARKING

LOT F

PARKING

LOT E

(RESERVED)

AUTHORIZED

VEHICLES

ONLY

LOT W

PARKING

LOT M

PARKING LOT L

PARKING

LOT K

PARKING

LOT J

PARKING

LOT U

PARKING

TO YAVAPAI COLLEGE

SITE AREA = 4,830,763 SQUARE FEET OR 110.89 ACRES

7 8

4°

EXISTING PANEL 'SES'-12, IN BASEMENT

NEW WIREWAY

NEW WIREWAY

EXISTING PANEL '115-1X-2'

BLDG 115, ROOM 100

NEW 'ATS-166'

(2) 4" C

(2) 4" C

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

NOT FOR

CONSTRUCTION

NOT FOR

CONSTRUCTION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

5/

/2

6:

:0

PM

C :\U se rs

\w re ed \D oc um en ts

\E _2

2-

VA

P re sc ot t-E H

R M

D C

_w re ed R

G 8R

E.

rv t

ES101

ELECTRICAL SITE PLAN

2 9TT

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

JAV

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L.

H

O

LM

BE

R

G R

O

AD

Scale: 1/16" = 1'-0"1 ELECTRICAL POWER SITE PLAN

A. FOR INFORMATION ON CONDUCTORS,

CONDUITS QUANTITIES AND SIZES, SEE SINGLE

LINE DIAGRAM ON SHEET E-601.

B. NEW ELECTRICAL DUCTBANK SHALL BE

CONCRETE ENCASED.

C. ROUTING AND INFORMATION SHOWN IS BASED

ON BEST AVAILABLE INFORMATION AT TIME OF

FIELD INVESTIGATION. CONTRACTOR IS

RESPONSIBLE FOR CONDUCTING THEIR OWN

SURVEY TO CONFIRM ROUTING AND EXISTING

CONDITIONS ARE AS INDICATED.

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L.

H

O

LM

BE

R

G R

O

AD

NORTH

0 2 4 8

1 EXISTING PANEL 'SES' LOCATED IN

BASEMENT OF BLDG 12. PROVIDE NEW

BREAKER AND CONDUCTORS IN CONDUIT TO

NEW DATA CENTER ATS. SEE SHEET E-601

FOR SINGLE LINE.

2 PROVIDE WIREWAY FOR TRANSITION OF

CABLING THROUGH BLDG ENVELOPE.

CONTINUE ROUTING OF CONDUCTORS

UNDERGROUND.

3 EXISTING PANEL '115-1X-2'. PROVIDE NEW

BREAKER AND CONDUCTORS IN CONDUIT

FROM PANEL THROUGH TO NEW ATS IN NEW

DATA CENTER. SEE SHEET E-601 FOR SINGLE

LINE.

4 NEW SERVICE ENTRANCE RATED ATS

LOCATED IN NEW DATA CENTER. PROVIDE

NEW CONNECTIONS FOR EMERGENCY AND

NORMAL POWER SYSTEMS STUBBED UP AT

APPROXIMATE ATS LOCATION. COORDINATE

FINAL LOCATION OF ALL SURROUNDING

EQUIPMENT FOR STUBBED UP CONDUIT.

5 EXISTING LOCATIONS OF UPS'S TO BE

RELOCATED.

GFI

J

GFI

GFI

J

E E

E

E

EE

E

ATS

J

E

E

E

W

E

J

J

J

JA

CRAC-1 CRAC-2

FC-1

LALB

LDC-1,3

LDC-2,4,6

PANEL 'LDC'

MDP-1

CONNECT TO

BUILDING 12. SEE

ES101 AND E-601 FOR

MORE INFO.

MDP-1-5

MDP-1-6

MDP-1-1

MDP-1-2

UPS-B

ODU-2

ODU-1

CU-1

MDP-1-3

'LDC'- 9

'LDC'- 11

'LDC'- 10

'LDC'- 13

MDP-1-4

'LDC'- 12

ATS B166

CONNECT TO

BUILDING 115 ROOM 100. SEE ES101

AND E-601 FOR MORE INFO.

'LDC'- 17

'LDC'- 16,18

FUTURE

USE

IWH-104

'LDC'- 14

EDH-1

'LDC'- 19,21,23

'LDC'- 22

LDC-24 LDC-24

LDC-24

LDC-24

UPS-A

B

1.0 2.0 3.0

C

4.0

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

NOT FOR

CONSTRUCTION

NOT FOR

CONSTRUCTION

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

5/

/2

6:

:0

PM

C :\U se rs

\w re ed \D oc um en ts

\E _2

2-

VA

P re sc ot t-E H

R M

D C

_w re ed R

G 8R

E.

rv t

EP101

FIRST FLOOR POWER PLAN

3 9CNJ

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

JAV

Scale: 1/4" = 1'-0"1 FIRST FLOOR POWER PLAN

1 BUSWAY, SEE SINGLELINE AND DETAIL FOR

SIZING.

2 UPS RELOCATED FROM BASEMENT OF

BUILDING 12 WITH BATTERY CABINET

ADDITION.

3 EMERGENCY POWER OFF SWITCH. SHALL BE

A DISCONNECTING MEANS FOR POWER TO IT

EQUIPMENT AND HVAC EQUIPMENT.

4 FOR MORE INFORMATION, SEE SHEET ES101.

5 FOR MORE INFORMATION ON ROUTING, SEE

SHEET ES101.

6 PROVIDE A AND B STARLINE E-CONNECT

"U225T3C4 BUSWAY WITH PLUG UNIT

CB25E92-L620-4". PROVIDE TWO

CHATSWORTH EO-1013-C VERTICAL PDU’S

FOR RACK.

7 120V POWER CIRCUIT FOR DOOR

COMPONENTS FOR PACS.

8 POWER CIRCUIT FOR FACP.

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L.

H

O

LM

BE

R

G R

O

AD

NORTH

0 2 4 8

A.

B.

C.

D.

PROVIDE AND INSTALL ALL ELECTRICAL

DEVICES SHOWN.

SEE SINGLE-LINE DIAGRAM FOR

DISTRIBUTION COMPONENT SIZING.

ALL INFORMATION TECHNOLOGY RACKS TO

BE FITTED WITH PDUS PER DETAIL 5/E-502.

PROVIDE POWER CONECTIONS TO

MECHANICAL EQUIPMENT SHOWN. SEE

EQUIPMENT CONDUCTOR SCHEDULE ON

E-602.

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L.

