These are mechanical HVAC and piping design drawings for a federal contract to correct heating, ventilation, and air conditioning systems in procedure rooms at the Veterans Affairs St. Louis Medical Center (Building 657), located at 915 North Grand Boulevard, St. Louis, Missouri 63106. The project, identified as 657-21-115JC, is issued as 100% Bid Documents dated January 31, 2023, prepared by Romanyk Consulting Corp. as the Architect/Engineer of Record.
The scope encompasses demolition and installation of new HVAC systems across ten building levels and multiple roof areas, affecting patient isolation rooms, procedure rooms, and treatment spaces including rooms E128, B124, D220, A164, A165, B503, C510, C615, A658, A663, A707, A720, and A757. The work involves routing exhaust air ducts on building exteriors to roof-mounted exhaust fans, installing low-profile air handling units with steam humidifiers, providing temperature and humidity sensors connected to building automation systems, and connecting heating hot water, chilled water, low-pressure steam, and steam condensate piping to existing mains. Key components include fan-powered VAV boxes, filter boxes, pre-heat coils, motorized dampers, in-line booster fans, and digital direct control (DDC) panels. The design specifies pressurization requirements of -0.02 inches water column for isolation rooms and detailed CFM settings for supply, exhaust, and transfer air flows. All exterior ductwork is specified to be brown color with matching lagging, and duct penetrations must be routed through insulated roof curbs flashed and sealed to the roof.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SCOPE OF WORK
KEYNOTES
P
P P
T
P
P
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MD-101
01-MD-101
E126
TOILET
E127
ANTE RM.
E128
PATIENT ISO.
E133
EXAM TREATMENT
S107A
VESTIBULE
UP 9
(TYP)
B124
PROCEDURE ROOM
E X
IS
T
IN
G
D U
C T
MONITOR
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:0
:4
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 01
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-101
NTS
KEYPLAN - LEVEL 01
NO. DESCRIPTION
1 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING THIS ROOM BACK TO EXHAUST FAN
ON ROOF.
2 EXISTING LINEAR SUPPLY AIR DIFFUSER AND ASSOCIATED DUCT TO BE DEMOLISHED
BACK TO MAIN.
3 DEMOLISH EXISTING THERMOSTAT AND PRESSURE MONITOR.
4 DEMOLISH EXISTING HEATING HOT WATER SUPPLY / RETURN FOR RE-CONNECTION.
5 DEMOLISH EXISTING RETURN AIR GRILLE AND ASSOCIATED DUCT.
6 EXISTING SUPPLY AIR DUCT TO REMAIN.
7 EXISTING SUPPLY AIR DIFFUSER AND ASSOCIATED DUCT TO BE DEMOLISHED BACK
TO MAIN.
8 EXISTING 6" FIRE SPRINKLER WATER MAIN TO REMAIN (SHOWN FOR REFERENCE)
9 SEE DETAIL 1 ON SHEET 01-MD-103 FOR CONTINUATION.
1/2" = 1'-0"
LEVEL 01 - ENLARGED MECHANICAL DEMOLITION PLAN - E128
1/2" = 1'-0"
LEVEL 01 - ENLARGED MECHANICAL DEMOLITION PLAN - B124
Revisions: Date:
user Snapshot
T
P
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MD-102
A163B
EXAM
A156
NURSE STATION
A158
OFFICE
A157
MED. PREP.
A164
PATIENT ISO.
A164A
TOILET
A165A
TOILET
S105
STAIR 05
A165
PATIENT ISO.
H108
CORRIDOR
A170I
OI&T
F.E. CLST
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:0
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 01
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-102
NTS
KEYPLAN - LEVEL 01
NO. DESCRIPTION
1 DEMOLISH ENTIRE EXHAUST SYSTEM BACK TO EXHAUST FAN ON ROOF.
2 EXISTING LINEAR SUPPLY AIR DIFFUSER AND ASSOCIATED DUCT TO BE DEMOLISHED
BACK TO MAIN.
3 DEMOLISH EXISTING THERMOSTAT AND PRESSURE MONITOR.
1/2" = 1'-0"
LEVEL 01 - MECHANICAL ENLARGED DEMOLITION PLAN - A164 & A165
Revisions: Date:
T
P P
P
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MD-103
01-MD-103
01-MD-103
D219
ANTE RM.
D220
TB RM.
D221
MICROBIOLOGY LAB
16"x12" SA(EX)
MONITOR
D204
OFFICE
D203
OFFICE / EXAM
D202
LOCKER RM,
FEMALE
H216
CORRIDOR
H216
CORRIDOR
D247
OFFICE
A244
OFFICE
S205
STAIR 05
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:1
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 02
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-103
NTS
KEYPLAN - LEVEL 02
NO. DESCRIPTION
1 DEMOLISH ENTIRE EXISTING SUPPLY AIR SYSTEM (DUCTWORK, DIFFUSERS,
HANGERS, ETC) SERVING TB ROOM D220 BACK TO MAIN.
2 DEMOLISH ENTIRE EXHAUST SYSTEM BACK TO EXHAUST FAN ON ROOF. SEE DETAIL
1 ON SHEET 01-MD-104 FOR CONTINUATION.
3 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOMS A164 &
A165 BACK TO EXHAUST FAN ON ROOF.
4 DEMOLISH EXISTING THERMOSTAT AND PRESSURE MONITOR.
5 SEE DETAIL 2 ON SHEET 01-MD-104 FOR CONTINUATION.
1/2" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 02 - D220
1/4" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 02 - EXHAUST
1/4" = 1'-0"
ENLARGED MECHANICAL DEMOLITION PLAN -
LEVEL 02 - EXHAUST
Revisions: Date:
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
D302C
MECH. RM.
C301
MECH. RM.
STAIR 09
01-MD-104
01-MD-104
01-MD-104
D302
MECH. RM.
DOWN
UP
A345
PT WORK
S305
STAIR 5
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:2
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 03
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-104
NO. DESCRIPTION
1 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOMS A164 &
A165 BACK TO EXHAUST FAN ON ROOF.
2 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING TB. ROOM D220 BACK TO EXHAUST
FAN ON ROOF.
3 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOM E128
BACK TO EXHAUST FAN ON ROOF.
