S06-657A4-25-107-STL24210-250 SB Services-VA Poplar Bluff Report Additional Disconnect Testing.pdf

PDF 898 KB Posted

Attached to
H259--657A4-25-107, Triennial Electrical Testing
Solicitation number
36C25525R0136
Issued by

About this file

This document is an Electrical Equipment Test Report for low-voltage air switches at the VA Hospital in Poplar Bluff, Missouri, performed by Electric Power Systems on May 23, 2024. The report covers testing of seven low-voltage disconnect switches located in the hospital's Building 1 Basement Chiller Room, including units for Pumps 9, 10, 11, 15, a water heater, and two condensate pump disconnects. The testing involved comprehensive visual, mechanical, and electrical inspections, including insulation resistance and contact resistance tests.

The test results revealed multiple contact resistance failures across different switches. Specifically, Pumps 9 and 15 had multiple phase contact resistance issues, the water heater passed all tests, and the condensate pump disconnects also showed contact resistance problems. The report recommends a thermographic scan to identify potential deficiencies causing the higher-than-expected measurements. The switches were from manufacturers including Siemens, Square D, and General Electric, with system voltages of 240V and rated currents ranging from 30 to 100 amps. The job number for this testing was STL24210-250, and the testing was conducted by W. Bahr from Electric Power Systems.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S&B Services / VA Hospital, Poplar Bluff, MO

STL24210-250

ELECTRICAL EQUIPMENT TEST REPORT

ST. LOUIS OFFICE

Charles Moses – Field Service Manager STL 10330 Page Industrial Blvd, St Louis MO

P: (314) 890-9999 www.epsii.com

1 | P a g e

Electric Power Systems 10330 Page Industrial Blvd.

St. Louis, Missouri 63132

(314) 890-9999

Stephen Sanders S & B Services 7 Summit Dr.

Canyon, Texas 79015

SUBJECT: Electrical Equipment Test Report.

EPS JOB: STL24210-250

Mr. Stephen Sanders, This report summarizes the maintenance testing of the LV Disconnects located at the VA Hospital in Poplar Bluff, MO. It has been Electric Power Systems pleasure in providing testing services to S&B Services. If there are any questions, comments or concerns please do not hesitate to contact us directly at our St. Louis Area Office.

Report Prepared by: Report Approved by:

Walter Bahr Charles Moses Senior Field Technician Field Service Manager STL Electrical Power Systems Electrical Power Systems St. Louis, MO St. Louis, MO

(314) 890-9999 (314) 890-9999

2 | P a g e

Table of Contents

Purpose Page 3

Equipment Tested Page 3

Procedures Page 4

Summary Page 5

Test Data Sheets See Attached

3 | P a g e

Purpose:

Electrical systems begin to degrade at the onset of installation and operation. There are many factors, such as design intent, environmental conditions, shipping / handling and installation practices to consider regarding electrical equipment related to power system safety and reliability. Maintenance testing of electrical equipment and apparatus is a useful tool in determining the continued condition of electrical equipment and systems.

Maintenance testing procedures aid in providing critical information as to the functionality, safety and reliability of electrical equipment and systems as a whole, as well as providing baselines for continued monitoring of the lifetime of the electrical equipment. This will aid in planning for future replacement or upgrading.

The equipment and components listed in this report have been inspected and tested to help assure their proper and safe operation. Defective or marginal equipment can be identified, repaired, replaced or scheduled for future repairs without costly or unexpected interruptions during normal operating periods

Equipment Tested

(7) LV Disconnect Switches

4 | P a g e

Procedures:

Air Switches, Low-Voltage

A. Visual and Mechanical Inspection

1. Compare equipment nameplate data with drawings and specifications.

2. Inspect physical and mechanical condition.

3. Confirm correct application of manufacturer’s recommended lubricants.

4. Verify appropriate equipment grounding.

5. Verify correct blade alignment, blade penetration, travel stops, and mechanical operation.

6. Verify that fuse sizes and types are in accordance with drawings and short-circuit and coordination studies.

7. Verify that each fuse holder has adequate mechanical support.

8. Verify tightness of accessible bolted electrical connections.

10. Test all interlocking systems for correct operation and sequencing.

11. Verify correct phase barrier materials and installation.

12. Inspect all indicating and control devices for correct operation.

B. Electrical Test

1. Perform insulation-resistance tests on each pole.

2. Measure contact-resistance across each switchblade and fuse holder.

3. Measure fuse resistance.

4. Perform insulation resistance tests on all control wiring.

5 | P a g e

Summary:

The switches and fuses exceeded the NETA specifications of 50% difference from phase to phase with the exception of the water heater. It is recommended to perform a Thermographic scan to identify any deficiencies that may be causing the higher than expected measurements.