H

O

LM

BE

R

G R

O

AD

VS

A

1.0

B

3.0 4.0

A

2.0

C

VESTIBULE

126 SF

DATA

CENTER

1071 SF

SERVICE

YARD

898 SF

TOILET

69 SF

STORAGE

194 SF

SECURE

STORAGE

65 SF

W W W

W

W W

W

D

D

B B

C C C

CE C CE CC

CECCCEC

C C CE C C

LL5

'LDC'- 5

'LDC'- 5 'LDC'- 5

'LDC'- 5

'LDC'- 7

E1

E1

E1

E1

C

C C

C

'LDC'- 8

B

1.0 2.0 3.0

C

4.0

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

NOT FOR

CONSTRUCTION

NOT FOR

CONSTRUCTION

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

5/

/2

6:

:1

PM

C :\U se rs

\w re ed \D oc um en ts

\E _2

2-

VA

P re sc ot t-E H

R M

D C

_w re ed R

G 8R

E.

rv t

EL101

FIRST FLOOR LIGHTING PLAN

4 9CNJ

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

JAV

Scale: 1/4" = 1'-0"1 FIRST FLOOR LIGHTING PLAN

NORTH

0 2 4 8

1 208V ASTRONOMICAL TIME CLOCK BASIS OF

DESIGN INTERMATIC ET8000

2 LIGHTS IN DATA CENTER TO BE UNSWITCHED

FOR SECURITY.

3 COORDINATE LIGHT FIXTURE MOUNTING

WITH MECHANICAL TRAPEZE MOUNTING

HARDWARE.

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L.

H

O

LM

BE

R

G R

O

AD

A.

B.

a.

b.

c.

C.

D.

E.

F.

G.

PROVIDE AND INSTALL ALL ELECTRICAL

DEVICES SHOWN.

ALL 208 VOLT 20 AMP BRANCH CIRCUIT

CONDUCTORS SHALL BE 2-12 AWG, 1-12 AWG

EG IN 3/4" CONDUIT, UNLESS NOTED

OTHERWISE.

RUNS LESS THAN 300' SHALL BE

MINIMUM 2-12 AWG, 1-12 AWG EG IN

3/4" C.

RUNS BETWEEN 300'-500' SHALL BE

MINIMUM 2-10 AWG, 1-10 AWG EG IN

3/4" C.

RUNS GREATER THAN 500' SHALL BE

MINIMUM 2-8 AWG, 1-8 AWG EG IN 3/4"

C.

ALL INTERIOR UN-SWITCHED EXIT SIGNS AND

EMERGENCY LIGHTING SHALL BE CIRCUITED

FROM LIFE SAFETY EMERGENCY LIGHTING

CIRCUIT, BUT AHEAD OF ANY SWITCHING. E1

AND CE FIXTURES UNSWITCH ON DEDICATED

PNL-166-19.

CONTRACTOR SHALL VERIFY COMPATIBILITY

OF ALL LIGHTING CONTROLS WITH THE LED

DRIVERS TO BE CONTROLLED.

COORDINATE ALL TIME DELAY, AUTO DIM,

PRESET DIMMING LEVELS, SENSOR

SENSITIVITY AND OTHER CONFIGURATIONS

WITH THE VA.

SEE LUMINAIRE SCHEDULE ON SHEET E-602

FOR LIGHTING TYPES & CHARACTERISTIC

DETAILS.

FOR EXTERIOR WALL PACK FIXTURES,

COORDINATE MOUNTING HEIGHT WITH

ARCHITECTURAL ELEVATIONS.

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L.

H

O

LM

BE

R

G R

O

AD

GFI

WP

E

A

1.0

B

3.0 4.0

A

2.0

C

SERVICE

YARD BELOW

3'-0"

3'-0" 4'-0" 4'-0" 3'-0"

HIGH ROOF

LOW ROOF

4'-0"4'-0" 3'-0" 1

1 1

LDC-15

EF-1

'LDC'- 20

B

1.0 2.0 3.0

C

4.0

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

NOT FOR

CONSTRUCTION

NOT FOR

CONSTRUCTION

WALL RATING LEGEND

1 HR - FIRE SEPARATION

2 HR - FIRE SEPARATION

SMOKE RESISTIVE HAZARDOUS AREA

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

S S S S

5/

/2

6:

:1

PM

C :\U se rs

\w re ed \D oc um en ts

\E _2

2-

VA

P re sc ot t-E H

R M

D C

_w re ed R

G 8R

E.

rv t

EP102

ELECTRICAL ROOF PLAN

5 9HT

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

JAV

NORTH

0 4 8 16

Scale: 1/4" = 1'-0"1 ROOFTOP POWER AND LIGHTNING PROTECTION PLAN

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L.

H

O

LM

BE

R

G R

O

AD

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

CONTRACTOR SHALL PROVIDE A LIGHTNING

PROTECTION SYSTEM THAT MEETS UFC

3-600-01 AND UL AND NFPA RELATED

DOCUMENTS.

LIGHTNING PROTECTION SYSTEM SHALL

MEET UL REQUIREMENTS SUCH THAT THE

SYSTEM SHALL HAVE A MASTER LABEL

CERTIFICATE.

THE COMPLETED INSTALLATION SHALL MEET

THE REQUIREMENTS OF THE NATIONAL FIRE

PROTECTION ASSOCIATIONS’ LIGHTNING

PROTECTION CODE – 2020 (NFPA 780), IAW

UFC 3-600-01, 03 AND THE INSTALLATION

REQUIREMENTS FOR LIGHTNING

PROTECTION SYSTEMS, UL 96A’ OF

UNDERWRITERS LABORATORIES INC. THE

MASTER LABEL SHALL BE FURNISHED TO THE

OWNER UPON COMPLETION.

COPPER LIGHTNING PROTECTION SYSTEM

COMPONENTS SHALL NOT BE MOUNTED TO

ALUMINUM SURFACES UNLESS THEY ARE

ISOLATED BY ADHESIVE.

GROUNDED METAL BODIES WITHIN THE

BONDING DISTANCE DETERMINED BY NFPA

780-2020 SHALL BE BONDED TO THE SYSTEM

IN ACCORDANCE WITH CODE

REQUIREMENTS.

UNDER GROUND METALLIC PIPING ENTERING

THE BUILDING SHALL BE BONDED TO THE

NEAREST DOWN CONDUCTOR OR GROUND

ELECTRODE.

