This is a solicitation for construction services to build a new Adult Day Health and Extended Care Support Building adjacent to Building 116 at the St. Cloud VA Medical Center. The project involves general construction and alterations to construct the new building, along with associated site work including walks, grading, drainage, and necessary removal of existing structures. The work also requires electrical and mechanical construction services. The solicitation is issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The response due date and award date are not provided.
View the file
Other files
Show 40 more
Latest 50 of 74 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
St. Cloud VAMC
St. Cloud, MN Adult Day Health Care Extended Care Support
VA263—15—C—0137
DOOR HARDWARE
08 71 00-1
SECTION 08 71 00
PART 1 - GENERAL
1.1 DESCRIPTION
A. Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
A. Caulking: Section 07 92 00 JOINT SEALANTS.
B. Application of Hardware: Section 08 14 00, WOOD DOORS, Section 08 11
13, HOLLOW METAL DOORS AND FRAMES,
C. Finishes: Section 09 06 00, SCHEDULE FOR FINISHES.
D. Painting: Section 09 91 00, PAINTING.
E. Card Readers: Section 28 13 00, PHYSICAL ACCESS CONTROL SYSTEMS.
F. Electrical: Division 26, ELECTRICAL.
G. Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.
1.3 GENERAL
A. All hardware shall comply with UFAS, (Uniform Federal Accessible
Standards) unless specified otherwise.
B. Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).
C. Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.
D. Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.
E. The following items shall be of the same manufacturer, except as otherwise specified:
1. Mortise locksets.
2. Hinges for hollow metal and wood doors.
3. Surface applied overhead door closers.
4. Exit devices.
08 71 00-2
SP.C1o+dVAMC
SP.C1o+d,MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
5. Floor closers.
1.4 WARRANTY
A. Automatic door operators shall be subject to the terms of FAR Clause
52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:
1. Locks, latchsets, and panic hardware: 5 years.
2. Door closers and continuous hinges: 10 years.
1.5 MAINTENANCE MANUALS
A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. Submit 6 copies of the schedule per Section
01 33 23. Submit 2 final copies of the final approved schedules to VAMC
Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).
B. Hardware Schedule: Prepare and submit hardware schedule in the following form:
Hardware Quantity Size Reference Finish Mfr. Key UL Mark ANSI/BHMA
Item Publication Name Control (if Finish
Type No. and
Catalog No.
Symbols fire rated and
Designation listed)
C. Samples and Manufacturers' Literature:
1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers
Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.
2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.
08 71 00-3
St. Cloud VAMC
St. Cloud, MN
D. Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.
1.7 DELIVERY AND MARKING
A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to
COR for reference purposes. Tag shall identify items by Project
Specification number and manufacturer's catalog number. These items shall remain on file in COR’S office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 PREINSTALLATION MEETING
A. Convene a pre-installation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and
Installer, Architect, Project Engineer and VA Locksmith, Hardware
Consultant, and Hardware Manufacturer’s Representative. Review the following:
1. Inspection of door hardware.
2. Job and surface readiness.
3. Coordination with other work.
4. Protection of hardware surfaces.
5. Substrate surface protection.
6. Installation.
7. Adjusting.
8. Repair.
9. Field quality control.
10. Cleaning.
1.9 INSTRUCTIONS
A. Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware
08 71 00-4
St. Cloud VAMC
St. Cloud, MN requirements for each door are indicated on drawings by symbols.
Symbols for hardware sets consist of letters (e.g., "HW“) followed by a number. Each number designates a set of hardware items applicable to a door type.
1.10 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.
B. American Society for Testing and Materials (ASTM):
F883-04.................Padlocks
E2180-07................Standard Test Method for Determining the
Activity of Incorporated Antimicrobial Agent(s)
In Polymeric or Hydrophobic Materials
C. American National Standards Institute/Builders Hardware Manufacturers
Association (ANSI/BHMA) :
Al56.1-06...............Butts and Hinges
Al56.2-03...............Bored and Pre-assembled Locks and Latches
Al56.3-08...............Exit Devices, Coordinators, and Auto Flush
Bolts
A156.4-08...............Door Controls (Closers)
A156.5-14...............Cylinders and Input Devices for Locks.
A156.6-05...............Architectural Door Trim
A156.8-05...............Door Controls-Overhead Stops and Holders
A156.11-14..............Cabinet Locks
A156.12-05 .............Interconnected Locks and Latches
A156.13-05..............Mortise Locks and Latches Series 1000
A156.14-07 .............Sliding and Folding Door Hardware
A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical
A156.16-08..............Auxiliary Hardware
A156.17-04 .............Self-Closing Hinges and Pivots
A156.18-06..............Materials and Finishes
A156.20-06 .............Strap and Tee Hinges, and Hasps
A156.21-09..............Thresholds
A156.22-05..............Door Gasketing and Edge Seal Systems
08 71 00-5
St. Cloud VAMC
St. Cloud, MN
A156.23-04..............Electromagnetic Locks
A156.24-03..............Delayed Egress Locking Systems
A156.25-07 .............Electrified Locking Devices
A156.26-06..............Continuous Hinges
A156.28-07 .............Master Keying Systems
A156.29-07 .............Exit Locks and Alarms
Al56.30-03 .............High Security Cylinders
Al56.31-07 .............Electric Strikes and Frame Mounted Actuators
A156.36-10..............Auxiliary Locks
A250.8-03...............Standard Steel Doors and Frames
D. National Fire Protection Association (NFPA):
80-10...................Fire Doors and Other Opening Protectives
101-09..................Life Safety Code
E. Underwriters Laboratories, Inc. (UL):
Building Materials Directory (2008)
PART 2 - PRODUCTS
2.1 BUTT HINGES
A. ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:
1. Exterior Doors: Type A2112/A5112 for doors (3 feet) wide or less and
Type A2111/A5111 for doors over (3 feet) wide. Hinges for exterior outswing doors shall have non-removable pins. Hinges for exterior fire-rated doors shall be of stainless-steel material.
