This is a NESHAP (National Emissions Standards for Hazardous Air Pollutants) asbestos renovation inspection report for the VA Miles City Medical Campus, conducted on August 7, 2014, by Marc Ingraham (Montana Accreditation MTA 2700-IN, expiring October 27, 2014).

The inspection covered Buildings 2, 3, 5, and 10 at the facility to identify asbestos-containing materials (ACM) prior to renovation activities in compliance with 40 CFR 763 Subpart E requirements. Sixty-four (64) samples were collected and analyzed by CEI Laboratories using Polarized Light Microscopy (PLM) EPA 600 Method. Results identified two materials testing positive for greater than 1% asbestos: popcorn ceiling texture found in Buildings 2 and 3, containing approximately 2% Chrysotile Asbestos. All roofing materials tested negative for asbestos. The popcorn texture is categorized as regulated asbestos-containing material (RACM) requiring Class I abatement by an OSHA competent person accredited by the Montana DEQ Asbestos Control Program. A permit application and at least 10 days' advance notice to regulatory agencies are required before abatement. All other tested materials, including styrofoam, built-up roofing, roof sealant, and miscellaneous materials from all four buildings, returned negative results. The report notes that materials not readily accessible during the occupied building inspection may require additional testing. The inspection was limited to exterior roofing materials and interior popcorn texture; additional areas would require separate testing and evaluation.

View the file

Other files

File Type Posted
13081 VA MC Managment Plan Update Report.pdf PDF
UCS_Asbestos_Bulk_Results_Bldg_1_Miles_City.pdf PDF
36C25926R0047 0002.docx DOCX document
Miles City VA Asbestos Abatement Final Drawings - May 2013 - Volume 1 of 2.pdf PDF
Miles City Asbestos Inspection Report Addendum 4-20-13.pdf PDF
S02-3-10-2021 Past Performance Questionnaire_Blank_Fillable PDF.pdf PDF
36C25926R0047 0001.pdf PDF
436-1948 MILES CITY MISC HVAC AND UTLITIES.pdf PDF
Veterans Hospital_Part7.pdf PDF
Veterans Hospital_Part8.pdf PDF
Veterans Hospital_Part9.pdf PDF
Veterans Hospital_Part11.pdf PDF
VHA PCRA-1.1 Miles City Campus Demolition.pdf PDF
Veterans Hospital_Part2.pdf PDF
Veterans Hospital_Part4.pdf PDF
Veterans Hospital_Part6.pdf PDF
Veterans Hospital_Part10.pdf PDF
Veterans Hospital_Part13.pdf PDF
Veterans Hospital_Part18.pdf PDF
S04 436-24-105 Miles City VA Campus Demolition Site Visit Attendance.pdf PDF
10_436GJ_20_TT110_BUILDING 20 FLOOR PLANS.pdf PDF
0_436GJ_1_TT100_COVER SHEET.pdf PDF
Veterans Hospital_Part1.pdf PDF
Veterans Hospital_Part3.pdf PDF
Veterans Hospital_Part12.pdf PDF
Veterans Hospital_Part14.pdf PDF
Well Information.pdf PDF
12_436GJ_1_TT112_NURSING HOME FLOOR PLANS.pdf PDF
11_436GJ_OPC_TT111_FLOOR PLAN BUILDING OPC - 1ST FLOOR.pdf PDF
7_436GJ_8_TT107_FLOOR PLANS BUILDING 8.pdf PDF
4_436GJ_1_TT104_FLOOR PLAN BUILDING 1 3RD FLOOR.pdf PDF
3_436GJ_1_TT103_SECOND FLOOR PLAN.pdf PDF
2_436GJ_1_TT102_BUILDING 1 CABLE PLANT INFRASTRUCTURE.pdf PDF
Veterans Hospital_Part5.pdf PDF
Veterans Hospital_Part15.pdf PDF
Veterans Hospital_Part16.pdf PDF
Veterans Hospital_Part17.pdf PDF
S04 - 436-24-105 Miles City VA Campus Demolition Site Visit Meeting Doc.pdf PDF
S22- 852.219-75 LOS Certification.pdf PDF
13_436GJ_TT113_SITE PLAN.pdf PDF
9_436GJ_10_TT109_BOILER PLANT FLOOR PLANS.pdf PDF
6_436GJ_3_TT106_FLOOR PLAN BUILDING 3 - 1ST FLOOR.pdf PDF
5_436GJ_1_TT105_FLOOR PLAN BUILDING 1 - 4TH FLOOR.pdf PDF
1_436GJ_1_TT101_MILES CITY MONTANA SYMBOLS LEGEND AND GENERAL NOTES.pdf PDF
SCA Wage Determination 15-5395 12-03-2025.pdf PDF
436-24-105 Miles City Campus Demolition -SPECS.pdf PDF
436-24-105 Miles City Campus Demolition - APPENDIX A.pdf PDF
S22- 852.219-75 LOS Certification.docx DOCX document
36C25926R0047.docx DOCX document
Miles City VA Phase 2 ESA Report -Final 122719.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Marc Ingraham – MTA 2700‐IN

NESHAP

Renovation Inspection

IEI Project Number 14190

Property VA Miles City Medical – Limited Inspections Buildings 2, 3, 5 & 10, Miles City, MT 59301

Inspection Date August 7, 2014

- 1 -

Toll Free (877) 723‐7885 Fax (406) 723‐7886 info@ieimt.com www.ingrahamenvironmental.com

August 19, 2014

VA Montana Healthcare contracted with Ingraham Environmental Inc. (IEI) to perform the NESHAP asbestos identification inspection of certain elements of Buildings 2, 3, 5, & 10 at the Miles City, MT VA Medical Campus.