ADHESIVE USED WITH ADHESIVE AIR

TERMINAL BASES AND CONDUCTOR

FASTENERS SHALL BE COMPATIBLE WITH

ROOFING MEMBRANE – VERIFY WITH

ROOFING CONTRACTOR.

AIR TERMINALS HAVE BEEN LOCATED ON THE

ROOF TOP EQUIPMENT AS REQUIRED. IF THE

METAL THICKNESS OF AN OBJECT IS 3/16’’ OF

GREATER, AIR TERMINALS MAY BE

ELIMINATED IF THE OBJECT IS PROPERLY

CONNECTED TO THE SYSTEM.

ALL LIGHTNING PROTECTION MATERIALS

SHALL BE CLASS II.

LIGHTNING PROTECTION CONDUCTORS

SHALL BE SIZED PER NFPA 780-20.

PROVIDE LIGHTNING PROTECTION GROUND

BUS.

THE LIGHTNING PROTECTION CONTRACTOR

SHALL BOND THE ROOF’S “FALL SYSTEM” AND

ITS ASSOCIATED RAILINGS AND BASES TO

THE NEW LIGHTNING PROTECTION SYSTEM.

ALL INTERCONNECTIONS BETWEEN LPS AND

GROUND SYSTEMS TO BE 4/0 AWG COPPER

UNO.

SEE EQUIPMENT CONDUCTOR SCHEDULE

E-602 FOR MECH EQUIPMENT CONNECTORS.

1 DOWN CONDUCTOR TO GROUND ROD. SEE

DETAIL 5/E-501.

2 PROVIDE NEW CONVENIENCE OUTLET FOR

MECHANICAL EQUIPMENT.

N

AREA OF WORK

KEY PLAN - SITE

SCALE: NO SCALE

BLDG

157BLDG

BLDG

BLDG

BLDG

C O

L.

H

O

LM

BE

R

G R

O

AD

ROOF

COPPER CONDUCTOR

CONNECT TO PERIMETER

CONDUCTOR

THRU-ROOF ROD

#SNHB-95D

ROOF FLASHING PROVIDED

BY THE ROOFING

CONTRACTOR

BRASS CONNECTOR

COPPER CONDUCTOR

#CCHB-28-14

THRU-ROOF ROD

SEAL PVC CONDUIT WITH

SILICONE SEALANT TO

PREVENT INGRESS OF

WATER

THRU-ROOF ROD

#SNHB-950

ROOF CONDUCTOR

CCHB-28-14

PROPER ROOF FLASHING

(FURNISHED AND

INSTALLED BY THE

ROOFING CONTRACTOR)

DOWN CONDUCTOR IN 1" PVC

CONDUIT (ALL CONDUIT SHALL

BE FURNISHED, INSTALLED,

WEATHERPROOFED, AND

MAINTAINED FREE FROM

OBSTRUCTIONS BY THE

ELECTRICAL CONTRACTOR)

INTERMEDIATE-LEVEL POTENTIAL

EQUALIZATION LOOP #CCHB-28-14

NOTE: ALL DOWN CONDUCTORS AND

OTHER GROUNDED MEDIA SHALL BE

INTERCONNECTED WITH THE

INTERMEDIATE LEVEL LOOP.

ALL JUNCTION BOXES SHALL

BE PROVIDED BY THE ELEC.

CONTR. (TYP.)

COLUMN/EXTERIOR WALL

BARE COPPER

CONUCTOR CCHB-28-14

FLOOR SLAB

GROUND ROD

CONNECTOR

#CGHB-57D

3/4" X 10'-0' COPPERWELD

GROUND ROD #CGHB-107GR

GROUND LOOP

BY OTHERS

12"

24" MIN.

24" MIN.

AIR TERMINAL

NOTES:

1. SEE PLATE E-001 FOR LEGEND.

2. ALL SPLICES BELOW GRADE SHALL BE THE

EXOTHERMIC

WELD TYPE.

3. AIR TERMINALS SHALL EXTEND NO LESS THAN 24

INCHES

ABOVE THE ROOF.

4. ALL METAL EQUIPMENT ON THE ROOF SHALL BE

BONDED

TO THE LIGHTNING PROTECTION SYSTEM.

5. THRU ROOF FLASHING SHALL BE COPPER WITH 8 INCH

ROUND BASE AND VERTICAL TUBE WITH NEOPRENE

SEAL.

FLASHING SHALL BE THE PRODUCT OF THE

MANUFACTURER

OF THE LIGHTNING PROTECTION SYSTEM. A MEMBRANE

FLASHING SHALL BE PROVIDED OVER THE THRU ROOF

FLASHING.

MAIN CONDUCTOR

CLIP CABLE SUPPORT

SEALING WASHER

2' -0

M

IN

FINISHED GRADE

TOP OF GROUND ROD, 24" BELOW FINAL

GRADE

GROUND ROD SHALL NOT BE ANGLED MORE

THAN 30° FROM VERTICAL WHERE

POSSIBLE.

EXOTHERMIC WELD CONNECTION

TREATED WITH TWO (2) COATS COLD

GALVANIZED PAINT

3/4" DIAMETER COPPER CLAD STEEL GROUND

ROD 10' LONG. AT LEAST 8' OF GROUND ROD

IN

CONTACT WITH SOIL

30° MAX

Typical adhesive parapet air terminal placement.

LIGHTNING PROTECTION

GROUND BUS

COPPER GROUND BAR PER

MANUFACTURER STANDARDS

NEMA 3R ENCLOSURE

MOUNTED TO EXTERIOR OF

BUILDING PER MANUFACTURER

STANDARDS

TELEPHONE GROUNDING CONDUCTOR

CATV GROUNDING CONDUCTOR

LIGHTNING PROTECTION DOWN CONDUCTOR

GROUNDING ELECTRODE CONDUCTOR

WALL

UNISTRUT-

MOUNTED

TO WALL

UNISTRUT

SPRING

CLIP

ELECTRICAL

PANEL

P1000 STEEL

UNISTRUT

MOUNTED TO

WALL

UNISTRUT MOUNTED PANEL

BOLT

ELECTRICAL

PANEL

CONDUIT FITTING

JUNCTION BOX

(SIZE AS

REQUIRED)

PROVIDE PROPER

SUPPORT FOR

JUCTIONBOX PER NEC

314.23

JUNCTION BOX, TYP

(SIZE AS REQUIRED)

MAXIMUM 6' -

FLEXIBLE METAL

CONDUIT

1.

2.