2. Interior Doors: Type A8112/A5112 for doors (3 feet) wide or less and
Type A8111/A5111 for doors over (3 feet) wide. Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless-steel material.
B. Provide quantity and size of hinges per door leaf as follows:
1. Doors up to (4 feet) high: 2 hinges.
2. Doors (4 feet) to (7 feet 5 inches) high: 3 hinges minimum.
3. Doors greater than (7 feet 5 inches) high: 4 hinges.
4. Doors up to (3 feet) wide, standard weight: (4-1/2 inches x 4-1/2 inches) hinges.
08 71 00-6
St. Cloud VAMC
St. Cloud, MN
5. Doors over (3 feet) to (3 feet 6 inches) wide, standard weight: (5 inches x 4-1/2 inches).
6. Doors over (3 feet 6 inches) to (4 feet), heavy weight: (5 inches x
4-1/2 inches).
7. Provide heavy-weight hinges where specified.
8. At doors weighing (150 lbs.) or more, furnish (5 inch) high hinges.
C. See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS“ for pivots and hinges other than butts specified above and continuous hinges specified below.
2.2 CONTINUOUS HINGES
A. ANSI/BHMA A156.26, Grade 1-600.
1. Listed under Category N in BHMA's "Certified Product Directory."
B. General: Minimum 0.120-inch- thick, hinge leaves with minimum overall width of 4 inches; fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete
C. Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a
Teflon-coated (0.25-inch) minimum diameter pin that extends entire length of hinge.
1. Base Metal for Exterior Hinges: Stainless steel.
2. Base Metal for Interior Hinges: Stainless steel.
3. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.
4. Provide with non-removable pin (hospital tip option) at lockable outswing doors.
5. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.
6. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.
7. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.
8. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.
08 71 00-7
St. Cloud VAMC
St. Cloud, MN
2.3 DOOR CLOSING DEVICES
A. Closing devices shall be products of one manufacturer.
2.4 OVERHEAD CLOSERS
A. Conform to ANSI A156.4, Grade 1.
B. Closers shall conform to the following:
1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.
2. Where specified, closer shall have hold-open feature.
3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.
4. Material of closer body shall be forged or cast.
5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.
6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless-steel material.
7. Closers shall have full size metal cover; plastic covers will not be accepted.
8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.
9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.
10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.
11 . Provide parallel arm closers with heavy duty rigid arm.
08 71 00-8
St. Cloud VAMC
St. Cloud, MN
12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.
13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
14. All closers shall have a 1 H” minimum piston diameter.
2.5 DOOR STOPS
A. Conform to ANSI A156.16.
B. Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use lead expansion shields for mounting door stops.
C. Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.
D. Provide floor stops (Type L02141 or L02161 in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.
E. Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.
F. Provide stop Type L020ll, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in (3-inch) core-drilled hole and filled with quick-setting cement.
G. Omit stops where floor mounted door holders are required and where automatic operated doors occur.
H. Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.
I. Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.
J. Provide overhead surface applied stop Type C02541, ANSI Al56.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.
08 71 00-9
St. Cloud VAMC
St. Cloud, MN Adult Day Health Care Extended Care Support
VA263—15—C—0137
K. Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.
L. Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).
2.6 LOCKS AND LATCHES
A. Conform to ANSI A156.2. Locks and latches for doors (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have not less than seven pins. Cylinders for all locksets shall be removable core type. Cylinders shall be furnished with construction removable cores and construction master keys. Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, and any other type lock included in the Great Grand Master Key
System. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.
B. In addition to above requirements, locks and latches shall comply with following requirements:
1. Lock and Latch Sets: levers shall meet ADA (Americans with
Disabilities Act) requirements. All locks and latchsets shall be furnished with (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with (7/8-inch) lip-to-center dimension. Provide lever design to match design selected by Architect or to match existing lever design. Where two turn pieces are specified for lock F76, turn piece on inside knob shall lock and unlock inside knob, and turn piece on outside knob shall unlock outside knob when inside knob is in the locked position. (This function is intended to allow emergency entry into these rooms without an emergency key or any special tool.)
2. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.
08 71 00-10
St. Cloud VAMC
St. Cloud, MN
3. Privacy locks in non-mental-health patient rooms shall have an inside thumbturn for privacy and an outside thumbturn for emergency entrance. Single occupancy patient privacy doors shall typically swing out; where such doors cannot swing out, provide center-pivoted doors with rescue hardware (see HW-2B).
2.11 ELECTRIC STRIKES
A. ANSI/ BHMA A156.31 Grade 1.
B. General: Use fail-secure electric strikes at fire-rated doors and for
’Panic-Activated’ doors indicated.
