22-117 MECH ADD NO-1_Rev.pdf
PDF 928 KB Posted
- Solicitation number
- 36C77624B0008
About this file
This document appears to be a set of technical drawings and specifications for a mechanical system upgrade project at a Department of Veterans Affairs (VA) data center facility in Prescott, Arizona. The drawings provide details on the HVAC equipment, ductwork, controls, and other mechanical systems required for the data center infrastructure upgrade. Key details include:
The project involves upgrading the HVAC systems for a data center, including the installation of new computer room air conditioning (CRAC) units, ductwork, humidification equipment, and controls. The drawings specify the equipment sizes, airflows, electrical requirements, and control sequences. A hot aisle containment system is also called for to improve cooling efficiency. The project requires coordination with the campus building automation system and integration of the CRAC unit controls. Specific products and manufacturers are referenced as the basis of design. No pricing, award dates, or set-aside information is provided in these technical documents.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W
F
F
F
F
1.0 3.0 4.02.0
A
B
C
TOILET
VESTIBULE
STORAGE
DATA
CENTER
SERVICE
YARD
14ø RA
10ø RA
10ø SA
6ø SA
8ø EA
14ø SA
150RG-23
200SD-12
100EG-19
50SD-17
60x24 RA
ODU-2
CU-1
ODU-1
CRAC-1 CRAC-2
3FC-1
T
EDH-1
10ø SA
12ø RA
H
10ø RA
T
T
8ø SA
TYP-9
-RG-10
RL RS
RL
RS
RL
RS
RS
RL
RS
RL
250 CFM
350 CFM
14x14 RA
14x14 SA
RL
RS
CPLC CONTROLLER
HU-1
PB CONTROL CENTER
WT-1
AIR COMPRESSOR
AIR DRYER 1314
RETURN GRILLES 6" GAP
RETURN DUCT
SERVER
SERVER
HOT AISLE
CONTAINMENT
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:0
:4
P
M C
U s e rs \t b u d a i\ D o c u m e n ts
\F M
P
-1
V A
P re s c o tt -E
H R
M D
C tb u d a i.
rv t
MH101
FIRST FLOOR MECHANICAL PLAN AND
SECTION VIEW OF DUCT ABOVE
SERVER
2 5PRP
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
SPG
1 PROVIDE 1/2" WIRE MESH SCREEN AT OPEN
DUCT INLET/OUTLET.
2 8" DUCT UP THROUGH ROOF TO EF-1.
3 10" UP THROUGH ROOF TO ROOF INTAKE HOOD,
150CFM OFA. INSULATE PER SPECIFICATIONS.
4 FIRE ALARM CONTRACTOR TO COORDINATE
INTEGRATION OF CRAC UNIT CONTROL
(ON/OFF/OVERRIDE) INTO CLEAN AGENT
CONTROL PANEL.
5 THERMOSTATS GO IN RACK. HUMIDSTAT IS ON
THE WALL ONE THERMOSTAT PER RACK.
6 PROVIDE BACKDRAFT DAMPER. INSTALL TO
PREVENT AIR FROM FLOWING THROUGH THE
UNIT IN REVERSE WHEN THE UNIT IS OFF.
7 HUMIDIFIER WATER TREATMENT CABINET.
REFER TO HUMIDIFIER DIAGRAM FOR DETAILS.
8 MOUNT HUMIDIFIER DISPERSION UNIT BOTTOM
AT 12'-0"AFF. REFER TO HUMIDIFIER DIAGRAM
FOR PIPING ARRANGEMENT AND SIZING.
9 HUMIDIFIER CONTROL BOX.
10 INSTALL RETURN DUCT 6" ABOVE HOT AISLE
CONTAINMENT BOX (FROM SERVERS).
11 AIR COMPRESSOR, REFER TO HUMIDIFIER
SCHEDULE AND DIAGRAM FOR INFORMATION.
12 PROVIDE 3/4" UNDERCUT IN DOOR.
13 1" COMPRESSED AIR LINE FROM AIR
COMPRESSOR TO AIR FILTER. 3/4"
COMPRESSED AIR LINE FROM AIR FILTER TO
AIR DRYER.
14 3/4" COMPRESSED AIR LINE FROM AIR FILTER.
1/2" COMPRESSED AIR LINE TO PB CABINET.