GENERAL NOTE:

COORDINATE FINAL ELECTRICAL CONNECTIONS FOR MECHANICAL EQUIPMENT WITH MECHANICAL CONTRACTOR.

PERFORM FINAL TERMINATIONS IN MECHANICAL EQUIPMENT PER MANUFACTURER'S INSTRUCTIONS.

MECHANICAL

EQUIPMENT

Engineers Architects Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

NOT FOR

CONSTRUCTION

NOT FOR

CONSTRUCTION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

5/

/2

6:

:1

PM

C :\U se rs

\w re ed \D oc um en ts

\E _2

2-

VA

P re sc ot t-E H

R M

D C

_w re ed R

G 8R

E.

rv t

E-501

ELECTRICAL DETAILS

6 9HT

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

JAV

Scale: No Scale1

LIGHTING PROTECTION THOUGH ROOF PENETRATION

DETAIL

Scale: No Scale4 LIGHTNING PROTECTION AIR TERMINAL

Scale: No Scale5 GROUND ROD DETAIL

Scale: No Scale3 LIGHTNING PROTECTION AIR PARAPET

Scale: 1 1/2" = 1'-0"2 LIGHTNING PROTECTION GROUND BUS

Scale: No Scale6 UNISTRUT PANEL MOUNTING

Scale: No Scale7 MECHANICAL EQUIPMENT ELECTRICAL CONNECTION

2X4 LED LIGHT PANEL

OR 1X4 LED FIXTURES

ALL FIXTURES MOUNTED

BELOW MECH EQUIPMENT

AT SAME HEIGHT AFF.

CONCRETE CEILING

3/4"C

CONCRETE CEILING ANCHORS

CEILING MOUNTED

METAL BOX

3/4"C

PENDANT MOUNT

FIXTURE

CEILING HANGER WIRE

ARCHITECTURAL

CEILING GRID

HANGER WIRE AND MOUNTING

CHANNEL ATTACHED TO

STRUCTURE. REFER TO

SPECIFICATION SECTION 26 51 00

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

WIRE TIE THROUGH

MOUNTING CHANNEL

& CROSS BEAM, TYP.

ARCHITECTURAL

CEILING GRID

ACOUSTICAL CEILING

TILE, TYP.

ARCHITECTURAL

CEILING GRID

1/4" SCREW

JUNCTION BOX

LOCKING SQUARE

WASHER & NUT

FIXTURE WHIP FROM JUNCTION

BOX (6' [1829MM] LONG MAX)

1.

GENERAL NOTE:

INSTALL IN ACCORDANCE WITH MANUFACTURER'S MOUNTING

INSTRUCTIONS AND USING THE RECOMMENDED MOUNTING

HARDWARE.

INTEGRATED UPS LINE UP WITH TWO (2) BATTERY CABINETS,

MAINTENANCE BYPASS CABINET AND OUTPUT DISTRIBUTION.

(RELOCATED)

UPS A

70KVA,

MODULAR

208V-3PH

INPUT

208Y/120V-3PH

OUTPUT

BUSWAY

POWER FEED

UNIT, TYP.

BUSWAY, WITH

TAPS AND DROP

CORDS FOR

CABINETS, TYP.

(3) #2, #4 GND

IN 2-1/2" C

BUSWAY 1-B

BUSWAY 1-A

(NEW)

PANEL

LA

225A

208Y/120

V-3PH

(4) 4/0, #2 GND IN

2-1/2"C (4) 3/0, #4 GND IN

2-1/2"C

(NEW)

PANEL

LB

225A

208Y/120

V-3PH

BUSWAY

POWER FEED

UNIT, TYP. BUSWAY, WITH

TAPS AND DROP

CORDS FOR

CABINETS, TYP.

BUSWAY 2-B

BUSWAY 2-A

(4) 3/0, #4 GND IN

2-1/2"C

(RELOCATED)

UPS B

70KVA,

MODULAR

208V-3PH

INPUT

208Y/120V-3P

H OUTPUT

PANEL

MDP-1

400A

208Y/120

V-3PH

ATS-B166

(4) 4/0, #2 GND IN

2-1/2"C

FINISHED FLOOR

3 4

RACK 1

CIRCUIT A FIBER LOOP

REMOTE BUILDINGS

FINISHED FLOOR

3 4

RACK 2

CIRCUIT B FIBER LOOP

REMOTE BUILDINGS

7'

0"7'

6"

9'

0"

8'

3.

6"

"12

RETURN AIR DUCT

FLOOR TO ENCLOSURE TOP

FLOOR TO BOTTOM OF CABLE TRAY

FLOOR TO BOTTOM OF BUSWAY

FLOOR TO BOTTOM OF RETURN DUCT

FLOOR TO TOP OF RETURN DUCT

FLOOR TO SLAB ABOVE

NO SUSPENDED CEILING

MINIMUM 12' REQUIRED

RECOMMENDED 16'

WIRE MESH

CABLE TRAY

POWER FEED UNIT WITH

CURRENT MONITOR TO

SUPPORT EACH ROW

VERTICAL EXAUST DUCT

208V 3 PHASE POWER BUSBAR

HINGED FIBER CHANNEL PATHWAY

BUSWAY TAP - PROVIDE

(12) 20A DISCONNECTS PER

BUSWAY. SPACING OF

DISCONNECT CONNECTION

POINTS TO BE MAX 30"

REAR VIEW

BUSWAY

FIBER CABLE TRAY WITH

1'' BEND RADIUS CONTROL

VERTICAL TEE OR TRUMPET

UTP CABLE TRAY

WITH DROP OUT KIT

RETURN AIR DUCT TO CRACS

SIZED TO SUPPORT HEAT REJECTION

IN ACCORDANCE WITH COMPUTATIONAL

FLUID DYNAMICS (CFD) ANALYSIS (3W X 2.5H)

VERTICAL EXHAUST DUCT

ENCLOSURE

SIDE VIEW

POWER BUSWAY TAP WITH SINGLE

BREAKER 3' DROP CORD (WITH

STRAIN RELIEF) WITH L21-20R TO

CONNECT TO RACK PDU

VERTICAL PDUs

VERTICAL PDUs VERTICAL PDUs

Engineers Architects Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

NOT FOR

CONSTRUCTION

NOT FOR

CONSTRUCTION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

5/

/2

6:

:2

PM

C :\U se rs

\w re ed \D oc um en ts

\E _2

2-

VA

P re sc ot t-E H

R M

D C

_w re ed R

G 8R

E.

rv t

E-502

ELECTRICAL DETAILS

7 9HT

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

JAV

Scale: 1" = 1'-0"1 PENDENT MOUNTED FIXTURES (FOR OPTIONS 2&3)

Scale: N.T.S.2 EXIT SIGN MOUNTING - LAY-IN CEILING

Scale: 3/16" = 1'-0"3 NEW MCR RISER DIAGRAMS

1.

