This is an Asbestos Assessment Report Addendum prepared for the Department of Veterans Affairs, VA Montana Healthcare System, for the Veterans Administration Medical Center in Miles City, Montana, covering Buildings 1, 8, and 20.
The addendum, dated April 20, 2013, modifies the original asbestos assessment completed in March 2011 by providing additional inspection and testing. The original assessment assumed the presence of asbestos-containing floor tile in the Fourth Floor "Victory Insurance" area (Room Numbers 407A, 418B, 425, 425A, 426, 431, 432, 433, 433A, 433B, 434, 434A, 434B, 435, 437, and 438). On March 21, 2013, certified asbestos inspector Tom Heinecke conducted a follow-up inspection and found no floor tiles present in these areas; however, mastic was identified and sampled. Laboratory analysis confirmed no asbestos was detected in the mastic samples. Additionally, the original assessment had identified Tan HVAC Mastic (Material H1.1) in Room #451 without sampling. Heinecke re-inspected this area, reclassified the material, and collected three samples for testing. Results confirmed no asbestos was detected. The analytical testing was performed by Cardno ATC laboratory using EPA Method 600/R-93/11 (PLM analysis), with all six samples analyzed returning results of "None Detected" for asbestos content. The inspector credentials confirm Tom Heinecke's Montana Certification Number MTA0079 and Accreditation Number I-88-1-19.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Morrison-Maierle Project #5218.001
ASBESTOS ASSESSMENT REPORT
Veterans Administration Medical Center
Buildings: 1, 8, and 20 Miles City, Montana
ADDENDUM
Performed under the rules of:
Montana Asbestos Work Practices & Procedures Manual
AND
National Emissions Standards for
Hazardous Air Pollutants (NESHAP)
Original Assessment Date: March 21, 2011 Addendum Date: April 20, 2013
Prepared for:
Department of Veterans Affairs VA Montana Healthcare System 1892 Williams Street P.O. Box 187 Fort Harrison, MT 59636
Original Assessment Prepared by:
CTA Construction & Environmental, LLC
Addendum Prepared by:
Tom Heinecke, P.E.
Morrison-Maierle P.O. Box 8057 1228 Whitefish Stage Road Kalispell, MT 59904-8057 Accreditation Number: I-88-1-19
Montana Certification: MTA0079
Morrison-Maierle Project #5218.001
Executive Summary:
This Addendum is intended to modify the original assessment of the building by providing additional inspection and testing. All other assessments remain unchanged.
The original asbestos assessment prepared by CTA Construction & Environmental was prepared in March of 2011 and assumed asbestos containing floor tile to be present in the Fourth Floor Area defined as “Victory Insurance”. The rooms are identified as Room Numbers 407A, 418B, 425, 425A, 426, 431, 432, 433, 433A, 433B, 434, 434A, 434B, 435, 437, and 438.
On March 21, 2013, Tom Heinecke, a certified asbestos inspector, inspected the floor in the areas listed above and did not find any floor tiles. Mastic was present, however.
The mastic was sampled and sent to a certified laboratory for analysis. The results of the testing indicate no asbestos was detected.
The original asbestos assessment prepared by CTA Construction & Environmental identified Tan HVAC Mastic (Material Identification Number H1.1) to be present in Room #451. In the CTA Assessment, no samples were taken of this material from this Room.
It is believed that there was a simple mistake in identifying the material.
On March 21, 2013, Tom Heinecke, a certified asbestos inspector inspected this area and determined that the material identified as Material H1.1 should have been classified as a different material. Three samples were taken of the material and sent to a certified laboratory for testing. The results confirm that no asbestos was detected in the material.
As a result of the actions outlined above, no asbestos containing flooring materials are present in the “Victory Insurance” area of the building AND no asbestos containing materials are present in Room #451 of the building.
The name, signature, and certification number of the inspector who prepared this report is listed below:
Tom Heinecke, P.E.
Morrison-Maierle P.O. Box 8057 125 Schoolhouse Loop Kalispell, MT 59904-8057 Accreditation Number: I-88-1-19 State: Utah Montana Certification Number: MTA0079
Attachments:
Floor Plan – Sample Locations Test Report Inspector Credentials
ANALYTICAL REPORT
04/01/2013
0015974Order No.:
Report Date:
Project: Miles City VA Hospital
Prepared for:
PO Box 8057 Kalispell, MT 59904
Morrison-Maierle, Inc.
8985 E. Nichols Avenue, Suite 350, Centennial, CO 80112 Ph: 303-799-6100Cardno ATC
PLM REPORT SUMMARY
EPA Method 600/M4-82-020; 600/R-93/11
035.22121.2013.0001
Date Analyzed:
PO Box 8057
Kalispell MT 59904
Morrison-Maierle, Inc.