15 1/2" COMPRESSED AIR LINE TO HU-1. 1/4"
CONTROL AIR LINE FROM PB CABINET TO HU-1.
Scale: 1/4" = 1'-0"
FIRST FLOOR MECHANICAL PLAN
NORTH
0 4 8 16
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L H
O L M
B E
R G
R O
A D
A. PROVIDE NEW CONNECTION TO THIS BUILDING
FROM MAIN CAMPUS ECC FOR CONTROLS
INTEGRATION. PROVIDE ALL NECESSARY
PANELS, CONDUIT, WIRE, FIBER,
ACCESSORIES, PROGRAMMING AND TRAINING
NECESSARY FOR A SEAMLESS CONNECTION TO
MAIN CAMPUS SYSTEM.
B. HOT AISLE CONTAINMENT (HAC) IS LOCATED
BETWEEN THE ROWS OF SERVERS AND IS A
PRODUCT PROVIDED BY THE SERVER
MANUFACTURER. HAC IS OPEN ENDED AT THE
TOP TO ALLOW SERVER HEAT TO BE DRAWN
INTO THE RETURN SYSTEM.
Scale: No Scale
SECTION VIEW OF DUCT ABOVE SERVER
N
AREA OF WORK
KEY PLAN - SITE
SCALE: NO SCALE
BLDG
157BLDG
BLDG
BLDG
BLDG
C O
L H
O L M
B E
R G
R O
A D
1 ADDENDUM #1 4/29/2024
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:5
P
M C
U s e rs \t b u d a i\ D o c u m e n ts
\F M
P
-1
V A
P re s c o tt -E
H R
M D
C tb u d a i.
rv t
M-601
MECHANICAL SCHEDULES
5 5PRP
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
SPG
AIR DEVICE SCHEDULE (RETURN)
MARK TYPE
AIR FLOW
MAX. APD MOUNTING
PANEL/FRAME
SIZE NECK SIZE MAX NC DAMPER FINISH MATERIAL REMARKSMIN. MAX.
RG-10 EGG CRATE 950 1900 0.06 in-wg CEILING 24x24 22x22 24 Yes WHITE STEEL
RG-23 EGG CRATE 170 250 0.09 in-wg CEILING 24x24 10"Ø 14 No WHITE STEEL
AIR DEVICE SCHEDULE (SUPPLY)
DIFFUSER
MARK TYPE
AIR FLOW
MAX. APD MOUNTING
PANEL/FRAME
SIZE NECK SIZE MAX NC DAMPER FINISH MATERIAL REMARKSMIN. MAX.
SD-12 LOUVERED FACE 101 200 0.08 in-wg CEILING 24x24 8"Ø 20 No WHITE STEEL
SD-17 LOUVERED FACE 40 100 0.08 in-wg CEILING 12x12 6"Ø 19 No WHITE STEEL
EF-1 ROOF TOILET TOILET... 100 [ 47 ] 0.35 [ 88 ] CENTRIFUGAL BACKWAR... II UPBLAST 10 [ 250 ] 75% BELT 1323 0.048 0.167 [ ] 1 120 1750 CONSTANT ---
CFM [L/s] IN [Pa] IN [mm] BHP HP [kW]
TYPE WHEEL CLASS
ARRANGEMENT, ROTATION,
AND DISCHARGE
DIAMETER MIN %
EFF
DRIVE
FAN MAX
RPM
NOMINAL POWER
PHASE VOLT RPM
SPEED
CONTROL
MARK LOCATION
AREA AND/OR
BLDG
SERVED
SYSTEM
AND/OR
SERVICE
AIR FLOW ESP
FAN MOTOR ELECTRICAL
CONTROL
SEQUENCE
REMARKS
FAN SCHEDULE
CRAC-2 DATA CENTER 15,750 26.0 80 149 200 208 3 ODU-2 MECHANICAL YARD SCROLL 21.2 25 208 3 1,2,3,4,5,6,7,8
CRAC-1 DATA CENTER 15,750 26.0 80 149 200 208 3 ODU-1 MECHANICAL YARD SCROLL 21.2 25 208 3 1,2,3,4,5,6,7,8
MARK NO. LOCATION AIRFLOW (CFM) NORMAL CAPACITY (TONS) ENTERING AIR TEMPERATURE (DEGREES F) MCA MOCP VOLTS PHASE MARK NO. LOCATION COMPRESSOR TYPE MCA MOCP VOLTS PHASE
