About this file

This is an electrical equipment schedule document that inventories motor control center (MCC) loads and configurations across multiple buildings at a VA facility. The spreadsheet details four separate MCCs distributed across Buildings 1D, 8, and 12, with specific information on each unit's voltage rating (480V), amperage capacity (ranging from 400-600 amps), manufacturer (Siemens, Westinghouse, or Cutler-Hammer), location within the facility, and the connected electrical loads by disconnect switch position. The Building 1D MCCs (BEMCC1, 1EMCC2, 1MCC2, and 2EMCC-1) service various HVAC loads including air handling units, exhaust fans, compressors, and cooling tower systems. Building 8's MCCA (Siemens, 400 amps) controls boiler equipment, condensing pumps, and related heating systems. Building 12's BEMCC (Cutler-Hammer, 600 amps) primarily feeds water and medical air/vacuum systems for the facility.

This baseline electrical panel schedule serves as reference documentation for the Building 12 Pump Power Relocation project (Solicitation 36C26126R0050) issued by the VA Sierra Nevada Health Care System. The MCC schedule is incorporated as Attachment 2 in Amendment 0001 and establishes the existing electrical infrastructure parameters for contractors bidding on the project. The solicitation, set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB), requires relocation of pump power onto the existing Building 12 MCC and installation of a manual transfer switch to provide emergency power capability. Contractors must use this schedule as the baseline for post-award panel updates, red-line modifications, and one-line diagram revisions required under the Statement of Work Section 4.

View the file

Other files

File Type Posted
36C26126R0050 0002.docx DOCX document
36C26126R0050 0001.docx DOCX document
Bldg 12 Basement Pump Power Brief Routing Diagram.pdf PDF
GNHA 9-18-19.xls XLS spreadsheet
36C26126R0050_1.docx DOCX document
S02- Specification 013526-2024-05.docx DOCX document
S02 - VAAR 852.219-75.pdf PDF
S02- Specification 260541-2026-01.docx DOCX document
S02- Specification 010000-2021-11.docx DOCX document
S02 - RFI FORM.docx DOCX document
S02 - Attachment - Price Breakdown Sheet.docx DOCX document
S02 - RNLS Zero Floor Plan.pdf PDF
S02- Specification 260511-2022-11.docx DOCX document
S02 - Key Personnel Attachment for Evaluation.docx DOCX document
S02 - Attachment - EMR Sheet.docx DOCX document
Wage determination NV20260093.docx DOCX document
Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BLDG 1D

MOTOR CONTROL CENTER LOADS

M.C.C. I.D.BEMCC1M.C.C. I.D.1EMCC2
VOLTAGE RATING480VOLTAGE RATING480
AMP RATING600AMP RATING
FED FROMDBHEEAFED FROMDBHEEA
M.C.C. MANUFACTURESIEMENSM.C.C. MANUFACTURESIEMENS
BUILDING1DBUILDING1D
LOCATIONB1542ALOCATIONG2652
LOADS:DESCRIPTIONSWITCH POSITIONLOADS:DESCRIPTIONSWITCH POSITION
DISCONNECT #1HWCP-1ONDISCONNECT #1AHU-10 SUPPLYON
DISCONNECT #2HWCP-6 BD101ONDISCONNECT #2AHU-10 EXHAUSTON
DISCONNECT #3HWCP-7ONDISCONNECT #3RU-7ON
DISONNECT #4/5SPS AIR COMP.ON/ONDISCONNECT #4I.P.P. HOOD SUPPLYON
DISCONNECT #6/7CART LIFT/NOT USEDON/OFFDISCONNECT #5I.P.P. HOOD RETURNON
DISCONNECT #8EMER. GEN. HEATER?ONDISCONNECT #6AC-2OFF
DISCONNECT #7CRF-2OFF
M.C.C. I.D.1MCC2M.C.C. I.D.2EMCC-1
VOLTAGE RATING480VOLTAGE RATING480
AMP RATING600AMP RATING600
FED FROMDBHEEAFED FROMDBHEEA
M.C.C. MANUFACTUREWESTINGHOUSEM.C.C. MANUFACTUREWESTINGHOUSE
BUILDING1DBUILDING1D
LOCATIONG2534LOCATIONG3540
LOADS:DESCRIPTIONSWITCH POSITIONLOADS:DESCRIPTIONSWITCH POSITION
DISCONNECT #1NOT USEDOFFDISCONNECT #1AHU-14 (O.R.)ON
DISCONNECT #2NOT USEDOFFDISCONNECT #2NOT USEDOFF
DISCONNECT #3NOT USEDOFFDISCONNECT #3CWCP-P1ON
DISCONNECT #4NOT USEDOFFDISCONNECT #4CWCP-P2ON
DISCONNECT #5NOT USEDOFFDISCONNECT #5ICU (1D) ISO EXHAUST FANSON
DISCONNECT #6EXHAUST FAN ROOF 5D100ONDISCONNECT #6E.D. TRIAGE NEG. AIR (EF-2)
DISCONNECT #7AC-8 (NOT USED)OFFDISCONNECT #7EF-4ON
DISCONNECT #8NOT USEDOFF
DISCONNECT #9UNKNOWNON

BLDG 8

MOTOR CONTROL CENTER LOADS

M.C.C. I.D.MCCA
VOLTAGE RATING480
AMP RATING400
FED FROMSE0- MB1
M.C.C. MANUFACTURESIEMENS
BUILDING8
LOCATIONN107
LOADS:DESCRIPTIONSWITCH POSITIONLOADS:DESCRIPTIONSWITCH POSITION
DISCONNECT #1CHP-1ONDISCONNECT #6/7COND. PUMP #1ON
DISCONNECT #2EF-5ONDISCONNECT #7COND. PUMP #2ON
DISCONNECT #3BOILER FAN #1ONDISCONNECT #8OIL SKIDON
DISONNECT #4BOILER FAN #2ONDISONNECT #9BOILER #1 F.C. HEATERON
DISCONNECT #5BOILER FAN #3ONDISCONNECT #10MCC SURGE PROTECTIONON

BLDG 12

MOTOR CONTROL CENTER LOADS

M.C.C. I.D.BEMCC
VOLTAGE RATING480
AMP RATING600
FED FROMGEHE VIA ATS-E
M.C.C. MANUFACTURECUTLER-HAMMER
BUILDING12
LOCATIONBLDG 12 BASEMENT
LOADS:DESCRIPTIONSWITCH POSITIONLOADS:DESCRIPTIONSWITCH POSITION
DISCONNECT #112-HWP 1ONDISCONNECT #812- EF 1ON
DISCONNECT #212-HWP 2ONDISCONNECT #9SPACEN/A
DISCONNECT #312-EP 9ONDISCONNECT #10SPACEN/A
DISONNECT #4BLDG 12 MED AIRONDISONNECT #11SPACEN/A
DISCONNECT #5BLDG 12 MED VAC.ONDISCONNECT #12SPACEN/A
DISCONNECT #6SPACEONDISCONNECT #13SPACEN/A
DISCONNECT #7SPACEONDISCONNECT #14SPACEN/A