2.

3.

4.

5.

6.

DETAIL NOTES:

144 PORT FIBER OPTIC ANGLED PATCH PANEL WITH

COUPLERS.

HORIZONTAL WIRE MANAGMENT (1U).

TR CHANNEL RACK 30" DEEP.

6"W X 10"D VERTICAL WIRE MANAGEMENT WITH DOORS, IF

RACKS ARE GANGABLE THEN PROVIDE ONLY ONE VERTICAL

WIRE MANAGEMENT BETWEEN THEM.

RACK, WIRE MANAGEMENT, AND RACK MOUNTED

EQUIPMENT SHALL BE WHITE IN COLOR.

1.

2.

3.

4.

5.

6.

DETAIL NOTES:

144 PORT FIBER OPTIC ANGLED PATCH PANEL WITH

COUPLERS.

HORIZONTAL WIRE MANAGMENT (1U).

TR CHANNEL RACK 30" DEEP.

6"W X 10"D VERTICAL WIRE MANAGEMENT WITH DOORS, IF

RACKS ARE GANGABLE THEN PROVIDE ONLY ONE VERTICAL

WIRE MANAGEMENT BETWEEN THEM.

RACK, WIRE MANAGEMENT, AND RACK MOUNTED

EQUIPMENT SHALL BE WHITE IN COLOR.

Scale: No Scale5 FIBER OPTIC DISTRIBUTION CABINET MDA-1

Scale: No Scale6 FIBER OPTIC DISTRIBUTION CABINET MDA-2 Scale: N.T.S.4 POWER MECH RACK ELEVATION

200A 208/120V

PANELBOARD

'LDC'

200A 200A 200A 225A

30A30A

70kVA

208/120V INPUT

208/120V OUTPUT

UPS-A

(RELOCATED) 225A

225A 208/120V

3-PHASE 4-WIRE

LA

400A 208/120V

3-PHASE 4-WIRE

MDP-1

200A

CRAC-1

26 TON

225A 225A

CRAC-2

26 TON

CONDENSER

'ODU-2'

CONDENSER

'ODU-1'

BLDG 12

BASEMENT

225A

70kVA

208/120V INPUT

208/120V OUTPUT

UPS-B

(RELOCATED)

225A

225A 208/120V

3-PHASE 4-WIRE

LB

225A 225A

225A BUSWAY

ROW 1

225A BUSWAY

ROW 2

225A BUSWAY

ROW 3

225A BUSWAY

ROW 4

SPACE SPACE SPACE

SPACE SPACE SPACE

400A

ATS B166

3-PHASE

400A

800A 208/120V

EXISTING

PANELBOARD

'115-1X-2'

400A

800A 208/120V

EXISTING

PANELBOARD

'SES-12'

400A

BLDG 115

ROOM 100

200NG

225NG

225NG

400G

400G 400G

225NG

225NG

CIRCUIT BREAKER

GENERATOR

CONTACTOR

FUSED SWITCH

MOTOR

SURGE PROTECTION DEVICE

SYMBOL DESCRIPTION

METER

DIGITAL POWER METER

ELECTRONIC OVERLOAD

FUSE

GROUND

TRANSFER SWITCH

DPM

G

M

SPD

100A4G

SWITCH

TRANSFORMER

UTILITY LINE SERVICE DROP

ELECTRICAL PANEL

NOTE: PANEL SHOWN HERE IS MAIN LUGS

ONLY. MCB PANEL IS INDICATED BY

REPLACING MLO SYMBOL WITH CIRCUIT

BREAKER SYMBOL. ADDITIONAL PANEL

INFORMATION INDICATED BELOW SYMBOL.

WIRE TAG INDICATING FEEDER SIZE. SEE FEEDER

SCHEDULE.

Engineers Architects Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

NOT FOR

CONSTRUCTION

NOT FOR

CONSTRUCTION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

5/

/2

6:

:2

PM

C :\U se rs

\w re ed \D oc um en ts

\E _2

2-

VA

P re sc ot t-E H

R M

D C

_w re ed R

G 8R

E.

rv t

E-601

SINGLE LINE DIAGRAM

8 9CNJ

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

JAV

Scale: No Scale1 SINGLE LINE DIAGRAM

ELECTRICAL SYMBOL LEGEND

10. INDICATED FEEDERS ARE SIZED LARGER TO PREVENT EXCESSIVE VOLTAGE DROP. IF THE

INSTALLED CONDUIT TYPE AND CONDUCTOR TYPE ARE DIFFERENT THAN THE INDICATED

TYPES, RE-EVALUATE CONDUCTOR AND CONDUIT SIZE FOR VOLTAGE DROP AND RESIZE IF

REQUIRED. EVALUATE VOLTAGE DROP AT THE FARTHEST OUTLET OF POWER, HEATING AND

LIGHTING LOADS, OR COMBINATIONS OF SUCH LOADS. SIZE CONDUCTORS FOR FEEDERS TO

PREVENT A VOLTAGE DROP EXCEEDING 2 PERCENT. SIZE CONDUCTORS FOR BRANCH

CIRCUITS TO PREVENT A VOLTAGE DROP EXCEEDING 3 PERCENT. THE MAXIMUM TOTAL

VOLTAGE DROP ACROSS BOTH FEEDERS AND BRANCH CIRCUITS IN SERIES TO THE FARTHEST

OUTLET SHALL NOT EXCEED 5 PERCENT.

9. INDICATED FEEDERS SHALL USE COPPER CONDUCTORS.

8. INDICATED FEEDER CONDUCTORS ARE SIZED BASED ON THE NEUTRAL CONDUCTOR BEING

COUNTED AS A CURRENT CARRYING CONDUCTOR.

7. INDICATED FEEDERS SHALL HAVE RACEWAYS SIZED BASED ON SCHEDULE 40 PVC CONDUIT.

USE OF OTHER CONDUIT TYPES SHALL REQUIRE RESIZING OF CONDUIT.

