D.9 Room dimensions.pdf
PDF 2 MB Posted
- Solicitation number
- 36C26325Q0777
About this file
The document is a detailed architectural drawing set for audiovisual (AV) and electrical systems in three surgery rooms (S222, S224, S226) and a nurses station at the VA Black Hills Health Care facility in Fort Meade, South Dakota. The technical drawings specify precise conduit, electrical outlet, and equipment placement requirements, including specifications for:
- Ceiling and floor-mounted AV equipment locations such as monitors, cameras, status boards, and boom-mounted displays
- Electrical requirements including dedicated AV circuits, hospital-grade outlets, and specific conduit sizes
- Precise mounting instructions for various components like wall-mount connection plates, junction boxes, and electrical boxes
- Detailed notes on electrical specifications, cable management, and installation requirements for each room, with standardized layouts across the three operating rooms
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26325Q0777 A0001.pdf | ||
| 36C26325Q0777 A0001_1.docx | DOCX document | |
| 36C26325Q0777_1.docx | DOCX document | |
| 36C26325Q0777.pdf | ||
| D.1 Evaluated Salient Characteristics.xlsx | XLSX spreadsheet | |
| D.5 ICRA Introductory Information and Instruction.docx | DOCX document | |
| D.2 Supply Line Item Template.xlsx | XLSX spreadsheet | |
| D.4 Surgery structure.pdf | ||
| D.3 Floor plans.pdf | ||
| D.8 BUSINESS ASSOCIATE AGREEMENT.docx | DOCX document | |
| D.7 VA Directive 6550 App A Fillable.pdf | ||
| D.6 PCRA Introductory Information and Instructions.docx | DOCX document |
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CEILING
96" A.F.F.
72" A.F.F.
18" A.F.F.
1.25 1.25
1.52x
P1
AN EQM M
.75
WP
C1
.752x
N
C2
1.251.52x
.75(TYP)
TYPICAL EASYPORT
LOCATIONSAV2
NOTE 1: AV POWER RECEPTACLES (BY EC) SHALL BE PROVIDED WITH HOSPITAL GRADE OUTLETS WIRED IN ACCORDANCE WITH NEC ARTICLE 517 AND ALL APPLICABLE CODES. AV BRANCH CIRCUITS SHALL BE DEDICATED (FOR LOCAL AV/IT EQUIPMENT ONLY) AND WITH RESPECT
TO ANY GIVEN OR, SHALL BE FED FROM A COMMON SUBPANEL.
NOTE 2: PROVIDE ALL SPECIFIED CONDUIT FREE OF OTHER CABLE, AND WITH INSTALLED PULL STRINGS.
SYMBOL LEGEND
(1) ANALOG (POTS) PHONE LINE & (4) DATA
DROPS (BY FACILITY) REQUIRED FOR RACK MOUNTED
EQUIPMENT BY ISM14
N
NURSE STATION: PROVIDE 4GA ELECTRICAL BOX NO LESS
THAN 2.5" DEEP (PASS-THROUGH FOR ALL VIDEO &
CONTROL CABLES TO STATION) W/ 4GA PLASTER RING.
4" EMT CONDUIT
(BY EC).75
1" EMT CONDUIT
(BY EC)1
114" EMT CONDUIT
(BY EC)1.25
112" EMT CONDUIT
(BY EC)1.5
8x8x4 JUNCTION BOX (BY EC) NEAR ACCESS HATCH
ABOVE BOOM (TYP FOR ALL BOOMS)8
RECESSED SIMPLEX (CLOCK) OUTLET (BY EC) BEHIND
DISPLAY ON DEDICATED 15-20A CIRCUIT - COORDINATE
EXACT LOCATION WITH ISM (SEE NOTE 1.)AV
DUPLEX OUTLET(S) (BY EC) FOR AV/IT EQUIPMENT ON
DEDICATED 20A CIRCUIT (SEE NOTE 1.)AV
VOICE & DATA DROPS (BY FACILITY) RECOMMENDED
FOR EQUIPMENT BY FACILITY
ANESTHESIA BOOM
(TYP - BY OTHERS)AN
CEILING-MOUNT STATUS BOARD CAMERA: PROVIDE
CONDUIT STUB W/BUSHING ABOVE CAMERA LOCATION.C2
EQUIPMENT BOOM
(TYP - BY OTHERS)EQ
MONITOR BOOM
(TYP - BY OTHERS)M
FLAT PANEL DISPLAY: PROVIDE 41116'' ELECTRICAL BOX W/
1-GA PLASTER RING.P1
12x12x4 JUNCTION BOX (BY EC) IN WALL
BEHIND EQUIPMENT RACKR
OPTIONAL ROOM LIGHTING CONTROL INTERFACE
(BY OTHERS) IN ACCESSIBLE LOCATIONRL
RECESSED CEILING MOUNTED LOUDSPEAKER (TYP)S
OPTIONAL SURGICAL LIGHTING CONTROL INTERFACE
(BY OTHERS) IN ACCESSIBLE LOCATIONSL
WALL MOUNT CONNECTION PLATE: PROVIDE
41116" ELECTRICAL BOX W/ 1GA PLASTER RING.WPWALL-MOUNT CAMERA: PROVIDE 41116" ELECTRICAL BOX
ANCHORED FIRMLY TO STUD, W/ 2GA PLASTER RING.C1
24x24x6 JUNCTION BOX (BY EC) ABOVE CEILING
IN ACCESSIBLE LOCATION IN OR NEAR ROOM24
32.00
.0
IF REQUIRED, ADA COMPLIANCE
OF DISPLAY AREAS TO BE
ENSURED BY FACILITY.
