This document is an Electrical Equipment Test Report for low-voltage air switches at the VA Hospital in Poplar Bluff, Missouri, performed by Electric Power Systems on May 23, 2024. The report covers testing of seven low-voltage disconnect switches located in the hospital's Building 1 Basement Chiller Room, including units for Pumps 9, 10, 11, 15, a water heater, and two condensate pump disconnects. The testing involved comprehensive visual, mechanical, and electrical inspections, including insulation resistance and contact resistance tests.
The test results revealed multiple contact resistance failures across different switches. Specifically, Pumps 9 and 15 had multiple phase contact resistance issues, the water heater passed all tests, and the condensate pump disconnects also showed contact resistance problems. The report recommends a thermographic scan to identify potential deficiencies causing the higher-than-expected measurements. The switches were from manufacturers including Siemens, Square D, and General Electric, with system voltages of 240V and rated currents ranging from 30 to 100 amps. The job number for this testing was STL24210-250, and the testing was conducted by W. Bahr from Electric Power Systems.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25525R0136 0006.docx | DOCX document | |
| 36C25525R0136 0005.docx | DOCX document | |
| 36C25525R0136 0004.docx | DOCX document | |
| S06-657A4-25-107-FINAL STL22279-250 VA Hospital-Poplar Bluff MO Report.pdf | ||
| S06-657A-25-107-SPG22461-Poplar Bluff VA Arc Flash Study-Systems Studies-Rev 1.pdf | ||
| S06-657A4-25-107-LPS - Existing System Notes for Facility File.pdf | ||
| 36C25525R0136 0003.docx | DOCX document | |
| S06-657A4-25-107-Gen Fuel Tank and Temp Gen Laydown Locations.pdf | ||
| 36C25525R0136 0002.docx | DOCX document | |
| 36C25525R0136 0001.docx | DOCX document | |
| S06-657A4-25-107 Pre-Bid Site Visit Attendance.pdf | ||
| S02-657A4-25-107-Electrical - One-Line Diagrams - 9-8-2023-.pdf | ||
| 36C25525R0136_1.docx | DOCX document |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S&B Services / VA Hospital, Poplar Bluff, MO
STL24210-250
ELECTRICAL EQUIPMENT TEST REPORT
ST. LOUIS OFFICE
Charles Moses – Field Service Manager STL 10330 Page Industrial Blvd, St Louis MO
P: (314) 890-9999 www.epsii.com
1 | P a g e
Electric Power Systems 10330 Page Industrial Blvd.
St. Louis, Missouri 63132
(314) 890-9999
Stephen Sanders S & B Services 7 Summit Dr.
Canyon, Texas 79015
SUBJECT: Electrical Equipment Test Report.
EPS JOB: STL24210-250
Mr. Stephen Sanders, This report summarizes the maintenance testing of the LV Disconnects located at the VA Hospital in Poplar Bluff, MO. It has been Electric Power Systems pleasure in providing testing services to S&B Services. If there are any questions, comments or concerns please do not hesitate to contact us directly at our St. Louis Area Office.
Report Prepared by: Report Approved by:
Walter Bahr Charles Moses Senior Field Technician Field Service Manager STL Electrical Power Systems Electrical Power Systems St. Louis, MO St. Louis, MO
(314) 890-9999 (314) 890-9999
2 | P a g e
Table of Contents
Purpose Page 3
Equipment Tested Page 3
Procedures Page 4
Summary Page 5
Test Data Sheets See Attached
3 | P a g e
Purpose:
Electrical systems begin to degrade at the onset of installation and operation. There are many factors, such as design intent, environmental conditions, shipping / handling and installation practices to consider regarding electrical equipment related to power system safety and reliability. Maintenance testing of electrical equipment and apparatus is a useful tool in determining the continued condition of electrical equipment and systems.