6. INDICATED FEEDERS SHALL BE FOR SINGLE MOTOR BRANCH CIRCUITS. FEEDERS SERVING

MOTOR CIRCUITS EQUIPPED WITH ADJUSTABLE SPEED DRIVES SHALL BE PROVIDED WITH

STRANDED CONDUCTORS

5. EACH CONDUIT COMPRISING INDICATED FEEDERS SHALL HAVE A FULL SIZE EQUIPMENT

GROUND CONDUCTOR BASED ON THE TRIP RATING OF THE FEEDER OVERCURRENT

PROTECTIVE DEVICE. PROVIDE PROPERLY SIZED TERMINATIONS.

4. INDICATED FEEDERS SHALL HAVE AN EQUIPMENT GROUNDING CONDUCTOR AND AN ISOLATED

EQUIPMENT GROUNDING CONDUCTOR. PROVIDE PROPERLY SIZED TERMINATIONS..

3. DUE TO HARMONIC CURRENTS CARRIED BY THE NEUTRAL, THE NEUTRAL OF THE INDICATED

FEEDER SHALL CONSIST OF TWO CONDUCTORS IN EACH RACEWAY TERMINATED TO THE SAME

LUGS, AND HAS COMPOSITE AMPACITY THAT IS 200% OF THE AMPACITY OF THE INDIVIDUAL

PHASE CONDUCTORS. THE FEEDER SIZES ARE BASED ON 75 DEGREE CENTIGRADE

TEMPERATURE RATINGS FOR THE CONDUCTORS AND THE TERMINATIONS.

2. INDICATED FEEDERS SHALL HAVE AN EQUIPMENT BONDING JUMPER. PROVIDE PROPERLY

SIZED TERMINATIONS.

1. AMPACITIES USED IN THIS FEEDER SCHEDULE ARE BASED ON MAXIMUM 60 DEGREE

CENTIGRADE FOR WIRE AND TERMINATIONS FOR SIZES #14 TO #1, AND MAXIMUM 75 DEGREE

CENTIGRADE FOR WIRE AND TERMINATIONS FOR SIZES #1/0 AND LARGER. UNLESS NOTED

OTHERWISE, CONDUIT IS SIZED BASED ON TYPE EMT CONDUIT. USE OF OTHER CONDUIT

TYPES REQUIRES RESIZING OF CONDUIT.

REMARKS:

FEEDER SCHEDULE

TAG CONDUIT & CONDUCTORS REMARKS

200NG 3-3/0 AWG, 1-3/0 AWG NEU, 1-6 AWG EG, IN 2-1/2" C

225NG 3-4/0 AWG, 1-4/0 AWG NEU, 1-4 AWG EG, IN 2-1/2" C

400G 3-600 KCMIL, 1-1/0 AWG EG, IN 4" C

EQUIPMENT CONDUCTOR SCHEDULE

TAG DESCRIPTION VOLTS PHASE LOAD MOCP CONDUCTORS NEUTRAL GROUND CONDUIT DISCONNECT TYPE CRAC-1 AIR CONDITIONING UNIT 208V 3 42.9 kVA 200A 3 3/0 AWG 3/0 AWG 4 AWG 2" DISCONNECT SWITCH

CRAC-2 AIR CONDITIONING UNIT 208V 3 42.9 kVA 200A 3 3/0 AWG 3/0 AWG 4 AWG 2" DISCONNECT SWITCH

ODU-1 CONDENSER 208V 3 3.062 KVA 30A 3 10 AWG 10 AWG 10 AWG 3/4" DISCONNECT SWITCH

ODU-2 CONDENSER 208V 3 3.062 KVA 30A 3 10 AWG 10 AWG 10 AWG 3/4" DISCONNECT SWITCH

EF-1 EXHAUST FAN 120V 1 0.5 kVA 20A 1 12 AWG 12 AWG 12 AWG 3/4" MOTOR RATED SWITCH

EDH-1 SPLIT SYSTEM HEAT PUMP 208V 3 4.96 kVA 20A 3 12 AWG 12 AWG 12 AWG 3/4" MOTOR RATED SWITCH

FC-1 ELECTRICAL DUCT MOUNTED HEATER 208V 3 0.260 kVA 20A 1 12 AWG 12 AWG 12 AWG 3/4" MOTOR RATED SWITCH

HU-1 HEATER UNIT 120V 1 0.5 kVA 20A 1 12 AWG 12 AWG 12 AWG 3/4" MOTOR RATED SWITCH

CU-1 CONDENSING UNIT 208V 1 5.0 kVA 20A 1 12 AWG 12 AWG 12 AWG 3/4" 15A NF DISCONNECT SWITCH

Engineers Architects Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

NOT FOR

CONSTRUCTION

NOT FOR

CONSTRUCTION

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

5/

/2

6:

:2

PM

C :\U se rs

\w re ed \D oc um en ts

\E _2

2-

VA

P re sc ot t-E H

R M

D C

_w re ed R

G 8R

E.

rv t

E-602

ELECTRICAL SCHEDULES

9 9CNJ

EHRM INFRASTRUCTURE UPGRADE

- DATA CENTER

NORTHERN ARIZONA VA HEALTH CARE SYSTEM

500 NORTH HIGHWAY 89

PRESCOTT, ARIZONA 86313 AUGUST 31, 2023

100% BID DOCUMENTS

649-22-70122-117

JAV

2. (*) NUMBER INDICATES BREAKER TYPE: 1 = AFCI, 2 = CLASS A 5mA GFCI, 3 = 30mA GFPE, 4 = SHUNT TRIP ACTIVATED, 5 = PANELBOARD FEEDER SERVING UNIT SHALL BE LOCKABLE USING A PADLOCK, IN ACCORDANCE WITH OSHA LOCK-OUT-TAG RULES, 6 = LSI, 7 = LSIG.

