This document contains a series of questions and answers related to a Request for Information (RFI) for a project to replace the canteen dishwashing utilities at the Sheridan VA Medical Center.

The key details are:

  • The project will renovate the canteen dishwashing room in Building 86 at the Sheridan VAMC, including replacing plumbing, floor drains, exhaust systems, and other utilities.
  • The RFI provides responses to 6 questions from contractors about the project, including clarifying the location of plumbing, confirming the ability to tie into the sewer line, and determining if additional investigation is needed on the hot water recirculation line.
  • The related federal contract opportunity is Solicitation Number 36C25924Q0678 for the "Replace Canteen Dishwashing Utilities | 666-24-129" project, which is being procured by the Department of Veterans Affairs, Veterans Integrated Service Network 19.
  • The contract will be for general construction services to be completed within 180 calendar days, including demolition, new plumbing, HVAC, and finishes.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Replace Canteen Dishwashing Utilities | 666-24-129, newest first.
File Type Posted
36C25924Q0678 0009.docx DOCX document
36C25924Q0678 0008.docx DOCX document
36C25924Q0678 0007.docx DOCX document
S04 - Site Visit 3 Sign In Sheet - FE.pdf PDF
S04 - Site Visit 3 Meeting Doc - FE.docx DOCX document
36C25924Q0678 0006.docx DOCX document
S04 - Site Visit 2 Meeting Doc - FE.docx DOCX document
36C25924Q0678 0005.docx DOCX document
S04 - Site Visit 2 Attendance - FE.pdf PDF
36C25924Q0678 0003.docx DOCX document
P09 - SOW - Revised - 10 03 2024.docx DOCX document
S02 - Site Visit 1 RFI - Responses.docx DOCX document
S02 - 18 666-14-108 M501 Details.pdf PDF
S02 - 1992-08-21 - 86 - Nursing Home Care Remodel Bldg 86 - 50 Bed Unit - 066 HVAC Floor Plan Level One South - 86-H2 - 66 of 92.pdf PDF
S02 - 17 666-14-108 M401 Schedules.pdf PDF
S02 - 11 666-14-108 M203 Bldg 86 1st-S HVAC Plan.pdf PDF
S04 - Site Visit Meeting Doc - FE.docx DOCX document
S04 - Sign in Sheet - FE.pdf PDF
36C25924Q0678 0002.docx DOCX document
S02 - Plumbing Plans B86.pdf PDF
S02 - 16 666-14-108 M303 Bldg 86 1st-S Piping Plan.pdf PDF
36C25924Q0678 0001.docx DOCX document
PPQ Blank - Past Performance Questionnaire -.docx DOCX document
S02 - Replace Canteen Dishwasher Utilities - Drawing.pdf PDF
36C25924Q0678.docx DOCX document
S22 - LOS - Attachment - 852.219-75 Blank -.docx DOCX document
Show all 26

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DEPARTMENT OF VETERANS AFFAIRS VHA Network Contracting Office 19 Rocky Mountain Acquisition Center 6162 South Willow Drive, Suite 300 Greenwood Village, CO 80111

CONTRACTOR Q&A’s

Project # 666-24-129

Replace Canteen Dishwashing Utilities Site Visit 3

Q&A No. 1: Looking through the drawings provided for Building 86 they gave us the south side and it looks to me that we need the north side. Can the VA provide the north side that shows the canteen in question?

Answer No. 1: The canteen Washroom is located in the southwest corner of the main building. I will add drawing P-157 that shows all the plumbing in the crawlspace for the entire building.

Q&A No. 2: Can the new hand sink tie directly into the sewer line or is a floor sink required under it to allow a indirect drain in this area?

Answer No. 2: Yes, it can tie into the sewer line.

Q&A No. 3: Existing floor drain is installed through existing concrete reinforcing web in floor, is structural repair required during installation of new floor sink.

Answer No. 3: No

Q&A No. 4: Existing recirculation line ties in less than 10 feet from dishwasher location, existing line did not seem to be circulating hot enough water. Does more investigation need to be accomplished to verify existing recirculation line is functioning properly?

Answer No. 4: Yes

Q&A No. 5: Am unable to locate existing mixing valve on domestic hot water line to verify tie-in location of new hot water line to dishwasher, can this location be specified please?

Answer No. 5: The station is working to find a response to this question and shall, if discovered prior to solicitation due date, provide a response in an additional amendment.

Q&A No. 6: Can the VA confirm there is no electrical on this project.

Answer No. 6: There is no new electrical work on this project. The only electrical would be reconnecting the existing electrical to the new disposal.