The purpose of the identification inspection was to identify materials that need to be abated prior to the renovation of the structure pursuant to the NESHAP requirements (40 CFR 763 Subpart E).

The regulations require the owner to have the facility inspected for the presence of asbestos containing material(s) (ACM) prior to construction, renovation or demolition projects and provide the information obtained to all contactors, sub‐contractors and/or employees involved. The State of Montana requires that the inspection be performed by a Montana accredited inspector. Below you will find the scope, date(s) of the inspection(s) and the accreditation(s) of the inspector(s).

Inspection Date: August 7, 2014

Inspector’s Name: Marc Ingraham Montana Accreditation Number: MTA 2700‐IN Expiration Date: October 27, 2014

- 2 -

Asbestos Regulatory Background

The intent of the inspection was to identify suspect materials, assume that materials contain asbestos, collect samples of materials to determine if they are ACM and assess the friability of these materials. Materials that were assumed to contain asbestos or that were identified as containing greater than 1% asbestos were categorized as a regulated asbestos containing material (RACM), Category I Non‐friable ACM or Category II Non‐friable ACM based on the type and the condition of the material.

The National Emissions Standards for Hazardous Air Pollutants (40 CFR Part 61) defines the three categories.

RACMs are:

Friable asbestos materials

Category 1 & 2 non‐friable materials which have become friable

Category 2 non‐friable ACM that will or has been subjected to sanding grinding, cutting or abrading

Category 2 non‐friable ACM that has a high probability of becoming or has become friable by the forces expected to act upon them in the course or demolition or renovation

Category 1 non‐friable materials include gaskets, packings, resilient floor coverings and asphalt roofing products containing more that 1% asbestos.

Category 2 non‐friable materials are all non‐friable materials not included in Category 1.

This asbestos inspection was limited to materials that were readily accessible. The inspection did not include extensive demolition of walls, ceilings, subsurface materials or similarly enclosed or encased building components or equipment, particularly floor to floor pipe chases.

Homogeneous materials are materials that are considered consistent throughout an area of the building based on the material’s appearance, including texture size and color, manufacturers’ labels and or construction era.

Asbestos Containing Building Materials (ACBMs) are placed into one of three general material categories which include surfacing materials, thermal system insulation, and miscellaneous materials. Surfacing materials are spray or trowel applied materials such as plasters, acoustical, or texturing products. Thermal system insulation materials are associated with HVAC systems and include pipe, boiler, tank insulation, duct insulation, seam tape, pipe insulation, and chimney or flue insulation. The final category is the miscellaneous materials which is any material that does not fall into one of the two prior categories. These include, but are not limited to: floor finishes, adhesives, cement asbestos boards, gypsum wall board, ceiling tiles, and window glazing.

After the category of building material is assessed, the condition is determined. Materials are divided into two condition categories: friable and non‐friable. This describes the materials potential to release asbestos fibers.

17.74.352 defines friable asbestos containing materials as any material containing more than 1% asbestos applied on ceilings, walls, structural members, piping, ducting, or any other part of a structure which when dry may be crumbled, pulverized, or reduced to powder by hand pressure. This also includes non‐friable material that may become damaged through such actions as sawing, grinding, abrading or chipping and may become friable and release fibers.

In accordance with state and EPA regulations, any material which test at less than 1% asbestos is not regulated by the state of Montana or the EPA. However, the State of Montana, by EPA reference, requires that any material less than 1% asbestos be confirmed by EPA 600 Method 400 or 1000 Point Count. OSHA safety regulations still apply no matter the asbestos content.

- 3 -

Scope of Inspection

The scope of the inspection included the roofing materials on Buildings 2, 3, 5, & 10. It also included the popcorn texture in texture in Buildings 2 & 3. These are the only areas from which samples were collected. Finally, only the materials listed on the attached chain of custody, described in the assumed materials and recommendation sections below have been inspected. Any materials not inclusive of the aforementioned location has NOT been inspected and will require additional testing. Please provide this information to all persons working in this area.

Assumed Materials

No materials were assumed to be asbestos containing.

Sampling

Testing of the suspect materials that were not assumed to contain asbestos was completed in accordance with state and federal regulation on the date(s) above by Marc Ingraham. These samples were sent to CEI Laboratories to be analyzed by Polarized Light Microscopy (PLM) EPA 600 Method. The report of those samples is attached.

Sixty‐four (64) samples were collected from the buildings. Of those samples, two materials, both popcorn textures found in Buildings 2 & 3 tested positive for greater than 1% asbestos. These materials, and the other materials assumed to be asbestos, and the recommended response actions are summarized on the chart below.

Please provide this report information to your contractor. If they should discover a material that was not readily accessible to the inspector during the occupied building inspection, they will know if it has been tested or if they need to contact IEI for further testing.

