Attachment 1 - 692-CSI-101 Drawings.pdf
PDF 30 MB Posted
- Attached to
- Y1DA--692-CSI-101 MRI Site Prep
- Solicitation number
- 36C26025R0023
About this file
This is a set of architectural/engineering drawings related to Project 692-CSI-101 for MRI site preparation at the VA Southern Oregon Rehab Center & Clinics. The drawings are referenced attachments that will be included with solicitation 36C26025R0023, which covers the relocation of a modular MRI and associated doublewide trailer from Vancouver, WA to White City, OR.
The project involves construction services with an estimated value between $1-2 million under NAICS 236220, with a 240-day period of performance. While the drawings were made available, the full solicitation is anticipated for release around December 2, 2024, with proposals due approximately 45 days later. A virtual pre-solicitation conference is scheduled for November 20, 2024, at 1300 Pacific time, with RSVPs required by November 19, 2024, to Meredith.valentine@va.gov.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING INDEX
PAGE # SHEET # SHEET NAME
GENERAL
1 OF 46 G-001 COVER & DRAWING INDEX
CIVIL
2 OF 46 C1.0 TESC AND DEMOLITION PLAN VANCOUVER
3 OF 46 C1.1 TESC AND DEMOLITION PLAN
4 OF 46 C1.2 TESC AND DEMOLITION NOTES AND DETAILS
5 OF 46 C2.0 CIVIL SITE PLAN
6 OF 46 C3.0 NOTES AND DETAILS
STRUCTURAL
7 OF 46 S-001 GENERAL NOTES
8 OF 46 S-002 GENERAL NOTES
9 OF 46 S-100 PLAN VIEW
10 OF 46 S-400 DETAILS
11 OF 46 S-401 DETAILS
ARCHITECTURAL
12 OF 46 A-001 ARCHITECTURAL SYMBOLS & ABBREVIATIONS
13 OF 46 GS101 SITE PLAN -EXISTING DEMOLITION PLAN
14 OF 46 GS202 SITE PLAN -NEW CONSTRUCTION
15 OF 46 AS001 OVERALL DEMO FLOOR & ROOF PLAN -EXISTING
16 OF 46 AS101 FLOOR PLAN -NEW CONSTRUCTION
17 OF 46 AS111 REFLECTED CEILING PLAN -NEW CONSTRUCTION
18 OF 46 AS121 ROOF AND FOUNDATION PLAN -NEW CONSTRUCTION
19 OF 46 AS201 EXTERIOR ELEVATIONS
20 OF 46 AS301 BUILDING SECTIONS
21 OF 46 AS421 INTERIOR ELEVATIONS
22 OF 46 AS501 DETAILS
23 OF 46 AS601 ROOM FINISH SCHEDULE AND WALL TYPE
ELECTRICAL
24 OF 46 E-001 ABBREVIATIONS, GENERAL NOTES, AND SHEET INDEX
25 OF 46 E-002 ELECTRICAL LEGENDS
26 OF 46 ES101a VANCOUVER -SITE PLAN -EXISTING
27 OF 46 ES101b VANCOUVER -SITE PLAN -REVISED
28 OF 46 ED101 VANCOUVER -POWER AND SPECIAL SYSTEMS DEMOLITION PLAN
29 OF 46 ES102a WHITE CITY -SITE PLAN -EXISTING
30 OF 46 ES102b WHITE CITY -SITE PLAN -REVISED
31 OF 46 EP102 WHITE CITY -POWER AND SPECIAL SYSTEMS PLAN
32 OF 46 E-401 ENLARGED ELECTRICAL PLANS
33 OF 46 E-501 WHITE CITY -ELECTRICAL DETAILS
34 OF 46 E-502 WHITE CITY -ELECTRICAL DETAILS
35 OF 46 E-503 WHITE CITY -ELECTRICAL DETAILS
36 OF 46 E-504 WHITE CITY -ELECTRICAL DETAILS
37 OF 46 E-601 VANCOUVER -ONE-LINE DIAGRAM -EXISTING
38 OF 46 E-602 VANCOUVER -ONE-LINE DIAGRAM -REVISED
39 OF 46 E-603 WHITE CITY -ONE-LINE DIAGRAM -PART 1 OF 2 -EXISTING
40 OF 46 E-604 WHITE CITY -ONE-LINE DIAGRAM -PART 2 OF 2 -EXISTING
41 OF 46 E-605 WHITE CITY -ONE-LINE DIAGRAM -PART 1 OF 3 -REVISED
42 OF 46 E-606 WHITE CITY -ONE-LINE DIAGRAM -PART 2 OF 3 -REVISED
43 OF 46 E-607 WHITE CITY -ONE-LINE DIAGRAM -PART 3 OF 3 -REVISED
44 OF 46 E-701 ELECTRICAL SCHEDULES
45 OF 46 E-702 ELECTRICAL SCHEDULES
46 OF 46 E-703 ELECTRICAL SCHEDULES
ARCHITECTURAL
SPEES DESIGN BUILD
23830 PACIFIC HWY S,
KENT, WA 98032
PHONE: (206) 590-2118
DESIGN TEAM
STRUCTURAL
WSP GLOBAL INC.
ELECTRICAL
SPEES DESIGN BUILD
4755 EASTGATE MALL, SUITE 150
SAN DIEGO, CA 98121
PHONE: (760) 705-4256
23830 PACIFIC HWY S,
KENT, WA 98032
PHONE: (206) 590-2118
CIVIL
ETHOS CIVIL
3418 70TH AVE CT W
UNIVERSITY PLACE, WA 98466
PHONE: (910) 916-0540
PROJECT INFORMATION
STATE:
COUNTY:
JURISTICTION:
OWNER:
SITE ZONING:
CONST TYPE:
OCCUPANCY:
CODE ANALYSIS
PROJECT DESCRIPTION
THE PROPOSED DESIGN SHALL RELOCATE
EXISTING MRI PORTABLE MODULAR BUILDING
FROM VANCOUVER VA MEDICAL CENTER TO
WHITE CITY VA MEDICAL CENTER. SITE
PREPARATION WORK SHALL BE DONE IN
WHITE CITY TO ACCOMMODATE NEW
MODULAR BUILDINGS.
APPLICABLE CLINIC
IMAGING SUITE
APPROX SQUARE FEET IN SCOPE
2,000 SF
OREGON
JACKSON
WHITE CITY
GOV, VETERANS AFFAIRS
B
RESOURCE DOCUMENTS
GENERAL NOTES
1. COORDINATE WORK WITH ALL CONTRACT DOCUMENTS, INCLUDING BUT NOT LIMITED TO DRAWINGS &
SPECIFICATIONS.
2. SPECIFICATIONS SHALL SUPERSEDE DRAWINGS IN THE CASE OF ANY CONFLICTING INFORMATION.
BRING TO THE AWARENESS OF AND VERIFY WITH VA COR PRIOR TO PROCEEDING.
3. THE CONTRACTOR AND ANY SUB CONTRACTORS SHALL FAMILIARIZE THEMSELVES WITH EXISTING CONDITIONS AND PROJECT REQUIREMENTS PRIOR TO SUBMITTING A BID OR BEGINNING WORK. NO ALLOWANCES WILL BE MADE ON BEHALF OF THE CONTRACTOR OR SUB-CONTRACTORS FOR FAILURE
TO VISIT THE SITE.
4. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS BEFORE BEGINNING WORK. ANY CONFLICTS BETWEEN EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS SHALL BE BROUGHT
IMMEDIATELY TO THE ATTENTION OF THE COR.
5. ALL WORK SHALL BE PERFORMED WITH A HIGH-LEVEL OF WORKMANSHIP.
6. THE CONTRACTOR SHALL VERIFY ALL PRODUCT TYPES AND QUANTITIES DURING SITE WALK
THROUGH, PRIOR TO PURCHASING ANY MATERIALS, EQUIPMENT, PRODUCTS OR LABOR.
7. THE CONTRACTOR SHALL VERIFY AND COORDINATE WITH ALL INSTALLERS TO ENSURE COMPLIANCE
WITH THE CONTRACT DOCUMENTS.
APPLICABLE PUBLICATIONS
AS AN AGENCY OF THE FEDERAL GOVERNMENT, THE VA IS NOT SUBJECT TO LOCAL IMPOSITIONS OF CODE ENFORCEMENT PROCEDURES ( DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC). THE VA
SHALL FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ).
VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION
GUIDE AND OTHER GUIDANCE ON THE TECHNICAL INFORMATION LIBRARY (TIL). SEE ABOVE.
INTERNATIONAL BUILDING CODE (IBC) 2018.
INTERNATIONAL EXISTING BUILDING CODE (IEBC) 2018.
NATIONAL FIRE PROTECTION AGENCY (NFPA) 101 LIFE SAFETY CODE. NFPA 101 TAKES PRECEDENCE OVER
IBC.
NFPA NATIONAL FIRE CODES, WITH THE EXCEPTION OF NFPA 5000 AND NFPA 900.
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
VA SEISMIC DESIGN REQUIREMENTS, H-18-8.
NATIONAL ELECTRICAL CODE (NEC).
INTERNATIONAL PLUMBING CODE (IPC).
SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS
(ASME) A 17.1.
ASME BOILER AND PRESSURE VESSEL CODE
ASME CODE FOR PRESSURE PIPING
BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE, AMERICAN CONCRETE INSTITUTE AND
COMMENTARY (ACI 318)
MANUAL OF STEEL CONSTRUCTION , LOAD AND RESISTANCE FACTOR DESIGN SPECIFICATIONS FOR
STRUCTURAL STEEL BUILDINGS, AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
ENERGY POLICY ACT OF 2005 (EPACT)
DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND NEW LOW-RESE RESIDENTIAL BUILDINGS, 10 CFR
PARTS 433,434 AND 435.
FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF
UNDERSTANDING (MOU)
EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY AND TRANSPORTATION
MANAGEMENT.
THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS
SECTION 01 01 0 OF THE VA MASTER CONSTRUCTION SPECIFICATION.
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY - ASHRAE STANDARD 62.1 - 2022.
SAFETY STANDARD FOR REFRIGERATION SYSTEMS - ASHRAE STANDARD 15 - 2007.
VAMC APPROVED HARDWARE LOCKING STANDARDS
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
AMERICAN SOCIETY FOR TESTING MATERIALS (ASTM)
FEDERAL COMMUNICATIONS COMMISSION (FCC), ALL REGULATIONS, PROCEDURES AND STANDARDS FOR
TWO-WAY RADIO EQUIPMENT, SYSTEMS AND OPERATION
ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA (IESNA)
INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE)
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO), STANDARDS FOR PROTOCOLS AND
INTERFACES THAT INCLUDE OPEN SYSTEM INTERCONNECTIONS (OSI)
JOINT COMMISSION ON ACCREDITATION OF HEALTHCARE ORGANIZATIONS (JACHO),
ENVIRONMENT OF CARE GUIDELINES AND STANDARDS
FACILITIES GUIDELINES INSTITUTE (FGI): 2010 , OR MOST CURRENT ISSUE, GUIDELINES FOR THE
DESIGN AND CONSTRUCTION OF HEALTH CARE FACILITIES
THE AMERICAN INSTITUTE OF ARCHITECTS (AIA) AND NATIONAL SOCIETY OF PROFESSIONAL
ENGINEERS(NSPE) RECENT ADDITIONS TO THEIR PROFESSIONAL CODES OF ETHICS ENCOURAGING
“ENVIRONMENTALLY RESPONSIBLE DESIGN”
APPLICABLE VA STANDARDS
DESIGN AND CONSTRUCTION PROCEDURES (PG 18-3), TOPIC 1 - CODES, STANDARDS & EXECUTIVE ORDERS
SEPTEMBER 2013
EQUIPMENT GUIDE LISTS (PG 18-5)
ARCHITECTURAL BARRIER ACT ACCESSIBILITY STANDARDS (ABAAS), INCLUDING VA SUPPLEMENT BARRIER
FREE DESIGN GUIDE (PG 18-13)
APPLICABLE DESIGN GUIDE
MRI BUILDING
WHITE CITY VAMC
VANCOUVER VAMC
BUILDING 21
C ST
P L A
IN
B
L V
D
C ST
C ST
BUILDING 28
VA WHITE CITY MRI SITE PREPARATION
WHITE CITY VAMC, 8495 CRATER LAKE HIGHWAY, WHITE CITY, OREGON
PROJECT #: 692-CSI-101
Project Number
Building Number
Drawing Number
Project Title
Project Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
G-001
COVER SHEET & DRAWING INDEX
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
VA WHITE CITY MRI SITE
PREPARATION
8495 CRATER LAKE HWY, WHITE CITY, OREGON
692-CSI-101
05/26/2023 EM JL
100% CONSTRUCTION
DOCUMENT
FACILITY SITE PLAN (WHITE CITY VAMC)
VICINITY PLAN
FACILITY SITE PLAN (VANCOUVER VAMC)
Revisions: Date:
CE
KEYNOTES
REMOVE EXISTING BUILDING LANDING AND STAIRS.
CONTRACTOR SHALL DISCONNECT ALL BUILDING UTILITIES AND CUT,
CAP, AND ABANDON BELOW GRADE.
BUILDING AND ASSOCIATE MECHANICAL EQUIPEMNT TO BE
RELOCATED.
PROTECT EXISTING UTILITY TO REMAIN.
PROTECT EXISTING SITE FEATURE TO REMAIN.
REMOVE AND RELOCATE CHILLER WITH BUILDING RELOCATION.
CONSTRUCTION ENTRANCE, SEE GENERAL NOTE 2.
PROTECT EXISTING BUILDING TO REMAIN.
DEMOLISH EXISTING FENCE.
CLEARING LIMITS NOTE
THE CLEARING LIMITS SHOWN MAY NEED TO BE ADJUSTED TO
PERFORM THE WORK. CONTRACTOR IS RESPONSIBLE FOR
REVIEWING LIMITS AND CONFIRMING SILT FENCE LOCATION PRIOR
TO WORK. ANY ADJUSTMENTS SHALL BE AT THE COST OF THE
CONTRACTOR.
1. CONTRACTOR SHALL PROVIDE INLET PROTECTION AT ALL CATCH
BASINS WITHIN 500 FEET OF THE DISTURBED AREA.
2. IF CONTRACTOR DESIRES AN ALTERNATE CONSTRUCTION ENTRANCE
TO THE SITE. THE PLAN SHALL BE SUBMITTED TO THE ENGINEER OR
PROJECT MANAGER PRIOR TO COMMENCING CONSTRUCTION.
3. CONTRACTOR SHALL STABILIZE THE SITE WITH THE SAME SURFACING
AS EXISTS IN THE SURROUNDING AREA IN THE EXISTING CONDITION.
4. ALL FOUNDATION BOLTS, RE-BAR, AND OTHER PROTRUSIONS SHALL BE
CUT FLUSH.
5. ANY SITE PAVING OR OTHER SITE FEATURES THAT ARE DAMAGED
DURING CONSTRUCTION SHALL BE REPLACED IN KIND.
6. THE CONSTRUCTION STAGING AREA SHALL BE COORDINATED BETWEEN
THE COR AND THE CONTRACTOR.
GENERAL NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA WHITE CITY MRI SITE
PREPARATION
692-CSI-101
N/A
05/26/2023 DGM ACP
Revisions: Date:
100% CONSTRUCTION
DOCUMENTA/E:
SPEES DESIGN BUILD
625 1ST AVE, STE 301
(206) 590-2118
RAY SPEES
ENGINEERING DISCIPLINE:
ETHOS CIVIL
748 MARKET ST, TACOMA, WA 98405
(253) 414-1989
DON MELLOTT
ethoscivil.com info@ethoscivil.com 253.414.1989
34821 C1.0
TESC AND DEMOLITION
PLAN - VANCOUVER SITE
CONTRACTOR SHALL FURNISH, INSTALL, ADJUST, AND MAINTAIN
TEMPORARY 6 FOOT CHAINLINK SECURITY FENCE AT SITE
PERIMETER FOR ENTIRE DURATION OF PROJECT. PERIMETER
SECURITY FENCE SHALL INCLUDE AT LEAST ONE VEHICLE GATE AND
ONE MAN GATE. SECURITY FENCE SHALL INCLUDE, BUT IS NOT
NECESSARILY LIMITED TO, CHAINLINK FABRIC, RAILS, POSTS, GATES,
LOCKS, AND BRACES.
LEGEND
RIGHT-OF-WAY / PROPERTY LINE
CLEARING / PROJECT LIMITS
REMOVE EXISTING ASPHALT
REMOVE EXISTING CONCRETE
REMOVE EXISTING GRAVEL
INLET PROTECTION
SAWCUT LINE
REMOVE EXISTING UTILITY
REMOVE EXISTING TREE
EXISTING TREE TO REMAIN
EXISTING MAJOR CONTOURS
EXISTING MINOR CONTOURS
C1.2
CE 2
C1.2
8495 CRATER LAKE AVE.,WHITE CITY, OREGON
5 6
CE
LEGEND
RIGHT-OF-WAY / PROPERTY LINE
CLEARING / PROJECT LIMITS
REMOVE EXISTING ASPHALT
REMOVE EXISTING CONCRETE
REMOVE EXISTING GRAVEL
INLET PROTECTION
SAWCUT LINE
REMOVE EXISTING UTILITY
REMOVE EXISTING TREE
EXISTING TREE TO REMAIN
EXISTING MAJOR CONTOURS
EXISTING MINOR CONTOURS
KEYNOTES
PRESERVE/PROTECT EXISTING TREE.
REMOVE EXISTING TREE INCLUDING THE STUMP AND ROOTS.
PROTECT EXISTING UTILITY TO REMAIN.
PROTECT EXISTING PAVEMENT TO REMAIN.
CAP EXISTING UTILITY AND ABANDON IN PLACE.
REMOVE AND SALVAGE EXISTING PICNIC TABLE. COORDINATE
RELOCATION WITH THE OWNER.
CONTRACTOR STAGING AREA. THE STAGING AREA SHALL BE
COORDINATED BETWEEN THE COR AND THE CONTRACTOR.
REMOVE EXISTING CONCRETE BUILDING SLAB AND FOOTING.
REMOVE EXISTING POWER STRUCTURE.
CONTRACTOR TO PRESERVE TREE OR REMOVE TREE INCLUDING
STUMP AND ROOTS AS NECESSARY.
PROTECT EXISTING LANDSCAPE AREA TO REMAIN.
CLEARING LIMITS NOTE
THE CLEARING LIMITS SHOWN MAY NEED TO BE ADJUSTED TO
PERFORM THE WORK. CONTRACTOR IS RESPONSIBLE FOR
REVIEWING LIMITS AND CONFIRMING SILT FENCE LOCATION PRIOR
TO WORK. ANY ADJUSTMENTS SHALL BE AT THE COST OF THE
CONTRACTOR.
1. CONTRACTOR SHALL ACQUIRE 1200 SERIES PERMIT FROM THE ROGUE
VALLEY SEWER SERVICE.
2. IF THE EXISTING IRRIGATION SYSTEM IS DAMAGED BY THE
CONTRACTOR, THE CONTRACTOR SHALL REPLACE THE DAMAGED
IRRIGATION SYSTEM IN KIND. SYSTEM SHALL BE BIDDER DESIGNED.
3. THE CONTRACTOR SHALL MAINTAIN A MINIMUM OF 6" OF TOPSOIL AT
ALL AREA TO REMAIN PERVIOUS. THE CONTRACTOR SHALL RESTORE
ALL PERVIOUS AREAS TO BE HYDROSEEDED PRIOR TO SEEDING.