2.12 KEYS
A. Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:
Locks/Keys
Cylinder locks
Cylinder lock change key blanks
Master—keyed sets
Grand Master sets
Great Grand Master set
Control key
Quantity
2 keys each
100 each different key way
6 keys each
6 keys each
5 keys
2 keys
2.13 KEY CABINET
A. ANSI Standard Al56.11. Provide key cabinet made of cold rolled, (0.0478 inch) thick furniture steel electro—welded. Doors shall have "no sag" continuous brass-pin piano type hinge and be equipped with chrome plated locking door handles, hook cam and mechanical pushbutton door lock. Key Cabinet and Key Control System shall accommodate all keys for this project plus 25 percent. Provide minimum number of multiple cabinets where a single cabinet of largest size will not accommodate the required number of keys.
B. Key tags shall consist of two sets: Permanent self-locking and loan key snaphook type with tag colors as follows: Red fiber marker of the permanent self-locking type approximately (1-1/4 inch) in diameter engraved with the legend "FILE KEY MUST NOT BE LOANED.“ Also furnish for each hook a white cloverleaf key marker with snap-hooks engraved with the legend "LOAN KEY."
08 71 00-11
St. Cloud VAMC
St. Cloud, MN
C. The manufacturer of the lock cylinders and locks shall attach a key tag to keys of each lock cylinder and shall mark thereon the respective item number and key change number. Provide each group of keys in a key gathering envelope (supplied by Key Cabinet Manufacturer) in which the lock manufacturer shall include the following information: Item number, key change number and door number. The contractor shall furnish the Key
Cabinet Manufacturer the hardware and keying schedules and change keys.
D. The Key Cabinet Manufacturer shall set up a three-way cross index system, including master keys, listing the keys alphabetically, the hooks numerically and the key changes numerically on different colored index cards. Index cards shall be typewritten and inserted in a durable binder. Attach the keys to the two sets of numbered tags supplied with the cabinet. (The permanent tag and the loan key tag). Instruct the owner in proper use of the system. Install cabinet as directed by the
COR.
2.14 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
A. Conform to ANSI Standard A156.6.
B. Provide protective plates and door edging as specified below:
1. Kick plates, mop plates and armor plates of metal, Type Jl00 series.
2. Provide kick plates and mop plates where specified. Kick plates shall be (10 inches) or (12 inches) high. Mop plates shall be (6 inches) high. Both kick and mop plates shall be minimum (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges
(B4E). On push side of doors where jamb stop extends to floor, make kick plates (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates (1 inch) less than width of each door. Extend all other kick and mop plates to within (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.
3. Kick plates and/or mop plates are not required on following door sides:
a. Armor plate side of doors;
b. Exterior side of exterior doors:
c. Closet side of closet doors;
d. Both sides of aluminum entrance doors.
08 71 00-12
St. Cloud VAMC
St. Cloud, MN
4. Armor plates for doors are listed under Article "Hardware Sets".
Armor plates shall be thickness as noted in the hardware set, (35 inches) high and (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all 4 edges
(B4E). Plates on pairs of metal doors shall be (1 inch) less than width of each door. Where top of intermediate rail of door is less than (35 inches) from door bottom, extend armor plates to within
(1/2 inch) of top of intermediate rail. On doors equipped with panic devices, extend armor plates to within (1/2 inch) of panic bolt push bar.
5. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be (10 inches) high.
6. Provide stainless steel edge guards where so specified at wood doors. Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.
2.15 EXIT DEVICES
A. Conform to ANSI Standard A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building. Trim shall have cast satin stainless steel lever handles of design similar to locksets, unless otherwise specified. Provide key cylinders for keyed operating trim and, where specified, cylinder dogging.
B. Surface vertical rod panics shall only be provided less bottom rod;
provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors.
C. Concealed vertical rod panics shall be provided less bottom rod at interior doors, unless lockable or otherwise specified; provide fire pins as required by exit device and door fire labels. Where concealed
08 71 00-13
St. Cloud VAMC
St. Cloud, MN vertical rod panics are specified at exterior doors, provide with both top and bottom rods.
D. Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature.
E. At non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature.
F. Exit devices for fire doors shall comply with Underwriters
Laboratories, Inc., requirements for Fire Exit Hardware. Submit proof of compliance.
2.16 FLUSH BOLTS (LEVER EXTENSION)
A. Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to
ANSI A156.16, for flush bolts required on lower part of doors.
B. Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel.
C. Face plates for cylindrical strikes shall be rectangular and not less than (1 inch by 2-1/2 inches).
D. Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.
E. Provide extension rods for top bolt where door height exceeds (7 feet 2 inches).
2.17 FLUSH BOLTS (AUTOMATIC)
A. Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI
All5. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than (1-1/2 by 3-1/2 inches).
B. At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than
20 minutes; provide fire pins as required by auto flush bolt and door fire labels.
2.18 DOOR PULLS WITH PLATES
A. Conform to ANSI A156.6. Pull Type J40l, 152 mm CTC (6 inches CTC) length by (3/4 inches) diameter minimum with plate Type J302, (3-1/2 inches by 15 inches), unless otherwise specified. Provide pull with projection of (2 1/4 inches) minimum and a clearance of (1 1/2 inches)
08 71 00-14
St. Cloud VAMC
St. Cloud, MN minimum. Cut plates of door pull plate for cylinders, or turn pieces where required.
2.19 PUSH PLATES
A. Conform to ANSI A156.6. Metal, Type J302, (8 inches) wide by (16 inches) high. Provide metal Type J302 plates (4 inches) wide by 406.4
(16 inches) high where push plates are specified for doors with stiles less than (8 inches) wide. Cut plates for cylinders, and turn pieces where required.