AV3FLUSH MOUNTED
SOLID BLOCKING
(TYP. BY GC)
S LOUDSPEAKER CABLE PASS-THROUGH PLATE: PROVIDE
41116" ELECTRICAL BOX W/ 1GA PLASTER RING.
TYP. EASYPORT
LOCATION
TYP. EASYPORT
LOCATION
DN
DN
UP.
S
PA
S
PA
S
PA
TV TV TV TV TV TV TV TV
TVTV S
PA
V
DN
DN
UP.
S
PA
S
PA
S
PA
TV TV TV TV TV TV TV TV
TVTV S
PA
V
OR 3
OR 2
OR 1
WP
S
S
AN
WP
M1
EQ
N
AV
C1
M
C2
SURGERY
ROOM #2
S224
SURGERY
ROOM #1
S222
SURGERY
ROOM #3
S226
WP
S
AN
WP
M
EQ
N
AV
C1
M
C2
WP
S
AN
WP
M
EQ
N AV
C1
M
C2
S
(UNDER
THE COUNTER) AV
AV2
AV
2 AV
2AV2AV
AV
PCPC
PC
PC
PC
PC
AV
SB
AV1
SB
AV SB
SB
AV
AV1
SB PC
NOTES:
NOTE 1: AV POWER RECEPTACLES (BY EC) SHALL BE PROVIDED WITH
HOSPITAL GRADE OUTLETS WIRED IN ACCORDANCE WITH ALL
APPLICABLE CODES. AV BRANCH CIRCUITS SHALL BE DEDICATED (FOR
LOCAL AV/IT EQUIPMENT ONLY).
NOTE 2: PROVIDE PULL STRING FROM SB TO PC. ENSURE THAT
CABLE PATH FROM SD TO PC IS FREE OF OBSTACLES AND/OR
ABRASIVE EDGES. BREADTH OF CABLE PATH FROM SB TO PC SHALL
BE EQUAL TO OR GREATER TO THAN THAT OF 2" DIAMETER CONDUIT.
NOTE 3: IF STATUS BOARD ENGINE COMPUTER IS TO BE PLACED ATOP
TYPICAL WORKSURFACE, THEN GROMMETTED CABLE PASSAGE THROUGH
WORKSURFACE SHALL BE PROVIDED BY GC OR MILLWORK PROVIDER.
NOTE 4:THE DVI-D CABLE CAN NEITHER BE PULLED
THROUGH PLENUMS, NOR RETURN-AIR SPACES, WITHOUT ENCLOSED
WIREWAY CONSISTENT WITH 2" EMT.
IF REQUIRED, SAME SHALL BE PROVIDED BY EC.
SYMBOL LEGEND
DESKTOP STATUS BOARD MONITORSB
DESKTOP STATUS BOARD MONITORSB
RECESSED SIMPLEX (CLOCK) OUTLET (BY EC) BEHIND
DISPLAY ON DEDICATED 15-20A CIRCUIT FOR ISM STATUS
BOARD DISPLAYAV
DUPLEX OUTLET (BY EC) FOR STATUS BOARD ENGINE
ON SAME DEDICATED 15-20A CIRCUIT AS DISPLAY
(SEE NOTE 1.)AV
(2) DATA DROPS (BY FACILITY): (1) ACTIVE AND (1) FUTURE
FOR STATUS BOARD DISPLAY, PC AND ACCESSORIES. ADJACENT
TO PASS-THROUGH WALL PLATE.2
STATUS BOARD ENGINEPC
PC
AV
SB
STATUS
BOARD
M1
.75
WP
FLOOR
R S
12" A.F.F.