GENERAL NOTES
C1.2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA WHITE CITY MRI SITE
PREPARATION
692-CSI-101
N/A
05/26/2023 DGM ACP
Revisions: Date:
100% CONSTRUCTION
DOCUMENTA/E:
SPEES DESIGN BUILD
625 1ST AVE, STE 301
(206) 590-2118
RAY SPEES
ENGINEERING DISCIPLINE:
ETHOS CIVIL
748 MARKET ST, TACOMA, WA 98405
(253) 414-1989
DON MELLOTT
ethoscivil.com info@ethoscivil.com 253.414.1989
34821 C1.1
TESC AND DEMOLITION
PLAN
CONTRACTOR SHALL FURNISH, INSTALL, ADJUST, AND MAINTAIN
TEMPORARY 6 FOOT CHAINLINK SECURITY FENCE AT SITE
PERIMETER FOR ENTIRE DURATION OF PROJECT. PERIMETER
SECURITY FENCE SHALL INCLUDE AT LEAST ONE VEHICLE GATE AND
ONE MAN GATE. SECURITY FENCE SHALL INCLUDE, BUT IS NOT
NECESSARILY LIMITED TO, CHAINLINK FABRIC, RAILS, POSTS, GATES,
LOCKS, AND BRACES.
CE 2
C1.2
1. PLASTIC SHEETING SHALL HAVE A MINIMUM THICKNESS OF 6 MILS.
2. COVERING SHALL BE INSTALLED AND MAINTAINED TIGHTLY IN PLACE BY USING SANDBAGS
OR TIRES ON ROPES WITH A MAXIMUM 10-FOOT GRID SPACING IN ALL DIRECTIONS. ALL
SEAMS SHALL BE TAPED OR WEIGHTED DOWN FULL LENGTH. SEAMS SHALL HAVE AT
LEAST A 12 INCH OVERLAP.
3. CLEAR PLASTIC COVERING SHALL BE INSTALLED IMMEDIATELY ON AREAS SEEDED
BETWEEN NOVEMBER 1 AND MARCH 31 AND REMAIN UNTIL VEGETATION IS FIRMLY
ESTABLISHED.
4. WHEN COVERING IS USED ON UN-SEEDED SLOPES, IT SHALL BE KEPT IN PLACE UNTIL THE
NEXT SEEDING PERIOD.
5. PLASTIC COVERING SHALL BE BURIED TWO FEET AT THE TOP OF SLOPES IN ORDER TO
PREVENT SURFACE WATER FLOW BENEATH SHEETS.
6. PROPER MAINTENANCE OF COVERING INCLUDES, BUT IS NOT NECESSARILY LIMITED TO,
REGULAR CHECKS FOR AND REPAIRS OF RIPS AND DISLODGED ENDS.
1. ALL LIMITS OF CLEARING AND AREAS OF VEGETATION PRESERVATION AS PRESCRIBED ON
THESE PLANS SHALL BE CLEARLY FLAGGED IN THE FIELD AND OBSERVED DURING
CONSTRUCTION.
2. ALL TEMPORARY SEDIMENTATION AND EROSION CONTROL MEASURES, AND PROTECTIVE
MEASURES FOR SIGNIFICANT TREES SHALL BE INSTALLED PRIOR TO INITIATING ANY
CONSTRUCTION ACTIVITIES.
3. ALL REQUIRED SEDIMENTATION AND EROSION CONTROL FACILITIES MUST BE
CONSTRUCTED AND IN OPERATION PRIOR TO ANY LAND CLEARING AND/OR OTHER
CONSTRUCTION ACTIVITIES TO ENSURE THAT SEDIMENT LADEN WATER DOES NOT ENTER
ANY EXISTING DRAINAGE SYSTEM. THE CONTRACTOR SHALL SCHEDULE AN INSPECTION
OF THE EROSION CONTROL FACILITIES PRIOR TO ANY LAND CLEARING AND/OR OTHER
CONSTRUCTION. ALL EROSION AND SEDIMENT CONTROL FACILITIES SHALL BE MAINTAINED
IN A SATISFACTORY CONDITION UNTIL SUCH TIME THAT CLEARING AND/OR
CONSTRUCTION IS COMPLETED AND THE POTENTIAL FOR ON-SITE EROSION HAS PASSED.
THE IMPLEMENTATION, MAINTENANCE, REPLACEMENT, AND ADDITIONS TO THE EROSION
AND SEDIMENTATION CONTROL MEASURES SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR.
4. THE EROSION AND SEDIMENTATION CONTROL SYSTEM MEASURES DEPICTED ON THESE
PLANS ARE INTENDED TO BE MINIMUM REQUIREMENTS TO MEET ANTICIPATED SITE
CONDITIONS. AS CONSTRUCTION PROGRESSES AND UNEXPECTED OR SEASONAL
CONDITIONS DICTATE, ADDITIONAL MEASURES MAY BE NECESSARY TO ENSURE
COMPLETE SILTATION CONTROL ON THE SITE. DURING THE COURSE OF CONSTRUCTION, IT
SHALL BE THE OBLIGATION AND RESPONSIBILITY OF THE CONTRACTOR TO ADDRESS ANY
NEW CONDITIONS THAT MAY BE CREATED BY CONSTRUCTION RELATED ACTIVITIES AND
TO PROVIDE ADDITIONAL FACILITIES, OVER AND ABOVE THE MINIMUM REQUIREMENTS, AS
MAY BE NEEDED TO PROTECT ADJACENT SITES, SENSITIVE AREAS, NATURAL WATER
COURSES, AND/OR STORM DRAINAGE SYSTEMS.
5. ANY DISTURBED AREA WHICH HAS BEEN STRIPPED OF VEGETATION AND WHERE NO
FURTHER WORK IS ANTICIPATED FOR A PERIOD OF 10 DAYS OR MORE DURING THE DRY
SEASON (MAY 1-SEPT 30) OR 5 DAYS OR MORE IN THE WET SEASON (OCT 1-APRIL 30),
SHALL BE IMMEDIATELY STABILIZED WITH MULCHING, GRASS PLANTING, OR OTHER
APPROVED EROSION CONTROL TREATMENT APPLICABLE TO THE TIME OF YEAR IN
QUESTION. GRASS SEEDING ALONE WILL BE ACCEPTABLE ONLY DURING THE MONTHS OF
MAY THROUGH SEPTEMBER INCLUSIVE. SEEDING MAY PROCEED OUTSIDE THE SPECIFIED
TIME PERIOD WHENEVER IT IS IN THE INTEREST OF THE CONTRACTOR BUT SHALL BE
AUGMENTED WITH MULCHING, NETTING, OR OTHER TREATMENT.
6. NO TEMPORARY OR PERMANENT STOCKPILING OF MATERIALS OR EQUIPMENT SHALL
OCCUR WITHIN CRITICAL AREAS OR ASSOCIATED BUFFERS, OR THE CRITICAL ROOT ZONE
FOR VEGETATION PROPOSED FOR RETENTION.
7. WATER SITE AS NECESSARY TO CONTROL DUST.
8. TOPSOIL SHALL NOT BE PLACED WHILE SUBGRADE IS IN A FROZEN OR MUDDY CONDITION,
WHEN THE SUBGRADE IS EXCESSIVELY WET, OR WHEN CONDITIONS EXIST THAT MAY
OTHERWISE BE DETRIMENTAL TO PROPER GRADING OR PROPOSED SODDING OR
SEEDING.
9. ON-SITE EROSION CONTROL MEASURES SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR. ANY PROBLEMS OCCURRING BEFORE FINAL STABILIZATION OF THE SITE
SHALL BE CORRECTED BY THE CONTRACTOR.
10. IF EROSION OR SEDIMENTATION OCCURS ON ADJACENT SITES, ALL CONSTRUCTION WORK
WITHIN THE PROJECT LIMITS THAT WILL AGGRAVATE THE SITUATION MUST CEASE AND
THE CONTRACTOR SHALL IMMEDIATELY COMMENCE RESTORATION OR MITIGATION
MEASURES. RESTORATION ACTIVITY SHALL CONTINUE UNTIL SUCH TIME AS THE PROBLEM
IS RECTIFIED.
11. ALL EROSION AND SEDIMENTATION CONTROL MEASURES SHOWN ON THESE DRAWINGS
SHALL BE INSTALLED PRIOR TO, OR AS THE FIRST STAGE OF SITE PREPARATION.
12. SHOULD THE TEMPORARY EROSION AND SEDIMENTATION CONTROL MEASURES SHOWN
ON THESE DRAWINGS NOT PROVE ADEQUATE TO CONTROL EROSION AND
SEDIMENTATION, THE CONTRACTOR SHALL INSTALL ADDITIONAL FACILITIES AS
NECESSARY TO PROTECT ADJACENT SITES, SENSITIVE AREAS, NATURAL WATER
COURSES, AND/OR STORM DRAINAGE SYSTEMS.
13. ALL NECESSARY FACILITIES SHALL BE MAINTAINED ON SITE TO PREVENT DEBRIS, DUST, AND MUD FROM ACCUMULATING ON ADJACENT ROADWAYS.
14. RUNOFF SHALL NOT BE ALLOWED TO DRAIN INTO THE STORM DRAINAGE SYSTEM DURING
CONSTRUCTION. PROVIDE TEMPORARY PROTECTION FOR YARD DRAINS AS REQUIRED TO
PREVENT RUNOFF FROM ENTERING THE STORM DRAINAGE SYSTEM.
15. ALL TEMPORARY EROSION AND SEDIMENTATION CONTROL MEASURES SHALL BE
COMPLETELY REMOVED PRIOR TO PROJECT COMPLETION.
TESC NOTES PLASTIC COVERING NOTES
HYDROSEEDING NOTES
1. HYDROSEEDING SHALL BE APPLIED TO ALL DISTURBED NON-PAVED SURFACES, UNLESS
NOTED OTHERWISE.
2. HYDROSEEDING SHALL CONSIST OF RYEGRASS AND SHALL BE APPLIED AT A RATE OF 120
LBS/ACRE.
