S02 - 18 666-14-108 M501 Details.pdf

PDF 423 KB Posted

Attached to
Z2DA--Replace Canteen Dishwashing Utilities | 666-24-129 Federal contract opportunity
Solicitation number
36C25924Q0678
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

This document appears to be a set of technical drawings and specifications related to a federal contract opportunity. The drawings show details for plumbing, HVAC, and other utility work required to renovate the Canteen Dishwashing Room in Building 86 at the Sheridan VA Medical Center.

The key details include:

  • Demolishing and replacing the existing plumbing, floor drain, and hand sink to bring the facility up to code
  • Upgrading the room's exhaust system to improve ventilation
  • Removing and replacing floor tile, including sloping the concrete floor to direct water to the new floor sink
  • Completing all electrical, carpentry, architectural, and other work necessary for the renovation within 180 calendar days
  • Requiring the contractor to follow safety, infection control, and security measures due to the work being performed in an active medical facility

The renovation is part of Solicitation Number 36C25924Q0678, issued by the Department of Veterans Affairs Veterans Health Administration for the Veterans Integrated Service Network 19.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--Replace Canteen Dishwashing Utilities | 666-24-129, newest first.
File Type Posted
36C25924Q0678 0009.docx DOCX document
S05 - RFI Site Visit - Questions - 2.docx DOCX document
36C25924Q0678 0008.docx DOCX document
36C25924Q0678 0007.docx DOCX document
S04 - Site Visit 3 Sign In Sheet - FE.pdf PDF
S04 - Site Visit 3 Meeting Doc - FE.docx DOCX document
36C25924Q0678 0006.docx DOCX document
S04 - Site Visit 2 Meeting Doc - FE.docx DOCX document
36C25924Q0678 0005.docx DOCX document
S04 - Site Visit 2 Attendance - FE.pdf PDF
36C25924Q0678 0003.docx DOCX document
P09 - SOW - Revised - 10 03 2024.docx DOCX document
S02 - Site Visit 1 RFI - Responses.docx DOCX document
S02 - 1992-08-21 - 86 - Nursing Home Care Remodel Bldg 86 - 50 Bed Unit - 066 HVAC Floor Plan Level One South - 86-H2 - 66 of 92.pdf PDF
S02 - 17 666-14-108 M401 Schedules.pdf PDF
S02 - 11 666-14-108 M203 Bldg 86 1st-S HVAC Plan.pdf PDF
S04 - Site Visit Meeting Doc - FE.docx DOCX document
S04 - Sign in Sheet - FE.pdf PDF
36C25924Q0678 0002.docx DOCX document
S02 - Plumbing Plans B86.pdf PDF
S02 - 16 666-14-108 M303 Bldg 86 1st-S Piping Plan.pdf PDF
36C25924Q0678 0001.docx DOCX document
PPQ Blank - Past Performance Questionnaire -.docx DOCX document
S02 - Replace Canteen Dishwasher Utilities - Drawing.pdf PDF
36C25924Q0678.docx DOCX document
S22 - LOS - Attachment - 852.219-75 Blank -.docx DOCX document
Show all 26

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

3-WAY OR 2-WAY

CONTROL VALVE

REFER TO SCHEDULE

COIL

1/4"MANUAL

AIR VENT

FLOW CONTROL VALVE

BALL VALVE (TYP.)

STRAINER

1/2"DRAIN VALVE

UNION

COIL PIPING DETAIL

N.T.S. -

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

ACCESS PANEL

DUCT

GASKET

INSULATION

INSULATION

"A"

"A"

ACCESS PANEL DETAIL

SCALE: N.T.S. -

SECTION "A-A"

NOTE:

1.

2.

3.

4.

5.

6.

A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION, IS SIMILAR. FOLLOW

DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES

FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE

PARTITION OR FLOOR AND NOT OUTSIDE THE PENETRATION.

GALVANIZED SLEEVE: GAGE NOT LESS THAN CONNECTING DUCT. FASTEN SLEEVE TO

DAMPER FRAME AND TO PERIMETER ANGLES.

PERIMETER ANGELS: GALVANIZED STEEL, NOT LESS THAN 1 1/2"x1 1/2" [40x40mm], 14 GAGE, TO PROVIDE 1" [25mm] MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES.

BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES SHOWN IN SMACNA.

ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE LINK OR LINKS.