INDOOR UNIT ELECTRICAL OUTDOOR UNIT ELECTRICAL
REMARKS
COMPUTER ROOM AIR CONDITIONING
FC-1 STORAGE SUPPORT DX 600 [ 280 ] 150 [ 71 ] 0.7 [ 180 ] 18 [ 61 ] 14.8 [ 4 ] 16.7 83 [ 28 ] 63 [ 17 ] [ 95 ] [ 35 ] [ 20 ] [ 6 ] 65 [ 18 ] 85 [ 29 ] [ 17 ] [ -8 ] 1.6 1 208/230 16.5 20 208/230 5 3 208 1
CFM [L/s] CFM [L/s] IN [Pa] MBH [kW] MBH [kW] °F [°C] °F [°C] °F [°C] MBH KW °F [°C] °F [°C] °F [°C] Kw PHASE VOLT REMARKS
Db Wb
MIN TOTAL
CAPACITY
MIN SENS
CAPACITY MIN
SEER
EAT OSA DESIGN
TEMP COMP Kw
MIN. HEAT
CAPACITY
EAT DB LAT Db
OSA DESIGN
TEMP INDOOR
UNIT MCA
INDOOR
UNIT
PHASE
INDOOR
UNIT VOLT
OUTDOOR
UNIT MCA
OUTDOOR
UNIT
PHASE
OUTDOOR
UNIT VOLT
MARK LOCATION
AREA AND/OR
BLDG SERVED
TYPE
TOTAL SUPPLY AIR
FLOW
MIN. OUTSIDE AIR
FLOW
EXT STATIC
PRESSURE
COOLING CAPACITY HEATING CAPACITY
AIR FILTER
MARK NO
SUPPLEMENTAL HEAT REMARKS
SPLIT SYSTEM HEAT PUMP SCHEDULE
NOTE
1. ALL SELECTIONS ARE BASED ON AN ALTITUDE OF 5050 FEET ASL.
2. PROVIDE BACKDRAFT DAMPER.
GI-1 ROOF FC-1 INTAKE DUCTED 12.5 [ 317.5 ] 150 [ 71 ] 0.003 [ 1 ] BACKDRAFT ----
IN [mm] CFM [L/s] IN [Pa]
MARK LOCATION
SYSTEM
AND/OR...
TYPE APPLICATION
THROAT SIZE AIR FLOW APD
DAMPER TYPE REMARKS
INTAKE/EXHAUST HOOD SCHEDULE
REMARKS:
1. IN ROW DUCT HEATER, REFER TO EDH-1 SCHEDULE.
NOTES:
1. BASIS OF DESIGN IS STULTZ CFD, SCS.
2. PROVIDE EMERGENCY POWER OFF SWITCH.
3. PROVIDE DISCONNECT.
4. R-410A.
5. PROVIDE HOT GAS REHEAT.
6. DOWNFLOW CONFIGURATION.
7. PROVIDE DOWNFLOW UNIT STAND.
AIR DEVICE SCHEDULE (EXHAUST)
DIFFUSER
MARK LOCATION TYPE
AIRFLOW
MAX. APD MOUNTING
PANEL/FRAME
SIZE NECK SIZE MAX NC DAMPER FINISH MATERIAL REMARKSMIN. MAX.
EG-19 EGG CRATE 110 170 0.09 in-wg CEILING 12x12 8"Ø 13 No WHITE STEEL
EDH-1 STORAGE FC-1 OPEN COIL, HELICAL RESISTANCE ELEMENTS 600 [ 280 ] 17 [ -8 ] 0.15 [ 38 ] 14 [ 350 ] 10 [ 250 ] 17065 [ 5000 ] 3 208 13.879 SCR ----
CFM [L/s] °F [°C] IN WG [Pa] IN [mm] IN [mm] BTUH [W] PHASE VOLT AMPS
LENGTH WIDTHMARK LOCATION
SYSTEM
AND/OR
SERVICE
TYPE
AIR FLOW EAT APD
DUCT SIZE
CAPACITY POWER CONTROL
TYPE
REMARKS
ELECTRIC DUCT MOUNTED HEATER SCHEDULE
NOTES:
1. BASIS OF DESIGN IS SMARTFOG ES100-2.
2. PROVIDE WALL MOUNTED UL LISTED SMARTFOG CPLC1 CONTROL BOX
WITH BACNet MS/TP BMS CONTROLLER CARD COMMUNICATION TO
CAMPUS CONTROL SYSTEM. COORDINATE WITH CAMPUS
CONTROLS CONTRACTOR TO PROVIDE A FULLY SEAMLESS AND
FUNCTIONAL INTEGRATION. PROVIDE 120/1 POWER, 2.5A
DEDICATED CIRCUIT.