- 4 -

Summary & Recommendations

When evaluating the materials listed in the table below please remember that all homogenous materials (materials with the same manufacturing period, with similar size, shape, texture, color and install date) must be considered in the same manner. For example, an asbestos containing tile tested in one location in the building to greater than 1%. If this same tile is found in another area in the building then it too must be considered asbestos containing.

Summary information for the asbestos containing materials identified and general response action recommendations, based on the inspector’s understanding that this facility is intended for renovation, are below.

The following asbestos laden materials were found in the structures. The table below summaries the material(s):

Response action 1 –Regulated Asbestos Materials – Class I abatement required if impacted Buildings 2 & 3 was textured with a regulated asbestos containing texturizing material. This texture (surfacing material) is composed of approximately 2% Chrysotile Asbestos. Regulated materials, greater than three square feet) must be removed by an OSHA competent person, accredited by the Montana DEQ Asbestos Control Program, under an appropriately applied for permit. At this time this material is not recommended to impact this material until abated. If the material must be impacted consult an experienced abatement contractor able to remove the material in the proper manner. Regulated abatements require EPA/DEQ notice and a permit application and at least 10 days prior to abatement. Additional testing may, or may not, reduce the actual square footage of abatement by being able to delineate additional homogenous areas.

All Categories

Again, when evaluating the materials listed in the table above please remember that all homogenous materials (materials with the same manufacturing period, with similar size, shape, texture, color and install date) must be considered in the same manner. For example an asbestos containing tile tested in one location in the building is found to be greater than 1%. If this same type of tile is found in another area in the building then it too must be considered asbestos containing.

Until the time of renovation or abatement, avoid disturbing all asbestos materials. Properly inform all contractors and other employees of the risks associate with these materials. All waste must be properly disposed of according to state and federal regulations.

These recommendations are not intended to be used as removal specifications. It is the owner’s responsibility to provide specific response action information to the proper regulatory agencies; including the Montana DEQ. These specific regulated response actions should be completed by an accredited State of Montana Project Designer prior to any renovation project. Non‐regulated projects do not require notification or permitting, but do require OSHA competent person(s) to oversee the work. It is also the responsibility of the owner to ensure compliance with all Federal and State regulations, statutes, rules and codes.

Please keep this inspection report on site for all renovation or demolition activities covered by this report. Non‐ regulated projects and renovation do not require notifications, however, demolitions and regulated abatements

Samples Material Location Current State

Response Action

2‐1 to 2‐11, 3‐8 to 3‐16, 5‐1 to 5‐15, & 10‐1 to 10‐15

Roofing Material Exterior Buildings 2, 3, 5 & 10 NON ASBESTOS na

2‐12 to 2‐18 & 3‐1 to 3‐7 Popcorn Texture Throughout Buildings 2 & 3* *additional testing may or may not reduce actual square footage of abatement due to being able to delineate additional homogenous zones.

Regulated 1

- 5 -must be notified 10 days in advance of the work being conducted. Please contact IEI for more information on completing the required notifications in a timely manner.

Conclusion Marc Ingraham and Ingraham Environmental Inc. certify this inspection to be comprehensive and in substantial compliance with the requirements of NESHAP and State of Montana Regulations.

During the inspection process the inspector is required to assess the current condition of ACM and determine its potential for disturbance based on foreseeable renovation and/or demolition. There is no precise method to determine these factors. The inspector must rely on judgment and experience. When asked to predict and speculate future condition when determining the potential for disturbance, he will error on the side of public safety and shall choose the category that will provide the highest degree of protection from potential exposure to asbestos fibers.

The provided recommendations and response actions are to provide the client with general guidelines on how to proceed with the scheduled renovations and/or demolition activities. This report is not intended to be used as a design document as is required for an asbestos removal project.

Marc Ingraham and Ingraham Environmental Inc. shall not be held responsible for non‐identification of asbestos containing materials which:

Not common to the construction industry

Require destructive testing, extensive demolition, or disassembly of equipment to access

For information prepared by others.

And for area that were not safely accessible to the inspector.

Asbestos assessment and identification is representative of the day that the inspection was performed. Marc Ingraham and Ingraham Environmental Inc. shall not be held responsible for changed or differing site conditions which may have occurred since the performance of the inspection and shall not be held responsible for the client’s use of this report in determining the renovation or demolition requirements to comply with state and federal regulations. Should you have any additional questions, concerns or clarifications on this report or the inspection, please feel free to contact our offices at your earliest convenience.

Respectfully, Douglas Ingraham Ingraham Environmental Inc.

SAMPLE IDENTIFICATION Chain of Custody

Inspector: MTA# 2865 Exp

Ingraham Environmental Inc.

PO Box 545

Butte MT 59703-0545 8/7/14

1-406-723-7885 info@ingrahamenvironmental.com

Fax 406-723-7886

No Description Notes

2-1

2-2

2-3

2-4

2-5

2-6

2-7

2-8

2-9

2-10 a

2-11 a

2-12 b

2-13 b

2-14 b

2-15 c

2-16 c

2-17 d

2-18 d

Marc Ingraham 10/27/2014

Inspection Date:

Project: 14190 VA Medical

VA Out Building 2

Styrofoam No Asbestos Detected

Result

Styrofoam No Asbestos Detected

Styrofoam No Asbestos Detected

Built up Roofing No Asbestos Detected

Built up Roofing No Asbestos Detected

Built up Roofing No Asbestos Detected

No Asbestos Detected

Roof Sealant No Asbestos Detected

Roof Sealant

Roof Sealant No Asbestos Detected

Ceiling Texture No Asbestos Detected

Ceiling Texture No Asbestos Detected

Ceiling Texture

2% Chrysotile Asbestos

Ceiling Texture

Ceiling Texture

Ceiling Texture

Ceiling Texture

Ceiling Texture

Ceiling Texture mailto:info@ingrahamenvironmental.com

Ingraham Environmental Inc.