PROVIDE 1/4" TO 1/2" [6 TO 15mm] CLEARANCE ON HEIGHT AND WIDTH. FILL OPEN SPACE

WITH ROCK WOOL FIRESTOP FIBER.

ALL DUCT WORK RISERS WHICH ARE RUN EXPOSED, SUCH AS THRU ATTIC FLOORS AND

MECHANICAL ROOM FLOORS, SHALL BE PROVIDED WITH 3" [75mm] HIGH CONCRETE CURB

AROUND OPENING FOR DUCT.

SLEEVE, NOTE 2

DUCT

CONNECTION

NOTE 4

DAMPER,

NOTE 1

DAMPER COLLAR

EXTENSION

INTEGRAL PART

OF SLEEVE

SLEEVE, NOTE 2

NOTE 6

FIRE BARRIER

PARTITION OR CHASE

TYPICAL DUCT

INSULATION

PERIMETER ANGLE, NOTE 3 (NOTE

FASTENED TO PARTITION)

ACCESS

PANEL

NOTE 5

FIRE DAMPER INSTALLATION

SCALE: N.T.S. -

SECTION THRU

ROUND FLEXIBLE CONNECTION

RECTANGULAR FLEXIBLE CONNECTION

FLANGED CONNECTION

ON FAN SIDE

WASHER

1-1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL

WITH MATERIAL TAUT

FLEXIBLE

MATERIAL AS

SPECIFIED

1"x1/8" [25x3mm] DRAW BAND

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

5/16" [8mm] FLANGE

DUCT

SHEET METAL SCREWS ON

12" [300mm] CENTERS

RIVET ON 4"

[100mm]

CENTERS

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1"x1/8" [25x3mm] BAND IRON

BOLT ON 4" [100mm] CENTERS

1" [25mm] FLANGE & HEM

ALTERNATE

POSITION

OF BOLT

1 1/2" [40mm]

POCKET SLIP

DUCT

SHEET METAL AS

SPECIFIED FOR

DUCTWORK.

1/2"

[15mm]

1/2"

[15mm]

1 1/2"

[40mm]

1 1/2" [40mm] MIN. TO 3" [75mm] MAX.

INSTALLED. 6" [150mm] NOMINAL WITH

MATERIAL TAUT

FLANGED

CONNECTION

ON FAN SIDE

WASHER

FLEXIBLE MATERIAL

AS SPECIFIED

FLEXIBLE DUCT CONNECTIONS

SCALE: N.T.S. -

(WITH EQUIPMENT MOUNTED IN DUCT)

SCALE: N.T.S. -

NOTE:

UNLESS OTHERWISE INDICATED ON PLANS, MAXIMUM ANGLES SHOWN SHALL APPLY.

M

A

X

M

A

X

E Q

U I P

M E

N T

AIR

FLOW

AIR

FLOW

TYPICAL DUCTWORK TRANSITION

PLAN OR SIDE VIEW

TYPICAL DUCTWORK TRANSITION WITH

EQUIPMENT MOUNTED IN DUCT

PLAN OR SIDE VIEW

M

A

X

M

A

X

M A

X

M

A

X

DUCTWORK TRANSITIONS

MAIN EXHAUST OR RETURN

PLAN VIEW

AIR

FLOW

AIR

FLOW

W

PROVIDE VOLUME DAMPER

AT EACH BRANCH DUCT

1/4W OR 4" [100mm]

MIN.

BRANCH DUCT

VD

EXHAUST OR RETURN BRANCH DUCTWORK

SCALE: N.T.S. -

VANE

VANE

NOTE:

1.

2.

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS CAN BE SUBSTITUTED WITH SHORT RADIUS ELBOWS.

ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE CONSTRUCTED,

SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

R SHALL

EQUAL

OR BE

GREATER

THAN W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/3W.

W

R

R

W

W

R SHALL

EQUAL

OR BE

GREATER

THAN

1/6W.

STANDARD RADIUS OR

LONG RADIUS ELBOW

SHORT RADIUS

ELBOW WITH ONE

VANE

SHORT RADIUS

ELBOW WITH TWO

VANES

W W

W

W

1/6W

R

DUCTWORK RADIUS ELBOWS

SCALE: N.T.S. -

2500 [1133]

1320 [598]

420 [190]ONE 1 [25] x 18 GA STRAP36 [900]

TWO 1/2 [13]Ø RODS

TWO 3/8 [10]Ø. RODS

ONE 1 [25] x 16 GA STRAP

84 [2100]

60 [1500]

50 [1250] 700 [317]

ONE 1 [25] x 22 GA STRAP

QUANTITY/SIZE

MAX. DUCT Ø

26 [650]

HANGER STRAPS OR RODS

MAX. LOAD

LBS. [kg]

260 [119]

MAX.

144 [3600]

IN. [mm]

SPACING

IN. [mm]

IN. [mm]

144 [3600]

144 [3600]

144 [3600]

144 [3600]

NOTE:

TABULATED DATA FROM SMACNA ALLOWS FOR DUCT REINFORCING

AND INSULATION, BUT NO EXTERNAL LOAD.

BAND

OVER 50"

[1250mm]Ø

HANGER RODS

BAND OF SAME

SIZE AS HANGER

STRAP

LOAD RATED

FASTENERS

50" [1250mm]Ø

& UNDER

ROUND DUCT HANGERS

SCALE: N.T.S. -

NOTE:

1.

2.

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR

FOR MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION SEE

SPECIFICATION

DAMPER BLADE

1/8" [6mm]

CLEARANCE

ALL AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

INSULATION

STAND-OFF

1/2" [15mm] ROUND

ROD PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

VOLUME DAMPER DETAIL

SCALE: N.T.S. -

BRANCH DUCT TAKE-OFF PLAN VIEW

PROVIDE VOLUME

DAMPER

1/4 W OR 4"

[100mm] MIN.

AIR

FLOW

MAIN SUPPLY

DUCT

W

A I R

F L

O W

SUPPLY DUCTWORK TAKE-OFFS

SCALE: N.T.S. -

12"

SEE SPECIFICATIONS FOR

CLAMPS AND SEALANT (TYP.)

TYPICAL

DIFFUSER OR

REGISTER IN

LAY-IN CLG.

THERMAL INSULATION

SEE SPECIFICATIONS

FLEXIBLE AIR DUCT CONNECTOR DETAIL

SCALE: N.T.S. -

SUPPORT SADDLE

FROM STRUCTURE

FLEXIBLE DUCT SIZE

SAME AS DIFFUSER

INLET: 5'-0" MAX

LENGTH.

USE RIGID ELBOWS

FOR CHANGE OF

DIRECTION GREATER

THAN 45°

CEILING

SHEET METAL

SADDLE

VOLUME DAMPER

W/ LOCKING QUAD

BRANCH DUCT

CONICAL OUTLET

CONCRETE EQUIPMENT BASES

SCALE: N.T.S. -

SECTION A-A (BASE NOT POURED WITH SLAB)

SECTION A-A (BASE POURED WITH FLOOR SLAB)

PLAN

TYPICAL ANCHOR BOLT

NUT & WASHER

SECTION B-B

EQUIPMENT BASE PLATE

PROVIDE #3 BARS 12" [300mm] O.C.

EACH WAY IN THE BASE & DOWEL

BASE TO FLOOR

EQUIPMENT BASE PLATE

PROVIDE DOUBLE SLAB

REINFORCING IN BASE AREA

WELD HEAD TO PLATE OR

BEND OVER END 5D

FLOOR

PIPE SLEEVE (5D, 3" [75mm]

MIN.)

ANCHOR

BOLT (TYP)

CONCRETE BASE

NOTE:

L & W DIMENSIONS SHALL BE

6" [150mm] GREATER THAN

THE EQUIPMENT BASE PLATE.

L

W

A

A

D

2D

[400mm]

16"

M

I N m m

L

M

I N m

L

D

TYPICAL ANCHOR BOLT

NUT & WASHER

m

5D

SECURING HANGAR RODS IN CONCRETE

SCALE: N.T.S. -

STEEL EXPANSION SHIELD FOR EXISTING

CONSTRUCTION AND INSERTS FOR NEW

CONSTRICTION THIS TYPE SHALL BE USED

ONLY IN SLABS OR BEAMS OF 4" [100mm] MIN

DEPTH

3/8" [10mm] MIN DIA EXPANSION BOLTS FOR

EXISTING CONSTRUCTION AND INSERTS

FOR NEW CONSTRUCTION

CONCRETE

FLOOR SLAB

CLIP

ANGLE

NUTS & WASHERS

3/8" [10mm] MIN DIA

HANGER RODS

FOR PIPES UNDER 2" [50mm] IN SIZE USE

1 1/2"x1 1/2"x1/4" [40x40x6.4mm] ANGLE.

