657-26-105 GOVERNMENT RESPONSE TO RFI 1 OF 3.pdf

PDF 296 KB Posted

Attached to
657-26-105, Upgrade Interior Physical Security
Solicitation number
36C25526R0064_1
Issued by

About this file

This document is a Response to Request for Information (RFI) #1 of 3 issued by the Department of Veterans Affairs for Project 657-26-105, an Upgrade Interior Physical Security project at Saint Louis Veterans Medical Center in Saint Louis, Missouri, under Solicitation 36C25526R0064, Amendment 0002.

The RFI response provides clarifications and specifications for interior physical security upgrades across multiple VA facilities. For seven community-based outpatient clinics (CBOCs) and one recovery center—Hope Recovery Center, Manchester Ave CBOC, Washington Ave CBOC, St. Louis County CBOC, St. Charles County CBOC, Franklin County CBOC, and St. Clair County CBOC—floor plans and detailed scope locations for interior physical devices (IPDs) are attached. At John Cochran Building 75, four glass windows in fire doors (located in Rooms 1C 100, 1C 101, and 1C 102) measuring approximately 4"x25" must be replaced with fire-rated wired safety glass and recertified per NFPA and VA Technical Information Letter (TIL) standards. For John Cochran Building 8, three glass windows (two aluminum windows by door and one at ground level in brick) require installation of security screens conforming to VA Handbook 0730 and VA Physical Security Design Manual specifications, constructed of #304 stainless steel woven mesh with 0.7 mm wire diameter, 12x12 mesh per inch, and carbon steel frames with baked enamel finish. The project requires Class 2 ICRA (Infection Control Risk Assessment) level and mandates contractor superintendence on-site at all times during performance per FAR 52.236-6. Two additional RFI responses are scheduled for publication by 6:00 PM CST on Thursday, March 5, 2026.

View the file

Other files

File Type Posted
AMMENDMENT 0005 ATTACHMENT_PICTURE FROM DOOR REFERENCE.jpg JPG image
AMMENDMENT 0005 ATTACHMENT_657.313A.75.AE610.A6.pdf PDF
657-26-105 GOVERNMENT RESPONSE TO RFIs AMMENDMENT 0005.pdf PDF
AMMENDMENT 0005 ATTACHMENT_657.313A.75.AE101.A7.pdf PDF
AMMENDMENT 36C25526R0064 0005.pdf PDF
AMENDMENT 36C25526R0064 0004.pdf PDF
JB PANEL LOCATION FLOOR PLAN.pdf PDF
JC PANEL LOCATION FLOOR PLAN.pdf PDF
PROGRAM AND KEY CABINET LOCATIONS.pdf PDF
AMENDMENT 36C25526R0064 0003.pdf PDF
657-26-105 GOVERNMENT RESPONSE TO SC DATACOMS RFI 3 OF 3.pdf PDF
657-26-105 GOVERNMENT RESPONSE TO PASS_FIRE_SECURITY RFI 2 OF 3.pdf PDF
657-26-105 GOVERNMENT RESPONSE TO RFI 1 OF 3.pdf PDF
AMENDMENT 36C25526R0064 0001.pdf PDF
SAINT LOUIS NORTH COUNTY 657-26-105.pdf PDF
WINDOWS 657-26-105.pdf PDF
SAINT CLAIR COUNTY 657-26-105.pdf PDF
AMENDMENT 36C25526R0064 0002.pdf PDF
AMENDMENT 36C25526R0064 0001.pdf PDF
WASHINTON AVE CBOC 657-26-105.pdf PDF
HOPE RECOVERY CENTER 657-26-105.pdf PDF
SAINT CHARLES COUNTY 657-26-105.pdf PDF
FRANKLIN COUNTY 657-26-105.pdf PDF
MANCHESTER AVE 657-26-105.pdf PDF
SITE VISIT SIGN-IN SHEET_36C25526R0064.pdf PDF
AMMENDMENT 36C25526R0064 0001.pdf PDF
SOLICITATION 36C25526R0064_1 UPDATE INTERIOR PHYSICAL SECURITY.docx DOCX document
DRAWING JB CAMPUS_657-26-105.pdf PDF
DRAWINGS JC CAMPUS-657-26-105.pdf PDF
DOOR NUMBER LIST_657-26-105.pdf PDF
DOOR SIGN DETAILS_657-26-105.pdf PDF
COMBINED SPECIFICATIONS_657-26-105.pdf PDF
Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

March 4, 2026, )

Project: 657-26-105, Upgrade Interior Physical Security Solicitation: 36C25526R0064 Saint Louis Veterans Medical Center, Saint Louis MO 63103 Reference Amendment 36C25526R0064 0002

Response to RFI #1 of 3

Below are the answers to RFIs 1 of 3, attached are the floorplans and photos requested.

This is 1 of 3 responses on RFI’s for this project, the remaining 2 will be published by 6:00PM CST, Thursday3/5/2026.

1. Please provide floor plans, scope locations and or possible photos of areas of work to be performed at the following locations listed on page 14 of 95 of solicitation.

a. Hope Recovery Center – Floor plan attached – See SOW for locations for IPDs

b. Manchester Ave CBOC - Floor plan attached – See SOW for locations for IPDs

c. Washington Ave CBOC - Floor plan attached – See SOW for locations for IPDs

d. St Louis County CBOC - Floor plan attached – See SOW for locations for IPDs

e. St Charles County CBOC - Floor plan attached – See SOW for locations for IPDs

f. Franklin County CBOC - Floor plan attached – See SOW for locations for IPDs

g. St Clair County CBOC - Floor plan attached – See SOW for locations for IPDs

2. John Cochran Building 75 items G on scope of work. Please provide confirmation of which 4 each glass windows are to be replaced, possibly with photos?

a. As discussed during the pre bid walk at JB Bldg, Room 1C 100 single door, Room 1C 101 double door and 1C 102 single door.

Each of these doors currently have a glass window in them that will need to be replaced, 4 windows in total.

3. Please provide specification and or details of replacement windows.

a. Replace four (4) glass windows approximately 4”x25”

(contractor to verify measurements) in fire doors at JB bldg. 75 with fire rated wired safety glass, and recertify doors as required by NFPA and VA TIL.

4. John Cochran Building 8 items H on scope of work. Please provide confirmation of which 3 each glass windows are to get the security screens, possibly with photos?

DEPARTMENT OF VETERANS AFFAIRS

VA Heartland Network 15 3450 South Fourth Street

Leavenworth, KS 66048-5055

a. Two aluminum windows by door and one window at ground level in brick as shown on attached photo labeled 657-26-105 – Windows.pdf.

5. Please provide specification and or details of security screens.

a. Per VA Handbook 0730 and the VA Physical Security Design Manual (PSDM)– All

#304 stainless steel woven mesh 0.7 mm (.028 in.) wire diameter, with tensile strength of 15 kg/mm (800 pounds per linear inch). Mesh 12x12 per 25 mm (1 in.) with main and sub frames of 2.7 mm (12 gauges) carbon steel with baked enamel finish and internal key locking slide bolts.

6. What will be the ICRA requirements for this project if any?

a. ICRA level will be Class 2.

7. Will supervision be required when there is manpower on site?

a. Yes, per FAR 52.236-6 Superintendence by the Contractor. - At all times during performance of this contract and until the work is completed and accepted, the Contractor shall directly superintend the work or assign and have on the worksite a competent superintendent who is satisfactory to the Contracting Officer and has authority to act for the Contractor.

Gislaine Dorvil Contracting Officer

DEPARTMENT OF VETERANS AFFAIRS