2.20 COMBINATION PUSH AND PULL PLATES
A. Conform to ANSI 156.6. Type J303, stainless steel (1/8 inch) thick, (3-
1/3 inches) wide by (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with (1-1/2 inch) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.
2.21 COORDINATORS
A. Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.
2.22 THRESHOLDS
A. Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be installed in a bed of sealant with H-20 stainless steel machine screws and expansion shields. In new construction, embed aluminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for the full width of the openings.
B. For thresholds at elevators entrances see other sections of specifications.
08 71 00-15
St. Cloud VAMC
St. Cloud, MN
C. At exterior doors and any interior doors exposed to moisture, provide threshold with non-slip abrasive finish.
D. Provide with miter returns where threshold extends more than (0.5 inch) beyond face of frame.
2.23 AUTOMATIC DOOR BOTTOM SEAL AND RUBBER GASKET FOR LIGHT PROOF OR SOUND
CONTROL DOORS
A. Conform to ANSI A156.22. Provide mortise or under-door type, except where not practical. For mortise automatic door bottoms, provide type specific for door construction (wood or metal).
2.24 WEATHERSTRIPS (FOR EXTERIOR DOORS)
A. Conform to ANSI A156.22. Air leakage shall not to exceed 0.50 CFM per foot of crack length (0.000774m"/s/m).
2.25 MISCELLANEOUS HARDWARE
A. Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types):
Except for fire—rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.
B. Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur, except as otherwise specified. Provide cylinders to operate locking devices where specified for following partitions and doors:
1. Folding doors and partitions.
2. Wicket door (in roll-up door assemblies).
3. Slide-up doors.
4. Swing-up doors.
5. Fire-rated access doors-Engineer's key set.
6. Doors from corridor to electromagnetic shielded room.
7. Day gate on vault door.
C. Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers
Type L030ll or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors.
Provide 4 mutes or silencers for frames for each Dutch type door.
Provide 2 mutes for each edge of sliding door which would contact door frame.
08 71 00-16
St. Cloud VAMC
St. Cloud, MN Adult Day Health Care Extended Care Support
VA263—15—C—0137
2.26 PADLOCKS FOR VARIOUS DOORS, GATES AND HATCHES
A. ASTM E883, size (2 inch) wide chain; furnish extended shackles as required by job conditions. Provide padlocks, with key cylinders, for each door in following areas as noted.
B. Key padlocks as follows:
1. Chain Link Fence Gates for Electrical Substation and other Fenced
Buildings or Areas: Engineer's set, except as otherwise specified.
2.27 THERMOSTATIC TEMPERATURE CONTROL VALVE CABINETS
A. Where lock is shown, equip each cabinet door (metal) with lock Type
E06213, conforming to ANSI A156.36. Key locks in Key Sets approved by
Contracting Officer. See mechanical drawings and specifications for location of cabinets.
B. Cabinet manufacturer shall supply the hinges, bolts and pulls. Ship locks to cabinet manufacturer for installation.
2.28 FINISHES
A. Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes.“ For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING.
B. 626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.
C. Miscellaneous Finishes:
1. Hinges --exterior doors: 626 or 630.
2. Hinges --interior doors: 652 or 630.
3. Pivots: Match door trim.
4. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.
5. Thresholds: Mill finish aluminum.
6. Cover plates for floor hinges and pivots: 630.
D. Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces.
E. Special Finish: Exposed surfaces of hardware for dark bronze anodized aluminum doors shall have oxidized oil rubbed bronze finish (dark bronze) finish on door closers shall closely match doors.
F. Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an
08 71 00-17
St. Cloud VAMC
St. Cloud, MN Adult Day Health Care Extended Care Support
VA263—15—C—0137
anti-microbial/anti-fungal coating that has passed ASTM E2180 tests.
Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.
2.31 BASE METALS
A. Apply specified U.S. Standard finishes on different base metals as following:
Finish
PART 3 - EXECUTION
3.1 HARDWARE HEIGHTS
Base Metal
Steel
Brass or bronze
Stainless steel
A. For door pair located at existing building (Rehab Building, #116) — locate hardware on doors at heights to match existing hardware. The
Contractor shall visit the site, verify location of existing hardware and submit locations to VA COR for approval.
B. For new buildings locate hardware on doors at heights specified below, with all hand-operated hardware centered within (34 inches) to (48 inches), unless otherwise noted:
C. Hardware Heights from Finished Floor:
1. Exit devices centerline of strike (where applicable) (40-5/16 inches).
2. Locksets and latch sets centerline of strike (40-5/16 inches).
3. Deadlocks centerline of strike (48 inches).
4. Hospital arm pull (46 inches) to centerline of bottom supporting bracket.
5. Centerline of door pulls to be (40 inches).
6. Push plates and push-pull shall be (50 inches) to top of plate.
7. Push-pull latch to be (40-5/16 inches) to centerline of strike.
8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.
3.2 INSTALLATION
A. Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors. At exterior
08 71 00-18
St. Cloud VAMC
St. Cloud, MN Adult Day Health Care Extended Care Support
VA263—15—C—0137
doors, closers shall be mounted on interior side. Where closers are mounted on doors they shall be mounted with hex nuts and bolts; foot shall be fastened to frame with machine screws.
