657-21-115JC_100 Bid Documents_5of5.pdf
PDF 15 MB Posted
- Attached to
- Z2DA--657-21-115JC - Correct Heating, Ventilation, and Air Conditioning Systems in Procedure Rooms
- Solicitation number
- 36C25526R0059
About this file
This document is a set of electrical engineering drawings and schedules for a federal construction project at a Veterans Health Administration facility in St. Louis, Missouri. The project involves correcting heating, ventilation, and air conditioning (HVAC) systems in procedure rooms across multiple building levels.
The electrical work includes installing new air handler units, supply fans, exhaust fans, and terminal units in various patient care rooms and procedure areas, with corresponding power distribution, control wiring, and lighting modifications. New mechanical equipment requiring electrical service is being added to rooms across levels 1 through 10, including patient isolation rooms, exam rooms, and specialized treatment spaces such as hemodialysis bays and bronchoscopy suites. The project requires extensive conduit routing, junction boxes, pull boxes, and interconnections between existing electrical panels and new mechanical equipment. Lighting fixture replacements are specified with LED technology, using sealed troffers and downlights with 3500K color temperature and 80 CRI minimum. The electrical contractor is responsible for coordinating with mechanical contractors, temporary removal and reinstallation of existing fixtures during above-ceiling work, updating panel schedules, and ensuring continuity of circuits during the renovation. Circuit breaker additions and modifications are required across multiple existing panels (1BE, 1E2, 5BE, 6DE, 7CE, 7DE, E2AL2, E5E, EDP6, 8BE, EQHD5, and EQA10), with detailed load calculations and demand factors provided. The document includes comprehensive electrical schedules, mechanical equipment specifications with voltage and amperage requirements, conduit support details, roof penetration requirements, and mounting instructions for luminaires and receptacles.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
ELECTRICAL NOTES
DEMOLITION NOTES
ELECTRICAL ABBREVIATIONS POWER SYMBOLSSYSTEMS LEGEND
LIGHTING SYMBOLS
RECEPTACLE, DUPLEX
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER
WEATHER PROOF RECEPTACLE WITH GROUND FAULT CIRCUIT
INTERRUPTER
JUNCTION BOX, WALL/CEILING/FLOOR MOUNTED:
SIZE PER N.E.C., REFER TO SPECIFICATIONS FOR GENERAL
CONSTRUCTION, SYMBOL DOES NOT INDICATE ALL JUNCTION BOXES
THAT ARE REQUIRED FOR THIS PROJECT ARE SHOWN ON PLAN(S).
PULL BOX
PANELBOARD
TRANSFORMER
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
MOTOR RATED MANUAL TOGGLE CONTROLLER WITH OVERLOAD
ELEMENT FOR CONTROL OF EQUIPMENT
WYE CONNECTION
EARTH GROUND
CONDUIT TURNING DOWN
CONDUIT TURNING UP
T
PB
J J
VOICE/DATA PORT
X PORT DATA OUTLET (1-ONE DATA, 2-2 DATA)
CABLE TELEVISION OUTLET BOX MOUNTED AT 82" A.F.F. OR AS
INDICATED WITH ONE 1"C STUBBED UP ABOVE ACCESSIBLE CEILING
AND PULL CORD
NURSE CALL, LETTER DENOTES TYPE:
BLANK - PATIENT STATION
CB - CODE BLUE STATION
D - STAFF/DUTY STATION
E - EMERGENCY STATION
M - MASTER STATION
H4
H7
A
26-SF 3
26-TU-I-I
DETAIL NUMBER
DRAWING NUMBER WHERE SHOWN
SECTION LETTER
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
SUPPLY FAN NO. 3 IN BUILDING NO. 26
EQUIPMENT ABBREVIATION (SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
DRAWING NUMBER WHERE DRAWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED
NOTES:
1. LETTER OR NUMBER DENOTES FIXTURE TYPE, REFER TO LIGHTING FIXTURE
SCHEDULE AND LIGHTING PLANS FOR DETAILS.
2. ALL SYMBOLS SHOWN WITH DASHED LINES DENOTES THAT FIXTURES ARE TO BE
REMOVED - THIS APPLIES ONLY TO DEMOLITION SHEETS.
2' x 4' FIXTURE
2' x 4' EMERGENCY FIXTURE
2' x 2' FIXTURE
2' x 2' EMERGENCY FIXTURE
SWITCH, LETTER DENOTES TYPE:
BLANK - SINGLE POLE, SINGLE THROW, 120/277 VOLT, 20 AMP.
3 - THREE WAY, 120/277 VOLT 20 AMP
D - DIMMER: LED ELECTRONIC DRIVERS, 277 VOLT, DECORA
STYLE LINEAR SLIDER OPERATOR WITH POSITIVE OFF.
COLOR TO MATCH DEVICES.
O - CEILING MOUNT OCCUPANCY SENSOR,
DUAL TECHNOLOGY, WALL MOUNT
1. INSTALL GREEN INSULATED GROUND WIRE WITH EACH LIGHTING, RECEPTACLE,
AND EQUIPMENT BRANCH CIRCUIT.
2. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT
REQUIRING A NEUTRAL, UNLESS OTHERWISE NOTED.
3. CONCEAL CONDUITS INSTALLED IN NEW WALLS, EXISTING STUD WALLS AND IN
AREAS WITH SUSPENDED CEILINGS.
4. REPAIR OR REPLACE BUILDING ELEMENTS THAT ARE DAMAGED AS PART OF
ELECTRICAL WORK.
5. SEAL PENETRATIONS IN FIRE RATED CONSTRUCTION TO MAINTAIN RATINGS.
6. COORDINATE PHASING REQUIREMENTS, BOUNDARIES, ETC., WITH ARCHITECTUAL
DRAWINGS AND DETAILS.
7. PROVIDE POWER CONNECTION TO CONTROL PANELS, TRANSFORMERS, AND
OTHER ITEMS FURNISHED BY MECHANICAL CONTRACTOR FOR HVAC CONTROL.
COORDINATE LOCATIONS OF DEVICES REQUIRING POWER CONNECTIONS WITH
MECHANICAL CONTRACTOR.
8. LABEL OUTLET WALL PLATES WITH CORRESPONDING PANEL AND CIRCUIT NUMBER.
DRAWING SYMBOLS
1. FIRE STOP SHALL BE PROVIDED AT ALL LOCATIONS WHERE ELECTRICAL
EQUIPMENT OR SYSTEMS PENETRATE FIRE RATED WALLS. SEE ARCHITECTURAL
PLANS FOR RATED WALL LOCATIONS.
2. CONTROL WIRING TO MECHANICAL EQUIPMENT IS NOT SHOWN ON THESE SHEETS.
3. ONE-LINE DIAGRAMS ARE MEANT TO SHOW ONLY ELECTRICAL RELATIONSHIPS AND
THEREFORE MAY NOT INCLUDE ALL REQUIRED EQUIPMENT, DEVICES AND
ACCESSORIES.
4. ALL ELECTRICAL WORK SHALL COMPLY WITH ALL LOCAL, STATE, AND FEDERAL
CODES, PARTICULARLY THE LATEST APPLICABLE VERSION OF THE NATIONAL
ELECTRIC CODE (NFPA 70).
5. ELECTRICAL CONTRACTOR SHALL COORDINATE REQUIREMENTS OF ALL
EQUIPMENT PROVIDED BY OTHER TRADES PRIOR TO ROUGH-IN.
6. DO NOT SCALE DRAWINGS. IF EXACT LOCATION OF EQUIPMENT CANNOT BE
DETERMINED CONTACT THE ARCHITECT/ENGINEER FOR DIRECTION.
7. ALL SIZES ARE BASED ON COPPER CONDUCTORS. SIZES SHALL NOT BE LESS THAN
INDICATED.
8. ELECTRICAL CONTRACTOR SHALL NOT SHARE NEUTRALS, UNLESS SPECIFICALLY
NOTED OTHERWISE. ALL LIGHTING CIRCUITS SHALL HAVE A SEPARATE INSULATED
GROUNDING CONDUCTOR INSTALLED WITH EACH CIRCUIT.
9. ALL HEIGHTS OF ELECTRICAL DEVICES NOTED SHALL BE TO THE CENTER OF THE
DEVICE.