PO Box 545

Butte MT 59703-0545 8/7/14

1-406-723-7885 info@ingrahamenvironmental.com

Fax 406-723-7886

No Description Notes

3-1

3-2

3-3

3-4

3-5

3-6

3-7

3-8

3-9

3-10

3-11

3-12

3-13

3-14

3-15

3-16

Marc Ingraham 10/27/2014

Inspection Date:

Project: 14090 VA Medical

VA Out Building 3

Ceiling Texture

Result

2% Chrysotile Asbestos

Ceiling Texture

Ceiling Texture

Ceiling Texture

Ceiling Texture

Ceiling Texture

Built up Roofing No Asbestos Detected

Ceiling Texture

Built up Roofing No Asbestos Detected

Roof Sealant No Asbestos Detected

Built up Roofing No Asbestos Detected

Roof Sealant No Asbestos Detected

Styrofoam No Asbestos Detected

Roof Sealant No Asbestos Detected

Styrofoam No Asbestos Detected

Styrofoam No Asbestos Detected

Ingraham Environmental Inc.

PO Box 545

Butte MT 59703-0545 8/7/14

1-406-723-7885 info@ingrahamenvironmental.com

Fax 406-723-7886

No Description Notes

5-1

5-2

5-3

5-4

5-5

5-6

5-7

5-8

5-9

5-10

5-11

5-12

5-13

5-14

5-15 Roof Sealant No Asbestos Detected

Roof Sealant No Asbestos Detected

Roof Sealant No Asbestos Detected

Built up Roofing Bottom Layer No Asbestos Detected

Built up Roofing Bottom Layer No Asbestos Detected

Built up Roofing Bottom Layer No Asbestos Detected

Buffalo Board No Asbestos Detected

Buffalo Board No Asbestos Detected

Buffalo Board No Asbestos Detected

Built up Roofing No Asbestos Detected

Built up Roofing No Asbestos Detected

Built up Roofing No Asbestos Detected

Styrofoam No Asbestos Detected

Styrofoam No Asbestos Detected

Styrofoam No Asbestos Detected

Result

VA Meducak

VA Out Building 5 Project: 14090

Inspection Date:

Marc Ingraham 10/27/2014

Inspector: MTA# 2865 Exp

Ingraham Environmental Inc.

PO Box 545 Butte MT 59703-0545 8/7/14 1-406-723-7885 info@ingrahamenvironmental.com Fax 406-723-7886

No Description Notes

10-1

10-2

10-3

10-4

10-5

10-6

10-7

10-8

10-9

10-10

10-11

10-12

10-13

10-14

10-15

Marc Ingraham 10/27/2014

Inspection Date:

Project: 14090 VA Medical

VA Out Building 10

Sheetrock No Asbestos Detected

Result

Sheetrock No Asbestos Detected

Sheetrock No Asbestos Detected

Foam Paper No Asbestos Detected

Foam Paper No Asbestos Detected

Foam Paper No Asbestos Detected

No Asbestos Detected

Foam No Asbestos Detected

Foam

Foam No Asbestos Detected

Roof Sealant No Asbestos Detected

Roof Sealant No Asbestos Detected

Roof Sealant No Asbestos Detected

Decking No Asbestos Detected

Decking No Asbestos Detected

Decking No Asbestos Detected

ASBESTOS LABORATORY REPORT

Prepared for

Ingraham Environmental, Inc.

TEL: 866-481-1412

www.ceilabs.com

PROJECT:

CEI LAB CODE:

DATE ANALYZED:

DATE REPORTED:

TOTAL SAMPLES ANALYZED:

# SAMPLES >1% ASBESTOS:

VA Out Building 2

A14-11023

08/13/14

08/13/14

Asbestos Report Summary By: POLARIZING LIGHT MICROSCOPY

PROJECT: VA Out Building 2 CEI LAB CODE: A14-11023

Client ID Lab ID Color Sample Description

ASBESTOS

%Layer

METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020

A1793502 White Styrofoam None Detected2-1

A1793503 White Styrofoam None Detected2-2

A1793504 White Styrofoam None Detected2-3

A1793505 Black Built-Up Roofing None Detected2-4

A1793506 Black Built-Up Roofing None Detected2-5

A1793507 Black Built-Up Roofing None Detected2-6

A1793508 Black Roof Sealant None Detected2-7

A1793509 Black Roof Sealant None Detected2-8

A1793510 Black Roof Sealant None Detected2-9

A1793511 White,Gold Ceiling Texture None Detected2-10

A1793512 White,Gold Ceiling Texture None Detected2-11

A1793513 White,Gold Ceiling Texture Chrysotile2-12 2%

A1793514 White,Gold Ceiling Texture Chrysotile2-13 2%

A1793515 White,Gold Ceiling Texture Chrysotile2-14 2%

A1793516 White,Gold Ceiling Texture Chrysotile2-15 2%

A1793517 White,Gold Ceiling Texture Chrysotile2-16 2%

A1793518 White,Gold Ceiling Texture Chrysotile2-17 2%

A1793519 White,Gold Ceiling Texture Chrysotile2-18 2%

ASBESTOS BULK ANALYSIS

CEI Lab Code: A14-11023 Date Received: 08-08-14 Date Analyzed: 08-13-14 Date Reported: 08-13-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 2