B. Hinge Size Requirements:
Door Thickness Door Width Hinge Height
45 mm (1—3/4 inch) 900 mm (3 feet) and less 113 mm (4—1/2 inches)
45 mm (1—3/4 inch) Over 900 not more feet) mm (3 than feet) but
1200 mm (4
125 mm (5 inches)
35 mm (1—3/8
(hollow core doors) inch) wood
Not over 1200 mm (4 feet) 113 mm (4—1/2 inches)
C. Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.
D. Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by
COR. Existing hinges shall not be reused on door openings having new doors and new frames. Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.
E. Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted.
All fastenings exposed to weather shall be of nonferrous metal.
F. After locks have been installed; show in presence of COR that keys operate their respective locks in accordance with keying requirements.
(All keys, Master Key level and above shall be sent Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the COR for his records. Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.
08 71 00-19
St. Cloud VAMC
St. Cloud, MN Adult Day Health Care Extended Care Support
VA263—15—C—0137
3.3 FINAL INSPECTION
A. Installer to provide letter to VA COR/Project Engineer that upon completion, installer has visited the Project and has accomplished the following:
1. Re-adjust hardware.
2. Evaluate maintenance procedures and recommend changes or additions and instruct VA personnel.
3. Identify items that have deteriorated or failed.
4. Submit written report identifying problems.
3.4 DEMONSTRATION
A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of COR/Project Engineer and VA Locksmith.
3.5 HARDWARE SETS
A. Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.
B. Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.
08 71 00-20
St. Cloud VAMC
St. Cloud, MN Adult Day Health Care Extended Care Support
VA263—15—C—0137
Door # HWSet #
102A 05
103A 06
103B 21
103C 07
103D 16
103E 07
103F 21
104A 18
104B 22
104C 07
104D 23
105A 05
106A 10
107A 14
108A 10
109A 19
110A 06
110B 21
111A 06
111B 21
112A 11
1128 21
113A 11
114A 02
115A 01
116A 01
117A 01
118A 01
119A 01
119B 13
119C 13
120A 07
121A 05
122A 08
1228 08
122C 25
123A 08
124A 02
125A 02
126A 04
1268 13
126C 12
127A 04
08 71 00-21
St. Cloud VAMC
St. Cloud, MN Adult Day Health Care Extended Care Support
VA263—15—C—0137
Door # HWSet #
127B 13
127C 12
128A 02
126B 03
129A 02
130A 02
131A 17
132A 02
133A 13
134A 13
135A 13
136A 13
137A 13
138A 13
139A 13
140A 07
141A 08
141B 08
141C 17
141D 17
142A 15
143A 14
144A 07
145A 17
146A 07
B001A 07
B003A 26 B003B 26 C100 22
C101A 21
C101B 21
C112A 06
C112B 09
C112C 09
201A 24
Door hardware, specification, 08 71 00, was written using Schlage 6 pin locksets. The VA standard is to use Corbin Russwin 7 pin locksets.
Bidders shall substitute Corbin Russwin 7 pin locksets instead of the
Schlage hardware. Cross reference the Schlage part numbers in each hardware group to equivalent Corbin Russwin lockset part numbers.
Use the information below as a reference for VA preferences for additional door hardware:
-Use Corbin Russwin Mortise locks. Use Best cylinders 7-pin TE keyway.
-Corbin ML2000 SERIES locksets, ML2055 Classroom, ML2057 Storeroom, ML2069
Patient Bathroom with 741F22-626 indicator, ML2065 Dormitory (Deadbolt Feature).
-Use Mortise locks only, no cylindrical locks
-Prefer electric strike located in door frame. Discourage use of electric mortise inside doors, maintenance issues with wiring failures when routing through hinge and door. No wires shall run through door hinges and door slabs.
-Core shall be removable with special tool or key.
-Detex, ECL-230D
-Closer, Corbin Russwin DC6210
-Exit device push bar, Von Duprin #98/99 series
-Hinges, Hager BB1279 4.5" x 4.5" 5 knuckle ball bearing US 26 D HT
-Card Reader, Best Basis 6 45HG7DV3MS626 RHTRK3
-Electric Strikes, Folger Adam 12/24v failsafe.
-Public restrooms shall have occupied latch identification.