Maintenance testing procedures aid in providing critical information as to the functionality, safety and reliability of electrical equipment and systems as a whole, as well as providing baselines for continued monitoring of the lifetime of the electrical equipment. This will aid in planning for future replacement or upgrading.
The equipment and components listed in this report have been inspected and tested to help assure their proper and safe operation. Defective or marginal equipment can be identified, repaired, replaced or scheduled for future repairs without costly or unexpected interruptions during normal operating periods
Equipment Tested
(7) LV Disconnect Switches
4 | P a g e
Procedures:
Air Switches, Low-Voltage
A. Visual and Mechanical Inspection
1. Compare equipment nameplate data with drawings and specifications.
2. Inspect physical and mechanical condition.
3. Confirm correct application of manufacturer’s recommended lubricants.
4. Verify appropriate equipment grounding.
5. Verify correct blade alignment, blade penetration, travel stops, and mechanical operation.
6. Verify that fuse sizes and types are in accordance with drawings and short-circuit and coordination studies.
7. Verify that each fuse holder has adequate mechanical support.
8. Verify tightness of accessible bolted electrical connections.
10. Test all interlocking systems for correct operation and sequencing.
11. Verify correct phase barrier materials and installation.
12. Inspect all indicating and control devices for correct operation.
B. Electrical Test
1. Perform insulation-resistance tests on each pole.
2. Measure contact-resistance across each switchblade and fuse holder.
3. Measure fuse resistance.
4. Perform insulation resistance tests on all control wiring.
5 | P a g e
Summary:
The switches and fuses exceeded the NETA specifications of 50% difference from phase to phase with the exception of the water heater. It is recommended to perform a Thermographic scan to identify any deficiencies that may be causing the higher than expected measurements.
Ductor W. BahrTESTED BY:
16500 - 7.5.1.1, REVISED 4/9/2024www.epsii.com
TEST EQUIPMENT USED:
HUMIDITY 50 Building 1 Basement
SUBSTATION
DATE
Chiller Room POSITION Pump 10
5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION
TELEPHONE 469-394-8789
CUSTOMER
ADDRESS 7 Summit Drive; Canyon Texas USA 79015
S&B Services
OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901
Stephen Sanders
PAGE
JOB # STL24210-250
REPRESENTATIVE
7.5.1.1 LV AIR SWITCH
80 °F
NAMEPLATE DATA
MANUFACTURER
TYPE
CATALOG No.
SERIAL No.
SYSTEM VOLTAGE
POWER FUSE INFO
IMPULSE VOLTAGE
RATED VOLTAGE
Siemens
Vac
N/A
240 Vac RATED CURRENT
MAX INTERRUPT
MISCELLANEOUS
N/A
Amps100
100,000 Amps
LEGEND: A
VISUAL & MECHANICAL INSPECTION
C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE
CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING
1. NAMEPLATE COMPARABLE TO DWGS / SPECS
2. PHYSICAL / MECH. CONDITION
3. ANCHORAGE / ALIGNMENT & GROUNDING
4. OVERALL CLEANLINESS
5. CORRECT BLADE ALIGN. & PENETRATION
N/A
A
A
A
A
7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS
8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY
9. PHASE BARRIERS INSTALLED CORRECTLY
10. INDICATING / CONTROL DEVICE OPERATION
11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS
N/A
N/A
A
A
A
6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A
ELECTRICAL TESTS PERFORMED
Select tests not performed
INSULATION RESISTANCE CONTACT RESISTANCE
ELECTRICAL TESTS
RATING
C → GB → GA → G
PHASE to GROUND (MΩ)
C → AB → C
PHASE to PHASE (MΩ)
A → BC ↔ CB ↔ B
LINE to LOAD (MΩ)
A ↔ A
13. INSULATION RESISTANCE
500TEST Vdc
MIN (MΩ) 25
TEMP CORRECTED @ 20°C
A (µΩ) B (µΩ) RATING
4,524 4,575 0.713
△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)
SWITCHBLADES
FUSEHOLDERS
FUSES
R
1.1
14. CONTACT RESISTANCE
± 15 %
COMMENTS: All test results are in milliohms, not microohms.