Fibrous

White Styrofoam2-1

A1793502 Heterogeneous

Fibrous Bound

100% Foam None Detected

White Styrofoam2-2

A1793503 Heterogeneous

Fibrous Bound

100% Foam None Detected

White Styrofoam2-3

A1793504 Heterogeneous

Fibrous Bound

100% Foam None Detected

Black Built-Up Roofing2-4

A1793505 25%Heterogeneous

Fibrous Bound

60% 15%

Cellulose Tar Silicates

None Detected

Black Built-Up Roofing2-5

A1793506 25%Heterogeneous

Fibrous Bound

60% 15%

Cellulose Tar Silicates

None Detected

Black Built-Up Roofing2-6

A1793507 25%Heterogeneous

Fibrous Bound

60% 15%

Cellulose Tar Silicates

None Detected

Black Roof Sealant2-7

A1793508 <1%Heterogeneous

Fibrous Bound

25% 75%

Cellulose Calc Carb Binder

None Detected

CEI Lab Code: A14-11023 Date Received: 08-08-14 Date Analyzed: 08-13-14 Date Reported: 08-13-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 2

Fibrous

Black Roof Sealant2-8

A1793509 <1%Heterogeneous

Fibrous Bound

25% 75%

Cellulose Calc Carb Binder

None Detected

Black Roof Sealant2-9

A1793510 <1%Heterogeneous

Fibrous Bound

25% 75%

Cellulose Calc Carb Binder

None Detected

White,Gold Ceiling Texture2-10

A1793511 <1%Heterogeneous

Fibrous Bound

10% 65% 25%

Cellulose Paint Calc Carb Vermiculite

None Detected

White,Gold Ceiling Texture2-11

A1793512 <1%Heterogeneous

Fibrous Bound

10% 65% 25%

Cellulose Paint Calc Carb Vermiculite

None Detected

White,Gold Ceiling Texture2-12

A1793513 <1%Heterogeneous

Fibrous Bound

10% 63% 25%

Cellulose Paint Calc Carb Vermiculite

2% Chrysotile

White,Gold Ceiling Texture2-13

A1793514 <1%Heterogeneous

Fibrous Bound

10% 63% 25%

Cellulose Paint Calc Carb Vermiculite

2% Chrysotile

White,Gold Ceiling Texture2-14

A1793515 <1%Heterogeneous

Fibrous Bound

10% 63% 25%

Cellulose Paint Calc Carb Vermiculite

2% Chrysotile

CEI Lab Code: A14-11023 Date Received: 08-08-14 Date Analyzed: 08-13-14 Date Reported: 08-13-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 2

Fibrous

White,Gold Ceiling Texture2-15

A1793516 <1%Heterogeneous

Fibrous Bound

10% 63% 25%

Cellulose Paint Calc Carb Vermiculite

2% Chrysotile

White,Gold Ceiling Texture2-16

A1793517 <1%Heterogeneous

Fibrous Bound

10% 63% 25%

Cellulose Paint Calc Carb Vermiculite

2% Chrysotile

White,Gold Ceiling Texture2-17

A1793518 <1%Heterogeneous

Fibrous Bound

10% 63% 25%

Cellulose Paint Calc Carb Vermiculite

2% Chrysotile

White,Gold Ceiling Texture2-18

A1793519 <1%Heterogeneous

Fibrous Bound

10% 63% 25%

Cellulose Paint Calc Carb Vermiculite

2% Chrysotile

LEGEND: Non-Anth = Non-Asbestiform Anthophylite Non-Trem = Non-Asbestiform Tremolite Calc Carb = Calcium Carbonate

The detection limit for the method is <1% by visual estimation and 0.25% by 400 point counts or 0.1% by 1,000 point counts.

Due to the limitations of the EPA 600 Method, nonfriable organically bound materials (NOBs) such as vinyl floor tiles can be difficult to analyze via polarizing light microscopy (PLM). EPA recommends that all NOBs analyzed by PLM, and found not to contain asbestos, be further analyzed by Transmission Electron Microscopy (TEM). Please note that PLM analysis of dust and soil samples for asbestos is not covered under NVLAP accreditation.

CEI Labs, Inc. can perform positive stop analysis if requested by customer. However, it is the responsibility of the customer to determine if the samples grouped together are in fact the same type of material and belong to the same homogeneous area.

This report may not be reproduced, except in full, without written approval by CEI LABS. CEI LABS makes no warranty representation regarding the accuracy of client submitted information in preparing and presenting analytical results. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U. S. Government.

ANALYST: APPROVED BY:

Tianbao Bai, Ph.D.

Laboratory Director

Elizabeth Godwin

CEI Labs, 107 New Edition Court, Cary, NC 27511, Phone: (866) 481-1412

METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020

Ingraham Environmental, Inc.

