This document summarizes a federal contract opportunity for corrective fire alarm work at a Veterans Health Care facility. The solicitation requests proposals from Service-Disabled Veteran-Owned Small Businesses to perform corrective fire alarm work at the Veterans Health Care System of the Ozarks in Fayetteville, Arkansas for an estimated cost between $500,000 to $1,000,000. Interested vendors must check the SAM website for proposal due dates and amendments, with the tentative proposal due date of November 16, 2020. Offerors must represent their SDVOSB status and small business size, and have a CVE verification at time of proposal submission. The anticipated period of performance is 240 calendar days from notice to proceed.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A AMPERE, AMMETER
AF AMPERE FRAME
AFF ABOVE FINISHED FLOOR
AIC AMPERES INTERRUPTING CAPACITY
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
C CONDUIT
CL CENTER LINE
CR CARD READER ACCESS
CU COPPER
DR DOOR
EC EMPTY CONDUIT
EMER EMERGENCY
EWC ELECTRIC WATER HEATER
EX EXISTING
G, GND GROUND
GF GROUND FAULT INTERRUPTER
HH HANDHOLE
HP HORSEPOWER
HS HOOD SUPPRESSION CONTROL
HZ HERTZ
IG ISOLATED GROUND
JB JUNCTION BOX
KVA KILOVOLT-AMPERES
KW KILOWATTS
LC LIGHTING CONTACTOR
LTG LIGHTING
PROVIDE FURNISH, INSTALL & CONNECT
RECPT RECEPTACLE
RL EXISTING ITEM TO BE RELOCATED
RM EXISTING ITEM TO REMAIN
RP EXISTING ITEM TO BE REPLACED
SC SECURITY CAMERA OUTLET
SN SOLID NEUTRAL
SW SWITCH
SWBD SWITCHBOARD
TV COMBINATION TV & RECEPT OUTLET
TYP TYPICAL
UG UNDER GROUND
UNO UNLESS NOTED OTHERWISE
V VOLT
LC LIGHTING CONTACTOR
WP WEATHERTIGHT GFI
WAP WIRELESS ACCESS POINT
XFMR TRANSFORMER
THIS SCHEDULE IS REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE PLANS BUT NOT ALL MAY BE UTILIZED
FIRE ALARM MANUAL PULL STATION, MOUNT AT 48" ABOVE FINISHED FLOOR. SUBSCRIPT
"K" INDICATES KEY OPERATED INSTITUTIONAL DEVICE.
ELECTRICAL SYMBOL LEGEND
FIRE ALARM COMBINATION CHIME AND STROBE DEVICE, SUBSCRIPT INDICATES CANDELA
RATING OTHERWISE 15 CANDELA. MOUNT AT A MINIMUM OF 80" ABOVE FINISHED FLOOR AND A
MINIMUM OF 6" BELOW FINISHED CEILING HEIGHT.
FIRE ALARM STROBE DEVICE, SUBSCRIPT INDICATES CANDELA RATING OTHERWISE 15
CANDELA. MOUNT AT A MINIMUM OF 80" ABOVE FINISHED FLOOR AND A MINIMUM OF 6" BELOW
FINISHED CEILING HEIGHT.
FIRE ALARM SMOKE DETECTOR, CEILING SURFACE MOUNTED.
FIRE ALARM SYSTEM DUCT DETECTOR WITH SAMPLING TUBES, FURNISHED AND WIRED BY
ELECTRICAL CONTRACTOR TO THE LOCAL FACP, INSTALL BY MECHANICAL CONTRACTOR
UNLESS OTHERWISE INDICATED.
FIRE ALARM SYSTEM DUCT DETECTOR REMOTE INDICATOR LIGHT.
L
FIRE ALARM SYSTEM RELAY, CONTROL OR MONITORING TYPE AS REQUIRED.
FIRE ALARM END OF LINE RESISTOR.
EOLR
RM
FIRE ALARM SPRINKLER SYSTEM FLOW SWITCH.
FIRE ALARM SPRINKLER SYSTEM TAMPER SWITCH.
FIRE ALARM SYSTEM HEAT DETECTOR.
FIRE ALARM SYSTEM SPEAKER, WALL MOUNTED.
FIRE ALARM SYSTEM SPEAKER, CEILING MOUNTED.
FIRE ALARM SYSTEM HORN/STROBE, CEILING MOUNTED.
H
FIRE ALARM SYSTEM STROBE, CEILING MOUNTED.
FIRE ALARM SYSTEM DOOR HOLD OPEN DEVICE.
FIRE ALARM VOICE NOTIFICATION AMPLIFIER AND STROBE POWER SUPPLY
FAVP
FIRE ALARM ADDRESSABLE VOICE COMMAND CONTROL PANEL
FIRE ALARM STANDARD ADDRESSABLE CONTROL PANEL
A. ALL WORK SHALL BE DONE ACCORDING TO THE NATIONAL ELECTRICAL CODE AND OTHER
APPLICABLE REFERENCED CODES. TAKE PARTICULAR CARE TO OBSERVE DURING BID
PREPARATION ANY POSSIBLE CODE DISCREPANCIES AND BRING TO THE ATTENTION OF
THE ENGINEER FOR RESOLUTION.
B. THE CONTRACTOR SHALL MAINTAIN, ON THE SITE, AN ADEQUATE ADMINISTRATIVE SPACE
WHERE ONE COMPLETE SET OF PLANS AND SPECIFICATIONS SHALL BE KEPT FOR THE
WORK OF ALL TRADES ON THE PROJECT. THESE PLANS AND SPECIFICATIONS SHALL BE IN
ADDITION TO THE SETS USED BY THE INSTALLING ELECTRICIAN IN CARRYING OUT THEIR
DAY-TO-DAY WORK ON THE PROJECT.