22" A.F.F.
14 AV1AV1
M1
M
M1
18" A.F.F.
FLOOR
ISM STATUS BOARD DISPLAY:
LOCATION TO BE COORDINATED
WITH ROOM FURNITURE. SB
AV12
TYPICAL WORKSURFACE
(SEE NOTE 3.)
PC
CEILING
MONITOR ON ARM OFF EQUIPMENT BOOM
(TYP - BY OTHERS)M1
THIS NUMBER DENOTES TYPICAL DEDICATED AV/IT DEVICE CIRCUIT NUMBER
(PER ROOM)
1.52x
NURSES
STATION
S223
CORRIDOR
CS201C
MONITOR ARM NOT
SHOWN ON BASE
FLOOR PLAN
MONITOR ARM NOT
SHOWN ON BASE
FLOOR PLAN
MONITOR ARM NOT
SHOWN ON BASE
FLOOR PLAN
CC
CC
CC
.75
CC
CCU CONNECTION DEVICE PLATE FOR HOSPITAL FURNISHED
LIGHT CAM, IF INCLUDED: PROVIDE 41116" ELECTRICAL BOX
W/ 1GA PLASTER RING.
CC
CC LOCATION TO BE
COORDINATED WITH SURGICAL
LIGHT AND BOOM VENDOR
S
R
AV
AV
R
AV
AV
S
S
R
AV
AV
AV P1
AV P1
AVP1
5x5x 1.5
ORSUB-STER.
ROOM
.75
(OPT.)
RLSL
(OPT.)
.75
SS
SUB-STERILE
ROOM
S222A
SUB-STERILE
ROOM
S222A
SUB-STERILE
ROOM
S226A
RACK
RACK
RACK
S
DN
UP.
S
PA
S
PA
S
PA
TV TV TV TV TV TV TV TV
TVTV S
PA
V
DN
DN
UP.
S
PA
S
PA
S
PA
TV TV TV TV TV TV TV TV
TVTV S
PA
V
OR 3
OR 2
OR 1
STATUS
BOARD
RACK
RACK
RACK
AV-0.01
MASTER
FLOOR PLAN
EasySuite ORs
Drawing / Sheet Number:
Drawing Title:
System / Room:
Reviewed by:
Drawn by:
Quote #:
Scale:
Drawing History
Rev. Date Comment
One Monarch Drive Littleton, MA 01460
Phone: 978.486.8494 Fax: 978.428.2694 www.imagestreammedical.com
Issued For:
Project Name / Site Name / Site Location:
© 2015 Image Stream Medical
This document is proprietary and shall not be reproduced or redistributed without the express written permission of Image Stream Medical.
Rev./Date:
Project #:
Designed by:
- CF
- 23654b
BC / BN AS NOTED
1.0 / DEC.14.2015
VA Black Hills Health Care
Second Level ORs
Fort Meade, SD
REFERENCE ONLY
NOT FOR CONSTRUCTION
FOR REF. ONLY1.0 DEC.14.2015
SCALE: NTS
2ND LEVEL ORs - PARTIAL FLOOR PLAN
UP.
S
PA
S
PA
S
PA
TV TV TV TV TV TV TV TV
TVTV S
PA
V
SURGERY
ROOM #1
S222
WP
S
AN
WP
M
EQ
N AV
C1
M
C2
S
M1
MONITOR ARM NOT
SHOWN ON BASE
FLOOR PLAN
CC
S
R
AV
AV
S
AVP1
SUB-STERILE
ROOM
S222A
NOTE 1: AV POWER RECEPTACLES (BY EC) SHALL BE PROVIDED WITH HOSPITAL GRADE OUTLETS WIRED IN ACCORDANCE WITH NEC ARTICLE 517 AND ALL APPLICABLE CODES. AV BRANCH CIRCUITS SHALL BE DEDICATED (FOR LOCAL AV/IT EQUIPMENT ONLY) AND WITH RESPECT
TO ANY GIVEN OR, SHALL BE FED FROM A COMMON SUBPANEL.