1. ALL BREAKERS ARE STANDARD UNLESS OTHERWISE NOTED

NOTES:

LIGHTING (EXTERIOR) 0.28 kVA 125.00% 0.35 kVA LIGHTING (GENERAL) 0.95 kVA 125.00% 1.19 kVA TOTAL DEMAND CURRENT: 339 A SPEC 113.59 kVA 103.36% 117.40 kVA TOTAL CONNECTED CURRENT: 328 A RECEPTACLES (GENERAL) 3.06 kVA 100.00% 3.06 kVA TOTAL DEMAND: 122.12 kVA Power 0.80 kVA 100.00% 0.80 kVA TOTAL CONNECTED LOAD: 118.04 kVA Other 0.00 kVA 0.00% 0.00 kVA Load Classification Connected Load Demand Factor Demand Load PANEL TOTALS

TOTAL AMPS: 332 A 329 A 324 A

TOTAL CONNECTED LOAD: 39.76 kVA 39.38 kVA 38.89 kVA

7 LDC 400 A 20 A 3 17.85 kVA 17.43 kVA 16.94 kVA 6 CRAC UNIT 2 400 A 200 A 3 0.00 kVA 0.00 kVA 0.00 kVA 5 CRAC UNIT 1 400 A 200 A 3 14.29 kVA 14.29 kVA 14.29 kVA 4 UPS2 400 A 225 A 3 0.00 kVA 0.00 kVA 0.00 kVA 3 UPS1 400 A 225 A 3 7.81 kVA 7.81 kVA 7.81 kVA 2 ODU-2 400 A 30 A 3 0.00 kVA 0.00 kVA 0.00 kVA 1 ODU-1 400 A 30 A 3 1.02 kVA 1.02 kVA 1.02 kVA

ITEM NO. IDENTIFICATION BREAKER

FRAME

BREAKER

TRIP

TYPE

(*) POLE A B C REMARKS

MAIN: 400 A MCB BUSSING: SEE SPEC MCB 100% RATED (Y/N): N

RATED AMPERAGE: 400 A ISOLATED GROUND BUS (Y/N): N MCB SHUNT TRIP (Y/N): Y

PHASE / WIRE: 3Ø / 4W OPD INTERRUPTING RATING (SYM): MCB GROUND FAULT PROTECTION (Y/N): N

VOLTAGE: 208 SCC RATING (SYM): MOUNTING:

MDP-1

2. (*) NUMBER INDICATES BREAKER TYPE: 1 = AFCI, 2 = CLASS A 5mA GFCI, 3 = 30mA GFPE, 4 = SHUNT TRIP ACTIVATED, 5 = PANELBOARD FEEDER SERVING UNIT SHALL BE LOCKABLE USING A PADLOCK, IN ACCORDANCE WITH OSHA LOCK-OUT-TAG RULES, 6 = LSI, 7 = LSIG.

1. ALL BREAKERS ARE STANDARD UNLESS OTHERWISE NOTED

NOTES:

TOTAL DEMAND CURRENT: 97 A

TOTAL CONNECTED CURRENT: 97 A

TOTAL DEMAND: 34.98 kVA SPEC 34.98 kVA 100.00% 34.98 kVA TOTAL CONNECTED LOAD: 34.98 kVA Other 0.00 kVA 0.00% 0.00 kVA Load Classification Connected Load Demand Factor Demand Load PANEL TOTALS

TOTAL AMPS: 97 A 97 A 97 A

TOTAL CONNECTED LOAD: 11.66 kVA 11.66 kVA 11.66 kVA

2 BUSWAY 400 A 225 A 3 5.83 kVA 5.83 kVA 5.83 kVA 1 BUSWAY 400 A 225 A 3 5.83 kVA 5.83 kVA 5.83 kVA

ITEM NO. IDENTIFICATION BREAKER

FRAME

BREAKER

TRIP

TYPE

(*) POLE A B C REMARKS

MAIN: 225 A MCB BUSSING: SEE SPEC MCB 100% RATED (Y/N): N

RATED AMPERAGE: 225 A ISOLATED GROUND BUS (Y/N): N MCB SHUNT TRIP (Y/N): N

PHASE / WIRE: 3Ø / 4W OPD INTERRUPTING RATING (SYM): MCB GROUND FAULT PROTECTION (Y/N): N

VOLTAGE: 208Y/120 V SCC RATING (SYM): MOUNTING: SURFACE

LA

2. (*) NUMBER INDICATES BREAKER TYPE: 1 = AFCI, 2 = CLASS A 5mA GFCI, 3 = 30mA GFPE, 4 = SHUNT TRIP ACTIVATED, 5 = PANELBOARD FEEDER SERVING UNIT SHALL BE LOCKABLE USING A PADLOCK, IN ACCORDANCE WITH OSHA LOCK-OUT-TAG RULES, 6 = LSI, 7 = LSIG.

1. ALL BREAKERS ARE STANDARD UNLESS OTHERWISE NOTED

NOTES:

TOTAL DEMAND CURRENT: 97 A

TOTAL CONNECTED CURRENT: 97 A

TOTAL DEMAND: 34.98 kVA SPEC 34.98 kVA 100.00% 34.98 kVA TOTAL CONNECTED LOAD: 34.98 kVA Other 0.00 kVA 0.00% 0.00 kVA Load Classification Connected Load Demand Factor Demand Load PANEL TOTALS

TOTAL AMPS: 97 A 97 A 97 A

TOTAL CONNECTED LOAD: 11.66 kVA 11.66 kVA 11.66 kVA

2 BUSWAY 400 A 225 A 3 5.83 kVA 5.83 kVA 5.83 kVA 1 BUSWAY 400 A 225 A 3 5.83 kVA 5.83 kVA 5.83 kVA

ITEM NO. IDENTIFICATION BREAKER

FRAME

BREAKER

TRIP

TYPE

(*) POLE A B C REMARKS

MAIN: 225 A MCB BUSSING: SEE SPEC MCB 100% RATED (Y/N): N

RATED AMPERAGE: 225 A ISOLATED GROUND BUS (Y/N): N MCB SHUNT TRIP (Y/N): N

PHASE / WIRE: 3Ø / 4W OPD INTERRUPTING RATING (SYM): MCB GROUND FAULT PROTECTION (Y/N): N

VOLTAGE: 208Y/120 V SCC RATING (SYM): MOUNTING: SURFACE

LB

Notes:

LIGHTING (EXTERIOR) 0.28 kVA 125.00% 0.35 kVA LIGHTING (GENERAL) 0.95 kVA 125.00% 1.19 kVA Total Est. Demand: 146 A SPEC 48.05 kVA 100.00% 48.05 kVA Total Conn.: 145 A Power 0.80 kVA 100.00% 0.80 kVA Total Est. Demand: 52.47 kVA RECEPTACLES (GENERAL) 3.06 kVA 100.00% 3.06 kVA Total Conn. Load: 52.22 kVA Other 0.00 kVA 0.00% 0.00 kVA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 149 A 146 A 141 A Total Load: 17.85 kVA 17.43 kVA 16.94 kVA