TEL: 866-481-1412

www.ceilabs.com

PROJECT:

CEI LAB CODE:

DATE ANALYZED:

DATE REPORTED:

TOTAL SAMPLES ANALYZED:

# SAMPLES >1% ASBESTOS:

VA Out Building 3

A14-11025

08/12/14

08/12/14

PROJECT: VA Out Building 3 CEI LAB CODE: A14-11025

Client ID Lab ID Color Sample Description

ASBESTOS

%Layer

METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020

A1793535 White Ceiling Texture Chrysotile3-1 2%

A1793536 Sample Not Analyzed per COC3-2

A1793537 Sample Not Analyzed per COC3-3

A1793538 Sample Not Analyzed per COC3-4

A1793539 Sample Not Analyzed per COC3-5

A1793540 Sample Not Analyzed per COC3-6

A1793541 Sample Not Analyzed per COC3-7

A1793542 Black Built-Up Roofing None Detected3-8

A1793543 Black Built-Up Roofing None Detected3-9

A1793544 Black Built-Up Roofing None Detected3-10

A1793545A Black Roof Sealant None Detected3-11

A1793545B Black Felt Paper None Detected

A1793546 Black Roof Sealant None Detected3-12

A1793547 Black Roof Sealant None Detected3-13

CEI Lab Code: A14-11025 Date Received: 08-08-14 Date Analyzed: 08-12-14 Date Reported: 08-12-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 3

Fibrous

White Ceiling Texture3-1

A1793535 3%Homogeneous

Fibrous Loosely Bound

45% 30% 20%

Cellulose Calc Carb Vermiculite Paint

2% Chrysotile

Sample Not Analyzed per COC

3-2 A1793536

Sample Not Analyzed per COC

3-3 A1793537

Sample Not Analyzed per COC

3-4 A1793538

Sample Not Analyzed per COC

3-5 A1793539

Sample Not Analyzed per COC

3-6 A1793540

Sample Not Analyzed per COC

3-7 A1793541

Black Built-Up Roofing3-8

A1793542 30%Homogeneous

Fibrous Bound

60% 10%

Cellulose Tar Binder

None Detected

Black Built-Up Roofing3-9

A1793543 40%Homogeneous

Fibrous Bound

50% 10%

Cellulose Tar Binder

None Detected

Black Built-Up Roofing3-10

A1793544 40%Homogeneous

Fibrous Bound

50% 10%

Cellulose Tar Binder

CEI Lab Code: A14-11025 Date Received: 08-08-14 Date Analyzed: 08-12-14 Date Reported: 08-12-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 3

Fibrous

Black Roof Sealant3-11

A1793545A 2%Homogeneous

Fibrous Bound

60% 38%

Cellulose Calc Carb Binder

None Detected

Black Felt PaperA1793545B 30%Homogeneous

Fibrous Bound

60% 10%

Cellulose Tar Binder

None Detected

Black Roof Sealant3-12

A1793546 2%Homogeneous

Fibrous Bound

60% 38%

Cellulose Calc Carb Binder

None Detected

Black Roof Sealant3-13

A1793547 2%Homogeneous

Fibrous Bound

60% 38%

Cellulose Calc Carb Binder

Non-Trem = Non-Asbestiform Tremolite Calc Carb = Calcium Carbonate

The detection limit for the method is <1% by visual estimation and 0.25% by 400 point counts or 0.1% by 1,000 point counts.

Due to the limitations of the EPA 600 Method, nonfriable organically bound materials (NOBs) such as vinyl floor tiles can be difficult to analyze via polarizing light microscopy (PLM). EPA recommends that all NOBs analyzed by PLM, and found not to contain asbestos, be further analyzed by Transmission Electron Microscopy (TEM). Please note that PLM analysis of dust and soil samples for asbestos is not covered under NVLAP accreditation.

CEI Labs, Inc. can perform positive stop analysis if requested by customer. However, it is the responsibility of the customer to determine if the samples grouped together are in fact the same type of material and belong to the same homogeneous area.

This report may not be reproduced, except in full, without written approval by CEI LABS. CEI LABS makes no warranty representation regarding the accuracy of client submitted information in preparing and presenting analytical results. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U. S. Government.

ANALYST: APPROVED BY:

Tianbao Bai, Ph.D.

Laboratory Director

Sarah Talley

Ingraham Environmental, Inc.

TEL: 866-481-1412

www.ceilabs.com

PROJECT:

CEI LAB CODE:

DATE ANALYZED:

DATE REPORTED:

TOTAL SAMPLES ANALYZED:

# SAMPLES >1% ASBESTOS:

VA Out Building 5

A14-11024

08/12/14

PROJECT: VA Out Building 5 CEI LAB CODE: A14-11024

Client ID Lab ID Color Sample Description

ASBESTOS

%Layer

METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020

A1793520 White Styrofoam None Detected5-1

A1793521 White Styrofoam None Detected5-2

A1793522 White Styrofoam None Detected5-3

A1793523 Black Built-Up Roofing None Detected5-4

A1793524 Black Built-Up Roofing None Detected5-5

A1793525 Black Built-Up Roofing None Detected5-6

A1793526 Brown Buffalo Board None Detected5-7

A1793527 Brown Buffalo Board None Detected5-8

A1793528 Brown Buffalo Board None Detected5-9

A1793529 Black Built-up Roofing Bottom Layer None Detected5-10

A1793530 Black Built-up Roofing Bottom Layer None Detected5-11

A1793531 Black Built-up Roofing Bottom Layer None Detected5-12

A1793532 Black Roof Sealant None Detected5-13

A1793533 Black Roof Sealant None Detected5-14

A1793534 Black Roof Sealant None Detected5-15

CEI Lab Code: A14-11024 Date Received: 08-08-14 Date Analyzed: 08-12-14 Date Reported: 08-13-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 5