10. PROVIDE UPDATED DIRECTORY FOR ALL PANELS USED IN THIS PROJECT.
1. ELECTRICAL CONTRACTOR TO BE RESPONSIBLE FOR AREAS OF DEMOLITION AS
PART OF THIS PROJECT. CONTRACTOR IS TO ALSO TAKE MEASURES AS TO ENSURE
CONTINUITY OF CIRCUITS WHERE REQUIRED DUE TO RENOVATIONS. ANY OUTAGES
WHICH MAY RESULT AS A PART OF THIS PROJECT ARE TO BE COORDINATED WITH
THE COR TWO WEEKS PRIOR TO ANY WORK BEING COMPLETED.
2. ANY WIRING DEVICES, LIGHT FIXTURES, CONDUCTORS, AND CONDUITS THAT MAY
BE REMOVED AS PART OF THIS PROJECT ARE TO BE HANDED OVER TO THE OWNER
OR RELOCATED.
3. ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE FOR UPDATING SCHEDULES FOR
ANY SWITCHBOARDS AND PANELBOARDS THAT ARE AFFECTED BY THIS PROJECT
AND ARE TO BE TYPEWRITTEN.
4. THE ELECTRICAL CONTRACTOR WILL BE RESPONSIBLE FOR REQUIRED WORK
OUTSIDE THIS PROJECT BOUNDARY NECESSARY TO ENSURE ADJACENT SERVICES
REMAIN ENERGIZED DURING CONSTRUCTION OF THE RENOVATION PROJECT.
5. ALL EXISTING BRANCH CIRCUITS NOT USED ARE TO BE REMOVED BACK TO THE
PANEL. THE CIRCUIT BREAKERS ARE TO BE LABELED AS SPARE. EXISTING
CONDUITS FROM PANEL ARE TO REMAIN TO ABOVE CEILING.
6. ELECTRICAL CONTRACTOR TO PROVIDE COVERS FOR ANY EXISTING OPEN
BUSSING IN PANELBOARDS THAT ARE AFFECTED BY THIS PROJECT.
7. ELECTRICAL CONTRACTOR TO REMOVE ANY AND ALL UNUSED OR ABANDONED
ELECTRICAL EQUIPMENT THAT RESIDES WITHIN THE AREAS OF THE PROJECT
SCOPE.
8. REPAIR OR REPLACE BUILDING ELEMENTS WHICH ARE DAMAGED AS PART OF
DEMOLITION WORK.
9. DISCONNECT MECHNICAL EQUIPMENT BEING REMOVED BY MECHANICAL
CONTRACTOR. COORDINATE EQUIPMENT REMOVAL LOCATIONS WITH MECHANICAL
DRAWINGS.
10. COORDINATE DEMOLITION WITH THE WORK OF OTHER TRADES.
11. FOR EQUIPMENT AND DEVICES TO BE DEMOLISHED, THE EXISTING CABLING SHALL
BE REMOVED IN IT'S ENTIRETY.
12. PROVIDE BLANK COVERPLATES FOR ABANDONED RECESSED JUNCTION BOXES.
13. COORDINATE DEMOLITION OF TELECOMMUNICATIONS CABLING WITH OWNER AND
GENERAL CONTRACTOR.
14. ALL ELECTRICAL WORK SHALL COMPLY WITH ALL LOCAL, STATE, AND FEDERAL
CODES, PARTICULARLY THE LATEST APPLICABLE VERSION OF THE NATIONAL
ELECTRICAL CODE (NFPA 70).
15. COORDINATE ANY AND ALL OUTAGES WITH THE OWNER PRIOR TO ANY DISRUPTION
OF POWER.
16. EXISTING ELECTRICAL SYSTEM IS TO REMAIN IN SERVICE UNLESS OTHERWISE
NOTED. ALL CIRCUITS WHICH ARE DISTURBED BY DEMOLITION OR NEW
CONSTRUCTION ARE TO BE RECONNECTED AT NO ADDITIONAL COST TO THE
OWNER.
17. REMOVE ALL BRANCH CIRCUIT CONDUIT AND CONDUCTORS SERVING EQUIPMENT
AND DEVICES WHICH WILL NO LONGER BE USED, UNLESS OTHERWISE NOTED.
18. REMOVE ALL DEVICES INDICATED BY DARKENED OR DASHED LINES AND
ASSOCIATED KEYED NOTES. REMOVE ALL DEVICES IN WALLS AND CEILINGS WHICH
ARE SHOWN TO BE DEMOLISHED ON ARCHITECTURAL PLANS, WHETHER OR NOT
SUCH DEVICES ARE SHOWN ON THESE PLANS.
19. REMOVE ALL DEVICES, CONDUIT AND CONDUCTORS COMPLETE TO SOURCE
ASSOCIATED WITH MECHANICAL EQUIPMENT WHICH IS BEING DEMOLISHED.
COORDINATE WITH MECHANICAL PLANS FOR DETAILED INFORMATION.
20. WHERE CIRCUITS ARE REMOVED COMPLETELY, RELABEL EXISTING CIRCUIT
BREAKER AS "SPARE".
21. PORTIONS OF CONDUIT LOCATED WITHIN WALLS OR FLOORS WHICH ARE NOT TO
BE REMOVED MAY REMAIN IN PLACE AT THE CONTRACTOR'S OPTION. HOWEVER,
REMOVE ALL CONDUCTORS COMPLETELY BACK TO THE SOURCE.
22. EXISTING LIGHTING AND LIGHTING CONTROLS ARE TO REMAIN UNLESS OTHERWISE
NOTED ON THE LIGHTING PLANS.
GFI
J
TV
N #
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C UNIT AIR CONDITIONING UNIT
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER
AFCI ARC-FAULT CURRENT INTERRUPTER
Ah AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE AMP AMPERE
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BD BOARD
BFF BELOW FINISH FLOOR
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER OR C/B
CLF CURRENT LIMITING FUSE CLG CEILING
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CUR CURRENT
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DIAG DIAGRAM
DISC DISCONNECT
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH DS DISCONNECT SWITCH
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESC ESCUTCHEON
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FIXT FIXTURE
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FP FIRE PROTECTION
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G ELECTRICAL GROUND
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAh KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR kWhM KILOWATT HOUR METER
LED LIGHT EMITTING DIODE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MT MOUNT MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
NC NORMALLY CLOSED
NEUT NEUTRAL (OR N)
NL NIGHT LIGHT
NO NORMALLY OPEN
OL OVERLOAD
P POLE
PB PULL BOX
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
RCP REFLECTED CEILING PLAN
REC RECESSED
RECEP RECEPTACLE
RMS ROOT MEAN SQUARE
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TEL TELEPHONE
TV TELEVISION
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
WH WATER HEATER
WP WEATHERPROOF
XFMR TRANSFORMER
GFI,WP
M
X
' 6
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e ct
H V
A C
S ys te m s in
P ro ce d u re R m /S t L o u is
P ro cR m s-
JC
M
E P
V
.r vt
/3
/2
:2
:4
P
M
ELECTRICAL LEGEND, NOTES, AND
ABBREVIATIONS
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
YW SM
915 North Grand Blvd.
St. Louis, MO 63106
01-EG-001
Revisions: Date:
user Image
DN
PB
PB
PB
SCOPE OF WORK
KEYNOTES
EXAM
A139B
EXAM
A139A
MECH. RM.
B100A
INFORMATION
H100A
LOBBY
H100
MED. PREP.
B102A
ALCOVE
B102D
OFFICE
B102E
AGENT CASHIER
B102F
CORRIDOR
H118
CONFERENCE RM.
B106
ARMORY
B107
LOCKER RM.
C101
EVIDENCE
C102
OFFICE
C103
OFFICE
C104
OFFICE
C105
OFFICE
C106
HOLDING CELL
C107CONTROL
C108
ELEVATOR LOBBY
H122
CORRIDOR
H120
TOILET, MALE
C146
OI&T
B105
HAC
B103 CHUTE
B104
CORRIDOR
H113
OFFICE
B149B
TOILET, FEMALE
B122
OFFICE
B111
CORRIDOR
H124
EXAM
B112
EXAM
B113
EXAM
B114
EXAM
B116
EXAM
B117
OFFICE
B117A
OFFICE
C149
LOCKER RM.
C138
ELIGIBILITY
C140
OFFICE
C141
OFFICE
C141A
CORRIDOR
H125
WAITING RM.
C110
OFFICE
C109
TRIAGE
C109A
CONTROL RM.
C112
TRIAGE
C113
TRIAGE
E125
TOILET
E126
ANTE RM.
E127
PATIENT ISO.