4 SEE LEVEL 5 (SHEET 01-MD206) FOR CONTINUATION.
5 SEE DETAIL 1 ON SHEET 01-MD-103 FOR CONTINUATION.
6 SEE DETAIL 2 ON SHEET 01-MD-105 FOR CONTINUATION.
7 SEE DETAIL 2 ON SHEET 01-MD-103 FOR CONTINUATION.
3/16" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 03 - INTERSTITIAL
NTS
KEYPLAN - LEVEL 03
1/4" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN -
LEVEL 03 - MECH. RM. D302
Graphic Scale : 3/16" = 1'-0"
4'2' 8'0'
1/4" = 1'-0"
ENLARGED MECHANICAL DEMOLITION PLAN -
LEVEL 03 - EXHAUST
Revisions: Date:
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MD-105
01-MD-105
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:3
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 04
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-105
NTS
KEYPLAN - LEVEL 04
1/2" = 1'-0"
ENLARGED MECHANICAL DEMOLITION PLAN - LEVEL 04 - EXHAUST
1/2" = 1'-0"
LEVEL 04 - ROOF 30 - ENLARGED DEMOLITION PLAN
NO. DESCRIPTION
1 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOMS A164 &
A165 BACK TO EXHAUST FAN ON ROOF.
2 DEMOLISH EXHAUST FAN SERVING PATIENT ISOLATION E128 AND ASSOCIATED
DUCTWORK, CONTROLS, WIRING, ETC.
3 SEE DETAIL 1 ON SHEET 01-MD-104 FOR CONTINUATION.
Revisions: Date:
P
P
T P
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MD-106
01-MD-106
01-MD-106
EXISTING SUPPLY
AIR: 333 CFM
EXISTING EXHAUST
AIR: -473 CFM
B503
BRONCHOSCOPY
SUITE166
CHASE
C510A
ANTE
C510
ISOLATION
RECOVERY
A552
OFFICE
S505
STAIR 05
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:4
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 05
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-106
NTS
KEYPLAN - LEVEL 05
NO. DESCRIPTION
1 DEMOLISH EXISTING GRILLE AND ASSOCIATED DUCTWORK BACK TO MAIN DUCT
BRANCH.
2 DEMOLISH EXISTING EXHAUST DUCTWORK AND GRILLES SERVING THIS ROOM BACK
TO MAIN CORRIDOR. CAP AND SEAL EXISTING DUCT AS REQUIRED.
3 EXISTING 3/4 HP EXHAUST BOOSTER FAN TO REMAIN:
MANUFACTURER: COOK
MODEL: 135 SQN 135SQN17DEC 50
4 EXISTING VAV BOX TO REMAIN.
5 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOMS A164 &
A165 BACK TO EXHAUST FAN ON ROOF.
6 DEMOLISH EXISTING PRESSURE SENSOR.
7 DEMOLISH EXISTING THERMOSTAT AND PRESSURE MONITOR.
8 DEMOLISH EXISTING MAGNEHELIC GUAGE.
1/2" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 05 - B503
1/2" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 05 - C510
1/2" = 1'-0"
ENLARGED MECHANICAL DEMOLITION PLAN - LEVEL 05 - EXHAUST
Revisions: Date:
T
P P
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MD-107
01-MD-107
01-MD-107
01-MD-107
C615
ISOLATION
C615A
ANTE RM.
CHASE
A656
SOILED
A657
CLEAN
A658
ISOLATION
A658B
ANTE RM.
A658A
TOILET
H604
CORRIDOR
A663A
TOILET
A663B
ANTE RM.
A663
ISOLATION
A664
NURSE STATION
A664A
NOUR.
A655
ELEC
UP
A645
CLEAN
S605
STAIR 05
DOWN
UP
D601
MECH. RM.
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:5
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 06
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-107
NTS
KEYPLAN - LEVEL 06
NO. DESCRIPTION
1 DEMOLISH EXISTING SUPPLY AIR SYSTEM SERVING ISOLATION ROOM C615
(DUCTWORK, GRILLES, HANGERS, ETC.) BACK TO MAIN DUCT BRANCH.
2 DEMOLISH EXISTING EXHAUST DUCTWORK AND GRILLES (SERVING ISOLATION
ROOM C615 AND ANTE ROOM C615A) BACK TO MAIN IN CORRIDOR.
3 DEMOLISH EXISTING FAN FILTER UNIT AND ASSOCIATED DUCT, PIPING, CONTROLS,
ETC.
4 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING ISOLATION ROOM SYSTEMS A663 &
A658 BACK TO EXHAUST FAN ON ROOF.
5 DEMOLISH EXISTING EXHAUST GRILLE IN WALL AND ASSOCIATED DUCTWORK.
6 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOMS A164 &
A165 BACK TO EXHAUST FAN ON ROOF.
7 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING TB ROOM D220 BACK TO EXHAUST
FAN ON ROOF.
8 DEMOLISH EXISTING THERMOSTAT AND PRESSURE MONITOR.
9 DEMOLISH EXISTING STEAM RADIATOR CONVECTOR.
10 SEE DETAIL 1 ON SHEET 01-MD-109 FOR CONTINUATION.
1/2" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 06 - C615
1/2" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 06 - A658 & A663
1/4" = 1'-0"
ENLARGED LEVEL 06 MECHANICAL DEMOLITION PLAN
1/4" = 1'-0"
ENARGED LEVEL 06 EXHAUST DEMOLITION PLAN
Revisions: Date:
01-MD-108
01-MD-108
01-MD-108
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
A720
PATIENT ISO.
A720A
ANTE
A720B
TOILET
A721A
TOILET
A721
PATIENT ROOM
A748A
TOILET
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:0
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 07
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-108
NTS
KEYPLAN - LEVEL 07
NO. DESCRIPTION
1 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOM A720
BACK TO EXHAUST FAN ON ROOF.
2 DEMOLISH EXISTING EXHAUST FAN SERVING TB ROOM D220 AND ASSOCIATED
DUCTWORK, CONTROLS, WIRING, ETC.
3 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOMS A164 &
A165 BACK TO EXHAUST FAN ON ROOF.
1/2" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 07 - A720
1/2" = 1'-0"
ENLARGED DEMOLITION PLAN - LEVEL 07
1/4" = 1'-0"
ENLARGED DEMOLITION PLAN - LEVEL 07 - ROOF 32
Revisions: Date:
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MD-109
01-MD-109
A707
PATIENT ISO. A708
PATIENT ROOM
A709
TOILET
A707B
TOILET
A707A
ANTE RM.
2 3
H705
CORRIDOR
A756
CLEAN LINEN
A757
PATIENT ROOM
A757B
TOILET
A757A
ANTE RM.
A755
SOILED UTILITY
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:1
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 07
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-109
NTS
KEYPLAN - LEVEL 07
NO. DESCRIPTION
1 DEMOLISH EXISTING VAV BOX AND ASSOCIATED CONTROLS, WIRING, DUCTWORK,
ETC.
2 DEMOLISH ENTIRE EXHAUST SYSTEM BACK TO EXHAUST FAN ON ROOF.
3 DEMOLISH EXISTING EXHAUST DUCT UP TO ROOF. SEE DETAIL 1 ON SHEET
01-MD-111 FOR CONTINUATION.