Fibrous

White Styrofoam5-1

A1793520 Homogeneous

Non-fibrous Bound

100% Foam None Detected

White Styrofoam5-2

A1793521 Homogeneous

Non-fibrous Bound

100% Foam None Detected

White Styrofoam5-3

A1793522 Homogeneous

Non-fibrous Bound

100% Foam None Detected

Black Built-Up Roofing5-4

A1793523 30%Homogeneous

Fibrous Bound

40% 30%

Cellulose Tar Gravel

None Detected

Black Built-Up Roofing5-5

A1793524 30%Homogeneous

Fibrous Bound

40% 30%

Cellulose Tar Gravel

None Detected

Black Built-Up Roofing5-6

A1793525 30%Homogeneous

Fibrous Bound

40% 30%

Cellulose Tar Gravel

None Detected

Brown Buffalo Board5-7

A1793526 40%Homogeneous

Fibrous Bound

30% 30%

Cellulose Perlite Binder

CEI Lab Code: A14-11024 Date Received: 08-08-14 Date Analyzed: 08-12-14 Date Reported: 08-13-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 5

Fibrous

Brown Buffalo Board5-8

A1793527 40%Homogeneous

Fibrous Bound

30% 30%

Cellulose Perlite Binder

None Detected

Brown Buffalo Board5-9

A1793528 40%Homogeneous

Fibrous Bound

30% 30%

Cellulose Perlite Binder

None Detected

Black Built-up Roofing Bottom Layer

5-10 A1793529

50%Homogeneous

Fibrous Bound

50%Cellulose Tar None Detected

Black Built-up Roofing Bottom Layer

5-11 A1793530

50%Homogeneous

Fibrous Bound

50%Cellulose Tar None Detected

Black Built-up Roofing Bottom Layer

5-12 A1793531

50%Homogeneous

Fibrous Bound

50%Cellulose Tar None Detected

Black Roof Sealant5-13

A1793532 Homogeneous

Non-fibrous Bound

50% 50%

Calc Carb Binder

None Detected

Black Roof Sealant5-14

A1793533 Homogeneous

Non-fibrous Bound

50% 50%

Calc Carb Binder

CEI Lab Code: A14-11024 Date Received: 08-08-14 Date Analyzed: 08-12-14 Date Reported: 08-13-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 5

Fibrous

Black Roof Sealant5-15

A1793534 Homogeneous

Non-fibrous Bound

50% 50%

Calc Carb Binder

Non-Trem = Non-Asbestiform Tremolite Calc Carb = Calcium Carbonate

The detection limit for the method is <1% by visual estimation and 0.25% by 400 point counts or 0.1% by 1,000 point counts.

Due to the limitations of the EPA 600 Method, nonfriable organically bound materials (NOBs) such as vinyl floor tiles can be difficult to analyze via polarizing light microscopy (PLM). EPA recommends that all NOBs analyzed by PLM, and found not to contain asbestos, be further analyzed by Transmission Electron Microscopy (TEM). Please note that PLM analysis of dust and soil samples for asbestos is not covered under NVLAP accreditation.

CEI Labs, Inc. can perform positive stop analysis if requested by customer. However, it is the responsibility of the customer to determine if the samples grouped together are in fact the same type of material and belong to the same homogeneous area.

This report may not be reproduced, except in full, without written approval by CEI LABS. CEI LABS makes no warranty representation regarding the accuracy of client submitted information in preparing and presenting analytical results. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U. S. Government.

ANALYST: APPROVED BY:

Tianbao Bai, Ph.D.

Laboratory Director

Sarah Talley

Ingraham Environmental, Inc.

TEL: 866-481-1412

www.ceilabs.com

PROJECT:

CEI LAB CODE:

DATE ANALYZED:

DATE REPORTED:

TOTAL SAMPLES ANALYZED:

# SAMPLES >1% ASBESTOS:

VA Out Building 10

A14-11022

08/12/14

PROJECT: VA Out Building 10 CEI LAB CODE: A14-11022

Client ID Lab ID Color Sample Description

ASBESTOS

%Layer

METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020

A1793487 White Sheetrock None Detected10-1

A1793488 White Sheetrock None Detected10-2

A1793489 White Sheetrock None Detected10-3

A1793490 Black,White Foam Paper None Detected10-4

A1793491 Black,White Foam Paper None Detected10-5

A1793492 Black,White Foam Paper None Detected10-6

A1793493 White Foam None Detected10-7

A1793494 White Foam None Detected10-8

A1793495 White Foam None Detected10-9

A1793496 Black Roof Sealant None Detected10-10

A1793497 Black Roof Sealant None Detected10-11

A1793498 Black Roof Sealant None Detected10-12

A1793499 Gray Decking None Detected10-13

A1793500 Gray Decking None Detected10-14

A1793501 Gray Decking None Detected10-15

CEI Lab Code: A14-11022 Date Received: 08-08-14 Date Analyzed: 08-12-14 Date Reported: 08-13-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 10