E128
EXAM TREATMENT
E133
NURSE STATION
E103
HAC
E121
TOILET
E135
EXAM
C111B
EXAM
C111A
OFFICE
C126
OFFICE
C127
OFFICE
C129
STORAGE
C137
OFFICE
C148
EXAM
C150
EXAM
C151
EXAM
C152
CORRIDOR
H127
CORRIDOR
H127A
CORRIDOR
H114A
CORRIDOR
H119
CORRIDOR
H113C
HAC
C146A
ELEC
B120A
ENTRYWAY
H125B
VESTIBULE
C109B
VESTIBULE
H125A
VESTIBULE
S107A
F.E. CLOSET
H113B
Room
ELEV 7
ELEV 8
ELEV 9
CHASE
CH-C-2
CHASE
CH-B-1
CHASE
CH-B-4 CHASE
CH-B-5
CHASE
CH-B-6
CHASE
CH-C-3
CHASE
CH-B-8
CHASE
CH-B-9
CHASE
CH-C-4
CHASE
CH-C-8
CHASE
CH-E-1
CHASE
CH-C-6
10 6
1BE (EX)
ROUTE CONDUITS UP TO
LEVEL 2. SEE LEVEL 2
PLAN ON SHEET 03-EP105.
1E2 (EX)
E103
NURSE STATION
20 20 20 20 20 20 20 20 20 20
01-EP-102
01-EP-102
20 20
20 20
21 21
21 21
21 21 21
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-EP-101
GENERAL NOTES
1. SEE SHEET E-001 FOR SYMBOLS AND GENERAL ELECTRICAL NOTES.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. NOT ALL CEILING DEVICES ARE SHOWN. CONTRACTOR TO VERIFY EXISTING
EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
4. HALF TONE ITEMS INDICATE EXISTING TO REMAIN. FULLTONE AND DASHED ITEMS
INDICATE NEW OR DEMOLITION.
5. SEE SHEET E400 FOR MECHANICAL EQUIPMENT CIRCUITING AND DISCONNECT
INFORMATION.
6. PRIOR TO BIDDING, THE G.C. SHOULD VISIT THE PROJECT SITE AND INSPECT
EXISTING CONDITIONS. INSPECTION TIMES WILL BE AFTER NORMAL WORKING
HOURS TO AVOID IMPACT TO NORMAL OPERATIONS.
7. THE G.C. IS RESPONSIBLE FOR THE REMOVAL AND RESTORATION/RELOCATION OF
ALL EXISTING ABOVE CEILING CONDITIONS NECESSARY TO ACCOMODATE THE
NEW WORK. EXISTING ABOVE CEILING CONDITIONS INCLUDE BUT NOT LIMITED TO
LIGHTING, ELECTRICAL POWER, FIRE ALARM, SECURITY, NURSE CALL, DATA
CABLES, AND OTHER LOW VOLTAGE ALARM, TO INCLUDE RELATED CONDUIT
SYSTEMS AND HANGERS. THE EXISTING ABOVE CEILING CONDITIONS ARE OF
SUCH NATURE THAT ALL FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND
SPECIFY. IT IS THEREFORE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO
VISIT THE SITE PRIOR TO BIDDING AND INSPECT THE EXISTING CONDITIONS TO
COMPLETELY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND RELATE
SUCH CONDITIONS TO THE SCOPE OF THE PROPOSED NEW WORK.
NORTH
' 6
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e ct
H V
A C
S ys te m s in
P ro ce d u re R m /S t L o u is
P ro cR m s-
JC
M
E P
V
.r vt
/3
/2
:2
:1
P
M
ELECTRICAL ENLARGED PLAN - LEVEL 01
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
YW SM
915 North Grand Blvd.
St. Louis, MO 63106
01-EP-101
3/16" = 1'-0"1
ELECTRICAL ENLARGED PLAN - LEVEL 01
NO. DESCRIPTION
6 ALL CEILING MOUNTED ELECTRICAL LIGHTING FIXTURES AND DEVICES IN AFFECTED
AREA ARE TO BE TEMPORARILY REMOVED AND REINSTALLED AND RECONNECTED
UPON COMPLETION OF ABOVE CEILING WORK.
10 ROUTE CONDUIT ABOVE CEILING SPACE. SEE SHEET EP-201 FOR BRANCH CIRCUIT
INFORMATION.
17 PROVIDE PULLBOX ABOVE CEILING. COORDINATE NUMBER OF PULL BOXES
REQUIRED PER NEC CODE.
20 LIGHTING FIXTURES AND DEVICES IN AFFECTED AREA ARE TO BE TEMPORARILY
REMOVED AND REINSTALLED AND RECONNECTED UPON COMPLETION OF ABOVE
CEILING WORK.
21 EXISTING LIGHTING FIXTURE TO REMAIN.
NTS
KEYPLAN - LEVEL 01
Revisions: Date:
S P
S
S
S P
S
S
J
S M
S M
SCOPE OF WORK
KEYNOTES
TOILET
E126
ANTE RM.
E127
PATIENT ISO.
E128
EXAM TREATMENT
E133
VESTIBULE
S107A
CHASE
CH-E-1
E103
NURSE STATION
20 20
01-SCV-E128
01-ECV-E127
01-ECV-E128
B
B
B
TOILET
E126
ANTE RM.
E127
PATIENT ISO.
E128
EXAM TREATMENT
E133
VESTIBULE
S107A
CHASE
CH-E-1
01-SF-E128
1E2 (EX)-27
1E2 (EX)-29
1E2 (EX)-25
01-AHU-E128
1E2 (EX)-26
DDC
PANEL
E103
NURSE STATION
22 22
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-EP-102
01-EP-102
01-EP-102
1E2 (EX)
C138
LOCKER RM.
GENERAL NOTES
1. SEE SHEET E-001 FOR SYMBOLS AND GENERAL ELECTRICAL NOTES.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. NOT ALL CEILING DEVICES ARE SHOWN. CONTRACTOR TO VERIFY EXISTING
EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
4. HALF TONE ITEMS INDICATE EXISTING TO REMAIN. FULLTONE AND DASHED ITEMS
INDICATE NEW OR DEMOLITION.
5. SEE SHEET E400 FOR MECHANICAL EQUIPMENT CIRCUITING AND DISCONNECT
INFORMATION.
6. PRIOR TO BIDDING, THE G.C. SHOULD VISIT THE PROJECT SITE AND INSPECT
EXISTING CONDITIONS. INSPECTION TIMES WILL BE AFTER NORMAL WORKING
HOURS TO AVOID IMPACT TO NORMAL OPERATIONS.
7. THE G.C. IS RESPONSIBLE FOR THE REMOVAL AND RESTORATION/RELOCATION OF
ALL EXISTING ABOVE CEILING CONDITIONS NECESSARY TO ACCOMODATE THE
NEW WORK. EXISTING ABOVE CEILING CONDITIONS INCLUDE BUT NOT LIMITED TO
LIGHTING, ELECTRICAL POWER, FIRE ALARM, SECURITY, NURSE CALL, DATA
CABLES, AND OTHER LOW VOLTAGE ALARM, TO INCLUDE RELATED CONDUIT
SYSTEMS AND HANGERS. THE EXISTING ABOVE CEILING CONDITIONS ARE OF
SUCH NATURE THAT ALL FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND
SPECIFY. IT IS THEREFORE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO
VISIT THE SITE PRIOR TO BIDDING AND INSPECT THE EXISTING CONDITIONS TO
COMPLETELY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND RELATE
SUCH CONDITIONS TO THE SCOPE OF THE PROPOSED NEW WORK.
NORTH
' 6
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e ct
H V
A C
S ys te m s in
P ro ce d u re R m /S t L o u is
P ro cR m s-
JC
M
E P
V
.r vt
/3
/2
:2
:3
P
M
ELECTRICAL ENLARGED PLAN - LEVEL 01
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
YW SM
915 North Grand Blvd.
St. Louis, MO 63106
01-EP-102
1/2" = 1'-0"2
ELECTRICAL ENLARGED DEMOLITION PLAN - E128
1/2" = 1'-0"1
ELECTRICAL ENLARGED PLAN - E128
NO. DESCRIPTION
1 EXISTING ELECTRICAL PANEL TO REMAIN.
2 CONNECT NEW LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT IN ROOM. WHERE
EXISTING LIGHTS ARE ON EMERGENCY POWER, CONNECT NEW LIGHTS IN THOSE
LOCATIONS TO EXISTING EMERGENCY CIRCUIT IN ROOM.