DEFICIENCIES: A & B phases fail contact resistance.
N/A
TEST EQUIPMENT USED:
HUMIDITY 50 Building 1 Basement
SUBSTATION
DATE
Chiller Room POSITION Pump 11
5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION
TELEPHONE 469-394-8789
CUSTOMER
ADDRESS 7 Summit Drive; Canyon Texas USA 79015
S&B Services
OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901
Stephen Sanders
PAGE
JOB # STL24210-250
REPRESENTATIVE
7.5.1.1 LV AIR SWITCH
80 °F
NAMEPLATE DATA
MANUFACTURER
TYPE
CATALOG No.
SERIAL No.
SYSTEM VOLTAGE
POWER FUSE INFO
IMPULSE VOLTAGE
RATED VOLTAGE
Siemens
Vac
N/A
240 Vac RATED CURRENT
MAX INTERRUPT
MISCELLANEOUS
N/A
Amps100
10,000 Amps
LEGEND: A
VISUAL & MECHANICAL INSPECTION
C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE
CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING
1. NAMEPLATE COMPARABLE TO DWGS / SPECS
2. PHYSICAL / MECH. CONDITION
3. ANCHORAGE / ALIGNMENT & GROUNDING
4. OVERALL CLEANLINESS
5. CORRECT BLADE ALIGN. & PENETRATION
N/A
A
A
A
A
7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS
8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY
9. PHASE BARRIERS INSTALLED CORRECTLY
10. INDICATING / CONTROL DEVICE OPERATION
11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS
N/A
N/A
A
A
A
6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A
ELECTRICAL TESTS PERFORMED
Select tests not performed
INSULATION RESISTANCE CONTACT RESISTANCE
ELECTRICAL TESTS
RATING
C → GB → GA → G
PHASE to GROUND (MΩ)
C → AB → C
PHASE to PHASE (MΩ)
A → BC ↔ CB ↔ B
LINE to LOAD (MΩ)
A ↔ A
13. INSULATION RESISTANCE
500TEST Vdc
MIN (MΩ) 25
TEMP CORRECTED @ 20°C
A (µΩ) B (µΩ) RATING
5,060 3,393 15,747
△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)
SWITCHBLADES
FUSEHOLDERS
FUSES
R
5,089.5
14. CONTACT RESISTANCE
± 15 %
COMMENTS: All test results are in milliohms, not microohms.
DEFICIENCIES: C phase fails contact resistance.
TEST EQUIPMENT USED:
HUMIDITY 50 Building 1 Basement
SUBSTATION
DATE
Chiller Room POSITION Pump 15
5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION
TELEPHONE 469-394-8789
CUSTOMER
ADDRESS 7 Summit Drive; Canyon Texas USA 79015
S&B Services
OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901
Stephen Sanders
PAGE
JOB # STL24210-250
REPRESENTATIVE
7.5.1.1 LV AIR SWITCH
80 °F
NAMEPLATE DATA
MANUFACTURER
TYPE
CATALOG No.
SERIAL No.
SYSTEM VOLTAGE
POWER FUSE INFO
IMPULSE VOLTAGE
RATED VOLTAGE
Square D
Vac
N/A
240 Vac RATED CURRENT
MAX INTERRUPT
MISCELLANEOUS
Fusetron 20 amp FRS-R-20
Amps30
100,000 Amps
LEGEND: A
VISUAL & MECHANICAL INSPECTION
C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE
CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING
1. NAMEPLATE COMPARABLE TO DWGS / SPECS
2. PHYSICAL / MECH. CONDITION
3. ANCHORAGE / ALIGNMENT & GROUNDING
4. OVERALL CLEANLINESS
5. CORRECT BLADE ALIGN. & PENETRATION
N/A
A
A
A
A
7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS
8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY
9. PHASE BARRIERS INSTALLED CORRECTLY
10. INDICATING / CONTROL DEVICE OPERATION
11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS
N/A
N/A
A
A
A
6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A
ELECTRICAL TESTS PERFORMED
Select tests not performed
INSULATION RESISTANCE CONTACT RESISTANCE
ELECTRICAL TESTS
RATING
C → GB → GA → G
PHASE to GROUND (MΩ)
C → AB → C
PHASE to PHASE (MΩ)
A → BC ↔ CB ↔ B
LINE to LOAD (MΩ)
A ↔ A
13. INSULATION RESISTANCE
500TEST Vdc
MIN (MΩ) 25
TEMP CORRECTED @ 20°C
A (µΩ) B (µΩ) RATING
0.92 0.453 0.926
△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)
SWITCHBLADES
FUSEHOLDERS
FUSES
R
0.7
14. CONTACT RESISTANCE
± 15 % 1,119 15,304 1,107 1,273.1
COMMENTS: All test results are in milliohms, not microohms.
DEFICIENCIES: A & C phases fail contact resistance.
B phase fuse fails contact resistance.
TEST EQUIPMENT USED:
HUMIDITY 50 Building 1 Basement
SUBSTATION
DATE
Chiller Room POSITION Pump 9
5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION
TELEPHONE 469-394-8789
CUSTOMER
ADDRESS 7 Summit Drive; Canyon Texas USA 79015
S&B Services
OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901
Stephen Sanders
PAGE
JOB # STL24210-250
REPRESENTATIVE
7.5.1.1 LV AIR SWITCH
80 °F
NAMEPLATE DATA
MANUFACTURER
TYPE
CATALOG No.
SERIAL No.
SYSTEM VOLTAGE
POWER FUSE INFO
IMPULSE VOLTAGE
RATED VOLTAGE
Siemens
Vac
N/A
240 Vac RATED CURRENT
MAX INTERRUPT
MISCELLANEOUS
N/A
Amps100
100,000 Amps
LEGEND: A
VISUAL & MECHANICAL INSPECTION
C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE
CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING
1. NAMEPLATE COMPARABLE TO DWGS / SPECS
2. PHYSICAL / MECH. CONDITION
3. ANCHORAGE / ALIGNMENT & GROUNDING
4. OVERALL CLEANLINESS
5. CORRECT BLADE ALIGN. & PENETRATION
N/A
A
A
A
A
7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS
8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY
9. PHASE BARRIERS INSTALLED CORRECTLY
10. INDICATING / CONTROL DEVICE OPERATION
11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS
N/A
N/A
A
A
A
6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A
ELECTRICAL TESTS PERFORMED
Select tests not performed
INSULATION RESISTANCE CONTACT RESISTANCE
ELECTRICAL TESTS
RATING
C → GB → GA → G
PHASE to GROUND (MΩ)
C → AB → C
PHASE to PHASE (MΩ)
A → BC ↔ CB ↔ B
LINE to LOAD (MΩ)
A ↔ A
13. INSULATION RESISTANCE
500TEST Vdc
MIN (MΩ) 25
TEMP CORRECTED @ 20°C
A (µΩ) B (µΩ) RATING
0.807 2,196 1,266
△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)
SWITCHBLADES
FUSEHOLDERS
FUSES
R
1.2
14. CONTACT RESISTANCE
± 15 %
COMMENTS: All test results are in milliohms, not microohms.
DEFICIENCIES: B & C phases fail contact resistance.
TEST EQUIPMENT USED:
HUMIDITY 50 Building 1 Basement
SUBSTATION
DATE
Chiller Room POSITION Water Heater
5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION
TELEPHONE 469-394-8789
CUSTOMER
ADDRESS 7 Summit Drive; Canyon Texas USA 79015
S&B Services
OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901
Stephen Sanders
PAGE
JOB # STL24210-250
REPRESENTATIVE
7.5.1.1 LV AIR SWITCH
80 °F
NAMEPLATE DATA
MANUFACTURER
TYPE
CATALOG No.
