TJC Equipment Summary List.xlsx
XLSX spreadsheet 25 KB Posted
- Solicitation number
- 36C25925Q0740
About this file
This is an Equipment Summary List document detailing fire alarm and fire suppression system devices and components across multiple buildings at the VA Salt Lake City Health Care System, organized by equipment performance elements (EP).
The document catalogs supervisory signal devices (EP1) including elevator shunt trip controls and fire pump devices across five buildings; water flow devices and valve tamper switches (EP2) with control valve switches and waterflow devices ranging from 3 to 45 units per building; detection and alarm initiation equipment (EP3) including heat detectors, smoke detectors, manual pull stations, and carbon monoxide detectors with quantities ranging from 1 to 142 units; notification devices (EP4) such as alarm speakers, strobes, visual alarms, and door-locking hardware with quantities up to 304 units; emergency services notification transmission equipment (EP5) with documented testing results showing all alarm, restoration, trouble, and supervisory signals passing across all buildings; sprinkler system main drain tests (EP9) for wet sprinkler systems; fire department connections (EP10) with sprinkler and standpipe fire hose connections; fire pump equipment (EP11) including horizontal split-case pumps rated 500-750 GPM with associated electric motors and controllers; automatic standpipe systems (EP12); kitchen extinguishing systems (EP13); fire and smoke dampers (EP18) totaling up to 431 units in Building 14; smoke-detecting HVAC shutdown devices (EP19) with air-handling units ranging from 1 to 23 units per building; and rolling steel fire doors (EP20). All data reflects inspection and testing dates between January 2022 and September 2025, supporting the ongoing monitoring, inspection, testing, maintenance, and repair services required under solicitation 36C25925Q0740.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EC.02.03.05 EP1
| Supervisory signal devices | |||
| TJC | EC.02.03.05 EP1 | As of: | 1/31/25 |
| Building | Device or System Type | Quantity | |
| 1 | Elevator Shunt Trip Control Power Loss | 4 | |
| 1 | Fire Pump – Phase Reversal Device | 1 | |
| 1 | Fire Pump – Power Device | 1 | |
| 1 | Fire Pump – Running Device | 1 | |
| 3 | Elevator Shunt Trip Control Power Loss | 2 | |
| 5 | Elevator Shunt Trip Control Power Loss | 1 | |
| 14 | Elevator Shunt Trip Control Power Loss | 3 | |
| 14 | Fire Pump Phase Reversal Devices | 1 | |
| 14 | Fire Pump Power Devices | 1 | |
| 14 | Fire Pump Running Devices | 1 | |
| 14 | High- or Low-Pressure Switches | 4 |
EC.02.03.05 EP2
| Water flow devices and Valve tamper switches | |||
| TJC | EC.02.03.05 EP2 | As of: | 6/30/25 |
| Building | Device or System Type | Quantity | |
| 1 | Control Valve Switches | 45 | |
| 1 | Waterflow Devices | 31 | |
| 1 | Sprinkler Waterflow Alarm Devices | 1 | |
| 3 | Control Valve Switches | 16 | |
| 3 | Waterflow Devices | 15 | |
| 3 | Sprinkler Water Control Valve Devices | 3 | |
| 5 | Control Valve Switches | 8 | |
| 5 | Waterflow Devices | 4 | |
| 6 | Control Valve Switches | 3 | |
| 6 | Waterflow Devices | 3 | |