08 71 00-22
St
St
Cloud VAMC
Cloud, MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
Hardware Group No. 01
For use on mark/door #(s):
115A 116A
Each To Have:
117A 118A 119A 146A
Qty
3 EA
Description
HINGE
Catalog Number
5BB1HW 5 X 4.5
Finish
Mfr
IVE
1 EA PASSAGE SET L9010 17A 626 SCH
1 EA WALL STOP WS406/407CCV 630 IVE
3 EA SILENCER SR64 GRY IVE
Hardware Group No. 02
For use on mark/door #(s):
114A 124A 132A
Each To Have:
125A 128A 129A 130A
Qty Description Catalog Number Finish Mfr
3 EA HINGE 5BB1HW 5 X 4.5 652 IVE
1 EA CLASSROOM LOCK L9070BDC 17A 626 SCH
1 EA WALL STOP WS406/407CCV 630 IVE
3 EA SILENCER SR64 GRY IVE
Hardware Group No. 03
For use on mark/door #(s):
128B
Each To Have:
Qty Description Catalog Number Finish Mfr
6 EA HINGE 5BB1 4.5 X 4.5 652 IVE
2 EA MANUAL FLUSH BOLT FB458 626 IVE
1 EA DUST PROOF STRIKE DP2 626 IVE
1 EA STOREROOM LOCK L9080BDC 17A 626 SCH
1 EA PERMANENT CORE OWNER PROVIDED 626 BES
2 EA OH STOP 100S 630 GLY
2 EA SILENCER SR64 GRY IVE
08 71 00-23
St
St
Cloud VAMC
Cloud, MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
Hardware Group No. 04
For use on mark/door #(s):
126A 127A
Each To Have:
Qty Description
3 EA HINGE
1 EA PRIVACY LOCK
1 EA WALL STOP
3 EA SILENCER
Hardware Group No. 05
For use on mark/door #(s):
102A 105A 121A
Each To Have:
Catalog Number
5BB1HW 5 X 4.5
L9040 17A L583-363 L283-722
WS406/407CCV
SR64
Finish Mfr
652 IVE
626 SCH
630 IVE
GRY IVE
Qty
3 EA
Description
HINGE
Catalog Number
5BB1HW 5 X 4.5
Finish
Mfr
IVE
1 EA STOREROOM LOCK L9080BDC 17A 626 SCH
1 EA OH STOP 100S 630 GLY
1 EA SURFACE CLOSER 4040XP EDA 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA MOP PLATE 8400 4" X 1" LDW B-CS 630 IVE
1 EA GASKETING 188SBK PSA BK ZER
Hardware Group No. 06
For use on mark/door #(s):
103A 110A 111A
Each To Have:
C112A
Qty Description Catalog Number Finish Mfr
3 EA HINGE 5BB1HW 5 X 4.5 652 IVE
1 EA FIRE EXIT HARDWARE 99-L-F-17 626 VON
1 EA SFIC RIM CYLINDER 80-116 626 SCH
1 EA PERMANENT CORE OWNER PROVIDED 626 BES
1 EA OH STOP 100S 630 GLY
1 EA SURFACE CLOSER 4040XP EDA 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA MOP PLATE 8400 4" X 1" LDW B-CS 630 IVE
1 EA GASKETING 188SBK PSA BK ZER
08 71 00-24
St
St
Cloud VAMC
Cloud, MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
Hardware Group No. 07
For use on mark/door #(s):
103C 104C
B001B ST1-E
Each To Have:
120A 103E
140A
144A B001A
Qty
3 EA
Description
HINGE
Catalog Number
5BB1HW 5 X 4.5
Finish
Mfr
IVE
1 EA STOREROOM LOCK L9080BDC 17A 626 SCH
1 EA PERMANENT CORE OWNER PROVIDED 626 BES
1 EA SURFACE CLOSER 4040XP RW/PA 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA MOP PLATE 8400 4" X 1" LDW B-CS 630 IVE
1 EA WALL STOP WS406/407CCV 630 IVE
1 EA GASKETING 188SBK PSA BK ZER
Hardware Group No. 08
For use on mark/door #(s):
122A 122B 123A
Each To Have:
141A 141B
Qty Description Catalog Number Finish Mfr
3 EA HINGE 5BB1HW 5 X 4.5 652 IVE
1 EA CLASSROOM LOCK L9070BDC 17A 626 SCH
1 EA SURFACE CLOSER 4040XP RW/PA 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA MOP PLATE 8400 4" X 1" LDW B-CS 630 IVE
1 EA WALL STOP WS406/407CCV 630 IVE
1 EA GASKETING 188SBK PSA BK ZER
Hardware Group No. 09
For use on mark/door #(s):
C112B C112C
Each To Have:
Qty Description Catalog Number Finish Mfr
3 EA HINGE 5BB1HW 5 X 4.5 652 IVE
1 EA FIRE EXIT HARDWARE 99-L-F-17-SNB 626 VON
1 EA SFIC RIM CYLINDER 80-116 626 SCH
1 EA PERMANENT CORE OWNER PROVIDED 626 BES
1 EA SURFACE CLOSER 4040XP RW/PA 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA MOP PLATE 8400 4" X 1" LDW B-CS 630 IVE
1 EA WALL STOP WS406/407CCV 630 IVE
08 71 00-25
St
St
Cloud VAMC
Cloud, MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
Hardware Group No. 10
For use on mark/door #(s):
106A 108A
Each To Have:
Qty
3 EA
Description
HINGE
Catalog Number
5BB1HW 5 X 4.5
Finish
Mfr
IVE
1 EA CLASSROOM DEAD
LOCK