3 J-BOX ABOVE CEILING FOR MECHANICAL CONTROL POWER FOR AVA BOX, SH, SCV,
AND ECV UNITS.
4 MECHANICAL UNIT LOCATED ABOVE CEILING. MECHANICAL CONTRACTOR TO
COORDINATE UNIT LOCATION LEAVES 10" MINIMUM FROM CEILING TO BOTTOM OF
UNIT FOR LIGHTING FIXTURE.
7 LIGHTING FIXTURES TO BE DEMOLISHED. MAINTAIN EXISTING CIRCUIT AND
CONTROLS FOR CONNECTION TO NEW LIGHTING FIXTURES TO BE INSTALLED.
8 MECHANICAL UNIT TO BE DISCONNECTED AND DEMOLISHED. REMOVE ALL WIRING,
CONNDUIT, ETC. BACK TO SERVING PANEL.
18 DUE TO NEW MECHANICAL UNIT AND DUCTWORK IN EXISTING ABOVE CEILING
SPACES, ELECTRICAL CONDUITS AND CABLING WILL BE AFFECTED. PROVIDE
PULLBOX TO INTERCEPT AND REROUTE CONDUITS WHERE NEEDED. FOR
VOICE/DATA CABLING PROVIDE NEW CABLING TO MATCH EXISTING AS NECESSARY.
19 RECEPTACLE ABOVE CEILING IN AN ELECTRICAL BOX FOR NEW DDC CONTROL
PANEL. ROUTE CAT 6 DATA CABLE TO MAIN DDC CONTROL PANEL OR DATA CLOSET.
COORDINATE LOCATION WITH MECHANICAL CONTRACTOR.
20 LIGHTING FIXTURES AND DEVICES IN AFFECTED AREA ARE TO BE TEMPORARILY
REMOVED AND REINSTALLED AND RECONNECTED UPON COMPLETION OF ABOVE
CEILING WORK.
21 EXISTING LIGHTING FIXTURE TO REMAIN.
22 REINSTALL LIGHTING FIXTURE IN EXISTING LOCATION. RECONNECT TO EXISTING
LIGHTING CIRCUIT AND CONTROLS.
NTS
KEYPLAN - LEVEL 01
1/2" = 1'-0"3
ELECTRICAL ENLARGED POWER PLAN - C138
Revisions: Date:
SCOPE OF WORK
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
GENERAL NOTES
1. SEE SHEET E-001 FOR SYMBOLS AND GENERAL ELECTRICAL NOTES.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. NOT ALL CEILING DEVICES ARE SHOWN. CONTRACTOR TO VERIFY EXISTING
EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
4. HALF TONE ITEMS INDICATE EXISTING TO REMAIN. FULLTONE AND DASHED ITEMS
INDICATE NEW OR DEMOLITION.
5. SEE SHEET E400 FOR MECHANICAL EQUIPMENT CIRCUITING AND DISCONNECT
INFORMATION.
6. PRIOR TO BIDDING, THE G.C. SHOULD VISIT THE PROJECT SITE AND INSPECT
EXISTING CONDITIONS. INSPECTION TIMES WILL BE AFTER NORMAL WORKING
HOURS TO AVOID IMPACT TO NORMAL OPERATIONS.
7. THE G.C. IS RESPONSIBLE FOR THE REMOVAL AND RESTORATION/RELOCATION OF
ALL EXISTING ABOVE CEILING CONDITIONS NECESSARY TO ACCOMODATE THE
NEW WORK. EXISTING ABOVE CEILING CONDITIONS INCLUDE BUT NOT LIMITED TO
LIGHTING, ELECTRICAL POWER, FIRE ALARM, SECURITY, NURSE CALL, DATA
CABLES, AND OTHER LOW VOLTAGE ALARM, TO INCLUDE RELATED CONDUIT
SYSTEMS AND HANGERS. THE EXISTING ABOVE CEILING CONDITIONS ARE OF
SUCH NATURE THAT ALL FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND
SPECIFY. IT IS THEREFORE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO
VISIT THE SITE PRIOR TO BIDDING AND INSPECT THE EXISTING CONDITIONS TO
COMPLETELY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND RELATE
SUCH CONDITIONS TO THE SCOPE OF THE PROPOSED NEW WORK.
EXAM
A163A
EXAM
A163B
NURSE STATION
A156
NOUR.
A159
OFFICE
A158
MED. PREP.
A157
PATIENT ISO.
A164
TOILET
A164A
TOILET
A165A
STAIR 05
S105
PATIENT ISO.
A165
MECH. RM.
A155
SOILED
A154
CORRIDOR
H108
SCALE
H108B
HAC
A166
EQUIPMENT REPAIR
A167
PERITONEAL DIALYSIS
A168
EXAM
A169A
EXAM
A169B
OFFICE
A170A
DIETITIAN
A170C
IV TREATMENT
A170B
IV TREATMENT
A170D
CLEAN
A154A
TOILET
A174A
TOILET
A173A
CONFERENCE RM.
A153
OFFICE
A170F
SUPPLY
A170E
CORRIDOR
H109C
CORRIDOR
H108D
CORRIDOR
H109A
COATS
A173B
STORAGE
A168A
LOCKER RM.
A172A
RECEPTION
A173
DECONTAMINATION
A171
OFFICE
A170GLOUNGE
A172
WAITING
A174
CORRIDOR
H109
OFFICE
A177A OFFICE
A177B
OFFICE
A177C
STORAGE
A177D
OFFICE
A186
OFFICE
A187
ELEVATOR LOBBY
H111
OI&T
A170I
SUPPLY
A175
F.E. CLST
CHASE
CHASE
CHASE
CHASE
27 CHASE
20 21
01-EP-104
6 6 6
212121 1
01-EP-103
NORTH
' 6
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e ct
H V
A C
S ys te m s in
P ro ce d u re R m /S t L o u is
P ro cR m s-
JC
M
E P
V
.r vt
/3
/2
:2
:4
P
M
ELECTRICAL ENLARGED PLAN - LEVEL 01
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
YW SM
915 North Grand Blvd.
St. Louis, MO 63106
01-EP-103
3/16" = 1'-0"1
ELECTRICAL ENLARGED DEMOLITION PLAN - LEVEL 01
NTS
KEYPLAN - LEVEL 01
NO. DESCRIPTION
6 ALL CEILING MOUNTED ELECTRICAL LIGHTING FIXTURES AND DEVICES IN AFFECTED
AREA ARE TO BE TEMPORARILY REMOVED AND REINSTALLED AND RECONNECTED
UPON COMPLETION OF ABOVE CEILING WORK.
18 DUE TO NEW MECHANICAL UNIT AND DUCTWORK IN EXISTING ABOVE CEILING
SPACES, ELECTRICAL CONDUITS AND CABLING WILL BE AFFECTED. PROVIDE
PULLBOX TO INTERCEPT AND REROUTE CONDUITS WHERE NEEDED. FOR
VOICE/DATA CABLING PROVIDE NEW CABLING TO MATCH EXISTING AS NECESSARY.
20 LIGHTING FIXTURES AND DEVICES IN AFFECTED AREA ARE TO BE TEMPORARILY
REMOVED AND REINSTALLED AND RECONNECTED UPON COMPLETION OF ABOVE
CEILING WORK.
21 EXISTING LIGHTING FIXTURE TO REMAIN.
Revisions: Date:
SP
SP
S
SP
S
SP
S
J
S M
S M
S M
S M
SCOPE OF WORK
KEYNOTES
PATIENT ISO.
A164
TOILET
A164A
TOILET
A165A
PATIENT ISO.
A165
OI&T
A170I
F.E. CLST
7 7
A162E
HEMO DIAL TREAT
BAY
01-SCV-A165
01-ECV-A165A
01-SCV-A164
01-ECV-A165
01-ECV-A164
01-ECV-A164A
2 2
C
C
AA
A A
NURSE STATION
A156
PATIENT ISO.
A164
TOILET
A164A
TOILET
A165A
PATIENT ISO.
A165
OI&T
A170I
F.E. CLST
01-SF-A164
01-SF-A165
2DE (EX)-31
2DE (EX)-35
2DE (EX)-37
2DE (EX)-39
01-AHU-A165
01-AHU-A164
A162E
HEMO DIAL TREAT
BAY
2DE (EX)-41
DDC
PANEL
DDC
PANEL
2DE (EX)-33
2DE (EX)-41
D
D
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-EP-104
01-EP-104
GENERAL NOTES
1. SEE SHEET E-001 FOR SYMBOLS AND GENERAL ELECTRICAL NOTES.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. NOT ALL CEILING DEVICES ARE SHOWN. CONTRACTOR TO VERIFY EXISTING
EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
4. HALF TONE ITEMS INDICATE EXISTING TO REMAIN. FULLTONE AND DASHED ITEMS
INDICATE NEW OR DEMOLITION.