| 14 | Control Valve Switches | 41 | |
| 14 | Waterflow Devices | 23 |
EC.02.03.05 EP3
| Duct, heat, smoke detectors, and manual fire alarm boxes. | |||
| TJC | EC.02.03.05 EP3 | As of: | 1/31/25 |
| Building | Device or System Type | Quantity | |
| 1 | Electromechanical Releasing Device | 2 | |
| 1 | Heat Detectors | 13 | |
| 1 | Manual Pull Stations | 57 | |
| 1 | System Smoke Detectors (P) | 142 | |
| 1 | System Smoke Detectors (P) (Supv) | 45 | |
| 3 | Heat Detectors | 17 | |
| 3 | Manual Pull Stations | 24 | |
| 3 | System Smoke Detectors (P) | 102 | |
| 3 | System Smoke Detectors (P) (Supv) | 13 | |
| 5 | Heat Detectors | 17 | |
| 5 | Manual Pull Stations | 24 | |
| 5 | System Smoke Detectors (P) | 102 | |
| 5 | System Smoke Detectors (P) (Supv) | 13 | |
| 6 | Carbon Monoxide Fire Detectors (Supv) | 2 | |
| 6 | Manual Pull Stations | 16 | |
| 6 | Other Alarm Initiating Devices | 2 | |
| 6 | Other Alarm Initiating Systems | 2 | |
| 6 | System Smoke Detectors (P) | 2 | |
| 6 | System Smoke Detectors (P) (Supv) | 1 | |
| 14 | Heat Detectors | 3 | |
| 14 | Manual Pull Stations | 43 | |
| 14 | System Smoke Detectors (P) | 80 | |
| 14 | System Smoke Detectors (P) (Supv) | 18 |
EC.02.03.05 EP4
| Notification devices (audible & visual), and door- releasing devices | |||
| TJC | EC.02.03.05 EP4 | As of: | 1/31/25 |
| Building | Device or System Type | Quantity | |
| 1 | Alarm Speakers | 61 | |
| 1 | Alarm Speakers w/Strobe | 304 | |
| 1 | Visual Alarms | 42 | |
| 1 | Door Holders and Locking | 33 | |
| 3 | Alarm Horns w/Strobe | 17 | |
| 3 | Visual Alarms | 4 | |
| 3 | Door Holders and Locking | 3 | |
| 5 | Alarm Horns w/Strobe | 19 | |
| 5 | Alarm Speakers w/Strobe | 4 | |
| 5 | Visual Alarms | 4 | |
| 6 | Alarm Horns w/Strobe | 25 | |
| 6 | Visual Alarms | 3 | |
| 14 | Alarm Horns w/Strobe | 3 | |
| 14 | Alarm Speakers | 8 | |
| 14 | Alarm Speakers w/Strobe | 259 | |
| 14 | Visual Alarms | 32 | |
| 14 | Door Holders and Locking | 23 |
EC.02.03.05 EP5
| Emergency services notification transmission equipment | Name of the Activity: | Testing of fire alarm equipment for notifying off-site responders | |||
| TJC | EC 02.03.05 EP5 | As of: | 1/31/25 | ||
| Building | Tests and Inspections | Pass/Fail | |||
| 1 | Alarm signal | Pass | |||
| 1 | Alarm restoration | Pass | |||
| 1 | Trouble signal | Pass | |||
| 1 | Trouble restoration | Pass | |||
| 1 | Supervisory signal | Pass | |||
| 1 | Supervisory restoration | Pass | |||
| 3 | Alarm signal | Pass | |||
| 3 | Alarm restoration | Pass | |||
| 3 | Trouble signal | Pass | |||
| 3 | Trouble restoration | Pass | |||
| 3 | Supervisory signal | Pass | |||
| 3 | Supervisory restoration | Pass | |||
| 5 | Alarm signal | Pass | |||
| 5 | Alarm restoration | Pass | |||
| 5 | Trouble signal | Pass | |||
| 5 | Trouble restoration | Pass | |||
| 5 | Supervisory signal | Pass | |||
| 5 | Supervisory restoration | Pass | |||
| 6 | Alarm signal | Pass | |||
| 6 | Alarm restoration | Pass | |||
| 6 | Trouble signal | Pass | |||
| 6 | Trouble restoration | Pass | |||
| 6 | Supervisory signal | Pass | |||
| 6 | Supervisory restoration | Pass | |||
| 14 | Alarm signal | Pass | |||