Sample Date: 03/21/2013
0015974
ATC Job No.:
Miles City VA HospitalProject:
Tom Heinecke
04/01/2013Report Date:
NVLAP Lab Code 102031 AIHA Lab Code 101536
Customer Project No.:
Identification:
Test Method:
N/A
Batch No.:
04/01/2013
Customer:
8985 E. Nichols Avenue, Suite 350
Phone +1 303 799 6100 Centennial, CO 80112 www.cardno.com Fax +1 303 799 3441 www.cardnoatc.com
Lab No. Sample Description / LocationClient No. Asbestos Content
None DetectedMCVA-M1-1 0015974-001 Carpet Mastic, Tan/ Black, 23°C
None DetectedMCVA-M1-2 0015974-002 Carpet Mastic, Tan/ Black, 23°C
None DetectedMCVA-M1-3 0015974-003 Carpet Mastic, Tan/ Black, 23°C
None DetectedMCVA-H1-1 0015974-004 Sealant, Tan, 23°C
None DetectedMCVA-H1-2 0015974-005 Sealant, Tan, 23°C
None DetectedMCVA-H1-3 0015974-006 Sealant, Tan, 23°C
These samples were analyzed by layers. Specific layer or component asbestos content is indicated when relevant. The EPA considers a material to be asbestos containing only if it contains more than one percent asbestos by Calibrated Visual Area Estimation (CVAE). EPA regulations also indicate that Regulated Asbestos Containing Materials (RACM) -- materials which are friable or may become friable -- be further analyzed by point counting when the results indicate less than ten percent asbestos by CVAE. Our laboratory utilizes CVAE on a routine basis and does not include point counting unless specifically requested.
The results may not be reproduced except in full, and should not be used as a scope of work for abatement without consulting with Cardno ATC.
PLM REPORT SUMMARY
EPA Method 600/M4-82-020; 600/R-93/11
035.22121.2013.0001
Date Analyzed:
PO Box 8057
Kalispell MT 59904
Morrison-Maierle, Inc.
Sample Date: 03/21/2013
0015974
ATC Job No.:
Miles City VA HospitalProject:
Tom Heinecke
04/01/2013Report Date:
NVLAP Lab Code 102031 AIHA Lab Code 101536
Customer Project No.:
Identification:
Test Method:
N/A
Batch No.:
04/01/2013
Customer:
8985 E. Nichols Avenue, Suite 350
Phone +1 303 799 6100 Centennial, CO 80112 www.cardno.com Fax +1 303 799 3441 www.cardnoatc.com
PLM samples were analyzed utilizing the Environmental Protection Agency's Test Method: Method for the Determination of Asbestos in Building Materials (EPA 600/R-93/116. July, 1993). Reporting Limit <1% Asbestos. Additional treatment and tests may be required to accurately define composition (i.e. ashing, extractions, acetone treatment, andTEM). Unused portions of samples are archived for one year unless client requests special handling.
Asbestos content of mastic/adhesive is separated from total percent asbestos and other materials.
Laboratory analysis was accomplished utilizing an Olympus BH-2 polarized light microscope. The microscope is equipped with dispersion staining lenses.
Cardno ATC is accredited by NVLAP Bulk Asbestos Sample Quality Assurance Program (Lab Code 102031). Cardno ATC participates in the NVLAP Bulk Asbestos Sample Quality Assurance Program and maintains an in-house QC/QA program for bulk samples whereby 10% of all submitted samples are reanalyzed and documented in a Quality Control Manual. Cardno ATC also participates in a quarterly round robin QC/QA program for bulk samples with several accredited laboratories throughout the United States. Current and past QC/QA program results are available in the laboratory for inspection.
Samples were analyzed by Jeff Lomme, Laboratory Director. Mr. Lomme is a professional geologist who has successfully completed the McCrone Institutes's "Advanced Asbestos Identification" Course.
Approved Signatory :
The non-detection of asbestos fibers in floor tile by PLM is of itself inconclusive. Confirmation by Transmission Electron Microscope (TEM) is recommended for negative floor tile samples.
This report must not be used by the client to claim product endorsements by NVLAP or an agency of the U.S. government.
This test reports only to the items stated.
PLM Analysis Methodology
Laboratory Equipment
Quality Control
Laboratory Personnel
NVLAP LAB CODE 102031-0Jeff Lomme
Sample Location / Sample Description
Asbestos Constituents
Lab ID Non-Asbestos Constituents
(%)Sample #
BATCH NO.
0015974
Collected: 03/21/2013 Comments:Tom HeineckeCollected By:
PO Box 8057 Kalispell MT 59904
Morrison-Maierle, Inc.
Date Received: 03/27/2013 04/01/2013Date Analyzed:
Customer Project No.:
Miles City VA HospitalDescription:
Tom Heinecke
Collection Address:
04/01/2013Date Reported:
NVLAP Lab Code 102031 AIHA Lab Code 101536
Cellulose Fiber (Incom) Synthetic Fiber (Bie)
Carpet Mastic, Tan/ Black, 23°C
None Detected
MCVA-M1-1
10% 15%
Aggregate Tar Binder Binder/Filler
10% 20% 45%
0015974-001
Cellulose Fiber (Incom) Fibrous Glass (ISO) Synthetic Fiber (Bie)
Carpet Mastic, Tan/ Black, 23°C
None Detected
MCVA-M1-2
5% 5% 10%
Aggregate Tar Binder Binder/Filler
15% 40% 25%
0015974-002
Cellulose Fiber (Incom) Synthetic Fiber (Bie)
Carpet Mastic, Tan/ Black, 23°C
None Detected
MCVA-M1-3
10% 5%
Aggregate Tar Binder Binder/Filler
15% 40% 30%
0015974-003
Cellulose Fiber (Incom)
Sealant, Tan, 23°C
None Detected
MCVA-H1-1
5%
Binder/Filler 95%
0015974-004
Cellulose Fiber (Incom)
Sealant, Tan, 23°C
None Detected
MCVA-H1-2
5%
Binder/Filler 95%
0015974-005
Cellulose Fiber (Incom)
Sealant, Tan, 23°C
None Detected
MCVA-H1-3
5%
Binder/Filler 95%
0015974-006
Reviewed by: Page 1 of 1Analyzed by: