This document is an Invitation for Bid (IFB) for the replacement of boiler burners and controls for the Department of Veterans Affairs (VA) Veterans Integrated Service Network 17. The solicitation is a 100% set-aside for Service-Disabled Veteran Owned Small Businesses (SDVOSB). The work involves project #549A4-22-422 (VA-25-00003929) to replace the burner and controls. Award of the contract is contingent on the availability of appropriated funds. The IFB does not provide details on the specific products or services required, but it states that the Contracting Officer will confirm the availability of funds prior to contract award.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATE VETERANS HOME
CLYDE COSPER
1A
2A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
DESIGN DEVELOPMENT
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
1201 E. 9th St., Bonham, TX 75418
549A4-22-422
Building No. 11 Project Director
1/11/2024 RM, KP MHRevisions: Date:
MENDEZNGINEERINGE
Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com
REPLACE BOILER
BURNERS & CONTROLS
Fi le
P at h:
/1 1/
:4
AM
G :\P ro je ct s-
\2
VA
AE
R ep la ce
B oi le r B ur ne rs
C on tro ls
\C iv il\ C
O
VE
R S
H
EE
T.
dw g
BYRON A. ROWLAND
1/12/2024
VAU.S. Department of Veterans Affairs
VA - A/E DESIGN SERVICES
REPLACE BOILER BURNERS
& CONTROLS
1201 E 9TH ST.
BONHAM, TEXAS 75418
PROJECT No. 549A4-22-422
MENDEZNGINEERINGE
Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com
SITE
SITE MAP
COVER SHEET
C-000
ROOM 103
ROOM 102
ROOM 103
EX. TRENCH
(1ST FL)
EX. MEZZANINE
EX. M
EZZAN
IN
E
EX.
MEZZANINE
(3RD FL)
EX. MEZZANINE BOILER
#3
(1ST FL)
BOILER
#2
(1ST FL)
BOILER
#1
(1ST FL)
KEY NOTES
CAUTION:
CONTRACTOR TO VERIFY ALL EXISTING UTILITIES VERTICALLY AND
HORIZONTALLY PRIOR TO CONSTRUCTION. CONTRACTOR TO NOTIFY THE
ENGINEER IMMEDIATELY OF ANY DISCREPANCIES.
THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THE ACCURACY OF
THE LOCATION OF UNDERGROUND UTILITIES. THE CONTRACTOR SHALL
BE RESPONSIBLE FOR AVOIDING ALL EXISTING UTILITIES BY CALLING
DIGTESS @ 1-800-DIG-TESS FOR LOCATION OF ALL UTILITIES, AT LEAST 2
WORKING DAYS PRIOR TO BEGINNING CONSTRUCTION.
TRENCH EXCAVATION SAFETY PROTECTION:
CONTRACTOR AND/OR CONTRACTOR'S INDEPENDENTLY RETAINED
EMPLOYEE OR STRUCTURAL DESIGN/GEOTECHNICAL/SAFETY/EQUIPMENT
CONSULTANT, IF ANY, SHALL REVIEW THESE PLANS, AVAILABLE
GEOTECHNICAL INFORMATION, AND THE ANTICIPATED INSTALLATION
SITE(S) WITHIN THE PROJECT WORK AREA IN ORDER TO IMPLEMENT
CONTRACTOR'S TRENCH EXCAVATION SAFETY PROTECTION SYSTEMS,
PROGRAMS AND/OR PROCEDURES. THE CONTRACTOR'S
IMPLEMENTATION OF THE SYSTEMS, PROGRAMS AND/OR PROCEDURES
SHALL PROVIDE FOR ADEQUATE TRENCH EXCAVATION SAFETY
PROTECTION THAT COMPLIES WITH, AS A MINIMUM, OSHA STANDARDS
FOR TRENCH EXCAVATIONS. SPECIFICALLY, CONTRACTOR AND/OR
CONTRACTOR'S INDEPENDENTLY RETAINED EMPLOYEE OF SAFETY
CONSULTANT SHALL IMPLEMENT A TRENCH SAFETY PROGRAM IN
ACCORDANCE WITH OSHA STANDARDS GOVERNING THE PRESENCE AND
ACTIVITIES OF INDIVIDUALS WORKING IN AND AROUND TRENCH
EXCAVATION.
NOTES:
1. CONTRACTOR SHALL BE REQUIRED TO LOCATE ALL PUBLIC OR PRIVATE
UTILITIES INCLUDING BUT NOT LIMITING TO: WATER, SEWER, TELEPHONE
AND FIBER OPTIC LINES, SITE LIGHTING ELECTRIC, SECONDARY ELECTRIC,
PRIMARY ELECTRICAL DUCTBANKS, LANDSCAPE IRRIGATION FACILITIES,
AND GAS LINES. ANY UTILITY CONFLICTS THAT ARISE SHOULD BE
COMMUNICATED TO THE ENGINEER IMMEDIATELY AND THE VA'S COR
WITHIN A MINIMUM OF 48 HOURS PRIOR TO THE START OF CONSTRUCTION.