SERIAL No.
SYSTEM VOLTAGE
POWER FUSE INFO
IMPULSE VOLTAGE
RATED VOLTAGE
Square D
Vac
N/A
240 Vac RATED CURRENT
MAX INTERRUPT
MISCELLANEOUS
Gould Shamut Amptrap II 80 Amps A2D80R
Amps200
10,000 Amps
LEGEND: A
VISUAL & MECHANICAL INSPECTION
C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE
CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING
1. NAMEPLATE COMPARABLE TO DWGS / SPECS
2. PHYSICAL / MECH. CONDITION
3. ANCHORAGE / ALIGNMENT & GROUNDING
4. OVERALL CLEANLINESS
5. CORRECT BLADE ALIGN. & PENETRATION
N/A
A
A
A
A
7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS
8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY
9. PHASE BARRIERS INSTALLED CORRECTLY
10. INDICATING / CONTROL DEVICE OPERATION
11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS
N/A
N/A
A
A
A
6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A
ELECTRICAL TESTS PERFORMED
Select tests not performed
INSULATION RESISTANCE CONTACT RESISTANCE
ELECTRICAL TESTS
RATING
C → GB → GA → G
PHASE to GROUND (MΩ)
C → AB → C
PHASE to PHASE (MΩ)
A → BC ↔ CB ↔ B
LINE to LOAD (MΩ)
A ↔ A
13. INSULATION RESISTANCE
500TEST Vdc
MIN (MΩ) 25
TEMP CORRECTED @ 20°C
A (µΩ) B (µΩ) RATING
0.004 0.005 0.004
△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)
SWITCHBLADES
FUSEHOLDERS
FUSES
A
0.0
14. CONTACT RESISTANCE
± 15 % 1,119 1,116 1,107 1,273.1
COMMENTS: All test results are in milliohms, not microohms.
DEFICIENCIES:
TEST EQUIPMENT USED:
HUMIDITY 50 Building 1 Basement
SUBSTATION
DATE
Fwd Bsmnt Condensate Pump Old Set POSITION Disconnect 1
5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION
TELEPHONE 469-394-8789
CUSTOMER
ADDRESS 7 Summit Drive; Canyon Texas USA 79015
S&B Services
OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901
Stephen Sanders
PAGE
JOB # STL24210-250
REPRESENTATIVE
7.5.1.1 LV AIR SWITCH
80 °F
NAMEPLATE DATA
MANUFACTURER
TYPE
CATALOG No.
SERIAL No.
SYSTEM VOLTAGE
POWER FUSE INFO
IMPULSE VOLTAGE
RATED VOLTAGE
General Electric
Vac
N/A
240 Vac RATED CURRENT
MAX INTERRUPT
MISCELLANEOUS
N/A
Amps30
10,000 Amps
LEGEND: A
VISUAL & MECHANICAL INSPECTION
C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE
CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING
1. NAMEPLATE COMPARABLE TO DWGS / SPECS
2. PHYSICAL / MECH. CONDITION
3. ANCHORAGE / ALIGNMENT & GROUNDING
4. OVERALL CLEANLINESS
5. CORRECT BLADE ALIGN. & PENETRATION
N/A
A
A
A
A
7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS
8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY
9. PHASE BARRIERS INSTALLED CORRECTLY
10. INDICATING / CONTROL DEVICE OPERATION
11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS
N/A
N/A
A
A
A
6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A
ELECTRICAL TESTS PERFORMED
Select tests not performed
INSULATION RESISTANCE CONTACT RESISTANCE
ELECTRICAL TESTS
RATING
C → GB → GA → G
PHASE to GROUND (MΩ)
C → AB → C
PHASE to PHASE (MΩ)
A → BC ↔ CB ↔ B
LINE to LOAD (MΩ)
A ↔ A
13. INSULATION RESISTANCE
500TEST Vdc
MIN (MΩ) 25
TEMP CORRECTED @ 20°C
A (µΩ) B (µΩ) RATING
0.817 1,299 0.643
△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)
SWITCHBLADES
FUSEHOLDERS
FUSES
R
1.0
14. CONTACT RESISTANCE
± 15 %
COMMENTS: All test results are in milliohms, not microohms.
