B65 Electrical Study Table 3.1 - Protective Device Evaluation - 2015.pdf
PDF 15 KB Posted
- Attached to
- Y1DA--CON NRM 653-25-101 Replace Bldg 65 Chillers Federal contract opportunity
- Solicitation number
- 36C26025R0025
About this file
This document is a Protective Device Evaluation table for the VA Roseburg Healthcare System in Roseburg, Oregon, detailing electrical equipment assessment for Building 65. The table provides comprehensive technical data for multiple circuit breakers (CB), fuses (FU), and motor circuit protectors (MCP) across different voltage levels (208V and 480V) and equipment locations including distribution switchboards, chiller buildings, and various panels.
The evaluation categorizes protective devices by building number, device name, bus or equipment designation, and nominal line-to-line voltages. Each entry includes critical electrical parameters such as device rating (kAIC), maximum available short circuit amperage, and percent rating. The status column consistently shows "Adequate" for most entries, with some Motor Circuit Protector (MCP) entries marked as "Inadequate", suggesting potential electrical system components that may require further investigation or replacement. This detailed assessment appears to be part of a broader electrical infrastructure evaluation for the VA facility, likely supporting future maintenance or upgrade planning.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| B65 Generator Addition Mechanical Plan.pdf | ||
| B65 Generator Addition Electrical One-Line.pdf | ||
| B65 Electrical Study One-Line - 2015.pdf | ||
| B65 Chiller Rooms Electrical Floor Plan.pdf | ||
| RFI for Building 65 Replace Chillers at Roseburg COR and Contracting Responses.pdf | ||
| 36C26025R0025 0002.docx | DOCX document | |
| B65 Generator Addition Electrical Plan.pdf | ||
| B65 Chillers Mechanical Plan.pdf | ||
| 653-25-101 - 100 Pecent Specifications-Full Set R3.pdf | ||
| 36C26025R0025 0001.docx | DOCX document | |
| 653-25-101 Chiller Bldg 65 Sign-In Sheet.pdf | ||
| 653-25-101 - 100P Drawings -Full Set.pdf | ||
| CON SOW - 653-25-101 _ Remodel Bldg 65 to Replace Chillers_12.pdf | ||
| Wage Determination Douglas County January 3 2025.pdf | ||
| 36C26025R0025_2.docx | DOCX document | |
| 653-25-101 100 Specifications Full Set R2.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA Roseburg HCS - Roseburg, Oregon Electrical Condition Assessment - Equipment Evaluation
DEVICE
RATING
(kAIC)
MAXIMUM
AVAILABLE 3-PH
SCA (kAIC)
PERCENT
RATING
DEVICE
RATING
(kAIC)
CALCULATED
(kAIC)
PERCENT
RATING
TABLE 3.1 - PROTECTIVE DEVICE EVALUATION
BLDG NO. PROTECTIVE DEVICE NAME
BUS OR EQUIPMENT
DESIGNATION
NOMINAL
L-L VOLTS
INTERRUPTING CLOSE - LATCH
STATUS
65 CB: 65_1HQS1 SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 CB: 65_1HQS2 SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 CB: 65_A Main PNL: 65_A 208 42.00 9.29 22.12 0 0 0 Adequate
65 CB: 65_Air Compressor PNL: 65_A 208 22.00 9.29 42.22 0 0 0 Adequate
65 CB: 65_ATC SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
65 CB: 65_Bldg 60 XFMR SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 CB: 65_Bldg 64 EPSB SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 CB: 65_Bldg 71 SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 CB: 65_Bldg 72 PNL: 65_A 208 25.00 9.29 37.16 0 0 0 Adequate
65 CB: 65_CH-1 SWBD: 65_Chiller Bldg 480 30.00 23.03 76.76 0 0 0 Adequate
65 CB: 65_CH-1 Disc EP: 65_CH-1 480 35.00 20.15 57.58 0 0 0 Adequate
65 CB: 65_CH-2 SWBD: 65_Chiller Bldg 480 30.00 23.03 76.76 0 0 0 Adequate
65 CB: 65_CH-2 Disc EP: 65_CH-2 480 35.00 18.17 51.92 0 0 0 Adequate
65 CB: 65_CH-3 SWBD: 65_Chiller Bldg 480 30.00 23.03 76.76 0 0 0 Adequate
65 CB: 65_CH-3 Disc EP: 65_CH-3 480 35.00 17.42 49.76 0 0 0 Adequate
65 CB: 65_CH-4 MCC: 65_Chiller 4 480 65.00 26.15 40.23 0 0 0 Adequate
65 CB: 65_Chiller #4 MCC SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 CB: 65_Chiller Bldg Main SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