3. HYDROSEED SHALL INCLUDE A MINIMUM OF 1500 LBS/ACRE OF MULCH WITH 3% TACKIFIER.
IT SHALL ALSO INCLUDE A 10-4-6 FERTILIZER AT A RATE OF 90 LBS/ACRE.
4. SEED BEDS PLANTED BETWEEN MAY 1 AND OCTOBER 31 WILL REQUIRE IRRIGATION AND
OTHER MAINTENANCE AS NECESSARY TO FOSTER AND PROTECT THE ROOT STRUCTURE.
5. FOR SEED BEDS PLANTED BETWEEN OCTOBER 31 AND APRIL 30, ARMORING OF THE SEED
BED WILL BE NECESSARY TO FOSTER AND PROTECT THE ROOT STRUCTURE (E.G.
GEOTEXTILES, JUTE MAT, CLEAR PLASTIC COVERING).
6. BEFORE SEEDING, INSTALL ALL REQUIRED SURFACE RUNOFF CONTROL MEASURES SUCH
AS GRADIENT TERRACES, INTERCEPTOR DIKES, SWALES, LEVEL SPREADERS, AND
SEDIMENTATION BASINS.
7. THE SEED BED SHALL BE FIRM WITH A FAIRLY FINE SURFACE, FOLLOWING SURFACE
ROUGHENING. PERFORM ALL OPERATIONS ACROSS OR AT RIGHT ANGLES TO THE SLOPE.
8. FERTILIZERS ARE TO BE USED ACCORDING TO SUPPLIERS RECOMMENDATIONS. AMOUNTS
USED SHOULD BE MINIMIZED, ESPECIALLY ADJACENT TO WATER BODIES AND WETLANDS.
9. HYDROSEED SHALL NOT BE APPLIED TO AREAS SUBJECT TO WEAR BY CONSTRUCTION
TRAFFIC.
1. DEMOLITION: IT IS THE INTENT OF THE WORK UNDER THIS CONTRACT TO INCLUDE
THE DEMOLITION OF ALL EXISTING BUILDINGS, PAVING, UTILITIES AND OTHER
EXISTING SITE IMPROVEMENTS INCLUDING THEIR UNDERGROUND COMPONENTS
AS INDICATED BY THIS DRAWING AND AS REQUIRED FOR NEW CONSTRUCTION. IT
IS THE CONTRACTOR'S RESPONSIBILITY TO FULLY REVIEW THE SITE CONDITIONS
AND TO CORRELATE THESE OBSERVATIONS WITH THE PROJECT WORK AND
INCLUDE ALL NECESSARY DEMOLITION, WHETHER SHOWN OR NOT, AND INCLUDE
ALL SUCH COSTS IN THE BASE BID.
2. CLEARING: IT IS THE INTENT OF THE WORK UNDER THIS CONTRACT TO CONDUCT
ALL CLEARING NECESSARY TO BE ABLE TO COMPLETE ALL THE WORK OF THIS
PROJECT.
3. CONTRACTOR SHALL LEGALLY DISPOSE OF THE OWNER'S PROPERTY, ALL
DEMOLISHED AND REMOVED MATERIALS, UNLESS INDICATED OTHERWISE.
4. IT IS THE RESPONSIBILITY OF THE CONTRACTOR FOR ENSURING THAT ALL
UTILITIES HAVE BEEN DISCONNECTED PRIOR TO COMMENCING DEMOLITION.
CONTRACTOR SHALL COORDINATE UTILITY DEMOLITION WITH NEW
CONSTRUCTION.
5. COORDINATE POWER DEMOLITION WITH UTILITY PURVEYOR AND ELECTRICAL
PLANS. CONTRACTOR TO ENSURE THAT DEMOLITION OF LINES WILL NOT
COMPROMISE POWER TO OTHER AREAS.
6. COORDINATE GAS DISCONNECTION WITH UTILITY PURVEYOR CONTRACTOR TO
COORDINATE WORK WITH P.S.E. CONTRACTOR TO DEMOLISH ABANDONED
SERVICE. CONTRACTOR TO ENSURE THAT DEMOLITION OF GAS LINES WILL NOT
IMPACT GAS SERVICE TO OTHER AREAS. NO DISRUPTION IN SERVICE ALLOWED.
7. ANY ABANDONED SIDE SEWER(S) SHALL BE PLUGGED OR CAPPED AS SHOWN.
8. UTILITIES TO BE ABANDONED SHALL BE CAPPED. CONTRACTOR SHALL AS-BUILT
LOCATION.
9. PROTECT TREES AND TREE ROOTBALLS SCHEDULED TO REMAIN FROM DAMAGE.
10. CONTRACTOR SHALL ENSURE THAT ADEQUATE FIRE PROTECTION ACCESS IS
PROVIDED TO SITE AND EXISTING STRUCTURES TO REMAIN. CONTRACTOR SHALL
ALSO PROVIDE ADEQUATE FIRE PROTECTION FOR THE NEW BUILDING.
11. CONTRACTOR SHALL MINIMIZE DUST GENERATION ONSITE BY SPRINKLING THE
SITE WITH WATER UNTIL SURFACE IS WET.
12. SAWCUT CONCRETE SIDEWALK AT THE NEAREST JOINT.
DEMOLITION NOTES
48" 36"
24"
NOTES:
1. FILTERS SHALL BE INSPECTED AFTER EACH STORM EVENT AND
CLEANED OR REPLACED WHEN 1/3 FULL.
2. INSTALL INLET PROTECTION IN ALL NEW STORM STRUCTURES THAT
WILL COLLECT STORMWATER AS THEY ARE INSTALLED.
ADAPTOR SKIRT RETRIEVAL STRAP
OVERFLOW (TO PYPASS
PEAK STORM VOLUMES)
EXISTING
CATCH BASIN
GEOTEXTILE
FABRIC
SEDIMENT ACCUMULATION
1 NOT TO SCALE
INLET PROTECTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA WHITE CITY MRI SITE
PREPARATION
692-CSI-101
N/A
05/26/2023 DGM ACP
Revisions: Date:
100% CONSTRUCTION
DOCUMENTA/E:
SPEES DESIGN BUILD
625 1ST AVE, STE 301
(206) 590-2118
RAY SPEES
ENGINEERING DISCIPLINE:
ETHOS CIVIL
748 MARKET ST, TACOMA, WA 98405
(253) 414-1989
DON MELLOTT
ethoscivil.com info@ethoscivil.com 253.414.1989
34821 C1.2
TESC AND DEMOLITION
NOTES AND DETAILS
EGRESS
IN
GRESS/
FULL
W
ID
TH
' M
IN
12" MIN.
1. ROCK PAD MATERIAL SHALL BE 4"-6" QUARRY SPALLS AND MAY BE TOP-DRESSED WITH 1"-3" ROCK.
2. THE ROCK PAD SHALL BE AT LEAST 12 INCHES THICK AND 100 FEET LONG. WIDTH SHALL BE THE FULL WIDTH
OF THE VEHICLE INGRESS AND EGRESS AREA.
3. ADDITIONAL ROCK SHALL BE ADDED PERIODICALLY TO MAINTAIN PROPER FUNCTION OF THE PAD.
4. IF THE PAD DOES NOT ADEQUATELY REMOVE THE MUD FROM THE VEHICLE WHEELS, THE WHEELS SHALL BE
HOSED OFF BEFORE THE VEHICLE ENTERS A PAVED STREET. THE WASHING SHALL BE DONE ON AN AREA COVERED WITH CRUSHED ROCK, AND WASH WATER SHALL DRAIN TO A SEDIMENT RETENTION FACILITY OR
THROUGH A SILT FENCE.
5. GEOTEXTILE SHALL MEET THE FOLLOWING: GRAB TENSILE STRENGTH 200 PSI MIN, GRAB TENSILE LONGATION
30% MAX, MULLEN BURST STRENGTH 400 PSI MIN, AOS 2-45 (U.S. STANDARD SIEVE).
6. THE ROCK PAD SHALL BE REMOVED UPON COMPLETION OF ALL CONSTRUCTION.
100' MIN.
EDGE OF EXISTING PAVEMENT
EXISTING
FRONTAGE ROAD
R=25' MIN
GEOTEXTILE
ROCK PAD
2 NOT TO SCALE
CONSTRUCTION ENTRANCE
MATCH EX: 1326.15
MATCH EX: 1326.16
3.35%
1.5
1.5
1.5
1.5%
FFE: 1327.25
FFE: 1327.25
1TYP
77 8
SSMH #3, 48" Ø
N 291245.39
E 4289226.34
RIM: 1325.91
IE: 1316.40 12" (NE)
IE: 1316.50 12 (SW)
IE: 1316.60 8" (SE)
SSMH #2, 48" Ø
N 291203.35 E 4289266.17
RIM: 1325.89
IE: 1317.17 8" (NW)
IE: 1317.27 8" (NE)
SSMH #1, 48" Ø
N 291240.27 E 4289304.38
RIM: 1325.98
IE: 1317.67 8" (SW)
IE: 1317.77 8" (SE)
IE: 1317.87 6" (NE)
15TYP
15 TYP
1TYP
MATCH EX: 1327.14
MATCH EX: 1328.06
MATCH EX: 1327.80
MATCH EX: 1327.88
MATCH EX: 1327.87
MATCH EX: 1328.17
1.5%
161327.14
1327.14
1327.23
1327.23
1327.14
1327.23
1327.14
1727.23
1.5%
1.5%
4.5%
1327.04
1327.10
1327.82
1327.82
SDCB #1, TYPE 1
N 291259.84
E 4289347.67
RIM: 1326.50
IE: 1324.80 8" (NW)
MATCH EX: 1327.98
MATCH EX: 1327.82
IE: 1324.10 9
1727.14
1727.04
IE: 1324.609
1327.10
1327.10
1326.50
1326.00
1327.23
1326.00
1.5
1.5%
1327.08
1327.08
1.5
18 TYP
0.3 8%
5.8 7%
EG: 1327.77
LEGEND
PROPOSED BUILDING OUTLINE
FENCING - REFER TO ARCHITECTURAL
DRAWINGS.