3. PROVIDE NEW AIR COMPRESSOR, OIL LESS, ENCLOSED, SCROLL, 5.0 CFM
@ 110 PSI, 208/3/60, 3 HP, 9.0A (FLA). BASIS OF DESIGN - POWEREX SES0308.
4. PROVIDE ONE (1) HUMIDISTAT. S2E SENSOR, "E" SERIES. REFER TO FLOOR PLANS.
5. PROVIDE CONDUCTIVITY PROBE.
6. PROVIDE WATER TREATMENT SYSTEM, WT-1. (CONTRACTOR TO
TEST WATER QUALITY AND DETERMINE APPROPRIATE WATER
TREATMENT). BASIS OF DESIGN - ZEROTDS ZTDS300 "A" SERIES.
PROVIDE 120V/1 POWER, 4.0A DEDICATED CIRCUIT.
7. PROVIDE SHUT-OFF VALVE AND STRAINER PRIOR TO CONNECTION
FROM WATER TREATMENT SUPPLY PIPING.
8. PROVIDE AIR FILTER, AF-900.
9. ACCESSORIES FOR AIR COMPRESSOR:
PROVIDE AIR DRYER (POWEREX ABAC COOL25) - 120/1/60 (1/4 HP), INTAKE AIR FILTER, NYLON TUBING KIT.
1 ADDENDUM #1 4/29/2024
HU-1 DATA CENTER 3 1,2,3,4,5,6,7,8,9
MARK NO. LOCATION
CAPACITY
GAL/HR
NOTES
HUMIDIFIER SCHEDULE
SUPPORT
STRAPS OR
WIRES, TYP.
DRAIN PAN
NOTES:
1. DRAIN PAN TO BE GALVANIZED SHEETMETAL WITH WATER-TIGHT JOINTS.
2. LOCATE 4 TO 8 INCHES (10 TO 20 CM) BELOW PIPE OR EQUIPMENT THAT IS SUBJECT TO LEAK.
3. SUPPORT PAN WITH 1" (2.5 CM) WIDE STRAPS OR WIRES ATTACHED TO STRUCTURE.
4. WIDTH AND LENGTH SHALL BE A MINIMUM OF 2 INCHES (5 CM) LONGER THAN THE PIPE OR EQUIPMENT SIZE.
5. WATER DETECTOR SHALL ALARM TO THE BUILDING AUTOMATION SYSTEM (BAS). BAS SHALL SHOW ROOM LOCATION
WITH ALARM.
VARIESVARIES
WATER DETECTOR CONTROLLER
WATER DETECTOR SENSOR
MAIN SUPPLY
DUCT
PROVIDE VOLUME
DAMPER
PROVIDE VOLUME DAMPER
ON BRANCHES (TYP)
1/4 W OR
4" MIN.
SUPPLY REGISTER OR
BRANCH DUCT
MAIN
SUPPLY
DUCT
SEE FLOOR PLAN FOR
SPLIT DIMENSION
TURNING VANES
AIR FLOW
AIR FLOW
A
IR
F L O
W
AIR SPLIT DUCT TAKE-
OFF PLAN VIEW
BRANCH DUCT TAKE-OFF
PLAN VIEW
AIR FLOW
A
IR
F
LO
W
W
MAIN SUPPLY
DUCT
CONICAL TAP
TERMINAL UNIT DUCT TAKE-
OFF PLAN VIEW
AIR FLOW
A
IR
F
LO
W
W
NOTE:
TABULATED DATA FROM SMACNA ALLOWS FOR DUCT REINFORCING AND INSULATION, BUT NOT EXTERNAL LOAD.