4 DEMOLISH ENTIRE SUPPLY AIR SYSTEM SERVING PATIENT ISOLATION A707, TOILET
A707A, AND ANTE ROOM A707B (DUCTWORK, GRILLES, VAV BOX, HANGERS, ETC)
BACK TO MAIN IN CORRIDOR.
5 DEMOLISH EXISTING EXHAUST DUCT (SERVING A658 & A663) FROM LEVEL 6 UP TO
ROOF. SEE DETAIL 1 ON SHEET 01-MD-111 FOR CONTINUATION.
6 DEMOLISH EXISTING WINDOW-MOUNTED PTAC UNIT AND ASSOCIATED WIRING,
CONTROLS, ETC.
7 DEMOLISH ENTIRE SUPPLY AIR SYSTEM SERVING PATIENT ISOLATION A757, ANTE
ROOM A757A, AND TOILET A757AB. (DUCTWORK, GRILLES, AIRFLOW CONTROL
VALVES, HANGERS, ETC) BACK TO MAIN IN CORRIDOR.
1/2" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 07 - A707
1/2" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 07 - A757
Revisions: Date:
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
A810
EXAM
01-MD-110
01-MD-110
01-MD-110
A818A
EXAM
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:1
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 08
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-110
NO. DESCRIPTION
1 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOMS A164 &
A165 BACK TO EXHAUST FAN ON ROOF.
2 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOMS A707
BACK TO EXHAUST FAN ON ROOF.
3 DEMOLISH EXHAUST FAN SERVING PATIENT ISOLATION A720 AND ASSOCIATED
DUCTWORK, CONTROLS, WIRING, ETC.
1/2" = 1'-0"
ENLARGED MECHANICAL DEMOLITION PLAN - LEVEL 08
1/2" = 1'-0"
ENLARGED MECHANICAL DEMOLITION PLAN - LEVEL 08 - EXHAUST CHASE
NTS
KEYPLAN - LEVEL 08
3/8" = 1'-0"
ENLARGED MECHANICAL DEMOLITION PLAN - LEVEL 08 ROOF
Revisions: Date:
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
DOWN
DOWN
UP
UP
A934
EXAM
A939
EXAM TREATMENT
A940
STORAGE
A941
X-RAY PANO
A942
SOIL
A943B
HAC
A945A
TOILET
A945B
TOILET
A944
WAITING RM.
A943
RECEPTION
H904
CORRIDOR
A945
TOILET
A945C
HAC
A929
HAC
H906
CORRIDOR
H902
CORRIDOR
H902A
CORRIDOR
ELEV 6
A933
LAB
A932
EXAM
A931
OFFICE
A945C
HAC
H903
CORRIDOR
A901
WAIT ROOM
01-MD-111
01-MD-111
01-MD-111
A866
OFFICE
S805
STAIR 05
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:2
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 09
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-111
NO. DESCRIPTION
1 DEMOLISH EXHAUST SYSTEMS SERVING PATIENT ISOLATION ROOMS A658 & A663.
2 DEMOLISH EXHAUST FAN SERVING PATIENT ISOLATION A707 AND ASSOCIATED
DUCTWORK, CONTROLS, WIRING, ETC.
3 DEMOLISH EXHAUST SYSTEMS SERVING PATIENT ISOLATION ROOMS A757. SEE
DETAIL 1 ON SHEET 01-MD-109 FOR CONTINUATION.
4 DEMOLISH ENTIRE EXHAUST SYSTEM SERVING PATIENT ISOLATION ROOMS A164 &
A165 BACK TO EXHAUST FAN ON ROOF.
5 DEMOLISH EXHAUST SYSTEMS SERVING PATIENT ISOLATION ROOMS A658 & A663.
SEE DETAIL 1 ON SHEET 01-MD-109 FOR CONTINUATION.
6 DEMOLISH EXHAUST SYSTEMS SERVING PATIENT ISOLATION ROOMS A757.
7 SEE DETAIL 2 ON SHEET 01-MD-112 FOR CONTINUATION.
1/4" = 1'-0"
ENLARGED MECHANICAL DEMOLITION PLAN - LEVEL 09
1/4" = 1'-0"
ENLARGED MECHANICAL DEMOLITION PLAN - LEVEL 09 - ROOF
NTS
KEYPLAN - LEVEL 09
1/2" = 1'-0"
ENLARGED MECHANICAL DEMO PLAN - LEVEL 09
Revisions: Date:
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
DOWN
1 2
SP02
STAIR 2
ELEV 5
ELEV 4
DOWN 4
01-MD-112
01-MD-112
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:3
A
M
MECHANICAL DEMOLITION ENLARGED PLANS -
LEVEL 10
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MD-112
NO. DESCRIPTION
1 DEMOLISH EXHAUST FAN SERVING PATIENT ISOLATION A658 & A663 AND
ASSOCIATED DUCTWORK, CONTROLS, WIRING, ETC.
2 DEMOLISH EXHAUST FAN SERVING PATIENT ISOLATION A757 AND ASSOCIATED
DUCTWORK, CONTROLS, WIRING, ETC.
3 DEMOLISH EXHAUST FAN SERVING PATIENT ISOLATION ROOMS A164 & A165 AND
ASSOCIATED DUCTWORK, CONTROLS, WIRING, ETC.
4 SEE DETAIL 1 ON SHEET 01-MD-111 FOR CONTINUATION.
1/2" = 1'-0"
MECHANICAL ENLARGED DEMOLITION PLAN - LEVEL 10 - ROOF
1/2" = 1'-0"
MECHANICAL ENLARGED DEMOLTION PLAN - LEVEL 10 - PENTHOUSE
NTS
KEYPLAN - LEVEL 10
Revisions: Date:
P
P
P H
T
P
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-SCV-E128
SET TO 260 CFM
01-ECV-E127
SET TO 210 CFM
EG-1
210 CFM
RG-2
260 CFM
EG-2
440 CFM
01-ECV-E128
SET TO 440 CFM
PRESSURE:
-0.02 IN. W.C.
PRESSURE:
-0.02 IN. W.C.
E126
TOILET
E127
ANTE RM.
E128
PATIENT ISO.
E133
EXAM TREATMENT
S107A
VESTIBULE
01-SF-E128
SET TO 40 CFM
8"x8" SA
"x
S A
SD-4
190 CFM
SD-1
110 CFM
12"x12" EA12"x12" EA
8"Ø OA
"Ø O
A
8"x10" OA
8"Ø EA
01-AHU-E128
PHC-E128
LVR-E128
PF-E128
8"Ø EA 1
"x
E A
14"x12" EA (UP) 12
01-AF-E128
10"Ø OA
"Ø
O A
"x
O A
12"x18" OA
10"x10" SA
01-SH-E128
E103
NURSE STATION
01-MH-101
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:2
A
M
HVAC ENLARGED PLAN - LEVEL 01
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MH-101
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 01 - E128
NTS
KEYPLAN - LEVEL 01
NO. DESCRIPTION
1 ROUTE EXHAUST AIR DUCT ON EXTERIOR OF BUIDLING TO EXHAUST FANS ON
ROOF.
2 PROVIDE RG-2 RETURN GRILLE FOR AIR TRANSFER INTO ISOLATION ROOM.
3 FILTER BOX.
4 PRE-HEAT COIL.
5 DUCT MOUNTED STEAM HUMIDIFIER.
6 PROVIDE TEMPERATURE SENSOR, HUMIDITY SENSOR, AND ROOM PRESSURE
DIFFERENTIAL MONITOR. CONNECT TO BUILDING AUTOMATION SYSTEM.
7 LOW-PROFILE AIR HANDLING UNIT.
8 PROVIDE RG-2 RETURN GRILLE FOR AIR TRANSFER INTO ISOLATION ROOM.
9 AIR CONTROL VALVE FOR TRANSFERRED AIR. AIRFLOW TO FLUCTUATE TO MEET
-0.02 IN. W.C. PRESSURIZATION REQUIREMENTS.
10 AIR CONTROL VALVE FOR EXHAUST AIR. BALANCE VALVE TO CFM SPECIFIED ON
PLAN. AIRFLOW TO FLUCTUATE TO MEET -0.02 IN. W.C. PRESSURIZATION
REQUIREMENTS.
11 OUTSIDE AIR, IN-LINE BOOSTER FAN.
12 ROUTE EXHAUST AIR DUCT THROUGH EXISTING PENETRATION. USE SAME ROUTE
AS PREVIOUSLY DEMOLISHED DUCTWORK.
13 INSTALL DDC PANEL ABOVE CEILING. CONTRACTOR TO DETERMINE EXACT
LOCATION IN FIELD.
14 ELECTRIC HUMIDIFIER.
15 OFFSET DUCT AROUND EXISTING 6" FIRE MAIN.
Revisions: Date:
H
THP
T
P P
P
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MH-102
01-SCV-A165
SET TO 280 CFM
SD-1
80 CFM
01-ECV-A165A
SET TO 250 CFM
01-SCV-A164
SET TO 330 CFM
EG-2
500 CFM
01-ECV-A165
SET TO 500 CFM
EG-2
550 CFM
01-ECV-A164
SET TO 550 CFM
EG-1
250 CFM
01-ECV-A164A
SET TO 250 CFM
RG-2
280 CFM
RG-2
330 CFM
PRESSURE:
-0.02 IN. W.C.
PRESSURE:
-0.02 IN. W.C.
A162E
HEMO DIAL TREAT
BAY
A164
PATIENT ISO.
A164A
TOILET
A165A
TOILET
A165
PATIENT ISO.
601-SF-A165
SET TO 50 CFM
01-SF-A164
SET TO 50 CFM
22"x14" EA (UP)
EG-1
250 CFM
SD-1
80 CFM
SD-5
300 CFM
01-AHU-A164
SD-5
250 CFM
01-AHU-A165
01-PHC-A164
01-PHC-A165
01-LVR-A164
A157
MED. PREP.
A158
OFFICE
A162E
HEMO DIAL TREAT
BAY
S105
STAIR 05
01-PF-A164
-A F
-A
01-AF-A164
18"Ø EA
"x
E A
12"x18" SA
10"x10" OA
10"Ø SA
12"Ø
EA
18"Ø EA
12"Ø EA
18"Ø EA
12"Ø EA
12"x18" OA
12"x18" OA
10"Ø EA
6"Ø SA
10"Ø OA
10"x10" OA
12"x10" EA
22"x18" OA
10"x10" OA
"Ø
S A
12"x10" SA
10"Ø
TA
15R→
R
R
D
R→
D
10"x10" OA
"x
S A
10"ØTA
"Ø
S A
12"Ø EA
10"Ø SA
12"Ø EA
D ←D
"Ø E
A
12"Ø EA
"Ø E
A
01-SH-A164
01-SH-A165
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:4
A
M
HVAC ENLARGED PLAN - LEVEL 01
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MH-102
NTS
KEYPLAN - LEVEL 01
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 01 - A164 & A165
NO. DESCRIPTION
1 ROUTE EXHAUST AIR DUCT ON EXTERIOR OF BUIDLING TO EXHAUST FANS ON ROOF.
EXTERIOR DUCT TO BE BROWN COLOR, MATCHING LAGGING.
2 FAN-POWERED VAV BOX
3 PROVIDE TEMPERATURE SENSOR, HUMIDITY SENSOR, AND ROOM PRESSURE
DIFFERENTIAL MONITOR. CONNECT TO BUILDING AUTOMATION SYSTEM.
4 AIR VOLUME CONTROL VALVE FOR EXHAUST AIR. AIRFLOW TO FLUCTUATE TO MEET
-0.02 IN. W.C. PRESSURIZATION REQUIREMENTS.
5 AIR CONTROL VALVE FOR TRANSFERRED AIR. AIRFLOW TO FLUCTUATE TO MEET
-0.02 IN. W.C. PRESSURIZATION REQUIREMENTS.
6 OUTSIDE AIR, IN-LINE BOOSTER FAN.
7 STEAM HUMIDIFIER.
8 MOTORIZED DAMPER.
9 PRE-HEAT COIL.
10 LOW-PROFILE AIR HANDLING UNIT.
11 INSTALL OUTSIDE AIR INTAKE LOUVER IN EXTERIOR WALL. COORDINATE WITH
ARCHITECTURAL.
12 FILTER BOX.
13 INSTALL DDC PANEL ABOVE CEILING. CONTRACTOR TO DETERMINE EXACT
LOCATION IN FIELD.
14 EXISTING DUCTWORK TO REMAIN. SHOWN FOR REFERENCE.
15 ROUTE DUCT UP HIGH.
Revisions: Date:
H
T
P
P
H T
P
P
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MH-103
01-MH-103
PRESSURE:
-0.02 IN. W.C.
01-ECV-D220-2
SET TO 350 CFM
EG-2
350 CFM
8"Ø EA
01-ECV-D220-1
SET TO 180 CFM
EG-1
180 CFM
H232
CORRIDOR
D219
ANTE RM.
D220
TB RM.
D221
MICROBIOLOGY LAB
"Ø E
A
12"Ø EA (UP)
16"x12"(EX)
PRESSURE:
-0.02 IN. W.C.
"x
S A
8"Ø SA
SD-4
250 CFM
SD-1
80 CFM
8"Ø EA
01-ECV-D220-3
7 01-AF-D220
"x
E X
8"Ø EA
01-VAV-D220-1
01-SH-D220 8"Ø EA
"Ø
S A
8"Ø SA
8"Ø SA
01-AF-B124
PRESSURE:
+0.02 IN. W.C.
RG-1
400 CFM
SD-5
300 CFM
8"Ø SA
"x
E A
"Ø S
A
10"Ø SA
SD-5
300 CFM
B124
PROCEDURE ROOM
01-VAV-B124-1
01-VAV-B124-2
13"x14"TA
"x
S A
01-SH-B124
01-MH-103
22"x14" EA (UP/DN)
14"x12" EA (UP/DN)
D203
OFFICE / EXAM
D204
OFFICE
H216
CORRIDOR
D202
LOCKER RM,
FEMALE
D247
OFFICE
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:5
A
M
HVAC ENLARGED PLAN - LEVELS 01 & 02
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MH-103
NTS
KEYPLAN - LEVEL 02
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 02 - D220
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 01 - B124
NTS
KEYPLAN - LEVEL 01
NO. DESCRIPTION
1 CONNECT INTO EXISTING SUPPLY AIR DUCT MAIN.
2 FAN-POWERED VAV BOX
3 EXISTING SUPPLY AIR DUCT TO REMAIN.
4 DUCT MOUNTED STEAM HUMIDIFIER.
5 PROVIDE TEMPERATURE SENSOR, HUMIDITY SENSOR, AND ROOM PRESSURE
DIFFERENTIAL MONITOR. CONNECT TO BUILDING AUTOMATION SYSTEM.
6 PROVIDE RG-2 RETURN AIR GRILLE TO PROVIDE OPEN-PLENUM RETURN.
7 FILTER BOX.
8 CONNECT EXHAUST AIR DUCT INTO EXISTING HOOD.
9 AIR VOLUME CONTROL VALVE FOR EXHAUST AIR. AIRFLOW TO FLUCTUATE TO MEET
-0.02 IN. W.C. PRESSURIZATION REQUIREMENTS.
10 CONNECT SUPPLY AIR INTO EXISTING DUCT MAIN.
11 INSTALL DDC PANEL ABOVE CEILING. CONTRACTOR TO DETERMINE EXACT
LOCATION IN FIELD.
12 ROUTE EXHAUST AIR DUCT TO EXHAUST FANS ON ROOF. FOLLOW SAME ROUTE AS
DEMOLISHED SYSTEM.
13 AIR VOLUME CONTROL VALVE FOR EXHAUST AIR SERVING EXISTING HOOD.
AIRFLOW TO FLUCTUATE TO MEET HOOD PRESSURIZATION REQUIREMENTS.
INTEGRATE WITH HOOD CONTROLLER.
14 TRANSFER AIR TO BE DISTRIBUTED INTO PLENUM SPACE.
1/4" = 1'-0"
ENLARGED PLAN - LEVEL 02 - EXHAUST
1/4" = 1'-0"
HVAC EXHAUST ROUTING PLAN
Revisions: Date:
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
C301
MECH. RM.
12"Ø EA
12"Ø EA (UP)
12"Ø EA (DN)
16"x12"(EX)
"Ø E
A
12"Ø EA
"Ø E
A
12"Ø EA
"Ø E
A
"Ø E
A
D302
MECH. RM.
"x
E A
14"x12" EA (DN)
14"x12" EA (UP)
01-MH-104
01-MH-104
01-MH-104
22"x14" EA (UP/DN)
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:0
A
M
HVAC ENLARGED PLAN - LEVEL 03
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MH-104
NO. DESCRIPTION
1 ROUTE EXHAUST AIR DUCT (SERVING TB ROOM D220) TO EXHAUST FANS ON ROOF.
FOLLOW SAME ROUTE AS DEMOLISHED SYSTEM.
2 ROUTE EXHAUST AIR DUCT (SERVING PATIENT ISOLATION ROOM E128) TO EXHAUST
FANS ON ROOF. FOLLOW SAME ROUTE AS DEMOLISHED SYSTEM.
3 ROUTE EXHAUST AIR DUCT (SERVING PATIENT ISOLATION ROOMS A164 & A165) TO
EXHAUST FANS ON ROOF. FOLLOW SAME ROUTE AS DEMOLISHED SYSTEM.
EXTERIOR DUCT TO BE BROWN COLOR, MATCHING LAGGING.
4 EXISTING DUCTWORK TO REMAIN. SHOWN FOR REFERENCE.
3/16" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 03 INTERSTITIAL
1/4" = 1'-0"
ENLARGED PLAN - LEVEL 03 - MECH. RM. D302
NTS
KEYPLAN - LEVEL 3
1/4" = 1'-0"
ENLARGED PLAN - LEVEL 03 - EXHAUST
Revisions: Date:
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MH-105
01-MH-105
01-MH-105
22"x14" EA (UP/DN)
01-EF-E128A
01-EF-E128B
14"x12" EA (DN)
101-EFB-E128
14"x12" EA
14"x12" EA
14"x12" EA
12"Ø EA (UP/DN)6
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:2
A
M
HVAC ENLARGED PLAN - LEVEL 04
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MH-105
NTS
KEYPLAN - LEVEL 4
NO. DESCRIPTION
1 BAG-IN, BAG-OUT FILTER HOUSING.
2 MOTORIZED DAMPER
3 HIGH PLUME EXHAUST FAN
4 EXISTING DUCTWORK TO REMAIN. SHOWN FOR REFERENCE ONLY.
5 ROUTE EXHAUST AIR DUCT (SERVING PATIENT ISOLATION ROOMS A164 & A165) TO
EXHAUST FANS ON ROOF. FOLLOW SAME ROUTE AS DEMOLISHED SYSTEM.
EXTERIOR DUCT TO BE BROWN COLOR, MATCHING LAGGING.
6 ROUTE EXHAUST AIR DUCT (SERVING TB ROOM D220) TO EXHAUST FANS ON ROOF.
FOLLOW THE SAME ROUTE AS DEMOLISHED SYSTEM.
7 DUCT PENETRATION TO BE ROUTED THROUGH AN INSULATED ROOF CURB, FLASHED
& SEALED TO ROOF AND AROUND DUCT TO CURB.
1/2" = 1'-0"
ENLARGED PLAN - LEVEL 04 - EXHAUST
1/2" = 1'-0"
LEVEL 04 - ROOF 30 - ENLARGED PLAN
1/2" = 1'-0"
ENLARGED EXHAUST ROUTING PLAN - LEVEL 04
Revisions: Date:
P H T
P
P
H
T
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MH-106
01-MH-106
01-MH-106
01-MH-106
SD-6
540 CFM
01-ECV-B503
SET TO 640 CFM
12"Ø EA
PRESSURE:
-0.02 IN. W.C.