C. CONTRACTOR SHALL ALSO MAINTAIN AT THE SITE A COMPLETE SET OF ALL SHOP
DRAWINGS, EQUIPMENT CUTS, MANUFACTURER'S WIRING DIAGRAMS AND INSTALLATION
DATA. INSTALLING PERSONNEL SHALL STUDY THIS DATA BEFORE AND DURING
INSTALLATION AND ROUGH-IN SO AS TO PREPARE FOR THE PROPER FIT AND FUNCTION
UPON COMPLETION.
D. PENETRATIONS OF REQUIRED SMOKE TIGHT PARTITIONS SHALL BE SEALED USING U.L.
LISTED METHODS. COORDINATION WITH THE OWNER AND ENGINEER SHALL BE
MAINTAINED TO INSURE THAT THE INTEGRITY OF THE SMOKE BARRIER IN MAINTAINED.
E. WHERE PENETRATIONS ARE MADE THROUGH A REQUIRED FIRE-RESISTIVE WALL, FLOOR,
OR PARTITION FOR THE PURPOSE OF RUNNING CABLE OR RACEWAYS FIRE STOP PER
NFPA. COORDINATION WITH THE OWNER AND ENGINEER SHALL BE MAINTAINED TO
INSURE THAT THIS FIRE STOPPING IS ACCOMPLISHED. USE ONLY APPROVED ASSEMBLIES
SUCH AS THE FOLLOWING:
F. CONDUIT PENETRATIONS OF 1 & 2 HOUR GYPBOARD WALLS - U.L.#WL1001 CONDUIT
PENETRATIONS OF 1 & 2 HOUR CONCRETE OR BLOCK WALLS - U.L.#CAJ1001 CONDUIT
PENETRATIONS OF 1 & 2 HOUR CONCRETE FLOORS - U.L.#CAJ1001.
G. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE U.L.
LISTED AND LABELED.
H. NEW FLOOR AND WALL SLEEVES SHALL BE HILTI-CP653 FOUR INCH SPEED SLEEVES.
I. BEFORE STARTING WORK THE CONTRACTOR SHALL PERFORM A COMPLETE
WALK-THROUGH OF THE PROJECT TO EXAMINE EXISTING EQUIPMENT, DEVICES AND THE
WORK REQUIRED. PROVIDE A REPORT OF ANY OBSERVATIONS THAT MAY AFFECT THE
WORK.
K. ALL SMOKE DETECTORS SHALL BE LOCATED AT A MINIMUM OF 3' FROM A SUPPLY OR
RETURN GRILLE.
FIRE ALARM SYSTEM SPEAKER/STROBE, CEILING MOUNTED.
M
F
F
FS
TS
F
GENERAL NOTES
ABBREVIATIONS & ACRONYMS
FAVC
FACP
FASP
FAVA
FAAP
FIRE ALARM STROBE POWER SUPPLY
FIRE ALARM VOICE DIGITAL AMPLIFIER
FIRE ALARM ANNUNCIATION PANEL
FIRE ALARM SYSTEM HORN/STROBE, WALL MOUNTED.
H
F
FIRE ALARM SYSTEM CARBON MONOXIDE DETECTOR
C
J. WHERE NEW DEVICES ARE INDICATED TO BE ADDED TO EXISTING
SYSTEMS, THE NEW DEVICES SHALL BE FULLY COMPATIBLE WITH
THE EXISTING SYSTEMS SO AS TO MAINTAIN ALL SYSTEM
FUNCTIONS AND ALL REQUIRED FIRE ALARM CONFORMANCE
LISTINGS, INDEPENDENT TESTING LABORATORY LABELINGS, AND
ALL EXISTING FIRE ALARM SERVICE CONTRACTS.
1 2 3 4 5
Drawing Title:Seal:
FULLY SPRINKLERED
ARCHITECT / ENGINEERS:
Project Title:
Date:
Project Number:
Drawing Number:
Drawn:Checked:
Building Number:
D C
B A
Revisions:
8016 TOWER POINT DRIVE
CHARLOTTE, NC 28227
P 704.814.1320
F 704.321.0833
Project Phase:
D C
B A
1 2 3 4 5 6
Location:
CONSULTANTS:
U.S. Department of Veterans Affairs
H A R R E L L
D E S I G N G R O U P , P C formerly HARRELL, SALTRICK & HOPPER, PC
HDG PROJECT: 18022
BID DOCUMENTS
JULY 16, 2020
564-17-103CORRECT FIRE ALARM
DEFICIENCIES
VETERANS HEALTHCARE
SYSTEM OF THE OZARKS
Sheet of
ETERANS EALTH ARE YSTEMV H C S
OF THE ZARKSO
Engineering Service
LEH GWG
GENERAL NOTES
AND LEGENDS
FA100
04 39
AutoCAD SHX Text
REVISION DESCRIPTION
AutoCAD SHX Text
REVISION NO.
AutoCAD SHX Text 1.
AutoCAD SHX Text
AMENDMENT 0003
AutoCAD SHX Text 2/2/2021
AutoCAD SHX Text
| Sheets and Views |
| FA100 |
| 2021-02-03T07:57:00-0500 | |
| John G. Ross, PE |
File details come from the government source that posted it. Updated .