5. SEE SHEET E400 FOR MECHANICAL EQUIPMENT CIRCUITING AND DISCONNECT
INFORMATION.
6. PRIOR TO BIDDING, THE G.C. SHOULD VISIT THE PROJECT SITE AND INSPECT
EXISTING CONDITIONS. INSPECTION TIMES WILL BE AFTER NORMAL WORKING
HOURS TO AVOID IMPACT TO NORMAL OPERATIONS.
7. THE G.C. IS RESPONSIBLE FOR THE REMOVAL AND RESTORATION/RELOCATION OF
ALL EXISTING ABOVE CEILING CONDITIONS NECESSARY TO ACCOMODATE THE
NEW WORK. EXISTING ABOVE CEILING CONDITIONS INCLUDE BUT NOT LIMITED TO
LIGHTING, ELECTRICAL POWER, FIRE ALARM, SECURITY, NURSE CALL, DATA
CABLES, AND OTHER LOW VOLTAGE ALARM, TO INCLUDE RELATED CONDUIT
SYSTEMS AND HANGERS. THE EXISTING ABOVE CEILING CONDITIONS ARE OF
SUCH NATURE THAT ALL FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND
SPECIFY. IT IS THEREFORE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO
VISIT THE SITE PRIOR TO BIDDING AND INSPECT THE EXISTING CONDITIONS TO
COMPLETELY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND RELATE
SUCH CONDITIONS TO THE SCOPE OF THE PROPOSED NEW WORK.
A245A
ELEC
2DE (EX)
2DR
2DL
01-EP-104
NORTH
' 6
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e ct
H V
A C
S ys te m s in
P ro ce d u re R m /S t L o u is
P ro cR m s-
JC
M
E P
V
.r vt
/3
/2
:2
:0
P
M
ELECTRICAL ENLARGED PLAN - LEVEL 01
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
YW SM
915 North Grand Blvd.
St. Louis, MO 63106
01-EP-104
1/2" = 1'-0"
ELECTRICAL ENLARGED DEMOLITION PLAN - A164 & A165
1/2" = 1'-0"
ELECTRICAL ENLARGED PLAN - A164 & A165
NO. DESCRIPTION
1 EXISTING ELECTRICAL PANEL TO REMAIN.
2 CONNECT NEW LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT IN ROOM. WHERE
EXISTING LIGHTS ARE ON EMERGENCY POWER, CONNECT NEW LIGHTS IN THOSE
LOCATIONS TO EXISTING EMERGENCY CIRCUIT IN ROOM.
3 J-BOX ABOVE CEILING FOR MECHANICAL CONTROL POWER FOR AVA BOX, SH, SCV,
AND ECV UNITS.
4 MECHANICAL UNIT LOCATED ABOVE CEILING. MECHANICAL CONTRACTOR TO
COORDINATE UNIT LOCATION LEAVES 10" MINIMUM FROM CEILING TO BOTTOM OF
UNIT FOR LIGHTING FIXTURE.
7 LIGHTING FIXTURES TO BE DEMOLISHED. MAINTAIN EXISTING CIRCUIT AND
CONTROLS FOR CONNECTION TO NEW LIGHTING FIXTURES TO BE INSTALLED.
18 DUE TO NEW MECHANICAL UNIT AND DUCTWORK IN EXISTING ABOVE CEILING
SPACES, ELECTRICAL CONDUITS AND CABLING WILL BE AFFECTED. PROVIDE
PULLBOX TO INTERCEPT AND REROUTE CONDUITS WHERE NEEDED. FOR
VOICE/DATA CABLING PROVIDE NEW CABLING TO MATCH EXISTING AS NECESSARY.
19 RECEPTACLE ABOVE CEILING IN AN ELECTRICAL BOX FOR NEW DDC CONTROL
PANEL. ROUTE CAT 6 DATA CABLE TO MAIN DDC CONTROL PANEL OR DATA CLOSET.
COORDINATE LOCATION WITH MECHANICAL CONTRACTOR.
20 LIGHTING FIXTURES AND DEVICES IN AFFECTED AREA ARE TO BE TEMPORARILY
REMOVED AND REINSTALLED AND RECONNECTED UPON COMPLETION OF ABOVE
CEILING WORK.
22 REINSTALL LIGHTING FIXTURE IN EXISTING LOCATION. RECONNECT TO EXISTING
LIGHTING CIRCUIT AND CONTROLS.
NTS
KEYPLAN - LEVEL 01
1/2" = 1'-0"3
ELECTRICAL ENLARGED POWER PLAN - A245A ELEC
NTS
KEYPLAN - LEVEL 02
Revisions: Date:
D
S D
J
S M
S M
SCOPE OF WORK
KEYNOTES
TOILET, FEMALE
B122
STAIR 03
S103
TOILET
B122A
PROCEDURE ROOM
B124
ELEC
B120A
F.E. CLOSET
H113B
CHASE
CH-B-1
CHASE
CH-B-2
7 7
1BE (EX)
TOILET, FEMALE
B122
STAIR 03
S103
TOILET
B122A
PROCEDURE ROOM
B124
ELEC
B120A
F.E. CLOSET
H113B
CHASE
CH-B-1
CHASE
CH-B-2
1BE (EX)-1
1BE (EX)-29
DDC
PANEL
1BE (EX)
AA
A A
01-VAV-B124-1
01-VAV-B124-2
1BE (EX)-26
1BE (EX)-28
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-EP-105
01-EP-105
GENERAL NOTES
1. SEE SHEET E-001 FOR SYMBOLS AND GENERAL ELECTRICAL NOTES.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. NOT ALL CEILING DEVICES ARE SHOWN. CONTRACTOR TO VERIFY EXISTING
EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
4. HALF TONE ITEMS INDICATE EXISTING TO REMAIN. FULLTONE AND DASHED ITEMS
INDICATE NEW OR DEMOLITION.
5. SEE SHEET E400 FOR MECHANICAL EQUIPMENT CIRCUITING AND DISCONNECT
INFORMATION.
6. PRIOR TO BIDDING, THE G.C. SHOULD VISIT THE PROJECT SITE AND INSPECT
EXISTING CONDITIONS. INSPECTION TIMES WILL BE AFTER NORMAL WORKING
HOURS TO AVOID IMPACT TO NORMAL OPERATIONS.
7. THE G.C. IS RESPONSIBLE FOR THE REMOVAL AND RESTORATION/RELOCATION OF
ALL EXISTING ABOVE CEILING CONDITIONS NECESSARY TO ACCOMODATE THE
NEW WORK. EXISTING ABOVE CEILING CONDITIONS INCLUDE BUT NOT LIMITED TO
LIGHTING, ELECTRICAL POWER, FIRE ALARM, SECURITY, NURSE CALL, DATA
CABLES, AND OTHER LOW VOLTAGE ALARM, TO INCLUDE RELATED CONDUIT
SYSTEMS AND HANGERS. THE EXISTING ABOVE CEILING CONDITIONS ARE OF
SUCH NATURE THAT ALL FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND
SPECIFY. IT IS THEREFORE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO
VISIT THE SITE PRIOR TO BIDDING AND INSPECT THE EXISTING CONDITIONS TO
COMPLETELY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND RELATE
SUCH CONDITIONS TO THE SCOPE OF THE PROPOSED NEW WORK.
NORTH
' 6
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e ct
H V
A C
S ys te m s in
P ro ce d u re R m /S t L o u is
P ro cR m s-
JC
M
E P
V
.r vt
/3
/2
:2
:2
P
M
ELECTRICAL ENLARGED PLAN - LEVEL 01
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
YW SM
915 North Grand Blvd.
St. Louis, MO 63106
01-EP-105
1/2" = 1'-0"2
ELECTRICAL ENLARGED DEMOLITION PLAN - B124
1/2" = 1'-0"1
ELECTRICAL ENLARGED PLAN - B124
NO. DESCRIPTION
1 EXISTING ELECTRICAL PANEL TO REMAIN.
2 CONNECT NEW LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT IN ROOM. WHERE
EXISTING LIGHTS ARE ON EMERGENCY POWER, CONNECT NEW LIGHTS IN THOSE
LOCATIONS TO EXISTING EMERGENCY CIRCUIT IN ROOM.