41 42 39 40 37 38 35 36 33 34 31 32 29 30 27 28 25 26

23 4.80 0.80 1 20 A POWER FOR PACS DOOR CONTROL 24

21 4.80 0.60 1 20 A POWER FOR FACP 22

EDH-1 20 A 3

4.80 0.00 1 20 A EF-1 20

17 FUTURE 20 A 1 0.00 10.40 18

15 RECEPTACLES (GENERAL) 20 A 1 0.18 10.40

2 20 A IWH-104 WATER HEATER

13 RECEPTACLES (GENERAL) 20 A 1 0.36 12.00 1 20 A HU-1 14

11 RECEPTACLES (GENERAL) 20 A 1 0.72 0.24 1 20 A WT-1 12

9 RECEPTACLES (GENERAL) 20 A 1 1.08 0.72 1 20 A RECEPTACLES (GENERAL) 10

7 LIGHTING (GENERAL) 20 A 1 0.65 0.28 1 20 A LIGHTING (EXTERIOR) 8

5 LIGHTING (GENERAL) 20 A 1 0.31 0.00 6

3 0.00 0.00 4

FC-1 20 A 2

0.00 0.00

3 20 A CU-1

CKT Circuit Description Trip Poles A B C A B C

Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 200 A Mounting: SURFACE Wires: 4 Mains Rating: 200 A

Supply From: MDP-1 Phases: 3 Mains Type: MAIN CB Location: DATA CENTER 102 Volts: 120/208 A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: LDC

GENERAL NOTES:

A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL.

CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE FOR MISMATCHED OR INACCURATE PART NUMBERS.

B. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

C. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH THE LIGHT FIXTURE SHOP

DRAWINGS, FOR A COMPLETE REVIEW.

LUMINAIRE SCHEDULE

TYPE DESCRIPTION MOUNTING LAMP DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER

B 2' X 4' LENSED TROFFER; RECESSED

GRID

LED; 4800

LUMENS;

80 CRI;

3500K

0-10V DIMMABLE TO

5% DRIVER

120.00 V 50 W - -

C 4' LINEAR LED STRIPLIGHT WITH FROSTED

LENS

CHANNEL

AND ROD

MOUNTED

LED; 4,585

LUMENS;

80 CRI;

4000K

ELECTRONIC LED

DRIVER

120.00 V 34 W LITHONIA ZL1N L48 5000LM FST MVOLT 40K 80CRI

CE 4' LINEAR LED STRIPLIGHT WITH FROSTED

LENS WITH BATTERY BACKUP

CHANNEL

AND ROD

MOUNTED

LED; 4,585

LUMENS;

80 CRI;

4000K

ELECTRONIC LED

DRIVER

120.00 V 34 W LITHONIA ZL1N L48 5000LM FST MVOLT 40K 80CRI

D 6" DIAMETER DIMMABLE LED WIDE

DISTRIBUTION DOWNLIGHT

RECESSED

GRID

LED; 2000

LUMENS;

3500K; 80

CRI

0-10V DIMMABLE TO

10% LED DRIVER

120.00 V 20 W GOTHAM EVO6 35/20 AR MWD LD MVOLT GZ10

E1 CONTEMPORARY LED SINGLE FACED EXIT

SIGN WITH BLACK POWDER PAINT ALUMINUM

HOUSING, BRUSHED ALUMINUM FACE, RED

LETTERS, AND CHEVRON ARROWS AS

SHOWN ON PLANS. INCLUDES BATTERY

BACKUP.

UNIVERSAL LED RED --- 120.00 V 5 W LITHONIA LES 1 R 120/277 EL-N

LL5 4' LINEAR SURFACE MOUNTED EXTREME

ENVIRONMENT LED ELEVATOR PIT LIGHT;

WITH RIBBED FROSTED ACRYLIC LENS;

ENCLOSED AND GASKETED; WET LOCATION

SURFACE

WALL

LED; 4,250

LUMENS;

80 CRI;

4000K

ELECTRONIC LED

DRIVER

120.00 V 33 W COLUMBIA LIGHTING LXEM4-40LW-RFA-EU

W EXTERIOR WALL PACK; DARK BRONZE FINISH

CONTROLLED BY ASTRO TIMER CONTROL

SURFACE

WALL

LED; 3400

LUMENS;

80 CRI;

3500K

ELECTRONIC LED

DRIVER

120.00 V 40 W LITHONIA DSWX1-10C-1000-40K-T3S-MVOLT-E20WC

TECHNOLOGY SYMBOL LEGEND

DATA OUTLET - N-4 PR UTP

TELCO OUTLET - N-4 PR UTP

SYMBOL HEIGHT DESCRIPTION

18"

48"

ELECTRONIC LOCKING MECHANISM

DOOR CONTACT

REQUEST FOR EXIT SENSOR

CARD READER

(K - KEYPAD, DUAL AUTHENTICATION)48"CR

ES

DC

RX

48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)

WIRELESS ACCESS POINT - N-4 PR UTP

WALL PHONEW

IC INTERCOM WITH CAMERA

IC INTERCOM MASTER WITH PUSH TO RELEASE DOORM

N

TV OUTLET WALL MOUNTED

48"

54"

DESK

CCTV DOME CAMERA FIXED

CCTV DOME CAMERA PAN/TILT/ZOOM

FOUR POST OIT EQUIPMENT RACK

OIT EQUIPMENT CABINET

MATV EQUIPMENT CABINET

CCTV EQUIPMENT CABINET

MATV

CCTV

BASKET CABLE TRAY

N

N

FLOOR BOX FOR DATA

AS NOTED

DOOR

DOOR

ABOVE

DOOR

6' TO TOP

FLOOR

PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP

ELECTRONIC PANIC HARDWAREEP

DO DOOR OPERATOR

GROUND BUS

CEILING

DOOR

DOOR

FLOOR

FLOOR

FLOOR

ABOVE

CEILING

18"

4'x8'x3/4" FIRE RATED TTB8"

88" MOTION DETECTORMD

FLOOR TWO POST OIT EQUIPMENT RACK

CEILING MOUNTED SPEAKERSCEILING

WALL MOUNTED SPEAKERS96"

S

S

SECURE WIRELESS ACCESS POINT - N-4 PR UTP

N

CEILING

S

(N - QUANTITY)

(N - QUANTITY)

(N - QUANTITY)

(N - QUANTITY)

CEILING

CEILING

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

SEE DRAWINGS FOR MORE INFORMATION.

NOTE: NOT ALL SYMBOLS ARE USED.

CCTV MULTISENSOR DOME CAMERA CEILING

MS

TECHNOLOGY GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS,…