Ductor W. BahrTESTED BY:

16500 - 7.5.1.1, REVISED 4/9/2024www.epsii.com

TEST EQUIPMENT USED:

HUMIDITY 50 Building 1 Basement

SUBSTATION

DATE

Chiller Room POSITION Pump 10

5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION

TELEPHONE 469-394-8789

CUSTOMER

ADDRESS 7 Summit Drive; Canyon Texas USA 79015

S&B Services

OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901

Stephen Sanders

PAGE

JOB # STL24210-250

REPRESENTATIVE

7.5.1.1 LV AIR SWITCH

80 °F

NAMEPLATE DATA

MANUFACTURER

TYPE

CATALOG No.

SERIAL No.

SYSTEM VOLTAGE

POWER FUSE INFO

IMPULSE VOLTAGE

RATED VOLTAGE

Siemens

Vac

N/A

240 Vac RATED CURRENT

MAX INTERRUPT

MISCELLANEOUS

N/A

Amps100

100,000 Amps

LEGEND: A

VISUAL & MECHANICAL INSPECTION

C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE

CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING

1. NAMEPLATE COMPARABLE TO DWGS / SPECS

2. PHYSICAL / MECH. CONDITION

3. ANCHORAGE / ALIGNMENT & GROUNDING

4. OVERALL CLEANLINESS

5. CORRECT BLADE ALIGN. & PENETRATION

N/A

A

A

A

A

7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS

8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY

9. PHASE BARRIERS INSTALLED CORRECTLY

10. INDICATING / CONTROL DEVICE OPERATION

11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS

N/A

N/A

A

A

A

6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A

ELECTRICAL TESTS PERFORMED

Select tests not performed

INSULATION RESISTANCE CONTACT RESISTANCE

ELECTRICAL TESTS

RATING

C → GB → GA → G

PHASE to GROUND (MΩ)

C → AB → C

PHASE to PHASE (MΩ)

A → BC ↔ CB ↔ B

LINE to LOAD (MΩ)

A ↔ A

13. INSULATION RESISTANCE

500TEST Vdc

MIN (MΩ) 25

TEMP CORRECTED @ 20°C

A (µΩ) B (µΩ) RATING

4,524 4,575 0.713

△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)

SWITCHBLADES

FUSEHOLDERS

FUSES

R

1.1

14. CONTACT RESISTANCE

± 15 %

COMMENTS: All test results are in milliohms, not microohms.

DEFICIENCIES: A & B phases fail contact resistance.

N/A

TEST EQUIPMENT USED:

HUMIDITY 50 Building 1 Basement

SUBSTATION

DATE

Chiller Room POSITION Pump 11

5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION

TELEPHONE 469-394-8789

CUSTOMER

ADDRESS 7 Summit Drive; Canyon Texas USA 79015

S&B Services

OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901

Stephen Sanders

PAGE

JOB # STL24210-250

REPRESENTATIVE

7.5.1.1 LV AIR SWITCH

80 °F

NAMEPLATE DATA

MANUFACTURER

TYPE

CATALOG No.

SERIAL No.

SYSTEM VOLTAGE

POWER FUSE INFO

IMPULSE VOLTAGE

RATED VOLTAGE

Siemens

Vac

N/A

240 Vac RATED CURRENT

MAX INTERRUPT

MISCELLANEOUS

N/A

Amps100

10,000 Amps

LEGEND: A

VISUAL & MECHANICAL INSPECTION

C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE

CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING

1. NAMEPLATE COMPARABLE TO DWGS / SPECS

2. PHYSICAL / MECH. CONDITION

3. ANCHORAGE / ALIGNMENT & GROUNDING

4. OVERALL CLEANLINESS

5. CORRECT BLADE ALIGN. & PENETRATION

N/A

A

A

A

A

7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS

8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY

9. PHASE BARRIERS INSTALLED CORRECTLY

10. INDICATING / CONTROL DEVICE OPERATION

11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS

N/A

N/A

A

A

A

6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A

ELECTRICAL TESTS PERFORMED

Select tests not performed

INSULATION RESISTANCE CONTACT RESISTANCE

ELECTRICAL TESTS

RATING

C → GB → GA → G

PHASE to GROUND (MΩ)