NOTE 2: PROVIDE ALL SPECIFIED CONDUIT FREE OF OTHER CABLE, AND WITH INSTALLED PULL STRINGS.
SYMBOL LEGEND
(1) ANALOG (POTS) PHONE LINE & (4) DATA
DROPS (BY FACILITY) REQUIRED FOR RACK MOUNTED
EQUIPMENT BY ISM14
N
NURSE STATION: PROVIDE 4GA ELECTRICAL BOX NO LESS
THAN 2.5" DEEP (PASS-THROUGH FOR ALL VIDEO &
CONTROL CABLES TO STATION) W/ 4GA PLASTER RING.
4" EMT CONDUIT
(BY EC).75
1" EMT CONDUIT
(BY EC)1
114" EMT CONDUIT
(BY EC)1.25
112" EMT CONDUIT
(BY EC)1.5
8x8x4 JUNCTION BOX (BY EC) NEAR ACCESS HATCH
ABOVE BOOM (TYP FOR ALL BOOMS)8
RECESSED SIMPLEX (CLOCK) OUTLET (BY EC) BEHIND
DISPLAY ON DEDICATED 15-20A CIRCUIT - COORDINATE
EXACT LOCATION WITH ISM (SEE NOTE 1.)AV
DUPLEX OUTLET(S) (BY EC) FOR AV/IT EQUIPMENT ON
DEDICATED 20A CIRCUIT (SEE NOTE 1.)AV
VOICE & DATA DROPS (BY FACILITY) RECOMMENDED
FOR EQUIPMENT BY FACILITY
ANESTHESIA BOOM
(TYP - BY OTHERS)AN
CEILING-MOUNT STATUS BOARD CAMERA: PROVIDE
CONDUIT STUB W/BUSHING ABOVE CAMERA LOCATION.C2
EQUIPMENT BOOM
(TYP - BY OTHERS)EQ
MONITOR BOOM
(TYP - BY OTHERS)M
FLAT PANEL DISPLAY: PROVIDE 41116'' ELECTRICAL BOX W/
1-GA PLASTER RING.P1
12x12x4 JUNCTION BOX (BY EC) IN WALL
BEHIND EQUIPMENT RACKR
OPTIONAL ROOM LIGHTING CONTROL INTERFACE
(BY OTHERS) IN ACCESSIBLE LOCATIONRL
RECESSED CEILING MOUNTED LOUDSPEAKER (TYP)S
OPTIONAL SURGICAL LIGHTING CONTROL INTERFACE
(BY OTHERS) IN ACCESSIBLE LOCATIONSL
WALL MOUNT CONNECTION PLATE: PROVIDE
41116" ELECTRICAL BOX W/ 1GA PLASTER RING.WPWALL-MOUNT CAMERA: PROVIDE 41116" ELECTRICAL BOX
ANCHORED FIRMLY TO STUD, W/ 2GA PLASTER RING.C1
24x24x6 JUNCTION BOX (BY EC) ABOVE CEILING
IN ACCESSIBLE LOCATION IN OR NEAR ROOM24
S LOUDSPEAKER CABLE PASS-THROUGH PLATE: PROVIDE
41116" ELECTRICAL BOX W/ 1GA PLASTER RING.
MONITOR ON ARM OFF EQUIPMENT BOOM
(TYP - BY OTHERS)M1
CCU CONNECTION DEVICE PLATE FOR HOSPITAL FURNISHED
LIGHT CAM, IF INCLUDED: PROVIDE 41116" ELECTRICAL BOX
W/ 1GA PLASTER RING.
CC
CEILING
96" A.F.F.
72" A.F.F.
18" A.F.F.
1.25 1.25
1.52x
P1
AN EQM M
.75
WP
C1
.752x
N
C2
1.251.52x
.75(TYP)
TYPICAL EASYPORT
LOCATIONSAV2
32.00
.0
IF REQUIRED, ADA COMPLIANCE
OF DISPLAY AREAS TO BE
ENSURED BY FACILITY.
AV3FLUSH MOUNTED
SOLID BLOCKING
(TYP. BY GC)
TYP. EASYPORT
LOCATION
TYP. EASYPORT
LOCATION
M1
.75
WP
FLOOR
R S
12" A.F.F.
22" A.F.F.