CEMENT CONCRETE PAVING
WATER PIPING
STORM DRAINAGE PIPING
FOOTING DRAIN
SANITARY SEWER MAIN
FORCE MAIN
UNDERGROUND POWER, SEE ELECTRICAL
PLAN FOR MORE INFORMATION
KEYNOTES
INSTALL SPLASHBLOCK AT DOWNSPOUT AND ROUTE STORMWATER
AWAY FROM BUILDING.
RECONNECT EXISTING UTILITY.
CONNECT NEW 1-INCH PE WATER SERVICE TO EXISTING WATER
MAIN. PROVIDE BRASS 1/4 TURN SHUTOFF VALVE IN DOMESTIC
METER BOX.
PROVIDE NEW SEWER MAIN CONNECTION AT EXISTING 12-INCH
SEWER MAIN WITH AN OVERBUILD MANHOLE. MAINTAIN SERVICE TO
EXISTING SEWER MAIN DURING CONSTRUCTION.
PROVIDE CONCRETE CHILLER PAD AT GRADE. SEE ARCHITECTURAL
SITE PLAN FOR MORE INFORMATION.
PROVIDE SUMP PUMP WITH 24"Ø X 48" DEEP WET WELL WITH SEALED
LID AND INLET/OUTLET SIDEWALL PENETRATIONS FOR FOOTING
DRAIN. ROUTE SUMP PUMP OUTLET WITH 2-INCH PE FORCE MAIN TO
CATCH BASIN. MOUNT CONTROL PANEL TO BUILDING, SEE
ARCHITECTURAL DRAWINGS FOR MORE INFORMATION. COORDINATE
POWER SUPPLY WITH ELECTRICAL ENGINEER. SEE GENERAL SUMP
PUMP AND CONTROL PANEL SELECTION NOTES ON THIS SHEET.
STRUCTURE ELEVATION INFORMATION:
RIM = 1326.50
FOOTING DRAIN INLET IE = 1324.00
ALARM ON = 1323.66
PUMP ON = 1323.16
PUMP OFF = 1322.75
BOTT OF WET WELL = 1322.50
ROUTE PROPOSED SEWER SERVICE UNDER BUILDING AND CONNECT
ALL PROPOSED DRAINS WITHIN BUILDING.
ROUTE PROPOSED WATER SERVICE UNDER BUILDING AND CONNECT
ALL PROPOSED FIXTURES WITHIN BUILDING.
CONNECT TO EXISTING CATCH BASIN. CORE DRILL AND GROUT
STRUCTURE AS NECESSARY.
RE-ROUTE EXISTING IRRIGATION LINE. MATCH PIPE SIZE AND PIPE
TYPE IN KIND.
MINIMIZE EXCAVATION IMPACT TO EXISTING TREE ROOTS.
NEW 6-INCH SEWER SERVICE, PVC SDR 35 @ 2.00% MIN.
NEW 8-INCH SEWER MAIN, PVC SDR 35 @ 1.00% MIN.
CONTRACTOR SHALL POTHOLE EXISTING UTILITY TO VERIFY INVERT
ELEVATION. CONTACT THE ENGINEER IF EXISTING INVERT ELEVATION
IS DIFFERENT THAN SHOWN.
PROVIDE EXTENDED BUILDING FOOTING AS NECESSARY TO
MAINTAIN EXISTING GRADE OUTSIDE OF THE BUILDING FOOTPRINT.
PROVIDE CRAWL SPACE EXCAVATION PER BUILDING
MANUFACTURERS RECOMMENDATION.
RE-ROUTE EXISTING STORM AND POWER LINE. MATCH PIPE SIZE AND
PIPE TYPE IN KIND. PVC PIPE SHALL HAVE THRUSTBLOCKS AT ALL
BENDS. SEE ELECTRICAL PLANS FOR MORE INFORMATION ON
POWER ROUTING.
NEW 8-INCH STORM LINE, DIP CL52 @ 1.00% MIN.
IMPACT BARRIER BOULDERS 3' TALL X 4' DEEP X 5 WIDE, 9'
ON-CENTER MAXIMUM SPACING. CONTRACTOR SHALL PLACE
BOULDERS SUCH THAT A 4' MIN ACCESS PATH TO THE NEW BUILDING
IS PROVIDED.
FENCE PER ARCHITECTURAL PLANS.
PROVIDE SUMP PUMP FOR ELECTRICAL VAULT MEETING THE SUMP
PUMP SELECTION NOTES ON THIS SHEET. ROUTE SUMP PUMP
OUTLET WITH 2-INCH PE FORCE MAIN TO CATCH BASIN. PROVIDE
POST MOUNTED CONTROL PANEL WITH ALARM PER CONTROL PANEL
NOTES ON THIS SHEET. SEE ELECTRICAL PLAN FOR MORE
INFORMATION.
PROVIDE 48" DIAMETER CONCRETE DRY WELL WITH PERFORATED
BASE AND 5' TALL PERFORATED RISER. DRY WELL PERFORATIONS
SHALL BE 2-3/8" DIAMETER HOLES. STRUCTURE SHALL HAVE FLAT
TOP WITH 7" TALL 25" DIAMETER CAST IRON ACCESS COVER.
STRUCTURE SHALL BE SURROUNDED WITH 1' THICK WASHED
DRAINAGE FILL PER SPECIFICATIONS. COMPACT WASHED DRAINAGE
FILL UNDER STRUCTURE TO 95%. CONNECT 2" FORCE MAIN TO WET
WELL RISER.
EXISTING MINOR CONTOURS
EXISTING MAJOR CONTOURS
PROPOSED MINOR CONTOUR
PROPOSED MAJOR CONTOUR
SPOT ELEVATION
SLOPE
123.45
3:1OR1.0%
CLEANOUT
CATCH BASIN TYPE 1
1. PROVIDE PIPE BEDDING AND BACKFILL PER DETAIL
GENERAL NOTES
C3.0
C3.0
C3.0
C3.0
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA WHITE CITY MRI SITE
PREPARATION
692-CSI-101
N/A
05/26/2023 DGM ACP
Revisions: Date:
100% CONSTRUCTION
DOCUMENTA/E:
SPEES DESIGN BUILD
625 1ST AVE, STE 301
(206) 590-2118
RAY SPEES
ENGINEERING DISCIPLINE:
ETHOS CIVIL
748 MARKET ST, TACOMA, WA 98405
(253) 414-1989
DON MELLOTT
ethoscivil.com info@ethoscivil.com 253.414.1989
34821 C2.0
CIVIL SITE PLAN
SUMP PUMP SHALL MEET THE FOLLOWING CRITERIA:
· 3/10 HP, 115 V MOTOR, OIL FILLED, HERMETICALLY SEALED
· CAST IRON SWITCH CASE, MOTOR AND PUMP HOUSING
· CORROSION RESISTANT POWDER COATED EPOXY FINISH
· ENGINEERED THERMOPLASTIC OR CAST IRON BASE
· ENGINEERED GLASS FILLED PLASTIC IMPELLER WITH METAL INSERT OR
CAST IRON IMPELLER
· STAINLESS STEEL SCREWS, SWITCH GUARD AND HANDLE
· UPPER AND LOWER OIL FED CAST IRON SLEEVE BEARINGS
· 1-1/2" NPT DISCHARGE
· PASSES 1/2" SPHERICAL SOLIDS
· WITHOUT INLET/OUTLET SCREENS
· SOLID BUOYANT NEOPRENE FLOATS OR SOLID STATE FLOATS W/ ALARM
· UL LISTED 3-WIRE CORD TO BE DIRECTLY WIRED TO CONTROL PANEL
· MINIMUM OF 5-INCHES OF PUMPING DEPTH
· PUMP OUTLET PIPING SHALL HAVE BACKWATER CHECK VALVE
SUMP PUMP SELECTION NOTES
SUMP PUMP CONTROL PANEL SHALL MEET THE FOLLOWING CRITERIA:
· 115 V
· 7 - 15 AMPS
· CIRCUIT BREAKER DISCONNECT
· NEMA 4X ENCLOSURE WITH HINGED COVER AND LOCKING LATCH
· TERMINAL STRIP
· ALARM HORN (83 TO 85 DECIBEL RATING)
· HORN SILENCE SWITCH TO ALARM ON/OFF
· PUMP RUN INDICATOR LIGHT
· (3) 20 FOOT CONTROL FLOAT SWITCHES
· CONTROL PANEL SHALL BE COMPATIBLE WITH SUMP PUMP
CONTROL PANEL SELECTION NOTES
BEFORE INSTALLING ANY BUILDING FOUNDATIONS, CONTRACTOR
SHALL EMPLOY A LICENSED GEOTECHNICAL ENGINEER TO OBSERVE
ALL BUIILDING FOUNDATION SUBGRADES. GEOTECHNICAL ENGINEER
SHALL DOCUMENT THAT UNDERLYING SOILS ARE FIRM AND
UNYIELDING AND MEET THE PROJECT SPECIFICATIONS.
SUBGRADE
CEMENT CONCRETE PAVEMENT
4"
CRUSHED SURFACING BASE COURSE OR
BEDDING PER SPECIFICATIONS
2"
NOTES:
1. DEPTHS INDICATED ARE COMPACTED THICKNESS.
2. CEMENT CONCRETE PAVEMENT SHALL CONSIST OF PORTLAND CEMENT CONCRETE WITH A
MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI AND A MINIMUM RUPTURE MODULUS OF 580
PSI.
3. ALL BASE MATERIAL SHALL BE COMPACTED TO A MINIMUM DENSITY OF 95% BASED ON THE
MODIFIED PROCTOR MAXIMUM DRY DENSITY PER ASTM D-1557.