3 J-BOX ABOVE CEILING FOR MECHANICAL CONTROL POWER FOR AVA BOX, SH, SCV,
AND ECV UNITS.
4 MECHANICAL UNIT LOCATED ABOVE CEILING. MECHANICAL CONTRACTOR TO
COORDINATE UNIT LOCATION LEAVES 10" MINIMUM FROM CEILING TO BOTTOM OF
UNIT FOR LIGHTING FIXTURE.
7 LIGHTING FIXTURES TO BE DEMOLISHED. MAINTAIN EXISTING CIRCUIT AND
CONTROLS FOR CONNECTION TO NEW LIGHTING FIXTURES TO BE INSTALLED.
18 DUE TO NEW MECHANICAL UNIT AND DUCTWORK IN EXISTING ABOVE CEILING
SPACES, ELECTRICAL CONDUITS AND CABLING WILL BE AFFECTED. PROVIDE
PULLBOX TO INTERCEPT AND REROUTE CONDUITS WHERE NEEDED. FOR
VOICE/DATA CABLING PROVIDE NEW CABLING TO MATCH EXISTING AS NECESSARY.
19 RECEPTACLE ABOVE CEILING IN AN ELECTRICAL BOX FOR NEW DDC CONTROL
PANEL. ROUTE CAT 6 DATA CABLE TO MAIN DDC CONTROL PANEL OR DATA CLOSET.
COORDINATE LOCATION WITH MECHANICAL CONTRACTOR.
20 LIGHTING FIXTURES AND DEVICES IN AFFECTED AREA ARE TO BE TEMPORARILY
REMOVED AND REINSTALLED AND RECONNECTED UPON COMPLETION OF ABOVE
CEILING WORK.
22 REINSTALL LIGHTING FIXTURE IN EXISTING LOCATION. RECONNECT TO EXISTING
LIGHTING CIRCUIT AND CONTROLS.
NTS
KEYPLAN - LEVEL 01
Revisions: Date:
S
S
J
S M
SCOPE OF WORK
KEYNOTES
ANTE RM.
D219
TB RM.
D220
MICROBIOLOGY LAB
D221
01-ECV-D220-2
B
B
B
B
B
01-ECV-D220-1
ANTE RM.
D219
TB RM.
D220
MICROBIOLOGY LAB
D221
01-ECV-D220-3
E2AL2-18
DDC
PANEL
E2AL2-11
B
01-VAV-D220-1
E2AL2-18
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-EP-106
01-EP-106
01-EP-106
GENERAL NOTES
1. SEE SHEET E-001 FOR SYMBOLS AND GENERAL ELECTRICAL NOTES.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. NOT ALL CEILING DEVICES ARE SHOWN. CONTRACTOR TO VERIFY EXISTING
EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
4. HALF TONE ITEMS INDICATE EXISTING TO REMAIN. FULLTONE AND DASHED ITEMS
INDICATE NEW OR DEMOLITION.
5. SEE SHEET E400 FOR MECHANICAL EQUIPMENT CIRCUITING AND DISCONNECT
INFORMATION.
6. PRIOR TO BIDDING, THE G.C. SHOULD VISIT THE PROJECT SITE AND INSPECT
EXISTING CONDITIONS. INSPECTION TIMES WILL BE AFTER NORMAL WORKING
HOURS TO AVOID IMPACT TO NORMAL OPERATIONS.
7. THE G.C. IS RESPONSIBLE FOR THE REMOVAL AND RESTORATION/RELOCATION OF
ALL EXISTING ABOVE CEILING CONDITIONS NECESSARY TO ACCOMODATE THE
NEW WORK. EXISTING ABOVE CEILING CONDITIONS INCLUDE BUT NOT LIMITED TO
LIGHTING, ELECTRICAL POWER, FIRE ALARM, SECURITY, NURSE CALL, DATA
CABLES, AND OTHER LOW VOLTAGE ALARM, TO INCLUDE RELATED CONDUIT
SYSTEMS AND HANGERS. THE EXISTING ABOVE CEILING CONDITIONS ARE OF
SUCH NATURE THAT ALL FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND
SPECIFY. IT IS THEREFORE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO
VISIT THE SITE PRIOR TO BIDDING AND INSPECT THE EXISTING CONDITIONS TO
COMPLETELY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND RELATE
SUCH CONDITIONS TO THE SCOPE OF THE PROPOSED NEW WORK.
C301
MECH. RM.
E2AL2
CONDUITS COMING UP FROM
LEVEL 1 RM. E103. SEE
LEVEL 1 PLAN ON SHEET 01-
EP101.
D203
OFFICE / EXAM
ROUTE CONDUITS UP
TO LEVEL 3 RM. D302.
SEE LEVEL 3 PLAN ON
SHEET 03-EP107.
01-EP-106
NORTH
' 6
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e ct
H V
A C
S ys te m s in
P ro ce d u re R m /S t L o u is
P ro cR m s-
JC
M
E P
V
.r vt
/3
/2
:2
:4
P
M
ELECTRICAL ENLARGED PLAN - LEVEL 02
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
YW SM
915 North Grand Blvd.
St. Louis, MO 63106
01-EP-106
1/2" = 1'-0"2
ELECTRICAL ENLARGED DEMOLITION PLAN - D220
1/2" = 1'-0"1
ELECTRICAL ENLARGED PLAN - D220
NTS
KEYPLAN - LEVEL 02
NO. DESCRIPTION
1 EXISTING ELECTRICAL PANEL TO REMAIN.
2 CONNECT NEW LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT IN ROOM. WHERE
EXISTING LIGHTS ARE ON EMERGENCY POWER, CONNECT NEW LIGHTS IN THOSE
LOCATIONS TO EXISTING EMERGENCY CIRCUIT IN ROOM.
3 J-BOX ABOVE CEILING FOR MECHANICAL CONTROL POWER FOR AVA BOX, SH, SCV,
AND ECV UNITS.
4 MECHANICAL UNIT LOCATED ABOVE CEILING. MECHANICAL CONTRACTOR TO
COORDINATE UNIT LOCATION LEAVES 10" MINIMUM FROM CEILING TO BOTTOM OF
UNIT FOR LIGHTING FIXTURE.
6 ALL CEILING MOUNTED ELECTRICAL LIGHTING FIXTURES AND DEVICES IN AFFECTED
AREA ARE TO BE TEMPORARILY REMOVED AND REINSTALLED AND RECONNECTED
UPON COMPLETION OF ABOVE CEILING WORK.
7 LIGHTING FIXTURES TO BE DEMOLISHED. MAINTAIN EXISTING CIRCUIT AND
CONTROLS FOR CONNECTION TO NEW LIGHTING FIXTURES TO BE INSTALLED.
8 MECHANICAL UNIT TO BE DISCONNECTED AND DEMOLISHED. REMOVE ALL WIRING,
CONNDUIT, ETC. BACK TO SERVING PANEL.
10 ROUTE CONDUIT ABOVE CEILING SPACE. SEE SHEET EP-201 FOR BRANCH CIRCUIT
INFORMATION.
18 DUE TO NEW MECHANICAL UNIT AND DUCTWORK IN EXISTING ABOVE CEILING
SPACES, ELECTRICAL CONDUITS AND CABLING WILL BE AFFECTED. PROVIDE
PULLBOX TO INTERCEPT AND REROUTE CONDUITS WHERE NEEDED. FOR
VOICE/DATA CABLING PROVIDE NEW CABLING TO MATCH EXISTING AS NECESSARY.
19 RECEPTACLE ABOVE CEILING IN AN ELECTRICAL BOX FOR NEW DDC CONTROL
PANEL. ROUTE CAT 6 DATA CABLE TO MAIN DDC CONTROL PANEL OR DATA CLOSET.
COORDINATE LOCATION WITH MECHANICAL CONTRACTOR.
20 LIGHTING FIXTURES AND DEVICES IN AFFECTED AREA ARE TO BE TEMPORARILY
REMOVED AND REINSTALLED AND RECONNECTED UPON COMPLETION OF ABOVE
CEILING WORK.
22 REINSTALL LIGHTING FIXTURE IN EXISTING LOCATION. RECONNECT TO EXISTING
LIGHTING CIRCUIT AND CONTROLS.