ANY ADDITIONAL COMPONENTS SUPPORTED FROM DUCT HANGER ARE TO BE REVIEWED AND APPROVED BY STRUCTURAL
ENGINEER
MAXIMUM
HALF OF DUCT
PERIMETER
PAIR AT 10 FT SPACING
P/2 = 30"
RECTANGULAR DUCT HANGERS MINIMUM SIZE
1" MIN
SCREWS
SCREWS MAY BE
OMITTED IF HANGER
LOOPS
60" MAX
STRAP HANGERS
HANGER
STRAPS UNLESS FOOT OF
STRAP IS PLACED
UNDER A BOTTOM
REINFORCEMENT
TRAPEZE HANGERS
STRAP OR ANGLE
ROD
NUTS
ALTERNATE LOCATION
(VERIFY UPPER TRAPEZE
LOAD CAPACITY)
ANGLES
ROD
P/2 = 72"
P/2 = 96"
P/2 = 120"
P/2 = 168"
P/2 = 192"
P/2 = 193" UP
STRAP WIRE/ROD
1" x 22 GA.
1" x 18 GA.
1" x 16 GA.
1-1/2" x 16 GA.
1-1/2" x 16 GA.
NOT GIVEN
10 GA. (.135")
3/8"
3/8"
1/2"
1/2"
1/2"
PAIR AT 8 FT SPACING
STRAP WIRE/ROD
1" x 22 GA.
1" x 18 GA.
1" x 16 GA.
1-1/2" x 16 GA.
1-1/2" x 16 GA.
10 GA. (.135")
3/8"
3/8"
1/2"
1/2"
1/4"
PAIR AT 5 FT SPACING
STRAP WIRE/ROD
1" x 22 GA.
12 GA. (.106")
3/8"
3/8"
PAIR AT 4 FT SPACING
STRAP WIRE/ROD
1" x 22 GA. 10 GA. (.135")
1" x 20 GA.
1" x 18 GA.
1" x 16 GA.
1" x 16 GA.
1" x 20 GA.
1" x 22 GA.
3/8"
3/8"
1/4"
3/8"
3/8"
1/4"
1/4"
1/4"
1" x 22 GA.
1" x 18 GA.
1" x 16 GA.
1" x 20 GA.
1" x 22 GA.
SPECIAL ANALYSIS REQUIRED
H
BMS
CRAC-1
T
BMS
BMS
BMS
CRAC-2
HUMIDISTATS ON WALL
HUMIDIFIER
CONTROLLER
VIGILENT
CONTROL
OPTIMIZING
SYSTEM
VIGILENT
CONTROL
OPTIMIZING
SYSTEM
IN RACKS, (TYP)
VIGILENT
CONTROL
OPTIMIZING
SYSTEM
VIGILENT
CONTROL
OPTIMIZING
SYSTEM
CPLC
CONTROLLER
3 WIRE, 18 GA.
PB
CONTROL
CENTER
1/2" WATER LINE
4-10 WIRE, 18 GA. SHIELDED
(DEPENDS ON QTY. OF ZONES
RH
SENSOR
WATER
SOURCE
WATER
FILTER
1/2" WATER LINE1/2" WATER LINE
AIR FILTER
1/2" WATER LINE
1/4" AIR CONTROL LINE
1/2" COMPRESSED
AIR LINE
HU-1
NOTES: REFER TO MANUFACTURER
INSTALLATION REQUIREMENTS FOR DETAIL.
1/2" COMPRESSED
AIR LINE
AIR
COMPRESSOR
1" COMPRESSED
AIR LINE
1/4" DRAIN 1/2" DRAIN 1/2" DRAIN
3/4"
COMPRESSED
AIR LINE
AIR
DRYER
3/4" CONDENSATE
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:5
P
M C
U s e rs \t b u d a i\ D o c u m e n ts
\F M
P
-1
V A
P re s c o tt -E
H R
M D
C tb u d a i.
rv t
M-501
MECHANICAL DETAILS
4 5PRP
EHRM INFRASTRUCTURE UPGRADE
- DATA CENTER
NORTHERN ARIZONA VA HEALTH CARE SYSTEM
500 NORTH HIGHWAY 89
PRESCOTT, ARIZONA 86313 AUGUST 31, 2023
100% BID DOCUMENTS
649-22-70122-117
SPG
Scale: No Scale
PIPE SUPPORT DETAIL
Scale: No Scale
EXTERIOR WALL PIPE PENETRATION DETAIL
Scale: No Scale
CONDENSING UNIT DETAIL
Scale: No Scale
DRAIN PAN DETAIL
Scale: No Scale
DUCT BRANCH TAKE-OFFS
Scale: No Scale
RECTANGULAR DUCT HANGERS MINIMUM SIZE
Scale: No Scale
CONDENSING UNIT INSTALLATION DETAIL
Scale: No Scale
MECHANICAL CONTROLS DIAGRAM
1 ADDENDUM #1 4/29/2024
CONTROLS DESCRIPTION
CRAC UNIT TO PROVIDE MAXIMUM OF 60 DEGF SUPPLY AIR AND ADJUST TO MAINTAIN SPACE SETPOINT OF 72 DEGF TO 80.6 DEGF AT THE SERVER RACK INLET.