EG-2
640 CFM
(TYP)
B503
BRONCHOSCOPY
SUITE
H508
CORRIDOR
12"x12" SA
12"x12" EA
01-AF-B503
01-EF (EX)
12"Ø EA
"x
S A
(E X
01-SH-B503
01-VAV-B503-1
8"Ø SA
"Ø
S A
C510
ISOLATION
RECOVERY
C511A
TOILET C511
TOILET
H510B
CORRIDOR
C510A
ANTE
PRESSURE:
-0.02 IN. W.C.
PRESSURE:
-0.02 IN. W.C.
01-LVR-C510
01-PF-C510
01-SF-C510
SET TO 50 CFM
01-PHC-C510
01-AF-C510
01-AHU-C510
8"Ø SA
12"x12" SA
10"Ø RA
12"x18" RA
14"x8" EA
"x
E A
"x
E A
8"Ø SA
8"Ø EA
01-ECV-C510
14"x4" EA (DN)
14"x4" EA (DN)
(TYP)
SD-5
300 CFM
SD-1
100 CFM
1301-SCV-C510
20"x14" SA
"x
S A
14"x14"OA
14"x14" EA (UP)
301-ECV-C510A
EG-1
200 CFM
ER-1
400 CFM
ER-1
400 CFM
201-SH-C510
22"x14" EA (UP/DN)
12"Ø EA (UP/DN)
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:3
A
M
HVAC ENLARGED PLAN - LEVEL 05
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MH-106
NTS
KEYPLAN - LEVEL 05
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 05 - B503
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 05 - C510
NO. DESCRIPTION
1 INSTALL DIFFUSER IN CEILING.
2 STEAM HUMIDIFIER.
3 AIR CONTROL VALVE FOR EXHAUST AIR. AIRFLOW TO FLUCTUATE TO MEET -0.02 IN.
W.C. PRESSURIZATION REQUIREMENTS.
4 PROVIDE TEMPERATURE SENSOR, HUMIDITY SENSOR, AND ROOM PRESSURE
DIFFERENTIAL MONITOR. CONNECT TO BUILDING AUTOMATION SYSTEM.
5 CONNECT EXHAUST AIR DUCT TO EXISTING EXHAUST AIR DUCT SYSTEM.
6 EXISTING 3/4 HP EXHAUST BOOSTER FAN TO REMAIN.
MANUFACTURER: COOK
MODEL: 135 SQN 135SQN17DEC 50
7 CONNECT SUPPLY AIR DUCT TO EXISTING SUPPLY AIR SYSTEM.
8 FAN-POWERED VAV BOX WITH RE-HEAT COILS.
9 INSTALL OUTDOOR INTAKE LOUVER IN EXTERIOR WALL. COORDINATE WITH
ARCHITECTURAL.
10 MOTORIZED DAMPER.
11 OUTDOOR AIR, IN-LINE BOOSTER FAN.
12 INSTALL NEW SIDE-WALL EXHAUST AIR REGISTER ON EACH SIDE OF BED, 7 IN. AFF.
13 AIR VOLUME CONTROL VALVE FOR SUPPLY AIR. AIRFLOW TO FLUCTUATE TO MEET
-0.02" W.C. PRESSURIZATION REQUIREMENTS.
14 FILTER BOX
15 PRE-HEAT COILS.
16 LOW-PROFILE AIR HANDLING UNIT.
17 ROUTE EXHAUST AIR TO EXHAUST FANS ON ROOF.
18 ROUTE EXHAUST AIR DUCT (SERVING PATIENT ISOLATION ROOMS A164 & A165) TO
EXHAUST FANS ON ROOF. FOLLOW SAME ROUTE AS DEMOLISHED SYSTEM.
EXTERIOR DUCT TO BE BROWN COLOR, MATCHING LAGGING.
19 ROUTE EXHAUST AIR DUCT (SERVING TB ROOM D220) TO EXHAUST FANS ON ROOF.
FOLLOW SAME ROUTE AS DEMOLISHED SYSTEM.
20 INSTALL DDC PANEL ABOVE CEILING. CONTRACTOR TO DETERMINE EXACT
LOCATION IN FIELD.
21 EXISTING AIR-VALVE DEVICE TO REMAIN.
22 EXISTING DUCTWORK TO REMAIN. SHOWN FOR REFERENCE.
1/2" = 1'-0"
ENLARGED PLAN - LEVEL 05 - EXHAUST
1/2" = 1'-0"
ENLARGED EXHAUST PLAN - LEVEL 05
Revisions: Date:
T H
P
P
P H T
P
P H T
KEYNOTES
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MH-107
01-MH-107
01-MH-107
01-MH-107
C615
ISOLATION
C616
SOILED
H619
CORRIDOR
CHASE C615A
ANTE RM.
"Ø
S A
14"x8" EA
12"x18"OA
12"x12"SA
"x
E A
12"x10" EA
"x
E A
8"Ø SA
12"x10" OA
"Ø S
A
"Ø S
A
12"x4" EA (DN)
12"x4" EA (DN)
01-LVR-C615
01-AF-C615
01-AHU-C615
SD-1
100 CFM
SG-5
300 CFM
ER-1
400 CFM
ER-1
400 CFM
(TYP)
1 10
01-PF-C615
01-SF-C615
01-PHC-C615
1201-SCV-C615
SET TO 320 CFM
PRESSURE:
-0.02 IN. W.C.
PRESSURE:
-0.02 IN. W.C.
9 01-ECV-C615-2
SET TO 550 CFM
01-ECV-C615-1
SET TO 170 CFM
EG-1
200 CFM
12"x10" EA
18"x20" EA (UP)
"Ø
S
A 01-SH-C615
01-SCV-A658
SET TO 350 CFM
EG-1
150 CFM
EG-1
200 CFM
01-ECV-A658-2
SET TO 350 CFM
"Ø
E A
01-ECV-A663-2
SET TO 340 CFM
EG-1
140 CFM
EG-1
200 CFM
EG-2
490 CFM
EG-2
520 CFM
PRESSURE:
-0.02 IN. W.C.
ROOM
PRESSURIZATION:
-100 CFM
RG-2
360 CFM
PRESSURE:
-0.02 IN. W.C.
A658
ISOLATION
A658B
ANTE RM.
A658A
TOILET
H604
CORRIDOR
A663A
TOILET
A663B
ANTE RM.
A664A
NOUR.