C → AB → C

PHASE to PHASE (MΩ)

A → BC ↔ CB ↔ B

LINE to LOAD (MΩ)

A ↔ A

13. INSULATION RESISTANCE

500TEST Vdc

MIN (MΩ) 25

TEMP CORRECTED @ 20°C

A (µΩ) B (µΩ) RATING

5,060 3,393 15,747

△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)

SWITCHBLADES

FUSEHOLDERS

FUSES

R

5,089.5

14. CONTACT RESISTANCE

± 15 %

COMMENTS: All test results are in milliohms, not microohms.

DEFICIENCIES: C phase fails contact resistance.

TEST EQUIPMENT USED:

HUMIDITY 50 Building 1 Basement

SUBSTATION

DATE

Chiller Room POSITION Pump 15

5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION

TELEPHONE 469-394-8789

CUSTOMER

ADDRESS 7 Summit Drive; Canyon Texas USA 79015

S&B Services

OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901

Stephen Sanders

PAGE

JOB # STL24210-250

REPRESENTATIVE

7.5.1.1 LV AIR SWITCH

80 °F

NAMEPLATE DATA

MANUFACTURER

TYPE

CATALOG No.

SERIAL No.

SYSTEM VOLTAGE

POWER FUSE INFO

IMPULSE VOLTAGE

RATED VOLTAGE

Square D

Vac

N/A

240 Vac RATED CURRENT

MAX INTERRUPT

MISCELLANEOUS

Fusetron 20 amp FRS-R-20

Amps30

100,000 Amps

LEGEND: A

VISUAL & MECHANICAL INSPECTION

C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE

CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING

1. NAMEPLATE COMPARABLE TO DWGS / SPECS

2. PHYSICAL / MECH. CONDITION

3. ANCHORAGE / ALIGNMENT & GROUNDING

4. OVERALL CLEANLINESS

5. CORRECT BLADE ALIGN. & PENETRATION

N/A

A

A

A

A

7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS

8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY

9. PHASE BARRIERS INSTALLED CORRECTLY

10. INDICATING / CONTROL DEVICE OPERATION

11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS

N/A

N/A

A

A

A

6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A

ELECTRICAL TESTS PERFORMED

Select tests not performed

INSULATION RESISTANCE CONTACT RESISTANCE

ELECTRICAL TESTS

RATING

C → GB → GA → G

PHASE to GROUND (MΩ)

C → AB → C

PHASE to PHASE (MΩ)

A → BC ↔ CB ↔ B

LINE to LOAD (MΩ)

A ↔ A

13. INSULATION RESISTANCE

500TEST Vdc

MIN (MΩ) 25

TEMP CORRECTED @ 20°C

A (µΩ) B (µΩ) RATING

0.92 0.453 0.926

△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)

SWITCHBLADES

FUSEHOLDERS

FUSES

R

0.7

14. CONTACT RESISTANCE

± 15 % 1,119 15,304 1,107 1,273.1

COMMENTS: All test results are in milliohms, not microohms.

DEFICIENCIES: A & C phases fail contact resistance.

B phase fuse fails contact resistance.

TEST EQUIPMENT USED:

HUMIDITY 50 Building 1 Basement

SUBSTATION

DATE

Chiller Room POSITION Pump 9

5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION

TELEPHONE 469-394-8789

CUSTOMER

ADDRESS 7 Summit Drive; Canyon Texas USA 79015

S&B Services

OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901

Stephen Sanders

PAGE

JOB # STL24210-250

REPRESENTATIVE

7.5.1.1 LV AIR SWITCH

80 °F

NAMEPLATE DATA

MANUFACTURER

TYPE

CATALOG No.

SERIAL No.