DEFICIENCIES: B phase fails contact resistance.
TEST EQUIPMENT USED:
HUMIDITY 50 Building 1 Basement
SUBSTATION
DATE
Fwd Bsmnt Condensate Pump Old Set POSITION Disconnect 2
5/23/2024 %AMBIENT TEMPERATURE EQPT. LOCATION
TELEPHONE 469-394-8789
CUSTOMER
ADDRESS 7 Summit Drive; Canyon Texas USA 79015
S&B Services
OWNER VA Hospital - Facility Management; 1500 N Westwood Blvd.; Poplar Bluff Missouri USA 63901
Stephen Sanders
PAGE
JOB # STL24210-250
REPRESENTATIVE
7.5.1.1 LV AIR SWITCH
80 °F
NAMEPLATE DATA
MANUFACTURER
TYPE
CATALOG No.
SERIAL No.
SYSTEM VOLTAGE
POWER FUSE INFO
IMPULSE VOLTAGE
RATED VOLTAGE
General Electric
Vac
N/A
240 Vac RATED CURRENT
MAX INTERRUPT
MISCELLANEOUS
N/A
Amps30
10,000 Amps
LEGEND: A
VISUAL & MECHANICAL INSPECTION
C-CORRECTEDMD-MINOR DEFICIENCYR-REQUIRES REPAIRLEGEND: A-ACCEPTABLE N/S-NOT IN SCOPE N/A-NOT APPLICABLE
CONDITION CONDITION INSPECT THE FOLLOWINGINSPECT THE FOLLOWING
1. NAMEPLATE COMPARABLE TO DWGS / SPECS
2. PHYSICAL / MECH. CONDITION
3. ANCHORAGE / ALIGNMENT & GROUNDING
4. OVERALL CLEANLINESS
5. CORRECT BLADE ALIGN. & PENETRATION
N/A
A
A
A
A
7. FUSE SIZE & TYPES ARE IN ACCORDANCE TO DWGS / SPECS
8. FUSEHOLDER MECHANICAL SUPPORT / CONTACT INTEGRITY
9. PHASE BARRIERS INSTALLED CORRECTLY
10. INDICATING / CONTROL DEVICE OPERATION
11. LUBRICANT ON MOVABLE CURRENT CARRYING PARTS
N/A
N/A
A
A
A
6. CORRECT BLADE TRAVEL STOPS A 12. SAFETY INTERLOCKS A
ELECTRICAL TESTS PERFORMED
Select tests not performed
INSULATION RESISTANCE CONTACT RESISTANCE
ELECTRICAL TESTS
RATING
C → GB → GA → G
PHASE to GROUND (MΩ)
C → AB → C
PHASE to PHASE (MΩ)
A → BC ↔ CB ↔ B
LINE to LOAD (MΩ)
A ↔ A
13. INSULATION RESISTANCE
500TEST Vdc
MIN (MΩ) 25
TEMP CORRECTED @ 20°C
A (µΩ) B (µΩ) RATING
6,735 1,399 7,534
△CALC. MAX C (µΩ)TEST Amps MAX Δ % MFR MAX (µΩ)
SWITCHBLADES
FUSEHOLDERS
FUSES
R
2,098.5
14. CONTACT RESISTANCE
± 15 %
COMMENTS: All test results are in milliohms, not microohms.
DEFICIENCIES: A & B phases fails contact resistance.