1/2" = 1'-0"4
ELECTRICAL ENLARGED POWER PLAN - C301 ELEC
1/2" = 1'-0"3
ELECTRICAL ENLARGED PLAN - D203 ELEC
NTS
KEYPLAN - LEVEL 03_EP105
Revisions: Date:
G F
I, W
P
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
CONDUITS COMING UP
FROM LEVEL 2 RM. D203.
SEE LEVEL 2 PLAN ON
SHEET 03-EP106.
ROUTE CONDUITS UP TO
LEVEL 4 ROOF. SEE LEVEL 4
PLAN ON SHEET 01-EP107.
D302
MECH. RM.
01-EF-1B
01-EF-E128A
01-EF-E128B
1BE (EX)-27
CONDUITS COMING FROM
LEVEL 3 RM. D302. SEE
LEVEL 3 PLAN ON SHEET
03-EP107.
1BE (EX)-7,9,11
1BE (EX)-19,21,23
01-EP-107
01-EP-107
01-EP-107
GENERAL NOTES
1. SEE SHEET E-001 FOR SYMBOLS AND GENERAL ELECTRICAL NOTES.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. NOT ALL CEILING DEVICES ARE SHOWN. CONTRACTOR TO VERIFY EXISTING
EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
4. HALF TONE ITEMS INDICATE EXISTING TO REMAIN. FULLTONE AND DASHED ITEMS
INDICATE NEW OR DEMOLITION.
5. SEE SHEET E400 FOR MECHANICAL EQUIPMENT CIRCUITING AND DISCONNECT
INFORMATION.
6. PRIOR TO BIDDING, THE G.C. SHOULD VISIT THE PROJECT SITE AND INSPECT
EXISTING CONDITIONS. INSPECTION TIMES WILL BE AFTER NORMAL WORKING
HOURS TO AVOID IMPACT TO NORMAL OPERATIONS.
7. THE G.C. IS RESPONSIBLE FOR THE REMOVAL AND RESTORATION/RELOCATION OF
ALL EXISTING ABOVE CEILING CONDITIONS NECESSARY TO ACCOMODATE THE
NEW WORK. EXISTING ABOVE CEILING CONDITIONS INCLUDE BUT NOT LIMITED TO
LIGHTING, ELECTRICAL POWER, FIRE ALARM, SECURITY, NURSE CALL, DATA
CABLES, AND OTHER LOW VOLTAGE ALARM, TO INCLUDE RELATED CONDUIT
SYSTEMS AND HANGERS. THE EXISTING ABOVE CEILING CONDITIONS ARE OF
SUCH NATURE THAT ALL FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND
SPECIFY. IT IS THEREFORE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO
VISIT THE SITE PRIOR TO BIDDING AND INSPECT THE EXISTING CONDITIONS TO
COMPLETELY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND RELATE
SUCH CONDITIONS TO THE SCOPE OF THE PROPOSED NEW WORK.
NORTH
' 6
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e ct
H V
A C
S ys te m s in
P ro ce d u re R m /S t L o u is
P ro cR m s-
JC
M
E P
V
.r vt
/3
/2
:2
:5
P
M
ELECTRICAL ENLARGED PLAN - LEVEL 03
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
YW SM
915 North Grand Blvd.
St. Louis, MO 63106
01-EP-107
NO. DESCRIPTION
6 ALL CEILING MOUNTED ELECTRICAL LIGHTING FIXTURES AND DEVICES IN AFFECTED
AREA ARE TO BE TEMPORARILY REMOVED AND REINSTALLED AND RECONNECTED
UPON COMPLETION OF ABOVE CEILING WORK.
10 ROUTE CONDUIT ABOVE CEILING SPACE. SEE SHEET EP-201 FOR BRANCH CIRCUIT
INFORMATION.
11 MOUNT NEMA 3R FUSED DISCONNECT ON UNISTRUT.
12 MOUNT RECEPTACLE ON UNISTRUT.
13 ROUTE CONDUITS AND CONDUCTORS ALONG ROOFTOP. CORE DRILL AND
PENETRATE PENTHOUSE WALL. PROVIDE SUPPORTS FOR CONDUIT AS
NECCESSARY.
14 DISCONNECT AND REMOVE MOTOR DISCONNECT SWITCH AND FEEDER TO DEMOED
EXHAUST FAN. MAINTAIN EXISTING CONDUIT FOR CONNECTION TO NEW EQUIPMENT.
15 PROVIDE NEW LIGHTNING PROTECTION BONDING ON ALL NEW EQUIPMENT AND
CONNECT TO EXISTING LIGHTNING PROTECTION SYSTEM ON ROOF.
1/4" = 1'-0"3
ELECTRICAL ENLARGED PLAN - LEVEL 03 - RM. D302
1/4" = 1'-0"2
ENLARGED ELECTRICAL DEMO PLAN - LEVEL 04 - ROOF 30
1/4" = 1'-0"1
ENLARGED ELECTRICAL PLAN - LEVEL 04 - ROOF 30
NTS
KEYPLAN - LEVEL 03_EP106
NTS
KEYPLAN - LEVEL 04_EP106
Revisions: Date:
D502B
CART
ELEVATOR
EQUIPMENT
D502A
CART
ELEVATOR
EQUIPMENT
D502L
STORAGE
D502J
STORAGE
PLUMBING
SHOP
D502H
STORAGE
MASON
SHOP
S508
STAIR 08
D502G
STORAGE
CARPENTRY
SHOP
D502K
STORAGE
IHCG SHOP
D502F
STORAGE
ELECTRIC
SHOP
D502E
STORAGE
PIPE SHOP
D502D
STORAGE
A/C SHOP
H517
CORRIDOR
STORAGE
A/C SHOP
D505A
Room
D505
MECH. RM.
B528
STORAGE
B529
TOILET
B530
TOILET
B526
PREP /
RECOVERY
B527
MECH
B525
CONTROL
B523
EP LAB
H516
CORRIDOR
ELECTRO-
PHYSIOLOGY
C513
STERILIZER
C528
HAC
B532
MALE
LOCKER
B531
TOILET
H513A
CORRIDOR
H512A
SUPPLY
C510A
ANTE
C510
ISOLATION
RECOVERY
C509
RECOVERY
C511A
TOILET
C511
TOILET
H512
CORRIDOR
C512
STORAGE
C522
OI&T
C515
CLEAN RM.
H515
CORRIDOR
S506
STAIR 06
D502
MECH. RM.
STORAGE
D502C
STORAGE
BMET
S507
STAIR 07
S509
STAIR 09
CHASE
CHASE
C512A
ENTRY
CHASE
CHASE
CHASE
CHASE
EQHD5 (EX)
5EMCC
ROUTE CONDUITS UP TO
LEVEL 6 RM. D601. SEE
LEVEL 6 PLAN ON SHEET
03-EP112.
ROUTE CONDUITS UP TO
LEVEL 7 ROOF. SEE LEVEL 7
ROOF PLAN ON SHEET 04-
EP118.
D505
MECH. RM.
ROUTE CONDUITS
ELECTRICAL PANEL 'EQHD5'
IN RM. D505A.
01-EP-110
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-EP-108
GENERAL NOTES
1. SEE SHEET E-001 FOR SYMBOLS AND GENERAL ELECTRICAL NOTES.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. NOT ALL CEILING DEVICES ARE SHOWN. CONTRACTOR TO VERIFY EXISTING
EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
4. HALF TONE ITEMS INDICATE EXISTING TO REMAIN. FULLTONE AND DASHED ITEMS
INDICATE NEW OR DEMOLITION.
5. SEE SHEET E400 FOR MECHANICAL EQUIPMENT CIRCUITING AND DISCONNECT
INFORMATION.
6. PRIOR TO BIDDING, THE G.C. SHOULD VISIT THE PROJECT SITE AND INSPECT
EXISTING CONDITIONS. INSPECTION TIMES WILL BE AFTER NORMAL WORKING
HOURS TO AVOID IMPACT TO NORMAL OPERATIONS.
7. THE G.C. IS RESPONSIBLE FOR THE REMOVAL AND RESTORATION/RELOCATION OF
ALL EXISTING ABOVE CEILING CONDITIONS NECESSARY TO ACCOMODATE THE
NEW WORK. EXISTING ABOVE CEILING CONDITIONS INCLUDE BUT NOT LIMITED TO
LIGHTING, ELECTRICAL POWER, FIRE ALARM, SECURITY, NURSE CALL, DATA
CABLES, AND OTHER LOW VOLTAGE ALARM, TO INCLUDE RELATED CONDUIT
SYSTEMS AND HANGERS. THE EXISTING ABOVE CEILING CONDITIONS ARE OF
SUCH NATURE THAT ALL FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND
SPECIFY. IT IS THEREFORE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO
VISIT THE SITE PRIOR TO BIDDING AND INSPECT THE EXISTING CONDITIONS TO
COMPLETELY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND RELATE
SUCH CONDITIONS TO THE SCOPE OF THE PROPOSED NEW WORK.