SYSTEM VOLTAGE

POWER FUSE INFO

IMPULSE VOLTAGE

RATED VOLTAGE

Siemens

Vac

N/A

240 Vac RATED CURRENT

MAX INTERRUPT

MISCELLANEOUS

N/A

Amps100

100,000 Amps

LEGEND: A

VISUAL & MECHANICAL INSPECTION

C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE

CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING

1. NAMEPLATE COMPARABLE TO DWGS / SPECS

2. PHYSICAL / MECH. CONDITION

3. ANCHORAGE / ALIGNMENT & GROUNDING

4. OVERALL CLEANLINESS

5. CORRECT BLADE ALIGN. & PENETRATION

N/A

A

A

A

A

7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS

8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY

9. PHASE BARRIERS INSTALLED CORRECTLY

10. INDICATING / CONTROL DEVICE OPERATION

11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS

N/A

N/A

A

A

A

6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A

ELECTRICAL TESTS PERFORMED

Select tests not performed

INSULATION RESISTANCE CONTACT RESISTANCE

ELECTRICAL TESTS

RATING

C → GB → GA → G

PHASE to GROUND (MΩ)

C → AB → C

PHASE to PHASE (MΩ)

A → BC ↔ CB ↔ B

LINE to LOAD (MΩ)

A ↔ A

13. INSULATION RESISTANCE

500TEST Vdc

MIN (MΩ) 25

TEMP CORRECTED @ 20°C

A (µΩ) B (µΩ) RATING

0.807 2,196 1,266

△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)

SWITCHBLADES

FUSEHOLDERS

FUSES

R

1.2

14. CONTACT RESISTANCE

± 15 %

COMMENTS: All test results are in milliohms, not microohms.

DEFICIENCIES: B & C phases fail contact resistance.

TEST EQUIPMENT USED:

HUMIDITY 50 Building 1 Basement

SUBSTATION

DATE

Chiller Room POSITION Water Heater

5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION

TELEPHONE 469-394-8789

CUSTOMER

ADDRESS 7 Summit Drive; Canyon Texas USA 79015

S&B Services

OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901

Stephen Sanders

PAGE

JOB # STL24210-250

REPRESENTATIVE

7.5.1.1 LV AIR SWITCH

80 °F

NAMEPLATE DATA

MANUFACTURER

TYPE

CATALOG No.

SERIAL No.

SYSTEM VOLTAGE

POWER FUSE INFO

IMPULSE VOLTAGE

RATED VOLTAGE

Square D

Vac

N/A

240 Vac RATED CURRENT

MAX INTERRUPT

MISCELLANEOUS

Gould Shamut Amptrap II 80 Amps A2D80R

Amps200

10,000 Amps

LEGEND: A

VISUAL & MECHANICAL INSPECTION

C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE

CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING

1. NAMEPLATE COMPARABLE TO DWGS / SPECS

2. PHYSICAL / MECH. CONDITION

3. ANCHORAGE / ALIGNMENT & GROUNDING

4. OVERALL CLEANLINESS

5. CORRECT BLADE ALIGN. & PENETRATION

N/A

A

A

A

A

7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS

8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY

9. PHASE BARRIERS INSTALLED CORRECTLY

10. INDICATING / CONTROL DEVICE OPERATION

11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS

N/A

N/A

A

A

A

6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A

ELECTRICAL TESTS PERFORMED

Select tests not performed

INSULATION RESISTANCE CONTACT RESISTANCE

ELECTRICAL TESTS

RATING

C → GB → GA → G

PHASE to GROUND (MΩ)

C → AB → C

PHASE to PHASE (MΩ)

A → BC ↔ CB ↔ B

LINE to LOAD (MΩ)

A ↔ A

13. INSULATION RESISTANCE

500TEST Vdc

MIN (MΩ) 25

TEMP CORRECTED @ 20°C

A (µΩ) B (µΩ) RATING

0.004 0.005 0.004

△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)

SWITCHBLADES

FUSEHOLDERS

FUSES

A

0.0

14. CONTACT RESISTANCE

± 15 % 1,119 1,116 1,107 1,273.1

COMMENTS: All test results are in milliohms, not microohms.

DEFICIENCIES:

TEST EQUIPMENT USED:

HUMIDITY 50 Building 1 Basement

SUBSTATION

DATE

Fwd Bsmnt Condensate Pump Old Set POSITION Disconnect 1

5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION

TELEPHONE 469-394-8789

CUSTOMER

ADDRESS 7 Summit Drive; Canyon Texas USA 79015

S&B Services

OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901

Stephen Sanders

PAGE

JOB # STL24210-250

REPRESENTATIVE

7.5.1.1 LV AIR SWITCH

80 °F

NAMEPLATE DATA

MANUFACTURER

TYPE

CATALOG No.