L463BDC 626 SCH
1 EA PUSH PLATE 8200 4" X 16" 630 IVE
1 EA PULL PLATE 8302 8" 4" X 16" 630 IVE
1 EA SURFACE CLOSER 4040XP RW/PA 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA MOP PLATE 8400 4" X 1" LDW B-CS 630 IVE
1 EA WALL STOP WS406/407CCV 630 IVE
3 EA SILENCER SR64 GRY IVE
Hardware Group No. 11
For use on mark/door #(s):
112A 113A
Each To Have:
Qty Description Catalog Number Finish Mfr
3 EA HINGE 5BB1HW 5 X 4.5 652 IVE
1 EA PUSH PLATE 8200 4" X 16" 630 IVE
1 EA PULL PLATE 8302 8" 4" X 16" 630 IVE
1 EA SURFACE CLOSER 4040XP RW/PA 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA MOP PLATE 8400 4" X 1" LDW B-CS 630 IVE
1 EA WALL STOP WS406/407CCV 630 IVE
3 EA SILENCER SR64 GRY IVE
Hardware Group No. 12
For use on mark/door #(s):
126C 127C
Each To Have:
Qty
3 EA
Description
HINGE
Catalog Number
5BB1HW5 X4.5
Finish
Mfr
IVE
1 EA MORTISE LOCK L9056BDC 17A L583-363 L283-722 XL13- 626 SCH
1 EA PERMANENT CORE
OWNER PROVIDED 626 BES
1 EA WALL STOP WS406/407CCV 630 IVE
3 EA SILENCER SR64 GRY IVE
08 71 00-26
St. Cloud VAMC
St. Cloud, MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
Hardware Group No. 13
For use on mark/door #(s):
119B 119C 135A 136A
Each To Have:
126B 137A
127B 138A
133A 139A
134A
Qty
3 EA
Description
HINGE
Catalog Number
5BB1HW5 X4.5
Finish
Mfr
IVE
1 EA MORTISE LOCK L9056BDC 17A L583-363 L283-722 XL13- 626 SCH
1 EA PERMANENT CORE
OWNER PROVIDED 626 BES
1 EA OH STOP 100S 630 GLY
3 EA SILENCER SR64 GRY IVE
Hardware Group No. 14
For use on mark/door #(s):
107A 143A
Each To Have:
Qty Description Catalog Number Finish Mfr
3 EA HINGE 5BB1HW 5 X 4.5 652 IVE
1 EA PRIVACY LOCK L9040 17A L583-363 L283-722 626 SCH
1 EA OH STOP 100S 630 GLY
3 EA SILENCER SR64 GRY IVE
Hardware Group No. 15
For use on mark/door #(s):
142A
Each To Have:
Qty
4 EA
Description
HINGE
Catalog Number
5BB1 4.5 X 4.5
Finish
Mfr
IVE
1 EA DUTCH DOOR BOLT 054 626 IVE
1 EA OFFICE/ENTRY LOCK L9050BDC 17A 626 SCH
1 EA OH STOP 100S 630 GLY
3 EA SILENCER SR64 GRY IVE
08 71 00-27
St
St
Cloud VAMC
Cloud, MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
Hardware Group No. 16
For use on mark/door #(s):
103D
Each To Have:
Qty
3 EA
Description
HINGE
Catalog Number
5BB1 4.5 X 4.5
Finish
Mfr
IVE
1 EA FIRE EXIT HARDWARE 99-L-F-17-SNB 626 VON
1 EA SFIC RIM CYLINDER 80-116 626 SCH
1 EA PERMANENT CORE OWNER PROVIDED 626 BES
1 EA SURFACE CLOSER 4040XP RW/PA 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA MOP PLATE 8400 4" X 1" LDW B-CS 630 IVE
1 EA WALL STOP WS406/407CCV 630 IVE
1 EA GASKETING 188SBK PSA BK ZER
Hardware Group No. 17
For use on mark/door #(s):
131A 141C
Each To Have:
Qty Description
NOTE
Hardware Group No. 18
For use on mark/door #(s):
104A
Each To Have:
141D 145A
Catalog Number
NO HARDWARE REQUIRED
Finish Mfr
Qty
6 EA
Description
HINGE
Catalog Number
5BB1 4.5 X 4.5
Finish
Mfr
IVE
1 EA AUTO FLUSH BOLT FB31B 630 IVE
1 EA DUST PROOF STRIKE DP2 626 IVE
1 EA STOREROOM LOCK L9080BDC 17A 626 SCH
1 EA PERMANENT CORE OWNER PROVIDED 626 BES
1 EA COORDINATOR COR X FL 628 IVE
2 EA MOUNTING BRACKET MB USP IVE
2 EA SURFACE CLOSER 4040XP EDA 689 LCN
2 EA KICK PLATE 8400 10" X 1" LDW B-CS 630 IVE
2 EA MOP PLATE 8400 4" X 1" LDW B-CS 630 IVE
2 EA WALL STOP WS406/407CCV 630 IVE
2 EA SILENCER SR64 GRY IVE
08 71 00-28
St
St
Cloud VAMC
Cloud, MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
Hardware Group No. 19
For use on mark/door #(s):
109A
Each To Have:
Qty
2 EA
Description
HINGE
Catalog Number
5BB1HW 5 X 4.5
Finish
Mfr
IVE
1 EA ELECTRIC HINGE 5BB1HW 5 X 4.5 CON TW8 652 IVE
1 EA EU MORTISE LOCK L9092BDCEU 17A RX DPS CON 626 SCH
1 EA PERMANENT CORE OWNER PROVIDED 626 BES
1 EA SURFACE CLOSER 4040XP RW/PA 689 LCN
1 EA KICK PLATE 8400 10" X 2" LDW B-CS 630 IVE
1 EA MOP PLATE 8400 4" X 1" LDW B-CS 630 IVE
1 EA WALL STOP WS406/407CCV 630 IVE
1 EA GASKETING 188SBK PSA BK ZER
1 EA WIRE HARNESS CON-44 SCH