NORTH
' 6
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e ct
H V
A C
S ys te m s in
P ro ce d u re R m /S t L o u is
P ro cR m s-
JC
M
E P
V
.r vt
/3
/2
:2
:0
P
M
ELECTRICAL ENLARGED PLAN - LEVEL 05
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
YW SM
915 North Grand Blvd.
St. Louis, MO 63106
01-EP-108
1/8" = 1'-0"1
ELECTRICAL ENLARGED PLAN - LEVEL 05
NO. DESCRIPTION
6 ALL CEILING MOUNTED ELECTRICAL LIGHTING FIXTURES AND DEVICES IN AFFECTED
AREA ARE TO BE TEMPORARILY REMOVED AND REINSTALLED AND RECONNECTED
UPON COMPLETION OF ABOVE CEILING WORK.
10 ROUTE CONDUIT ABOVE CEILING SPACE. SEE SHEET EP-201 FOR BRANCH CIRCUIT
INFORMATION.
20 LIGHTING FIXTURES AND DEVICES IN AFFECTED AREA ARE TO BE TEMPORARILY
REMOVED AND REINSTALLED AND RECONNECTED UPON COMPLETION OF ABOVE
CEILING WORK.
NTS
KEYPLAN - LEVEL 05
Revisions: Date:
SSSS SSSS
J
S M
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
BRONCHOSCOPY SUITE
B503
CHASE
7 7 7
01-ECV-B503
5BE (EX)-15
B503
BRONCHOSCOPY
SUITE 18 19
5BE (EX)-13
DDC
PANEL
B B B
BBB
2 2 2
2 2
D
DD
D
01-VAV-B503-1
5BE (EX)-17
01-EP-109
01-EP-109
01-EP-109
5BE (EX) 5B1 1
B536
ELEC
GENERAL NOTES
1. SEE SHEET E-001 FOR SYMBOLS AND GENERAL ELECTRICAL NOTES.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. NOT ALL CEILING DEVICES ARE SHOWN. CONTRACTOR TO VERIFY EXISTING
EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
4. HALF TONE ITEMS INDICATE EXISTING TO REMAIN. FULLTONE AND DASHED ITEMS
INDICATE NEW OR DEMOLITION.
5. SEE SHEET E400 FOR MECHANICAL EQUIPMENT CIRCUITING AND DISCONNECT
INFORMATION.
6. PRIOR TO BIDDING, THE G.C. SHOULD VISIT THE PROJECT SITE AND INSPECT
EXISTING CONDITIONS. INSPECTION TIMES WILL BE AFTER NORMAL WORKING
HOURS TO AVOID IMPACT TO NORMAL OPERATIONS.
7. THE G.C. IS RESPONSIBLE FOR THE REMOVAL AND RESTORATION/RELOCATION OF
ALL EXISTING ABOVE CEILING CONDITIONS NECESSARY TO ACCOMODATE THE
NEW WORK. EXISTING ABOVE CEILING CONDITIONS INCLUDE BUT NOT LIMITED TO
LIGHTING, ELECTRICAL POWER, FIRE ALARM, SECURITY, NURSE CALL, DATA
CABLES, AND OTHER LOW VOLTAGE ALARM, TO INCLUDE RELATED CONDUIT
SYSTEMS AND HANGERS. THE EXISTING ABOVE CEILING CONDITIONS ARE OF
SUCH NATURE THAT ALL FACETS OF THE WORK ARE IMPOSSIBLE TO DETAIL AND
SPECIFY. IT IS THEREFORE THE GENERAL CONTRACTOR'S RESPONSIBILITY TO
VISIT THE SITE PRIOR TO BIDDING AND INSPECT THE EXISTING CONDITIONS TO
COMPLETELY FAMILIARIZE HIMSELF WITH THE EXISTING CONDITIONS AND RELATE
SUCH CONDITIONS TO THE SCOPE OF THE PROPOSED NEW WORK.
NORTH
' 6
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e ct
H V
A C
S ys te m s in
P ro ce d u re R m /S t L o u is
P ro cR m s-
JC
M
E P
V
.r vt
/3
/2
:2
:2
P
M
ELECTRICAL ENLARGED PLAN - LEVEL 05
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
YW SM
915 North Grand Blvd.
St. Louis, MO 63106
01-EP-109
1/2" = 1'-0"
ELECTRICAL ENLARGED DEMOLITION PLAN - B503
1/2" = 1'-0"
ELECTRICAL ENLARGED PLAN - B503
NO. DESCRIPTION
1 EXISTING ELECTRICAL PANEL TO REMAIN.
2 CONNECT NEW LIGHT FIXTURE TO EXISTING LIGHTING CIRCUIT IN ROOM. WHERE
EXISTING LIGHTS ARE ON EMERGENCY POWER, CONNECT NEW LIGHTS IN THOSE
LOCATIONS TO EXISTING EMERGENCY CIRCUIT IN ROOM.
3 J-BOX ABOVE CEILING FOR MECHANICAL CONTROL POWER FOR AVA BOX, SH, SCV,
AND ECV UNITS.
4 MECHANICAL UNIT LOCATED ABOVE CEILING. MECHANICAL CONTRACTOR TO
COORDINATE UNIT LOCATION LEAVES 10" MINIMUM FROM CEILING TO BOTTOM OF
UNIT FOR LIGHTING FIXTURE.
7 LIGHTING FIXTURES TO BE DEMOLISHED. MAINTAIN EXISTING CIRCUIT AND
CONTROLS FOR CONNECTION TO NEW LIGHTING FIXTURES TO BE INSTALLED.
18 DUE TO NEW MECHANICAL UNIT AND DUCTWORK IN EXISTING ABOVE CEILING
SPACES, ELECTRICAL CONDUITS AND CABLING WILL BE AFFECTED. PROVIDE
PULLBOX TO INTERCEPT AND REROUTE CONDUITS WHERE NEEDED. FOR
VOICE/DATA CABLING PROVIDE NEW CABLING TO MATCH EXISTING AS NECESSARY.
19 RECEPTACLE ABOVE CEILING IN AN ELECTRICAL BOX FOR NEW DDC CONTROL
PANEL. ROUTE CAT 6 DATA CABLE TO MAIN DDC CONTROL PANEL OR DATA CLOSET.
COORDINATE LOCATION WITH MECHANICAL CONTRACTOR.
22 REINSTALL LIGHTING FIXTURE IN EXISTING LOCATION. RECONNECT TO EXISTING
LIGHTING CIRCUIT AND CONTROLS.
NTS
KEYPLAN - LEVEL 05
1/2" = 1'-0"3
ELECTRICAL ENLARGED POWER PLAN - B536 ELEC
Revisions: Date:
J
M
S M
SCOPE OF WORK
KEYNOTES
ANTE
C510A
ISOLATION RECOVERY
C510
RECOVERY
C509
TOILET
C511A
TOILET
C511
7 7
20 20
01-ECV-C510A
01-SCV-C510
A
C
C510
ISOLATION
RECOVERY
01-SF-C510
01-ECV-C510
E5E (EX)-11
E5E (EX)-20
E5E (EX)-29
01-AHU-C510
C510A
ANTE
E5E (EX)-22
DDC
PANEL
C511
TOILET
C511A
TOILET 18
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-EP-110
01-EP-110
01-EP-110
GENERAL NOTES
1. SEE SHEET E-001 FOR SYMBOLS AND GENERAL ELECTRICAL NOTES.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. NOT ALL CEILING DEVICES ARE SHOWN. CONTRACTOR TO VERIFY EXISTING
EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
4. HALF TONE ITEMS INDICATE EXISTING TO REMAIN. FULLTONE AND DASHED ITEMS
INDICATE NEW OR DEMOLITION.
5. SEE SHEET E400 FOR MECHANICAL EQUIPMENT CIRCUITING AND DISCONNECT
INFORMATION.
6. PRIOR TO BIDDING, THE G.C. SHOULD VISIT THE PROJECT SITE AND INSPECT
EXISTING CONDITIONS. INSPECTION TIMES WILL BE AFTER NORMAL WORKING
HOURS TO…