SERIAL No.

SYSTEM VOLTAGE

POWER FUSE INFO

IMPULSE VOLTAGE

RATED VOLTAGE

General Electric

Vac

N/A

240 Vac RATED CURRENT

MAX INTERRUPT

MISCELLANEOUS

N/A

Amps30

10,000 Amps

LEGEND: A

VISUAL & MECHANICAL INSPECTION

C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE

CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING

1. NAMEPLATE COMPARABLE TO DWGS / SPECS

2. PHYSICAL / MECH. CONDITION

3. ANCHORAGE / ALIGNMENT & GROUNDING

4. OVERALL CLEANLINESS

5. CORRECT BLADE ALIGN. & PENETRATION

N/A

A

A

A

A

7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS

8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY

9. PHASE BARRIERS INSTALLED CORRECTLY

10. INDICATING / CONTROL DEVICE OPERATION

11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS

N/A

N/A

A

A

A

6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A

ELECTRICAL TESTS PERFORMED

Select tests not performed

INSULATION RESISTANCE CONTACT RESISTANCE

ELECTRICAL TESTS

RATING

C → GB → GA → G

PHASE to GROUND (MΩ)

C → AB → C

PHASE to PHASE (MΩ)

A → BC ↔ CB ↔ B

LINE to LOAD (MΩ)

A ↔ A

13. INSULATION RESISTANCE

500TEST Vdc

MIN (MΩ) 25

TEMP CORRECTED @ 20°C

A (µΩ) B (µΩ) RATING

0.817 1,299 0.643

△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)

SWITCHBLADES

FUSEHOLDERS

FUSES

R

1.0

14. CONTACT RESISTANCE

± 15 %

COMMENTS: All test results are in milliohms, not microohms.

DEFICIENCIES: B phase fails contact resistance.

TEST EQUIPMENT USED:

HUMIDITY 50 Building 1 Basement

SUBSTATION

DATE

Fwd Bsmnt Condensate Pump Old Set POSITION Disconnect 2

5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION

TELEPHONE 469-394-8789

CUSTOMER

ADDRESS 7 Summit Drive; Canyon Texas USA 79015

S&B Services

OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901

Stephen Sanders

PAGE

JOB # STL24210-250

REPRESENTATIVE

7.5.1.1 LV AIR SWITCH

80 °F

NAMEPLATE DATA

MANUFACTURER

TYPE

CATALOG No.

SERIAL No.

SYSTEM VOLTAGE

POWER FUSE INFO

IMPULSE VOLTAGE

RATED VOLTAGE

General Electric

Vac

N/A

240 Vac RATED CURRENT

MAX INTERRUPT

MISCELLANEOUS

N/A

Amps30

10,000 Amps

LEGEND: A

VISUAL & MECHANICAL INSPECTION

C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE

CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING

1. NAMEPLATE COMPARABLE TO DWGS / SPECS

2. PHYSICAL / MECH. CONDITION

3. ANCHORAGE / ALIGNMENT & GROUNDING

4. OVERALL CLEANLINESS

5. CORRECT BLADE ALIGN. & PENETRATION

N/A

A

A

A

A

7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS

8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY

9. PHASE BARRIERS INSTALLED CORRECTLY

10. INDICATING / CONTROL DEVICE OPERATION

11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS

N/A

N/A

A

A

A

6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A

ELECTRICAL TESTS PERFORMED

Select tests not performed

INSULATION RESISTANCE CONTACT RESISTANCE

ELECTRICAL TESTS

RATING

C → GB → GA → G

PHASE to GROUND (MΩ)

C → AB → C

PHASE to PHASE (MΩ)

A → BC ↔ CB ↔ B

LINE to LOAD (MΩ)

A ↔ A

13. INSULATION RESISTANCE

500TEST Vdc

MIN (MΩ) 25

TEMP CORRECTED @ 20°C

A (µΩ) B (µΩ) RATING

6,735 1,399 7,534

△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)

SWITCHBLADES

FUSEHOLDERS

FUSES

R

2,098.5

14. CONTACT RESISTANCE

± 15 %

COMMENTS: All test results are in milliohms, not microohms.

DEFICIENCIES: A & B phases fails contact resistance.

Cover
Report
Test Sheets