ANY DAMAGE TO EXISTING UTILITIES SHALL BE THE SOLE RESPONSIBILITY
OF THE CONTRACTOR AND THE REPAIR SHALL BE AT THE CONTRACTOR'S
SOLE EXPENSE WHETHER THE UTILITY IS SHOWN ON THESE PLANS OR
NOT.
2. THE LOCATIONS AND DEPTHS OF EXISTING UTILITIES, INCLUDING SERVICE
LATERALS AND DRAINAGE STRUCTURES SHOWN ON PLANS ARE
APPROXIMATE ONLY. THE CONTRACTOR SHALL VERIFY THE EXACT
LOCATION AND DEPTHS OF UNDERGROUND UTILITIES AT LEAST 48 HOURS
PRIOR TO CONSTRUCTION WHETHER SHOWN ON PLANS OR NOT, AND
PROTECT THE SAME DURING CONSTRUCTION.
3. ALL ITEMS ARE TO BE FURNISHED & INSTALLED BY CONTRACTOR.
REFERENCE CONSTRUCTION DETAILS SHEETS FOR ADDITIONAL
INFORMATION.
4. LIMITS OF CONSTRUCTION ARE SHOWN ON THE COVER SHEET'S SITE MAP.
LEGEND
BUILDING OUTLINE
EXISTING TRENCH (1ST FL)
EXISTING MEZZANINE
EXISTING MEZZANINE (3RD FL)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
DESIGN DEVELOPMENT
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
1201 E. 9th St., Bonham, TX 75418
549A4-22-422
Building No. 11 Project Director
1/11/2024 RM, KP MHRevisions: Date:
MENDEZNGINEERINGE
Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com
REPLACE BOILER
BURNERS & CONTROLS
Fi le
P at h:
/1 1/
:4
AM
G :\P ro je ct s-
\2
VA
AE
R ep la ce
B oi le r B ur ne rs
C on tro ls
\C iv il\ M
EZ
ZA
N
IN
E
SH
EE
TS
.d w g
BYRON A. ROWLAND
1/12/2024
SECTION A-A
SCALE: 1" = 5'
SECTION B-B
SCALE: 1" = 5'
EXISTING MEZZANINE AND
DEMOLITION PLAN
C-100
FLOOR PLAN OF
EXISTING MEZZANINE
SCALE: 1" = 5'
IMAGE 1
N.T.S.
IMAGE 2
N.T.S.
IMAGE 3
N.T.S.
PROPOSED HSS 6"x6"x1/4" COLUMN.
PROPOSED W14"X22" BEAM.
PROPOSED W8"X10" GIRDER.
NOTE USED.
STEEL STAIRS FOR LOWERED ACCESS TO BOILER 3.
PROPOSED 1" X 1/16" GRATING.
4" X 1/4" GUARD PLATE.
PROPOSED 1 1/4" PIPE HANDRAIL TO BE INSTALLED SIMILAR TO PER
EXISTING HANDRAILS.
CONCRETE COLUMN BASE.
ROOM 102
ROOM 103
EX. TRENCH
(1ST FL)
EX. MEZZANINE
EX. M
EZZAN
IN
E
EX.
MEZZANINE
(3RD FL)
EX. MEZZANINE
PROPOSED
CATWALK
BOILER
#3
(1ST FL)
BOILER
#2
(1ST FL)
BOILER
#1
(1ST FL)
ROOM 103 10
' 11
A
A
B
B
C
C
1 1
2 2
HSS 6"x6"x1/4"
EXISTING C8"x11 1/2"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W 8" x1 0"
W14"x22"W14"x22"
W14"x22" W14"x22"
4.02' 4.02' 4.02' 4.02' 4.02' 4.02' 4.02' 4.02' 4.02' 4.02' 4.02' 4.02'
2.5' 2.12' 9.83' 2.5' 2.5' 9.83' 2.5' 2.5' 13.96'
24.12' 24.12'
48.25'
5.
CAUTION:
CONTRACTOR TO VERIFY ALL EXISTING UTILITIES VERTICALLY AND
HORIZONTALLY PRIOR TO CONSTRUCTION. CONTRACTOR TO NOTIFY THE
ENGINEER IMMEDIATELY OF ANY DISCREPANCIES.
THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THE ACCURACY OF
THE LOCATION OF UNDERGROUND UTILITIES. THE CONTRACTOR SHALL
BE RESPONSIBLE FOR AVOIDING ALL EXISTING UTILITIES BY CALLING
DIGTESS @ 1-800-DIG-TESS FOR LOCATION OF ALL UTILITIES, AT LEAST 2
WORKING DAYS PRIOR TO BEGINNING CONSTRUCTION.