(TYP)
01-SCV-A663
SET TO 360 CFM
01-SF-A658
SET TO 40 CFM
01-SF-A663
SET TO 50 CFM
01-ECV-A658-1
SET TO 490 CFM
"Ø
S A
12"x8" EA
01-ECV-A663-1
SET TO 520 CFM
10"Ø SA
SD-1
50 CFM
SD-1
100 CFM
8"Ø SA
"x
E A
"x
S A
SD-5
240 CFM
SD-1
100 CFM
"x
O A
"x
S A
01-AHU-A663
SD-1
40 CFM
"Ø E
A
12"x12" SA
01-PHC-A658
01-LVR-A658
(TYP)
A663
ISOLATION
SD-5
270 CFM
01-LVR-A663
RG-2
350 CFM
01-PF-A658
01-AF-A658
01-PF-A663
01-AF-A663
10"Ø EA
17"x18" RA
"Ø
S A
10"x10" SA
01-AHU-A658
14"x12" EA
10"Ø EA 12"x8" EA
14"x12" EA
"x
E A
8 -
ROOM
PRESSURIZATION:
-100 CFM
12"x10" SA
8"Ø EA
10"Ø EA8"Ø EA
8"Ø EA
01-SH-A663
12"Ø EA (DN)
12"Ø EA (UP)
32"x16" EA (UP/DN)
18"x12" EA
18"x12" EA
"x
E A
12"x18" EA
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:4
A
M
HVAC ENLARGED PLAN - LEVEL 06
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MH-107
NTS
KEYPLAN - LEVEL 06
NO. DESCRIPTION
1 INSTALL OUTSIDE AIR INTAKE LOUVER IN EXTERIOR WALL. COORDINATE WITH
ARCHITECTURAL.
2 INSTALL DIFFUSER IN CEILING.
3 MOTORIZED DAMPER.
4 OUTDOOR AIR, IN-LINE BOOSTER FAN.
5 LOW-PROFILE AIR HANDLING UNIT.
6 STEAM HUMIDIFIER.
7 AIR VOLUME CONTROL VALVE FOR EXHAUST AIR. AIRFLOW TO FLUCTUATE TO MEET
-0.02 IN. W.C. PRESSURIZATION REQUIREMENTS.
8 PROVIDE TEMPERATURE SENSOR, HUMIDITY SENSOR, AND ROOM PRESSURE
DIFFERENTIAL MONITOR. CONNECT TO BUILDING AUTOMATION SYSTEM.
9 AIR CONTROL VALVE FOR EXHAUST AIR. AIRFLOW TO FLUCTUATE TO MEET -0.02"
W.C. PRESSURIZATION REQUIREMENTS.
10 FILTER BOX.
11 ROUTE EXHAUST AIR DUCT TO EXHAUST FANS ON ROOF. SEE DETAIL 4 ON THIS
SHEET FOR CONTINUATION.
12 AIR CONTROL VALVE FOR SUPPLY AIR. AIRFLOW TO FLUCTUATE TO MEET -0.02" W.C.
PRESSURIZATION REQUIREMENTS.
13 PRE-HEAT COILS.
14 INSTALL NEW SIDE-WALL EXHAUST AIR REGISTER ON EACH SIDE OF BED, 7 IN. AFF.
15 EXISTING 6" SPRINKLER PIPE SHOWN FOR REFERNCE. OFFSET MECHANICAL
SYSTEMS AROUND EXISTING SPIRNKLER SYSTEM AS REQUIRED.
16 RELOCATE EXISTING DATA CABLES AND CONDUIT AS REQUIRED FOR INSTALLATION
OF NEW MECHANICAL SYSTEMS. (TYP)
17 ROUTE EXHAUST AIR DUCT (SERVING TB ROOM D220) TO EXHAUST FANS ON ROOF.
FOLLOW SAME ROUTE AS DEMOLISHED SYSTEM.
18 ROUTE EXHAUST AIR DUCT TO EXHAUST FANS ON ROOF. SEE DETAIL 1 ON THIS
SHEET FOR CONTINUATION.
19 INSTALL DDC PANEL ABOVE CEILING. CONTRACTOR TO DETERMINE EXACT
LOCATION IN FIELD.
20 EXISTING DUCTWORK TO REMAIN. SHOWN FOR REFERENCE.
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 06 - C615
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 06 - A658 & A663
1/4" = 1'-0"
ENLARGED EXHAUST PLAN - LEVEL 06
1/4" = 1'-0"
ENLARGED EXHAUST PLAN 2 - LEVEL 06
Revisions: Date:
H
T
P
SCOPE OF WORK
P P
T H
KEYNOTES
EG-1
200 CFM
EG-1
150 CFM
10"ØTA
01-SCV-A720
SET TO 380 CFM
01-ECV-A720-1
SET TO 350 CFM
EG-2
560 CFM
01-ECV-A720-2
SET TO 560 CFM
PRESSURE:
-0.02 IN. W.C.
RG-2
380 CFM
A720
PATIENT ISO.
A720A
ANTE
A720B
TOILET
A721A
TOILET
A721
PATIENT ROOM
"x
E A
6 01-SF-A720
SET TO 60 CFM
SD-1
80 CFM
SD-5
310 CFM
SD-1
50 CFM 8"Ø SA
"Ø
S A
10"Ø SA
AHU-A720
8"Ø EA
10"Ø EA 8"Ø EA
01-PHC-A720
01-LVR-A720
1201-AF-A720
01-PF-A720
6" x1
E A
"x
E A
PRESSURE:
-0.02 IN. W.C.
01-SH-A720
12"x12" OA12"x12" SA
"Ø S
A
12"x12" SA
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-SCV-A707
SET TO 310 CFM
EG-1
130 CFM
8"Ø EA
EG-2
520 CFM
RG-2
310 CFM
PRESSURE:
-0.02 IN. W.C.
PRESSURE:
-0.02 IN. W.C.
A707
PATIENT ISO.
A708
PATIENT ROOM
A709
TOILET
H701
CORRIDOR
A707B
TOILET
A707A
ANTE RM.
01-ECV-A707-2
SET TO 520 CFM
10"x8" EA
01-SF-A707
SET TO 50 CFM
14"x14" EA
14"x14" EA (UP)
SD-1
60 CFM
EG-1
200 CFM
"Ø
T A
"x
E A
01-AHU-A707
SD-1
30 CFM
8"Ø SA
"Ø
S A
"Ø S
A
12"x12" SA
12"Ø EA
"Ø
E A
SD-4
270 CFM
01-PHC-A707
01-LVR-A707
"x
R
A
"Ø S
A
12 01-PF-A707
01-AF-A707
01-ECV-A707-1
SET TO 330 CFM
"Ø E
A
8"Ø EA
8"Ø EA
01-SH-A707
01-MH-108
01-MH-108
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:5
A
M
HVAC ENLARGED PLAN - LEVEL 07
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MH-108
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 07 - A720
NO. DESCRIPTION
1 ROUTE EXHAUST AIR DUCT TO EXHAUST FANS ON ROOF.
2 PROVIDE RG-2 RETURN GRILLE FOR AIR TRANSFER INTO ISOLATION ROOM.
3 PROVIDE TEMPERATURE SENSOR, HUMIDITY SENSOR, AND ROOM PRESSURE
DIFFERENTIAL MONITOR. CONNECT TO BUILDING AUTOMATION SYSTEM.