| 14 | Alarm restoration | Pass | |||
| 14 | Trouble signal | Pass | |||
| 14 | Trouble restoration | Pass | |||
| 14 | Supervisory signal | Pass | |||
| 14 | Supervisory restoration | Pass |
EC.02.03.05 EP9
| Sprinkler systems main drain tests (at lead-in to buildings) (quarterly where sole water source is through backflow preventer) | |||
| TJC | EC 02.03.05 EP9 | As of: | 1/31/25 |
| Building | Device or System Type | Quantity | |
| 1 | Wet Sprinkler Systems | 2 | |
| 3 | Wet Sprinkler Systems | 3 | |
| 5 | Wet Sprinkler Systems | 1 | |
| 6 | Wet Sprinkler Systems | 1 | |
| 14 | Wet Sprinkler Systems | 1 |
EC.02.03.05 EP10
| Fire department connections inspected (Fire hose connections N/A) | |||
| TJC | EC 02.03.05 EP10 | As of: | 1/31/25 |
| Building | Device or System Type | Quantity | |
| 1 | Sprinkler FDC - 2 Inlets | 1 | |
| 1 | Standpipe FDC - 2 Inlets | 1 | |
| 3 | Sprinkler FDC - 2 Inlets | 1 | |
| 5 | Sprinkler FDC - 2 Inlets | 1 | |
| 6 | Sprinkler FDC - 2 Inlets | 1 | |
| 14 | Sprinkler FDC - 2 Inlets | 1 |
EC.02.03.05 EP11
| Fire pump(s) tested – under flow Fire pump supervisory signals for pump running and pump power loss tested | |||
| TJC | EC 02.03.05 EP11 | As of: | 12/15/24 |
| Building | Device or System Type | Quantity | Equipment Description |
| 1 | Horizontal Split-Case | 1 | Pump Make & Model: Aurora 4-481-11D (Pump Rating: 750 GPM, 115 PSI, 3560 RPM, 87.9 BHP, 131.8 Max Church Pressure, 43.2 Max Suction Pressure, 8.375 Impeller Diameter) |
| 1 | Electric Motor | 1 | Electic Motor Make & Model: WEG |
| 1 | Controller | 1 | Controller Make & Model: Tornatech (Electronic Soft Start, H.P.: 100) |
| 14 | Horizontal Split-Case | 1 | Pump Make & Model: Aurora 3-481-10 (Pump Rating: 500 GPM, 50 PSI, 3560 RPM) |
| 14 | Electric Motor | 1 | Electic Motor Make & Model: WEG 040360P3EFP286TS |
| 14 | Controller | 1 | Controller Make & Model: Firetrol (Electronic Soft Start, H.P.: 40) |
EC.02.03.05 EP12
| Automatic Standpipe Systems | |||
| TJC | EC.02.03.05 EP12 | Performed on: | September 2025 |
| Buildings Tested | |||
| 1 | |||
| 3 | |||
| 5 | |||
| 6 | |||
| 14 |
EC.02.03.05 EP13
| Kitchen Extinguishing Systems | |||
| TJC | EC.02.03.05 EP13 | As of: | 4/4/25 |
| Building | Device or System Type | Quantity | |
| 5 | Commercial Kitchen Exhaust System | 1 | |
| 8 | Grill Hood System | 1 | |
| 8 | Steam/Oven Hood System | 1 |
EC.02.03.05 EP18
| Fire and smoke dampers | |||
| TJC | EC.02.03.05 EP18 | As of: | 5/2/22 |
| Building | Device or System Type | Quantity | |
| 1 | Fire Damper | 27 | |
| 3 | Fire Damper | 1 | |
| 14 | Fire Damper | 431 | |
| 14 | Fire & Smoke (Combination) Damper | 1 |
EC.02.03.05 EP19
| Smoke detecting shut down devices for HVAC | |||
| TJC | EC.02.03.05 EP19 | As of: | 1/31/25 |
| Building | Device or System Type | Quantity | |
| 1 | Air-Handling Unit(AHU) | 23 | |
| 3 | Air-Handling Unit(AHU) | 7 | |
| 5 | Air-Handling Unit(AHU) | 1 | |
| 6 | Air-Handling Unit(AHU) | 1 | |
| 14 | Air-Handling Unit(AHU) | 14 |
EC.02.03.05 EP20
| Horizontal & vertical rolling and sliding fire doors | |||
| TJC | EC.02.03.05 EP20 | As of: | 3/11/25 |
| Device or System Type | Quantity | ||
| Rolling Steel Fire Door | 3 |