TRENCH EXCAVATION SAFETY PROTECTION:
CONTRACTOR AND/OR CONTRACTOR'S INDEPENDENTLY RETAINED
EMPLOYEE OR STRUCTURAL DESIGN/GEOTECHNICAL/SAFETY/EQUIPMENT
CONSULTANT, IF ANY, SHALL REVIEW THESE PLANS, AVAILABLE
GEOTECHNICAL INFORMATION, AND THE ANTICIPATED INSTALLATION
SITE(S) WITHIN THE PROJECT WORK AREA IN ORDER TO IMPLEMENT
CONTRACTOR'S TRENCH EXCAVATION SAFETY PROTECTION SYSTEMS,
PROGRAMS AND/OR PROCEDURES. THE CONTRACTOR'S
IMPLEMENTATION OF THE SYSTEMS, PROGRAMS AND/OR PROCEDURES
SHALL PROVIDE FOR ADEQUATE TRENCH EXCAVATION SAFETY
PROTECTION THAT COMPLIES WITH, AS A MINIMUM, OSHA STANDARDS
FOR TRENCH EXCAVATIONS. SPECIFICALLY, CONTRACTOR AND/OR
CONTRACTOR'S INDEPENDENTLY RETAINED EMPLOYEE OF SAFETY
CONSULTANT SHALL IMPLEMENT A TRENCH SAFETY PROGRAM IN
ACCORDANCE WITH OSHA STANDARDS GOVERNING THE PRESENCE AND
ACTIVITIES OF INDIVIDUALS WORKING IN AND AROUND TRENCH
EXCAVATION.
NOTES:
1. CONTRACTOR SHALL BE REQUIRED TO LOCATE ALL PUBLIC OR PRIVATE
UTILITIES INCLUDING BUT NOT LIMITING TO: WATER, SEWER, TELEPHONE
AND FIBER OPTIC LINES, SITE LIGHTING ELECTRIC, SECONDARY ELECTRIC,
PRIMARY ELECTRICAL DUCTBANKS, LANDSCAPE IRRIGATION FACILITIES,
AND GAS LINES. ANY UTILITY CONFLICTS THAT ARISE SHOULD BE
COMMUNICATED TO THE ENGINEER IMMEDIATELY AND THE VA'S COR
WITHIN A MINIMUM OF 48 HOURS PRIOR TO THE START OF CONSTRUCTION.
ANY DAMAGE TO EXISTING UTILITIES SHALL BE THE SOLE RESPONSIBILITY
OF THE CONTRACTOR AND THE REPAIR SHALL BE AT THE CONTRACTOR'S
SOLE EXPENSE WHETHER THE UTILITY IS SHOWN ON THESE PLANS OR
NOT.
2. THE LOCATIONS AND DEPTHS OF EXISTING UTILITIES, INCLUDING SERVICE
LATERALS AND DRAINAGE STRUCTURES SHOWN ON PLANS ARE
APPROXIMATE ONLY. THE CONTRACTOR SHALL VERIFY THE EXACT
LOCATION AND DEPTHS OF UNDERGROUND UTILITIES AT LEAST 48 HOURS
PRIOR TO CONSTRUCTION WHETHER SHOWN ON PLANS OR NOT, AND
PROTECT THE SAME DURING CONSTRUCTION.
3. ALL ITEMS ARE TO BE FURNISHED & INSTALLED BY CONTRACTOR.
REFERENCE CONSTRUCTION DETAILS SHEETS FOR ADDITIONAL
INFORMATION.
4. LIMITS OF CONSTRUCTION ARE SHOWN ON THE COVER SHEET'S SITE MAP.
LEGEND
BUILDING OUTLINE
EXISTING TRENCH (1ST FL)
EXISTING MEZZANINE
EXISTING MEZZANINE (3RD FL)
PROPOSED CATWALK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
DESIGN DEVELOPMENT
Office of
Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
1201 E. 9th St., Bonham, TX 75418
549A4-22-422
Building No. 11 Project Director
1/11/2024 RM, KP MHRevisions: Date:
MENDEZNGINEERINGE
Registration # F-14070 12950 Country Parkway, Suite 120 San Antonio, Texas 78216 Office: 210-802-0808 www.MendezEngineering.com
REPLACE BOILER
BURNERS & CONTROLS
Fi le
P at h:
/1 1/
:4
AM
G :\P ro je ct s-
\2
VA
AE
R ep la ce
B oi le r B ur ne rs
C on tro ls
\C iv il\ M
EZ
ZA
N
IN
E
SH
EE
TS
.d w g
BYRON A. ROWLAND
1/12/2024
PROPOSED FLOOR PLAN OF
EXTENDED CATWALK
SCALE: 1" = 5'
SECTION C-C
SCALE: 1" = 5'
SECTION D-D
SCALE: 1" = 5'
CATWALK EXTENSION PLAN
AND SECTION DETAILS
C-101
KEY NOTES
PROPOSED HSS 6"x6"x1/4" COLUMN.
PROPOSED W14"X22" BEAM.
PROPOSED W8"X10" GIRDER.
NOTE USED.
STEEL STAIRS FOR LOWERED ACCESS TO BOILER 3.
PROPOSED 1" X 1/16" GRATING.
4" X 1/4" GUARD PLATE.
PROPOSED 1 1/4" PIPE HANDRAIL TO BE INSTALLED SIMILAR TO PER
EXISTING HANDRAILS.
CONCRETE COLUMN BASE.
PROPOSED FRAMING PLAN
SCALE: 1" = 5'