4 AIR VOLUME CONTROL VALVE FOR EXHAUST AIR. AIRFLOW TO FLUCTUATE TO MEET
-0.02 IN. W.C. PRESSURIZATION REQUIREMENTS.
5 AIR CONTROL VALVE FOR TRANSFERRED AIR. AIRFLOW TO FLUCTUATE TO MEET
-0.02 IN. W.C. PRESSURIZATION REQUIREMENTS.
6 OUTSIDE AIR, IN-LINE BOOSTER FAN.
7 STEAM HUMIDIFIER.
8 MOTORIZED DAMPER.
9 PRE-HEAT COILS.
10 LOW-PROFILE AIR HANDLING UNIT.
11 INSTALL OUTSIDE AIR INTAKE LOUVER IN EXTERIOR WALL. COORDINATE WITH
ARCHITECTURAL.
12 FILTER BOX.
13 HIGH PLUME EXHAUST FAN.
14 BAG-IN, BAG-OUT FILTER HOUSING.
15 INSTALL DDC PANEL ABOVE CEILING. CONTRACTOR TO DETERMINE EXACT
LOCATION IN FIELD.
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 07 - A707
NTS
KEYPLAN - LEVEL 07
Revisions: Date:
H
P
P
P
P
SCOPE OF WORK
KEYNOTES
01-SCV-A757
SET TO 370 CFM
01-ECV-A757-1
SET TO 360 CFM
EG-1
160 CFM
EG-1
200 CFM
EG-2
490 CFM
01-ECV-A757-2
SET TO 490 CFM
RG-2
370 CFM
PRESSURE:
-0.02 IN. W.C.
A756
CLEAN LINEN
A757
PATIENT ROOM
A757B
TOILET
A757A
ANTE RM.
01-SF-A757-1
SET TO 40 CFM
SD-1
110 CFM
SD-1
60 CFM
01-AHU-A757
"x
R
A
SD-3
240 CFM
01-PHC-A757
01-LVR-A757
PRESSURE:
-0.02 IN. W.C.
01-PF-A757
01-AF-A757
10"ØTA
"x
E A
14"x12" EA 10"x10" EA
"Ø
E A
8"Ø EA
"Ø
S A
"Ø
S A
10"x10" SA
12"x12" OA
8"Ø EA
"x
E A
12"x12" OA
12"x12" OA
12"x10" EA 1
"x
E A
01-SH-A757
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
01-MH-109
01-MH-109
01-MH-109
01-EF-C510A 01-EF-C510B
18"x20" EA (DN)
01-EFB-C510
"x
E A
12"Ø EA (DN)
01-EF-D220A 01-EF-D220B
01-EFB-D220
"x
E A
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
ARCHITECT/ENGINEER OF RECORDCONSULTANT
8910 7 6
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
U.S. Department of Veterans Affairs
Phase
STAMP
5 4 3 2 1
VETERANS
HEALTH
ADMINISTRATION
FULLY SPRINKLERED
B
IM
/V
IS
N
S t L o u is C o rr e c t H
V A
C S y s te m s i n P ro c e d u re R m /S t L o u is
P ro c R m s -1
J C
M
E P
V
.r v t
/1
/2
:1
:0
A
M
HVAC ENLARGED PLAN - LEVEL 07
JANUARY 31, 2023
657-21-115JC100% BID DOCUMENTS CORRECT HEATING, VENTILATION,
AND AIR CONDITIONING SYSTEMS
IN PROCEDURE ROOMS
AW MS
657 - ST. LOUIS, MO
915 NORTH GRAND BLVD., ST. LOUIS, MO 63106
01-MH-109
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 07 - A757
NTS
KEYPLAN - LEVEL 07
NO. DESCRIPTION
1 HIGH PLUME EXHAUST FAN.
2 PROVIDE RG-2 RETURN GRILLE FOR AIR TRANSFER INTO ISOLATION ROOM.
3 PROVIDE TEMPERATURE SENSOR, HUMIDITY SENSOR, AND ROOM PRESSURE
DIFFERENTIAL MONITOR. CONNECT TO BUILDING AUTOMATION SYSTEM.
4 AIR VOLUME CONTROL VALVE FOR EXHAUST AIR. AIRFLOW TO FLUCTUATE TO MEET
-0.02 IN. W.C. PRESSURIZATION REQUIREMENTS.
5 AIR CONTROL VALVE FOR TRANSFERRED AIR. AIRFLOW TO FLUCTUATE TO MEET
-0.02 IN. W.C. PRESSURIZATION REQUIREMENTS.
6 OUTSIDE AIR, IN-LINE BOOSTER FAN
7 STEAM HUMIDIFIER.
8 MOTORIZED DAMPER.
9 LOW-PROFILE AIR HANDLING UNIT.
10 PRE-HEAT COILS
11 INSTALL OUTSIDE AIR INTAKE LOUVER IN EXTERIOR WALL. COORDINATE WITH
ARCHITECTURAL.
12 FILTER BOX.
13 INSTALL DDC PANEL ABOVE CEILING. CONTRACTOR TO DETERMINE EXACT
LOCATION IN FIELD.
14 BAG-IN, BAG-OUT FILTER HOUSING
15 MOTORIZED DAMPER.
16 SEE DETAIL 1 ON SHEET 01-MH-110 FOR CONTINUATION.
17 DUCT PENETRATION TO BE ROUTED THROUGH AN INSULATED ROOF CURB, FLASHED
& SEALED TO ROOF AND AROUND DUCT TO CURB.
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 07 - ROOF 28
1/2" = 1'-0"
HVAC ENLARGED PLAN - LEVEL 07 - ROOF 32
Revisions: Date:
01-MH-110
S705
STAIR 05
A747
CLEAN UTIL
A747B
ELEC. CLOSET
A748A
TOILET
A748B
ELEC
A753A
STORAGE
A754A
TOILET
A754
PATIENT ROOM
H705A
F.E. CLOSET
36"x18" EA (UP)
"x
E A
14"x12" EA
"x
E A
14"x12" EA
14"x12" EA
14"x12" EA
NO SCOPE OF WORK ASSOCIATED WITH THIS AREA
PLAN NORTH
TRUE NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
VA FORM 08 - 6231
F
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1