4. SUBGRADE SHALL BE COMPACTED TO A FIRM AND UNYIELDING CONDITION PRIOR TO
PLACEMENT OF ANY PAVEMENT LAYERS. ANY LOCALIZED ZONES OF SOFT, ORGANIC-RICH,
OR DEBRIS-LADEN SOILS SHOULD BE OVEREXCAVATED AND REPLACED WITH STRUCTURAL
FILL MATERIAL.
5. RECYCLED CONCRETE IS NOT ACCEPTABLE.
NOTES:
1. BACKFILL MATERIAL SHALL NOT HAVE ROCKS OR PARTICLES LARGER THAN 1" WITHIN 12" OF THE PIPE.
BACKFILL MATERIAL SHALL BE PLACED IN 8" MAXIMUM LOOSE LIFTS AND COMPACTED TO 95% MAXIMUM
DRY DENSITY PER MODIFIED PROCTOR TEST (ASTM D-1557).
2. CONSTRUCT ALL STORM AND ROOF DRAINS IN CONFORMANCE WITH THIS DETAIL UNLESS NOTED
OTHERWISE ON THE PLANS.
3. ALL TRENCH EXCAVATIONS SHALL BE SLOPED, SHORED, SHEETED, BRACED, OR OTHERWISE
SUPPORTED IN COMPLIANCE WITH OSHA REGULATIONS AND LOCAL ORDINANCES.
4. IF ORGANIC MATERIAL IS ENCOUNTERED DURING UTILITY EXCAVATION, OVEREXCAVATE TRENCH TO INCREASE PIPE BEDDING DEPTH TO 18" OR MORE AS REQUIRED TO COMPACT BEDDING TO FIRM AND
UNYIELDING CONDITION.
BACKFILL WITH BANK RUN GRAVEL
FOR TRENCH BACKFILL OR
SUITABLE NATIVE MATERIAL
0.15 x DIA OR 4" MIN
PAVEMENT, BASE COURSE AND
SUBBASE PER PAVING SHEETS
8" TYP
RIGID
(DI, CONC)
FLEXIBLE
(CPEP, CMP, PVC)
PIPE AS SPECIFIED ON
PLAN OR SPECS
1.5 x I.D. + 18"
24" MIN
PIPE BEDDING PER
SPECIFICATIONS
6"
DI
A
6" MIN
4"Ø PERFORATED PVC SDR35
WITH PERFORATIONS DOWN. INVERT
SHALL BE AT OR BELOW THE BASE OF
THE PERIMETER FOOTINGS OR
GRADE BEAMS.
SURFACING PER PLAN
MIRAFI 140N NON-WOVEN GEOTEXTILE
FABRIC OR APPROVED EQUIVALENT
PLACED A MINIMUM OF 6" FROM FOOTING
DRAIN PIPE.
WASHED DRAINAGE FILL PER
SPECIFICATIONS
WASHED DRAINAGE FILL PER
SPECIFICATIONS
CAST IRON RING AND LOCKING COVER
SEWER
NOTES:
1. PIPE MATERIAL PER PLAN.
2. PIPE DIAMETER PER PLAN.
3. ABS TO PVC USE PVC ADAPTOR
OR FERNCO w/STAINLESS STEEL
CLAMPS OR APPROVED EQUAL.
4. PVC TO CAST IRON OR
CONCRETE USE FERNCO
w/STAINLESS STEEL CLAMPS OR
APPROVED EQUAL.
DRILL & TAP (SPLITTING THE
SEAM) SET MADE BOLT- DOWN
WITH 3/8" SS ALLEN- HEAD
BOLTS - 2 PLACES
"SEWER" LETTERING FOR SANITARY SEWER;
"STORM" LETTERING FOR STORM DRAINAGE
1"
1/8" RAISE - 1/2" WIDE BORDER
7"
7-3/4" 8-3/4" 15"
4"
5/8" 10" 9"
4-3/4"
2'-0"
3000 PSI CLASS C
CONCRETE (TYP)
12"Ø
FIBER JOINT PACKING
45° (1/8) BEND
PROVIDE
WATER
TIGHT PLUG
1. BARE GALVANIZED METAL SHALL NOT BE USED FOR MATERIALS THAT CONVEY
STORMWATER, SUCH AS ROOFS, CANOPIES, SIDING, GUTTERS, DOWNSPOUTS,
ROOF DRAINS AND PIPES. ANY GALVANIZED MATERIALS SHALL HAVE AN INERT,
NON-LEACHALBE FINISH, SUCH AS BAKED ENAMEL, FLUOROCARBON PAINT (SUCH
AS KYNAR OR HYLAR), FACTORY-APPLIED EPOXY, PURE ALUMINUM, OR ASPHALT
COATING. ACRYLIC PAINT, POLYESTER PAINT, FIELD-APPLIED, AND PART ZINC
(SUCH AS GALVALUME) COATINGS ARE NOT ACCEPTABLE.
2. BURIED UTILITIES ARE SHOWN IN THEIR APPROXIMATE LOCATION. PRIOR TO
INSTALLATION OF ANY PROJECT IMPROVEMENTS, CONTRACTOR SHALL VERIFY
LOCATION AND ELEVATION OF EXISTING UTILITIES. IN THE EVEN T OF ANY
DISCREPANCY FROM THE INFORMATION PRESENTED ON THESE PLANS,
CONTRACTOR SHALL NOTIFY THE DESIGN ENGINEER.
3. CONSTRUCT ALL UTILITIES IN CONFORMANCE WITH THE STORM AND ROOF DRAIN
TRENCH SECTION DETAIL UNLESS NOTED OTHERWISE.
4. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT QUANTITY AND LOCATION OF
DOWNSPOUTS. ALL DOWNSPOUTS SHALL BE SPLASHBLOCKED TO PROVIDE
POSITIVE DRAINAGE AWAY FROM THE BUILDING.
5. ALL STORM PIPES CONNECTING TO CONCRETE STRUCTURES SHALL BE GROUTED
TO ASSURE CONNECTION AT STRUCTURE IS WATERTIGHT.
6. ROOF AND FOOTING DRAIN TIGHT LINES ARE LOCATED ON DRAWINGS FOR
CLARITY AND ARE TO BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES.
ALL STORM DRAINAGE AND ROOF DRAIN LINE CLEANOUTS SHALL COMPLY WITH
THE CLEANOUT DETAIL.
7. ALL STORM DRAINAGE PIPE SHALL BE CPEP UNLESS NOTED OTHERWISE.
8. ALL TYPE 2 CATCH BASINS SHALL HAVE AN INSIDE DIAMETER OF 48" UNLESS
NOTED OTHERWISE.
STORM DRAINAGE NOTES
1 NOT TO SCALE
CONCRETE PAVING
3 NOT TO SCALE
TYPICAL TRENCH SECTION 4 NOT TO SCALE
CLEANOUT
2 NOT TO SCALE
FOOTING DRAIN
BUILDING FOOTING
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
VA WHITE CITY MRI SITE
PREPARATION
692-CSI-101
N/A
05/26/2023 DGM ACP
Revisions: Date:
100% CONSTRUCTION
DOCUMENTA/E:
SPEES DESIGN BUILD
625 1ST AVE, STE 301
(206) 590-2118
RAY SPEES
ENGINEERING DISCIPLINE:
ETHOS CIVIL
748 MARKET ST, TACOMA, WA 98405
(253) 414-1989
DON MELLOTT
ethoscivil.com info@ethoscivil.com 253.414.1989
34821 C3.0
NOTES AND DETAILS
S-001
GENERAL NOTES
CODES AND STANDARDS
1. 2018 INTERNATIONAL BUILDING CODE W/ VETERANS AFFAIRS AMENDMENTS
2. VA SEISMIC DESIGN REQUIREMENTS, H-18-8 NOVEMBER 1, 2019 REVISED MAY 1ST 2020
3. ASCE 7-16 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES
4. ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
5. TMS 402-16 BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES
6. AISC 360-16 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
7. AISC 341-16 SEISMIC PROVISIONS FOR STEEL BUILDINGS
8. AWS D1.1 2015 STRUCTURAL WELDING CODE - STEEL
9. AWS D1.3 2008 STRUCTURAL WELDING CODE - SHEET STEEL
10. RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS SPECIFICATION FOR STRUCTURAL JOINTS USING HIGH-STRENGTH
BOLTS
11. AISI S100-16 NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS
12. AISI S240-15 NORTH AMERICAN STANDARD FOR COLD-FORMED STEEL STRUCTURAL FRAMING
13. AISI S400-15 S1 NORTH AMERICAN STANDARD FOR SEISMIC DESIGN OF COLD-FORMED STEEL STRUCTURAL SYSTEMS WITH
SUPPLEMENT 1
GENERAL
1. CONTRACTOR SHALL BE RESPONSIBLE FOR MEANS, METHODS, TECHNIQUES, SEQUENCES, AND PROCEDURES REQUIRED
TO PERFORM THE WORK.
2. CONTRACTOR-INITIATED CHANGES REQUIRE BOTH DESIGNER OF RECORD AND GOVERNMENT APPROVAL AND SHALL BE SUBMITTED IN WRITING TO THE CONTRACTING OFFICER'S REPRESENTATIVE FOR APPROVAL PRIOR TO FABRICATION OR
CONSTRUCTION.
3. DIMENSIONS AND DETAILS SHALL BE VERIFIED BY THE CONTRACTOR PRIOR TO FABRICATION AND CONSTRUCTION. THIS INCLUDES, BUT IS NOT LIMITED TO, COORDINATING WITH THE CONTRACT DRAWINGS ON THE EXISTING BUILDING DIMENSIONS, SIZE AND LOCATION OF OPENINGS THROUGH CONCRETE, VERIFYING SIZE AND LOCATION OF MECHANICAL AND ELECTRICAL OPENINGS WITH THE RESPECTIVE SUBCONTRACTOR, AS WELL AS COORDINATING INSERTS AND
ATTACHMENTS FOR THE USE OF OTHER TRADES.
4. DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. TYPICAL DETAILS AND NOTES SHOWN ON DRAWINGS SHALL APPLY UNLESS NOTED OTHERWISE. TYPICAL DETAILS MAY NOT NECESSARILY BE INDICATED ON THE PLANS BUT SHALL STILL APPLY AS SHOWN OR DESCRIBED IN THE DETAILS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO CHOOSE THE APPROPRIATE TYPICAL DETAIL FROM THOSE PROVIDED. THE CONTRACTOR SHALL SUBMIT PROPOSED ALTERNATE DETAILS TO THOSE PROVIDED WITH RELATED CALCULATIONS TO THE ENGINEER FOR
APPROVAL PRIOR TO DETAILING OR USE.
5. SHOP DRAWING REVIEW: BY SUBMITTING THE SHOP DRAWINGS, THE CONTRACTOR REPRESENTS THAT THEY HAVE DETERMINED AND VERIFIED MATERIALS, FIELD MEASUREMENTS, AND RELATED FIELD CONSTRUCTION CRITERIA (MEANS, METHODS, TECHNIQUES, SEQUENCES, OPERATIONS OF CONSTRUCTION, AND SAFETY PRECAUTIONS AND PROGRAMS INCIDENTAL THERETO), AND THAT THE CONTRACTOR HAS CHECKED AND COORDINATED THE INFORMATION CONTAINED WITHIN THE SUBMITTAL WITH THE REQUIREMENTS OF THE WORK AND THE CONTRACT DOCUMENTS. REVIEW BY THE ENGINEER SHALL NOT RELIEVE THE CONTRACTOR FROM FULL RESPONSIBILITY FOR THE ACCURACY OF DIMENSIONS AND DETAILS. SUCH REVIEW SHALL NOT CONSTITUTE ACCEPTANCE BY THE ENGINEER OF THE CORRECTNESS OR ADEQUACY OF SUCH SUBMITTALS, NOR A WARRANTY THAT THE SUBMITTALS SATISFY THE REQUIREMENTS OF THE CONTRACT.
DESIGN LOADS
DEAD LOADS:
WEIGHT OF MATERIALS OF CONSTRUCTION AND PERMANENT EQUIPMENT.
LIVE LOADS
EXAM ROOM 50 PSF
RISK CATEGORY IV
SNOW LOAD
GROUND SNOW LOAD 0 PSF
WIND LOADS
WIND LOAD 105 PSF
SEISMIC LOADS
SEISMIC IMPORTANCE FACTOR, IP 1.5
SITE LATITUDE AND LONGITUDE 42.4393421° N,-122.8400281° W
MAPPED SPECTRAL RESPONSE ACCELERATION PARAMETERS
SHORT PERIOD, Ss 0.609g 1 SECOND PERIOD, S1 0.351g SDS 0.51g SD1 0.351g
SITE CLASS C
STRUCTURAL STEEL
1. STEEL CONSTRUCTION SHALL CONFORM TO AISC 360-16 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS AND AISC
341-16 SEISMIC PROVISIONS FOR STRUCTURAL STEEL BUILDINGS.
2. STEEL SHALL CONFORM TO THE FOLLOWING:
3. WORK SHALL BE IN ACCORDANCE WITH AISC 303, AS MODIFIED PER THE PROJECT SPECIFICATIONS.
4. HOLES IN STEEL CUT IN THE FIELD SHALL BE DRILLED, NOT BURNED.
5. ALL STEEL EXPOSED TO WEATHER SHALL BE HOT DIPPED GALVANIZED UNO. REPAIR ANY DAMAGED GALVANIZED STEEL
DUE TO FILED WITH A GALVANIZING REPAIR PAINT ACCORDING TO ASTM A780.
6. ALL GALVANIZED STEEL SHALL CONFORM TO THE MINIMUMS ESTABLISHED BY ASTM A123 OR A153 CLASS D.
7. MINIMUM CONNECTION SHALL BE A TWO-BOLT CONNECTION USING 7/8-INCH DIAMETER A325 BOLTS (TYPE N) IN SINGLE
SHEAR.
8. HIGH-STRENGTH BOLTS SHALL BE INSTALLED, TIGHTENED, AND INSPECTED IN ACCORDANCE WITH IBC, RCSC, AND AISC SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A352 OR A490 BOLTS. THE CRITERIA FOR SNUG-TIGHT
CONNECTIONS SHALL APPLY TO CONNECTIONS UNLESS NOTED OTHERWISE AS SLIP-CRITICAL.
9. BOLTS IN BEAM-TO-BEAM/GIRDER MAY BE SNUG TIGHT, UNLESS SPECIFICALLY CALLED OUT AS SLIP CRITICAL.
CONTRACTOR SHALL SUBMIT TIGHTENING PROCEDURES TO THE ENGINEER/ARCHITECT FOR REVIEW AND APPROVAL.
10. HEADED STUD ANCHORS (HSA) FOR COMPOSITE AND NON-COMPOSITE CONSTRUCTION
A. HEADED STUD ANCHORS SHALL BE 3 4 INCH DIAMETER, TYPE B, CONFORMING TO AWS D1.1, UNLESS NOTED
OTHERWISE.
B. HEADED STUD ANCHORS SHALL BE AUTOMATICALLY END WELDED IN SHOP OR FIELD WITH EQUIPMENT
RECOMMENDED BY STUD MANUFACTURER.
C. WELDING, AND INSPECTION SHALL BE IN ACCORDANCE WITH AWS D1.1.
11. STEEL ANCHORS, TIES AND OTHER MEMBERS EMBEDDED IN CONCRETE OR MASONRY SHALL BE LEFT UNPAINTED AT
INTERIOR, UNEXPOSED CONDITIONS.
12. ITEMS EMBEDDED IN CONCRETE OR MASONRY AND EXPOSED TO EARTH OR WEATHER SHALL BE HOT-DIPPED GALVANIZED
(UNLESS NOTED OTHERWISE):
A. CONCRETE & MASONRY ACCESSORIES OF FERROUS MATERIAL INCLUDING: INSERTS, EMBEDS, AND BRACKETS.
B. PIPE GUARDS, BOLLARDS AND HARDWARE FOR SAME.
C. WHERE NOTED AS "GALV".
13. LOCATIONS OF EMBEDDED ITEMS SHALL BE COORDINATED WITH VENDOR'S SHOP DRAWINGS.
14. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING THE SELECTION OF OPTIONAL DETAILS SHOWN ON THE
DRAWINGS.
15. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ERECTION AIDS THAT INCLUDE, BUT ARE NOT LIMITED TO, ERECTION ANGLES, LIFT HOLES, AND OTHER AIDS. REMOVE ERECTION AIDS, INCLUDING ERECTION BOLTS. PLUG WELD HOLES AND
GRIND SMOOTH.
16. MEANS AND METHODS OF ERECTION ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. CONNECTIONS AND DETAILS
DO NOT NECESSARILY SHOW ERECTION AIDS REQUIRED.
STRUCTURAL STEEL WELDING
1. WELDING SHALL BE DONE BY CERTIFIED WELDERS AND IN ACCORDANCE WITH AWS D1.1 AND D1.8.
2. WELD SIZES SHOWN ON THE DRAWINGS ARE MINIMUM AND EFFECTIVE SIZES. INCREASE WELD SIZE TO AWS/AISC MINIMUM SIZES AS REQUIRED FOR CONNECTION MATERIAL. THE MINIMUM WELD SIZE SHALL BE 3/16 INCHES (EFFECTIVE).
3. FIELD WELDING SYMBOLS HAVE NOT NECESSARILY BEEN INDICATED ON THE DRAWINGS. WHERE NO FIELD WELDING IS DETAILED ON THE DRAWINGS, IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE THE USE OF SHOP AND FIELD
WELDS.
4. PARTIAL JOINT PENETRATION (PJP) GROOVE WELDS SHOWN ON THE DRAWINGS REFER TO EFFECTIVE THROAT THICKNESS.
COMPLETE JOINT PENETRATION (CJP) WELDS SHALL BE ULTRASONICALLY TESTED (UT) UPON COMPLETION OF THE CONNECTION, EXCEPT PLATE LESS THAN OR EQUAL TO 5/16 INCH THICK SHALL BE MAGNETIC PARTICLE TESTED (MT).
5. WELDS SHALL BE MADE USING LOW HYDROGEN ELECTRODES WITH TENSILE STRENGTH PER AWS D1.1 AND D1.8 (MINIMUM
70 KSI).
6. WELDING SHALL BE PERFORMED IN STRICT ADHERENCE TO A WRITTEN WELDING PROCEDURE SPECIFICATION (WPS) PER AWS D1.1 AND D1.8. WELDING PROCEDURES SHALL BE SUBMITTED TO THE ENGINEER FOR REVIEW BEFORE STARTING FABRICATION OR ERECTION. COPIES OF THE WPS SHALL BE ON SITE AND AVAILABLE TO WELDERS AND THE SPECIAL
INSPECTOR.
7. WELDS THAT ARE PART OF THE SEISMIC FORCE-RESISTING SYSTEM SHALL HAVE A MINIMUM CHARPY V-NOTCH TOUGHNESS
OF 20 FOOT-POUNDS AT 0 DEGREES FAHRENHEIT.
SHAPE ASTM SPECIFICATION YIELD STRENGTH, Fy [KSI]
WIDE FLANGE A992 50
ANGLE & CHANNEL (UNO) A36 36
PLATE AND BAR STOCK A36 36
PIPE A53 GRADE B 35
STRUCTURAL TUBE (HSS) A500 GRADE D 50
ROUND STRUCTURAL TUBE (HSS) A500 GRADE C 46
OTHER STEEL UNO A572 50
ANCHORAGE TO CONCRETE AND MASONRY
1. EXCEPT WHERE INDICATED ON THE DRAWINGS, POST-INSTALLED ANCHORS SHALL CONSIST OF THE FOLLOWING
ANCHOR TYPES BELOW.