14 AV1AV1
THIS NUMBER DENOTES TYPICAL DEDICATED AV/IT DEVICE CIRCUIT NUMBER
(PER ROOM)
1.52x
.75
CC
CC LOCATION TO BE
COORDINATED WITH SURGICAL
LIGHT AND BOOM VENDOR
5x5x 1.5
ORSUB-STER.
ROOM
.75
(OPT.)
RLSL
(OPT.)
.75
SS
SCALE: 3/16" = 1'-0"
SURGERY ROOM #1 (RM# S222) - AV FLOOR / CEILING PLAN
SCALE: NTS
SURGICAL ROOM 1, 2 & 3 (RM#s S222, S224 & S226) - TYPICAL AV CONDUIT / ELEC. ELEVATION AV-1.01
SURGICAL ROOM # 1
PLAN
& TYP CONDUIT
EasySuite ORs (Typ. of 3)
NOTE: RACK LOCATION SAFETY GROUND
SHALL BE COMMON TO SAFETY GROUND
OF RESPECTIVE OR. RACK LOCATION
BRANCH CIRCUIT SHALL BE EXCLUSIVE TO
TWO (2) DUPLEX OUTLETS. SEE NOTE 1.
Drawing / Sheet Number:
Drawing Title:
System / Room:
Reviewed by:
Drawn by:
Quote #:
Scale:
Drawing History
Rev. Date Comment
One Monarch Drive Littleton, MA 01460
Phone: 978.486.8494 Fax: 978.428.2694 www.imagestreammedical.com
Issued For:
Project Name / Site Name / Site Location:
© 2015 Image Stream Medical
This document is proprietary and shall not be reproduced or redistributed without the express written permission of Image Stream Medical.
Rev./Date:
Project #:
Designed by:
- CF
- 23654b
BC / BN AS NOTED
1.0 / DEC.14.2015
VA Black Hills Health Care
Second Level ORs
Fort Meade, SD
REFERENCE ONLY
NOT FOR CONSTRUCTION
FOR REF. ONLY1.0 DEC.14.2015
UP.
S
PA
S
PA
S
PA
TV TV TV TV TV TV TV TV
TVTV S
PA
V
WP
S
S
AN
WP
M1
EQ
N
AV
C1
M
C2
SURGERY
ROOM #2
S224
M
MONITOR ARM NOT
SHOWN ON BASE
FLOOR PLAN
CC
S
R
AV
AV
S
AV P1
SUB-STERILE
ROOM
S222A
DN
DN
UP.
S
PA
S
PA
S
PA
TV TV TV TV TV TV TV TV
TVTV S
PA
V
SURGERY
ROOM #3
S226
WP
S
AN
WP
M
EQ
N
AV
C1
M
C2
M1
MONITOR ARM NOT
SHOWN ON BASE
FLOOR PLAN
CC
S
R
AV
AV
AV P1
SUB-STERILE
ROOM
S226A
S
SCALE: 3/16" = 1'-0"
SURGERY ROOM #2 (RM# S224) - AV FLOOR / CEILING PLAN
AV-1.02
SURGICAL ROOMS
2 & 3 FLOOR PLANS
EasySuite ORs (Typ. of 3)
NOTE: RACK LOCATION SAFETY
GROUND SHALL BE COMMON TO
SAFETY GROUND OF RESPECTIVE
OR. RACK LOCATION BRANCH
CIRCUIT SHALL BE EXCLUSIVE
TO TWO (2) DUPLEX OUTLETS.
SEE DRAWING AV-1.01 NOTE 1.
Drawing / Sheet Number:
Drawing Title:
System / Room:
Reviewed by:
Drawn by:
Quote #:
Scale:
Drawing History
Rev. Date Comment
One Monarch Drive Littleton, MA 01460
Phone: 978.486.8494 Fax: 978.428.2694 www.imagestreammedical.com
Issued For:
Project Name / Site Name / Site Location:
© 2015 Image Stream Medical
This document is proprietary and shall not be reproduced or redistributed without the express written permission of Image Stream Medical.
Rev./Date:
Project #:
Designed by:
- CF
- 23654b
BC / BN AS NOTED
1.0 / DEC.14.2015
VA Black Hills Health Care
Second Level ORs
Fort Meade, SD
REFERENCE ONLY
NOT FOR CONSTRUCTION
FOR REF. ONLY1.0 DEC.14.2015
SCALE: 3/16" = 1'-0"
SURGERY ROOM #3 (RM# S226) - AV FLOOR / CEILING PLAN
NOTE: RACK LOCATION SAFETY
GROUND SHALL BE COMMON TO
SAFETY GROUND OF RESPECTIVE
OR. RACK LOCATION BRANCH
CIRCUIT SHALL BE EXCLUSIVE
TO TWO (2) DUPLEX OUTLETS.