ALL PIPES 2" [50mm] & LARGER USE

3"x3"x1/4" [75x75x6.4mm] ANGLE

TURNBUCKLE

3/8" [10mm] MIN DIA

HANGER RODS

3/8" [10mm] MIN DIA

INSERTS NEW

CONSTRUCTION ONLY.

CONNECTIONS WITH FLEXIBLE CONNECTORS

SCALE: N.T.S. -

NOTES:

SEE SPECIFICATION SECTION "PUMPS" FOR Y STRAINER OPTION

FIRST 3 HANGERS FOR EACH PIPE AND

BRANCH SHALL BE SPRING & NEOPRENE

TYPE. TYPE "H" FOR 4" [100mm] DIA. PIPE

& SMALLER. TYPE "H-P" FOR 5" [125mm]

DIA. PIPE & LARGER.

RIGID PIPE

HANGER

INSTALL HANGER AS CLOSE

TO PIPE ELBOW AS POSSIBLE

(TYPICAL)

1/2" [15mm]

FLEXIBLE CONNECTOR (TYPICAL)

PUMP

FLOOR

VIBRATION ISOLATOR

(TYPICAL) 1" [25mm] MIN.

DIA. PIPE STAND

CONCRETE INERTIA

BASE

DRAIN

SUCTION DIFFUSER

WITH BUILT IN STRAINER.

OPTIONAL: LONG RADIUS

ELBOW AND INLET

STRAINER WITH 3XDIAM

STRAIGHT INLET TO PUMP

1/2" [15mm]

PRESSURE GAUGE

RIGID PIPE

HANGER

OPTIONAL STRAINER

BUTTERFLY OR BALL

SHUT OFF VALVE, TYP.

CHECK VALVE

SINGLE SUCTION FLOOR-MOUNTED PUMPS-

DUCT FLEX CONN. (TYP.) SUSPEND INDEPENDENTLY

FROM STRUCTURE. PROVIDE

ANGLE SUPPORT AS

REQUIRED.

NOTE: PROVIDE DUCT TRANSITION

TO MATCH S.A. & R.A. CONNECTIONS,

SIZE AS INDICATE ON PLANS

4-PIPE FAN COIL PIPING DETAIL

N.T.S. -

LOUVER LVR/OA

SEE PLANS.

CONNECT PLENUM

TO BOTTOM BLADE

OF LOUVER AND

WEATHER SEAL JOINT

BY THIS CONT'R

EXTENDED

SILL

HVAC CASING-SEE PLANS

FOR SIZING. SOLDER

JOINTS WATER TIGHT.

INSULATION

SEE SPECS

LOUVER DETAIL

SCALE: N.T.S. -

DUCT ROUTE UNDER STRUCT. BEAM DET.

SCALE: N.T.S. -

12"

SEE SPECIFICATIONS

FOR CLAMPS AND

SEALANT (TYP.)

TYPICAL

DIFFUSER OR

REGISTER IN

LAY-IN CLG.

THERMAL INSULATION

SEE SPECIFICATIONS

SUPPORT SADDLE

FROM STRUCTURE

FLEXIBLE DUCT SIZE

SAME AS DIFFUSER

INLET: 5'-0" MAX

LENGTH.

USE RIGID ELBOWS

FOR CHANGE OF

DIRECTION GREATER

THAN 45°

CEILING

SHEET METAL

SADDLE

VOLUME DAMPER

W/ LOCKING QUAD

BRANCH DUCT

CONICAL OUTLET

CONCRETE

BEAM

FLAT DUCT

(4" DEPTH)

RECORD DOCUMENTS

T C.

ARCHITECTURE

ENGINEERING

GIS

SURVEYING

These Record Documents conforming to the marked-up prints, drawings and other data furnished to the Design Professional by the Contractor. This set of Record Documents will show the reported location of the Work and significant changes made during the construction process. These Record

Documents are based on information provided by other parties which will be assumed reliable. The

Design Professional has not verified the accuracy and/or completeness of this information and shall not be responsible for any errors or omissions which may be incorporated herein as a result.

RECORD DOCUMENTS

File details come from the government source that posted it. Updated .