2. ANCHOR CAPACITY USED IN DESIGN SHALL BE BASED ON THE TECHNICAL DATA PUBLISHED IN THE ICC APPROVAL REPORT. SUBSTITUTION REQUESTS MUST INCLUDE ICC ESR REPORT SHOWING COMPLIANCE WITH RELEVANT BUILDING CODE AND INSTALLATION CATEGORY AND BE APPROVED IN WRITING BY THE CONTRACTING
OFFICER'S REPRESENTATIVE/ENGINEER OF RECORD PRIOR TO USE.
3. INSTALL ANCHORS PER THE MANUFACTURER INSTRUCTIONS, AS INCLUDED IN THE ANCHOR PACKAGING.
4. ANCHOR CAPACITY IS DEPENDENT UPON SPACING BETWEEN ADJACENT ANCHORS AND EDGE DISTANCE.
INSTALL ANCHORS IN ACCORDANCE WITH SPACING AND EDGE CLEARANCES INDICATED ON THE DRAWINGS.
5. EXISTING CONSTRUCTION: EXISTING REINFORCING BARS IN THE STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR LOCATIONS. UNLESS NOTED OTHERWISE ON THE DRAWINGS, THE CONTRACTOR SHALL LOCATE THE
POSITION OF THE EXISTING REINFORCING BARS AND AVOID CUTTING.
DRILLED-IN SCREW ANCHORS INTO CONCRETE
1. HILTI KWIK HUS-EZ SCREW ANCHORS PER ICC ESR-3027
2. SIMPSON TITEN HD SCREW ANCHOR PER ICC ESR-2713
3. DEWALT WEDGE-BOLT+ PER ICC ESR-2526
DRILLED-IN EXPANSION ANCHORS INTO CONCRETE
1. HILTI KWIK-BOLT TZ EXPANSION ANCHOR PER ICC ESR-1917
2. SIMPSON STRONG BOLT 2 WEDGE ANCHOR PER ICC ESR-3037
3. DEWALT POWER-STUD+ SD1 MECHANICAL ANCHOR PER ICC ESR-2818
ADHESIVE ANCHORS AND REBAR DOWELING INTO CONCRETE
1. HILTI HIT-HY 200 ADHESIVE ANCHOR SYSTEM PER ICC ESR-3187
2. SIMPSON SET-XP ADHESIVE ANCHOR SYSTEM PER ICC ESR-2508
3. DEWALT PE1000+ ADHESIVE ANCHOR SYSTEM PER ICC ESR-2583
DRILLED-IN SCREW ANCHORS INTO SOLID-GROUTED MASONRY
1. HILTI KWIK HUS-EZ SCREW ANCHORS PER ICC ESR-3056
2. SIMPSON TITEN HD SCREW ANCHOR PER ICC ESR-2713
3. DEWALT SCREW-BOLT+ PER ICC ESR-4042
DRILLED-IN EXPANSION ANCHORS INTO SOLID-GROUTED MASONRY
1. HILTI KWIK-BOLT 3 EXPANSION ANCHOR PER ICC ESR-1385
2. SIMPSON STRONG BOLT 2 WEDGE ANCHOR PER UES ER-240
3. DEWALT POWER-STUD+ SD1 MECHANICAL ANCHOR PER ICC ESR-2966
ADHESIVE ANCHORS AND REBAR DOWELING INTO SOLID-GROUTED MASONRY
1. HILTI HIT-HY 270 ADHESIVE ANCHOR SYSTEM PER ICC ESR-4143
2. SIMPSON SET-XP ADHESIVE ANCHOR SYSTEM PER IAPMO UES ER-265
3. DEWALT AC100+GOLD ADHESIVE ANCHOR SYSTEM PER ICC ESR-3200
4. STEEL ANCHOR ELEMENT SHALL BE ASTM F1554 GRADE 55 THREADED ROD OR STEEL REINFORCEMENT PER
DRAWINGS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
8495 CRATER LAKE HWY., WHITE CITY OREGON
Project Director
Revisions: Date:
692-CSI-101
A/E:
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590-2118
RAY SPEES, PRESIDENT
WSP USA Inc.
10525 Vista Sorrento Parkway Suite 350 San Diego, CA 92121-2704
TEL: 858-500-4500
FAX: 858-500-4501
100% CONSTRUCTION
DOCUMENTS
VA WHITE CITY MRI SITE
PREPARATION
SB DDV
RE
GI
STE
RED
PROFESSIONAL ENGINEER
STATE OF CALI FORNIA
STRUCTURAL
DAN
TE VALDEZ
No. 5752
EXP. 6/30/23
05/26/2023
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
8495 CRATER LAKE HWY., WHITE CITY OREGON
Project Director
Revisions: Date:
692-CSI-101
A/E:
SPEES DESIGN BUILD
625 1ST AVE #301
SEATTLE, WA, 98014
(206) 590-2118
RAY SPEES, PRESIDENT
WSP USA Inc.
10525 Vista Sorrento Parkway Suite 350 San Diego, CA 92121-2704
TEL: 858-500-4500
FAX: 858-500-4501
100% CONSTRUCTION
DOCUMENTS
VA WHITE CITY MRI SITE
PREPARATION
SB DDV
RE
GI
STE
RED
PROFESSIONAL ENGINEER
STATE OF CALI FORNIA
STRUCTURAL
DAN
TE VALDEZ
No. 5752
EXP. 6/30/23
05/26/2023 S-002
GENERAL NOTES
STATEMENT OF STRUCTURAL SPECIAL INSPECTION
1. SPECIAL INSPECTION SHALL CONFORM TO SPECIFICATION SECTION 01 45 35 AND CHAPTER 17 OF THE IBC
2. SPECIAL INSPECTIONS AND ASSOCIATED TESTING SHALL BE PERFORMED BY AN INSPECTION AND TESTING AGENCY
MEETING THE REQUIREMENTS OF SPECIFICATION SECTION 01 45 35.
3. STRUCTURAL OBSERVATION FOR SEISMIC RESISTANCE IS NOT REQUIRED PER IBC SECTION 1704.6.1.
4. STRUCTURAL OBSERVATION FOR WIND RESISTANCE IS NOT REQUIRED PER IBC SECTION 1704.6.2.
5. SPECIAL INSPECTION FOR WIND RESISTANCE IS NOT REQUIRED PER IBC SECTION 1705.11.
& AND
@ AT
ADDL ADDITIONAL
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
APPROX APPROXIMATE
AR ANCHOR RODS
ARCH ARCHITECT
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AVG AVERAGE
BAL BALANCE
BLDG BUILDING
BLKG BLOCKING
BOT BOTTOM
BRG BEARING
BTWN BETWEEN
C CHANNEL
CFS COLD-FORMED STEEL
CG CENTER OF GRAVITY
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONSTR CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CTR CENTER
db NOMINAL BAR DIAMETER
DBL DOUBLE
DEMO DEMOLISH
DET DETAIL
DIA OR Ø DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DIST DISTANCE
DL DEAD LOAD
DWG DRAWING
E EAST
EA EACH
EF EACH FACE
EL ELEVATION
ELEC ELECTRIC
EMBED EMBEDMENT
ENGR ENGINEER
EQ EQUAL
EQUIV EQUIVALENT
EW EACH WAY
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
f'c COMPRESSIVE STRENGTH OF CONCRETE
FD FLOOR DRAIN
FIN FINISH(ED)
FIN FLR FINISHED FLOOR
FLG FLANGE
FLR FLOOR
FND FOUNDATION
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FOS FACE OF STUD, FACE OF STEEL
FRMG FRAMING
FS FAR SIDE
FT FOOT, FEET
FTG FOOTING
Fu STEEL TENSILE STRENGTH
FV FIELD VERIFY
Fy STEEL YEILD STRENGTH
GA GAUGE
GALV GALVANIZED
HDG HOT-DIP GALVANIZED
HORIZ HORIZONTAL
HS HIGH STRENGTH
HSA HEADED STUD ANCHOR
HT HEIGHT
HSS HOLLOW STRUCTURAL SECTIONS (STEEL)
I MOMENT OF INERTIA
ID INSIDE DIAMETER
IJ ISOLATION JOINT
IN INCH
INFO INFORMATION
INT INTERIOR
JBE JOIST BEARING ELEVATION
JT JOINT
kN KILONEWTONS kPa KILOPASCALS
KSI KIPS PER SQUARE INCH
L STEEL ANGLE
LBS POUNDS
LF LINEAR FEET
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATE, LOCATION
LONG LONGINTUDINAL
LSL LONG SLOTTED HOLE
LT GA LIGHT GAUGE
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTL METAL
MPa MEGAPASCALS
# NUMBER
N NORTH
NA NOT APPLICABLE
NF NEAR FACE
No NUMBER
NIC NOT IN CONTRACT
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OPNG OPENING
OPP OPPOSITE
OVS OVERSIZED
OWJ OPEN WEB JOIST
PAF POWDER ACTUATED FASTENERS
PCF POUNDS PER CUBIC FOOT
PEMB PRE-ENGINEERED METAL BUILDING
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PH PHASE
PL PLATE
PLWD PLYWOOD
PNL PANEL
PQR PROCEDURE QUALIFICATION RECORD
PREFAB PREFABRICATED
PROJ PROJECT
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POST TENSIONED
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QTY QUANTITY
R RADIUS
REF REFERENCE
REINF REINFORCE, REINFORCEMENT
REQD REQUIRED
REV REVISION
RO ROUGH OPENING
S SOUTH
SC SLIP-CRITICAL
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SHT SHEET
SIM SIMILAR
SOG SLAB-ON-GRADE
SPA SPACE, SPACING
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STELL
SSL SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUCT STRUCTURAL
SUSP SUSPENDED
SW SHEAR WALL
SYMM SYMMETRICAL
T&B TOP AND BOTTOM
T/ TOP OF
TEMP TEMPORARY
THK THICK
THRU THROUGH
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TRANSV TRANSVERSE
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VOL VOLUME
W WEST
W/ WITH
W/O WITHOUT
WD WOOD
This is the start of the file's text. The full file is on GovTribe.