SENSORS ARE TO BE PROVIDED IN EVERY THIRD OR FOURTH RACK AT TWO LOCATIONS - ONE AT 2' AFF AND ONE AT 5' AFF.
SENSORS MANUFACTURED BY VIGILENT OR THIRD PARTY PROVIDED SENSORS MEET VIGILENT SPEC FOR PERFORMANCE, COMMUNCATIONS, AND INTEGRATION WITH VIGILENT SYSTEM.
BMS IS TO MONITOR THE CRAC UNIT PERFORMANCE AND DATA CENTER ENVIRONMENTAL CONDITIONS ONLY. ACTUAL CONTROL TO BE COMMANDED BY VIGILENT SYSTEM. ENSURE COMPATIBILITY OF VIGILENT SYSTEM OUTPUT TO BMS.
RH TO MAINTAIN 40% (ADJ).
HUMIDIFIER TO PROVIDE HUMIDIFICATION TO MAINTAIN SPACE SETPOINT AND IS TO MODULATE IN REAL TIME TO PREVENT UNDER AND OVER SHOOTING OF
SETPOINT. HUMIDIFIER TO HAVE STAND ALONE CONTROLLERS AND PROGRAMMING WITH OUTPUT TO VIGILENT SYSTEM FOR CONTROL AND TO BMS FOR MONITORING OF OPERATION AND ALARMS ONLY.
EACH CRAC UNIT WILL HAVE A BACKDRAFT DAMPER TO PREVENT BACKWARD FLOW OF AIR.
SEQUENCE OF OPERATIONS
SENSORS TO PROVIDE STATUS FOR THE FOLLOWING:
RACK INLET TEMPERATURES
DATA CENTER SPACE TEMPERATURE
CRAC UNIT DISCHARGE TEMPERATURE
CRAC UNIT RETURN TEMPERATURE
CRAC UNIT POWER DRAW
VIGILENT SYSTEM TO COMMAND CRAC UNIT ON AND OFF BASED ON THE TEMPERATURE FEEDBACK IN THE SPACE. SYSTEM TO ALSO MODULATE FAN SPEEDS AND ANY OTHER VARIABLE COMPONENTS FOR UNIT EFFICIENCY AND
PERFORMANCE. SYSTEM TO DETERMINE OPTIMAL USE OF EACH CRAC UNIT AT PARTIAL LOAD TO MEET DEMAND AND ACHIEVE EFFICIENCIES. CRAC UNIT SIZING AND QUANTITIES WERE DETERMINED BY SPACE LOAD REQUIRING ONE (1) CRAC UNIT. SYSTEM TO ALSO MONITOR AND TRACK RUN TIMES FOR UNITS AND TO ROTATE UNIT OPERATION TO PROVIDE EQUAL RUN TIMES TO THE EXTENT POSSIBLE.
PROVIDE ALL NECESSARY HARDWARE, SOFTWARE, ACCESSORIES, COMPONENTS, PROGRAMMING, ETC., REQUIRED FOR A FULLY FUNCTIONING CONTROL SYSTEM. SYSTEM DESCRIBED HEREIN IS THE VIGILENT DYNAMIC OPTIMIZED COOLING.
CRAC UNIT INTERNAL CONTROLS TO OPERATE CRAC COMPONENTS TO ACHIEVE SUPPLY DISCHARGE TEMPERATURE NEEDED IN RESPONSE TO SPACE CONDITIONS INCLUDING DATA CENTER TEMPERATURE AND RACK INLET TEMPERATURES.
Scale: No Scale
HUMIDIFIER DIAGRAM
| Sheets |
| MH101 - FIRST FLOOR MECHANICAL PLAN AND SECTION VIEW OF DUCT ABOVE SERVER |
| M-501 - MECHANICAL DETAILS |
| M-601 - MECHANICAL SCHEDULES |