SEE DRAWING AV-1.01 NOTE 1.
UP.
S
PA
S
PA
S
PA
TV TV TV TV TV TV TV TV
TVTV S
PA
V
PC
AV
SB
NURSES
STATION
S223
CORRIDOR
CS201C
NOTES:
NOTE 1: AV POWER RECEPTACLES (BY EC) SHALL BE PROVIDED WITH
HOSPITAL GRADE OUTLETS WIRED IN ACCORDANCE WITH ALL
APPLICABLE CODES. AV BRANCH CIRCUITS SHALL BE DEDICATED (FOR
LOCAL AV/IT EQUIPMENT ONLY).
NOTE 2: PROVIDE PULL STRING FROM SB TO PC. ENSURE THAT
CABLE PATH FROM SD TO PC IS FREE OF OBSTACLES AND/OR
ABRASIVE EDGES. BREADTH OF CABLE PATH FROM SB TO PC SHALL
BE EQUAL TO OR GREATER TO THAN THAT OF 2" DIAMETER CONDUIT.
NOTE 3: IF STATUS BOARD ENGINE COMPUTER IS TO BE PLACED ATOP
TYPICAL WORKSURFACE, THEN GROMMETTED CABLE PASSAGE THROUGH
WORKSURFACE SHALL BE PROVIDED BY GC OR MILLWORK PROVIDER.
NOTE 4:THE DVI-D CABLE CAN NEITHER BE PULLED
THROUGH PLENUMS, NOR RETURN-AIR SPACES, WITHOUT ENCLOSED
WIREWAY CONSISTENT WITH 2" EMT.
IF REQUIRED, SAME SHALL BE PROVIDED BY EC.
SYMBOL LEGEND
DESKTOP STATUS BOARD MONITORSB
RECESSED SIMPLEX (CLOCK) OUTLET (BY EC) BEHIND
DISPLAY ON DEDICATED 15-20A CIRCUIT FOR ISM STATUS
BOARD DISPLAYAV
DUPLEX OUTLET (BY EC) FOR STATUS BOARD ENGINE
ON SAME DEDICATED 15-20A CIRCUIT AS DISPLAY
(SEE NOTE 1.)AV
(2) DATA DROPS (BY FACILITY): (1) ACTIVE AND (1) FUTURE
FOR STATUS BOARD DISPLAY, PC AND ACCESSORIES. ADJACENT
TO PASS-THROUGH WALL PLATE.2
STATUS BOARD ENGINEPC
18" A.F.F.
FLOOR
ISM STATUS BOARD DISPLAY:
LOCATION TO BE COORDINATED
WITH ROOM FURNITURE. SB
AV12
TYPICAL WORKSURFACE
(SEE NOTE 3.)
PC
CEILING
AV-2.01
CONDUIT AND
ELECTRICAL
Status Board
Drawing / Sheet Number:
Drawing Title:
System / Room:
Reviewed by:
Drawn by:
Quote #:
Scale:
Drawing History
Rev. Date Comment
One Monarch Drive Littleton, MA 01460
Phone: 978.486.8494 Fax: 978.428.2694 www.imagestreammedical.com
Issued For:
Project Name / Site Name / Site Location:
© 2015 Image Stream Medical
This document is proprietary and shall not be reproduced or redistributed without the express written permission of Image Stream Medical.
Rev./Date:
Project #:
Designed by:
- CF
- 23654b
BC / BN AS NOTED
1.0 / DEC.14.2015
VA Black Hills Health Care
Second Level ORs
Fort Meade, SD
REFERENCE ONLY
NOT FOR CONSTRUCTION
FOR REF. ONLY1.0 DEC.14.2015
SCALE: NTS
STATUS BOARD DISPLAY - AV FLOOR / CEILING PLAN
SCALE: 3/16" = 1'-0"
STATUS BOARD DISPLAY - AV CONDUIT / ELEC. ELEVATION
| Model |
| MFP |
| OR1 |
| ORS 2-3 |
| SBrd |
File details come from the government source that posted it. Updated .