S05 - RFI Site Visit - Questions - 2.docx
DOCX document 16 KB Posted
- Attached to
- Z2DA--Replace Canteen Dishwashing Utilities | 666-24-129 Federal contract opportunity
- Solicitation number
- 36C25924Q0678
About this file
This document contains a series of questions and answers related to a Request for Information (RFI) for a project to replace the canteen dishwashing utilities at the Sheridan VA Medical Center.
The key details are:
- The project will renovate the canteen dishwashing room in Building 86 at the Sheridan VAMC, including replacing plumbing, floor drains, exhaust systems, and other utilities.
- The RFI provides responses to 6 questions from contractors about the project, including clarifying the location of plumbing, confirming the ability to tie into the sewer line, and determining if additional investigation is needed on the hot water recirculation line.
- The related federal contract opportunity is Solicitation Number 36C25924Q0678 for the "Replace Canteen Dishwashing Utilities | 666-24-129" project, which is being procured by the Department of Veterans Affairs, Veterans Integrated Service Network 19.
- The contract will be for general construction services to be completed within 180 calendar days, including demolition, new plumbing, HVAC, and finishes.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEPARTMENT OF VETERANS AFFAIRS VHA Network Contracting Office 19 Rocky Mountain Acquisition Center 6162 South Willow Drive, Suite 300 Greenwood Village, CO 80111
CONTRACTOR Q&A’s
Project # 666-24-129
Replace Canteen Dishwashing Utilities Site Visit 3
Q&A No. 1: Looking through the drawings provided for Building 86 they gave us the south side and it looks to me that we need the north side. Can the VA provide the north side that shows the canteen in question?
Answer No. 1: The canteen Washroom is located in the southwest corner of the main building. I will add drawing P-157 that shows all the plumbing in the crawlspace for the entire building.
Q&A No. 2: Can the new hand sink tie directly into the sewer line or is a floor sink required under it to allow a indirect drain in this area?
Answer No. 2: Yes, it can tie into the sewer line.
Q&A No. 3: Existing floor drain is installed through existing concrete reinforcing web in floor, is structural repair required during installation of new floor sink.
Answer No. 3: No
Q&A No. 4: Existing recirculation line ties in less than 10 feet from dishwasher location, existing line did not seem to be circulating hot enough water. Does more investigation need to be accomplished to verify existing recirculation line is functioning properly?
Answer No. 4: Yes
Q&A No. 5: Am unable to locate existing mixing valve on domestic hot water line to verify tie-in location of new hot water line to dishwasher, can this location be specified please?
Answer No. 5: The station is working to find a response to this question and shall, if discovered prior to solicitation due date, provide a response in an additional amendment.
Q&A No. 6: Can the VA confirm there is no electrical on this project.
Answer No. 6: There is no new electrical work on this project. The only electrical would be reconnecting the existing electrical to the new disposal.