Fibrous

White Sheetrock10-1

A1793487 5% 5%

Homogeneous

Fibrous Bound

60% 30%

Fiberglass Cellulose

Gypsum Binder

None Detected

White Sheetrock10-2

A1793488 5% 5%

Homogeneous

Fibrous Bound

60% 30%

Fiberglass Cellulose

Gypsum Binder

None Detected

White Sheetrock10-3

A1793489 5% 5%

Homogeneous

Fibrous Bound

60% 30%

Fiberglass Cellulose

Gypsum Binder

None Detected

Black,White Foam Paper10-4

A1793490 40% 20%

Homogeneous

Fibrous Bound

30% 10%

Cellulose Fiberglass

Foam Binder

None Detected

Black,White Foam Paper10-5

A1793491 40% 20%

Homogeneous

Fibrous Bound

30% 10%

Cellulose Fiberglass

Foam Binder

None Detected

Black,White Foam Paper10-6

A1793492 40% 20%

Homogeneous

Fibrous Bound

30% 10%

Cellulose Fiberglass

Foam Binder

None Detected

White Foam10-7

A1793493 Homogeneous

Non-fibrous Bound

100% Foam None Detected

CEI Lab Code: A14-11022 Date Received: 08-08-14 Date Analyzed: 08-12-14 Date Reported: 08-13-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 10

Fibrous

White Foam10-8

A1793494 Homogeneous

Non-fibrous Bound

100% Foam None Detected

White Foam10-9

A1793495 Homogeneous

Non-fibrous Bound

100% Foam None Detected

Black Roof Sealant10-10

A1793496 2%Homogeneous

Fibrous Bound

70% 28%

Cellulose Calc Carb Binder

None Detected

Black Roof Sealant10-11

A1793497 2%Homogeneous

Fibrous Bound

70% 28%

Cellulose Calc Carb Binder

None Detected

Black Roof Sealant10-12

A1793498 2%Homogeneous

Fibrous Bound

70% 28%

Cellulose Calc Carb Binder

None Detected

Gray Decking10-13

A1793499 <1%Homogeneous

Fibrous Bound

50% 40% 10%

Cellulose Binder Calc Carb Silicates

None Detected

Gray Decking10-14

A1793500 <1%Homogeneous

Fibrous Bound

50% 40% 10%

Cellulose Binder Calc Carb Silicates

CEI Lab Code: A14-11022 Date Received: 08-08-14 Date Analyzed: 08-12-14 Date Reported: 08-13-14

Client ID Lab ID

Lab Attributes

Lab Description

ASBESTOS

ASBESTOS BULK PLM, EPA 600 METHOD

NON-ASBESTOS COMPONENTS

Non-Fibrous

Client: Ingraham Environmental, Inc.

PO Box 545 Butte, MT 59703-0545

Project: VA Out Building 10

Fibrous

Gray Decking10-15

A1793501 <1%Homogeneous

Fibrous Bound

50% 40% 10%

Cellulose Binder Calc Carb Silicates

Non-Trem = Non-Asbestiform Tremolite Calc Carb = Calcium Carbonate

The detection limit for the method is <1% by visual estimation and 0.25% by 400 point counts or 0.1% by 1,000 point counts.

Due to the limitations of the EPA 600 Method, nonfriable organically bound materials (NOBs) such as vinyl floor tiles can be difficult to analyze via polarizing light microscopy (PLM). EPA recommends that all NOBs analyzed by PLM, and found not to contain asbestos, be further analyzed by Transmission Electron Microscopy (TEM). Please note that PLM analysis of dust and soil samples for asbestos is not covered under NVLAP accreditation.

CEI Labs, Inc. can perform positive stop analysis if requested by customer. However, it is the responsibility of the customer to determine if the samples grouped together are in fact the same type of material and belong to the same homogeneous area.

This report may not be reproduced, except in full, without written approval by CEI LABS. CEI LABS makes no warranty representation regarding the accuracy of client submitted information in preparing and presenting analytical results. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U. S. Government.

ANALYST: APPROVED BY:

Tianbao Bai, Ph.D.

Laboratory Director

Sarah Talley

IEI Project 14190

Miles City VA Medical Campus

Asbestos Sample Locations. Buildings 2, 3, 5, 10

Samples Collected 08/07/2014 from roofs of Buildings 2, 3, 5, 10

Interior Samples Collected from Buildings 2-3.

All Buildings determined to be homogenous unless otherwise specified.

N

Building 3

Sample Numbers 3-1 to 3-16

Building 10

Sample Numbers 10 –1 to 10-15

Building 2

Sample Numbers 2-1 to 2-18

Building 5

Sample Numbers 5-1 to 5-15

14090 Report
14090 Labs & COCs All Buildings
14090 COC - Building 2
14090 COC - Building 3
14090 COC - Building 5
14090 COC - Building 10
Lab Sheet to Use
14090 Labs - Building 2
A14-11023_Asbestos_Report
A14-11023
14090 Labs - Building 3
A14-11025_Asbestos_Report
A14-11025
14090 Labs - Building 5
A14-11024_Asbestos_Report
A14-11024
14090 Labs - Building 10
A14-11022_Asbestos_Report
A14-11022

14190 Drawing

File details come from the government source that posted it. Updated .