65 CB: 65_Chiller Plant SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 CB: 65_CHP-1 MCC: 65_Chiller 4 480 65.00 26.15 40.23 0 0 0 Adequate
65 CB: 65_CHP-2 MCC: 65_Chiller 4 480 65.00 26.15 40.23 0 0 0 Adequate
65 CB: 65_CT-2 DISC: 65_CT-2 480 14.00 6.20 44.28 0 0 0 Adequate
65 CB: 65_CWP-1 MCC: 65_Chiller 4 480 65.00 26.15 40.23 0 0 0 Adequate
65 CB: 65_Dental SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 CB: 65_EF-1 PNL: 65_A 208 22.00 9.29 42.22 0 0 0 Adequate
65 CB: 65_Glycol Makeup Pump PNL: 65_XCP 208 10.00 1.63 (*N1) 16.35 0 0 0 Adequate
65 CB: 65_P-6 Sump SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
65 CB: 65_P-9 SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
65 CB: 65_PCU SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 CB: 65_PowerLynx Dist Main SWBD: 65_Distribution 480 100.00 31.60 31.60 0 0 0 Adequate
65 CB: 65_T2 SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
65 CB: 65_Tower #1 SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
65 CB: 65_Tower #2 SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
65 CB: 65_Tower #3 SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
Prepared for: Dept. of Veterans Affairs Section 3 Page 305 Prepared by: Wiley|Wilson
VA Roseburg HCS - Roseburg, Oregon Electrical Condition Assessment - Equipment Evaluation
DEVICE
RATING
(kAIC)
MAXIMUM
AVAILABLE 3-PH
SCA (kAIC)
PERCENT
RATING
DEVICE
RATING
(kAIC)
CALCULATED
(kAIC)
PERCENT
RATING
TABLE 3.1 - PROTECTIVE DEVICE EVALUATION
BLDG NO. PROTECTIVE DEVICE NAME
BUS OR EQUIPMENT
DESIGNATION
NOMINAL
L-L VOLTS
INTERRUPTING CLOSE - LATCH
STATUS
65 CB: 65_Tower #4 SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 CB: 65_UH-1 SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
65 CB: 65_UH-1&2 MCC: 65_Chiller 4 480 65.00 26.15 40.23 0 0 0 Adequate
65 CB: 65_UH-2 SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
65 CB: 65_Unk SWBD: 65_Chiller Bldg 480 65.00 23.03 35.43 0 0 0 Adequate
65 CB: 65_Utility Main 1 SWBD: 65_Paralleling Gear 480 100.00 31.69 31.69 0 0 0 Adequate
65 CB: 65_XCP Main PNL: 65_XCP 208 10.00 1.63 (*N1) 16.35 0 0 0 Adequate
65 CB: 65_XFMR & Pnl A SWBD: 65_Distribution 480 65.00 31.60 48.61 0 0 0 Adequate
65 FU: 65_CH-4 DISC: 65_CH-4 480 200.00 22.83 11.42 0 0 0 Adequate
65 FU: 65_CT-3A EP: 65_CT-3 480 200.00 4.82 2.41 0 0 0 Adequate
65 FU: 65_CT-3B EP: 65_CT-3 480 200.00 4.82 2.41 0 0 0 Adequate
65 FU: 65_CT-3C EP: 65_CT-3 480 200.00 4.82 2.41 0 0 0 Adequate
65 FU: 65_CT-3D EP: 65_CT-3 480 200.00 4.82 2.41 0 0 0 Adequate
65 FU: 65_P-3 BUS-0062 480 200.00 21.66 10.83 0 0 0 Adequate
65 FU: 65_P-6 BUS-0068 480 200.00 21.64 10.82 0 0 0 Adequate
65 FU: 65_P-9 VFD DISC: 65_P-9 480 200.00 11.70 5.85 0 0 0 Adequate
65 MCP: 65_Antifreeze P-9 DISC: 65_Antifreeze P-9 208 10.00 0.64 6.37 0 0 0 Adequate
65 MCP: 65_P-1 MCC: 65_MS/MCC 480 10.00 *28.22 (*N1) *282.17 0 0 0 Inadequate
65 MCP: 65_P-2 MCC: 65_MS/MCC 480 10.00 *28.22 (*N1) *282.17 0 0 0 Inadequate
65 MCP: 65_P-3 MCC: 65_MS/MCC 480 10.00 *28.22 (*N1) *282.17 0 0 0 Inadequate
65 MCP: 65_P-4 MCC: 65_MS/MCC 480 10.00 *28.22 (*N1) *282.17 0 0 0 Inadequate
65 MCP: 65_P-5 MCC: 65_MS/MCC 480 10.00 *28.22 (*N1) *282.17 0 0 0 Inadequate
65 MCP: 65_P-6 MCC: 65_MS/MCC 480 10.00 *28.22 (*N1) *282.17 0 0 0 Inadequate
65 MCP: 65_P-6 Sump EP: 65_Pump P-6 Sump 480 65.00 2.82 4.34 0 0 0 Adequate
65 MCP: 65_P-7 MCC: 65_MS/MCC 480 10.00 *28.22 (*N1) *282.17 0 0 0 Inadequate
65 MCP: 65_P-8 MCC: 65_MS/MCC 480 10.00 *28.22 (*N1) *282.17 0 0 0 Inadequate
71 CB: 71_B71 Xfer Sw PNL: 71_Emerg PL EP 480 25.00 20.07 80.29 0 0 0 Adequate
71 CB: 71_B81 Xfer Sw PNL: 71_Emerg PL EP 480 25.00 20.07 80.29 0 0 0 Adequate
72 CB: 72_2A Main PNL: 72_2A 208 65.00 5.36 8.24 0 0 0 Adequate
72 CB: 72_AC-1 PNL: 72_2A 208 10.00 5.36 53.59 0 0 0 Adequate
72 CB: 72_Compactor PNL: 72_2A 208 10.00 5.36 53.59 0 0 0 Adequate
72 CB: 72_Compactor Dumper PNL: 72_2A 208 10.00 5.36 53.59 0 0 0 Adequate
72 CB: 72_Cooler Comp PNL: 72_2A 208 10.00 5.36 53.59 0 0 0 Adequate
72 CB: 72_CU-1 PNL: 72_2A 208 10.00 5.36 53.59 0 0 0 Adequate
Prepared for: Dept. of Veterans Affairs Section 3 Page 306 Prepared by: Wiley|Wilson