1 EA WIRE HARNESS CON-6W SCH
1 EA POWER SUPPLY
NOTE
PS902 900-2RS
CARD READER/KEYPAD BY OTHERS
LGR SCE
Operational Description Outside lever electrically unlocked (fail secure) by 12 or 24V DC with Allegion Connect molex 3" lead connector. Outside key allows manual retraction of latchbolt. Inside lever always free for immediate egress. Auxiliary latch deadlocks latchbolt when
SURFACE CLOSER
MOP PLATE
KICK PLATE
WALL STOP
GASKETING
Power Supply (2A @ 12/24 VDC-field selectable); Provided with Grey / Baked Enamel, High Voltage Protective Cover / Enclosure
08 71 00-29
St
St
Cloud VAMC
Cloud, MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
Hardware Group No. 20
For use on mark/door #(s):
C100A
Each To Have:
Qty
6 EA
Description
HINGE
Catalog Number
5BB1HW 5 X 4.5
Finish
Mfr
IVE
1 EA POWER TRANSFER EPT10 CON 689 VON
1 EA FIRE EXIT HARDWARE 9949-EO-F-LBL 626 VON
1 EA DELAYED FIRE EXIT CX9949-EO-F-LBL-CON 626 VON
HARDWARE
1 EA SFIC MORTISE CYL. 80-101 114 626 SCH
1 EA PERMANENT CORE OWNER PROVIDED 626 BES
2 EA OH STOP 100S 630 GLY
2 EA SURFACE CLOSER 4040XP EDA 689 LCN
2 EA KICK PLATE 8400 10" X 1" LDW B-CS 630 IVE
1 EA GASKETING 188SBK PSA BK ZER
2 EA WIRE HARNESS CON-26 SCH
2 EA WIRE HARNESS CON-6W SCH
2 EA DOOR CONTACT 7764 628 SCE
1 EA POWER SUPPLY PS914 900-2RS-FA VON
NOTE CARD READER/KEYPAD BY OTHERS
Operational Description with Connector, Free Egress at all times. Pressing Push Bar retracts latchbolts
#NAME?
OH STOP
SURFACE CLOSER
GASKETING
Door Position Switch monitors whether the door is open or closed
08 71 00-30
St
St
Cloud VAMC
Cloud, MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
Hardware Group No. 21
For use on mark/door #(s):
103B 110B
103F
Each To Have:
111B 112B C101A C101B
Qty
1 EA
Description
CONT. HINGE
Catalog Number
112XY EPT
Finish
313AN
Mfr
IVE
1 EA POWER TRANSFER EPT10 CON SP313 VON
1 EA ELEC FIRE EXIT RX-QEL-99-NL-OP-F-110MDCON 313 VON
HARDWARE
1 EA SFIC RIM CYLINDER 80-116 613 SCH
1 EA PERMANENT CORE OWNER PROVIDED 626 BES
1 EA 90 DEG OFFSET PULL 8190HD 10" A US10B IVE
1 EA OH STOP 100S US10B GLY
1 EA SURFACE CLOSER 4040XP EDA 695 LCN
provide all plates and brackets required for
1 EA RAIN DRIP
mounting
142D D ZER
1 EA DOOR SWEEP 8198D D ZER
1 EA THRESHOLD 65A-223 A ZER
1 EA WIRE HARNESS CON-26 SCH
1 EA WIRE HARNESS CON-6W SCH
1 EA DOOR CONTACT 7764 628 SCE
1 EA POWER SUPPLY PS902 900-2RS LGR SCE
NOTE CARD READER/KEYPAD BY OTHERS
NOTE SEALS BY DOOR MFR
Operational Description Free Egress at all times. Pressing Push Bar retracts latchbolts Self-Closing Interlocking Threshold,UL,Smoke Door Position Switch monitors whether the door is open or closed Power Supply (2A @ 12/24 VDC-field selectable); Provided with Grey / Baked Enamel, High Voltage
08 71 00-31
St
St
Cloud VAMC
Cloud, MN
Adult Day Health Care Extended Care Support
VA263—15—C—0137
Hardware Group No. 22
For use on mark/door #(s):
104B
Each To Have:
Qty
2 EA
Description
CONT. HINGE
Catalog Number
112XY EPT
Finish
Mfr
IVE
2 EA POWER TRANSFER EPT10 CON 689 VON
1 EA REMOVABLE MULLION KR4954 689 VON
2 EA ELEC PANIC RX-QEL-99-NL-OP-110MDCON 626 VON
HARDWARE
1 EA SFIC MORTISE CYL. 80-101 114 626 SCH
2 EA SFIC RIM CYLINDER 80-116 626 SCH
3 EA PERMANENT CORE OWNER PROVIDED 626 BES
2 EA 90 DEG OFFSET PULL 8190HD 10" A 630 IVE
2 EA OH STOP 100S 630 GLY
2 EA SURFACE CLOSER 4040XP EDA 689 LCN
2 EA KICK PLATE 8400 10" X 1" LDW B-CS 630 IVE
1 EA RAIN DRIP 142AA AA ZER
1 EA GASKETING 328AA-S AA ZER
2 EA DOOR SWEEP 8198AA AA ZER
1 EA THRESHOLD 65A-223 A ZER
2 EA WIRE HARNESS CON-26 SCH
2 EA WIRE HARNESS CON-6W SCH
2 EA DOOR CONTACT 7764 628 SCE
1 EA POWER SUPPLY PS902 900-2RS LGR SCE
NOTE CARD READER/KEYPAD BY OTHERS
Operational Description Geared Full Mortise Hinge, Electric Power Transfer with Connector, Free Egress at all times. Pressing Push Bar retracts latchbolts
SFIC RIM CYLINDER
90 Degree Offset Door Pull, 1"…