657A4-21-800-Revised Drawings PL000 PL100 PL101 PL102 PD100 PD101.pdf
PDF 1 MB Posted
- Attached to
- Z2DA--657A4-21-800, TF - FCA - Remove and Replace End-of-Life HVAC Infrastructure Building 1
- Solicitation number
- 36C25525R0009
About this file
The provided file contains plumbing drawings for a renovation project at the John J. Pershing VA Medical Center in Poplar Bluff, Missouri. The technical drawings detail plumbing demolition and new plumbing installations across ground, first, and second floors, showing pipe routing, fixture locations, and mechanical system modifications. Specific plumbing elements include sanitary drainage, cold and hot water lines, vent pipes, and connections for various medical and administrative spaces such as dental laboratories, exam rooms, restrooms, and break areas.
The associated federal contract opportunity is a pre-solicitation for a Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside project valued between $10-20 million. The project involves removing and replacing end-of-life HVAC infrastructure in Building 1, specifically targeting the Laboratory Service HVAC System and AC 9 system across ground floor, dental, administrative, and laundry areas. The contract has a 900-calendar-day performance period, with the solicitation package expected to be available by December 9, 2024. The procurement will use a Best Value Lowest Price Technically Acceptable source selection process under NAICS code 236220.
View the file
Other files
Show all 29
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PLUMBING SYMBOL LIST
SYMBOL: DESCRIPTION:
PIPE SERVING FIXTURE ON FLOOR ABOVE
(EXAMPLE: FD = FLOOR DRAIN)FD
PITCH PIPE IN DIRECTION
RD-1
6"(1000)
ROOF DRAIN PROPERTIES SYMBOL
SIZE (ROOF SQ. FT.)
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)
GPM
CHECK VALVE
REDUCER - REFERENCE SPECIFICATION
FOR CONCENTRIC/ECCENTRIC AND FOT/FOB
METERM
ALIGNMENT GUIDE
PIPE ANCHOR
EXPANSION JOINT
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
ACID VENTAV
ACID WASTEAW
COLD WATER - POTABLECW
DT DRAIN TILE
SANITARY DRAINAGE (GREASE SANITARY DRAINAGE)GSAN
HOT WATER - POTABLEHW
HOT WATER CIRCULATING - POTABLEHWC
HOT WATER - POTABLE NUMBER INDICATES TEMPHW140
HOT WATER CIRC. - POTABLE NUMBER INDICATES TEMPHWC140
NON-POTABLE COLD WATERNCW
NON-POTABLE HOT WATERNHW
PUMPED DISCHARGEPD
SANITARY DRAINAGESAN
SOFT COLD WATERSCW
SOFT HOT WATERSHW
STORM DRAINAGE (ROOF SQUARE FOOTAGE)ST(1,000)
STS STORM DRAINAGE (SECONDARY)
VENTV
WASTE ANETHESIA GAS DISPOSALWAGD
GREASE VENTGV
COMPRESSED AIRCA
DEIONIZED WATERDI
PROPANE GASP
REVERSE OSMOSIS WATERRO
STW SOFT TEMPERED WATER
TW TEMPERED WATER
DRAIND
G NATURAL GAS
NOT ALL SYMBOLS MAY APPLY.
PRESSURE REDUCING VALVE (LIQUID/GAS)
FUEL OIL RETURNFOR
FUEL OIL SUPPLYFOS
LAB VACUUMVAC
SOLENOID VALVE
SAFETY/RELIEF VALVE
VACUUM BREAKER
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
TEMPERATURE SENSOR WITH WELL
T
THERMOMETER WITH WELL (DIAL TYPE)T
THERMOMETER WITH WELL (FILLED TYPE)
PUMP
GRV GAS REGULATOR VENT
INSTRUMENT AIRIA
MEDICAL AIRMA
MEDICAL VACUUMMV
NITROGENN
NITROUS OXIDENO
OXYGENO
PURE WATERPW
SERVICE WATER - POTABLEW
PIPE CONTINUATION
PRESSURE SENSOR (FURNISHED WITH BALL VALVE)P
ROUTE TO DRAIN
BACKFLOW PREVENTER
MEDIUM PRESSURE GASMPG
PLUMBING ABBREVIATION KEY
BATHTUBBT
CO CLEANOUT
CLINICAL SINKCS
DRINKING FOUNTAINDF
EMERGENCY EYEWASHEE
FLOOR CLEANOUTFCO
FLOOR DRAINFD
FLOOR SINKFS
GARBAGE DISPOSERGD
GREASE INTERCEPTORGI
HOSE BIBBHB
I.E. INVERT ELEVATION (FOR REFERENCE ONLY)
LAVATORYLAV
MOP BASINMB
MH MANHOLE
MIXING VALVEMV
NEUTRALIZATION TANKNT
OIL SEPARATOROS
ROOF DRAINRD
SHOWERSH
SINKSK
SERVICE SINKSS
TRENCH DRAINTD
TRAP PRIMERTP
URINALUR
WATER CLOSETWC
WALL CLEANOUTWCO
WASH FOUNTAINWF
WATER HEATERWH
WASHING MACHINE FIXTUREWMF
YARD CLEANOUTYCO
EMERGENCY SHOWERES
EMERGENCY SHOWER/EYEWASHESE
ELECTRIC WATER COOLEREWC
VENT THROUGH ROOFVTR
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
BFP BACKFLOW PREVENTER
NOT IN CONTRACTNIC
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS OTHERWISE NOTESUON
EXISTINGE
FLOW METERFM
WATER SOFTENERWS
WATER METERWM
DIALYSIS BOXDB
CATCH BASINCB
CAST IRONCI
DUCTILE IRONDI
UTILITY BOXUB
SHORT CIRCUIT CURRENT RATINGSCCR
NOT ALL SYMBOLS MAY APPLY.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
TEMPERATURE CONTROLS CONTRACTORT.C.C.
CIVIL CONTRACTORC.C.
FIRE PROTECTION CONTRACTORF.P.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
ELECTRICAL CONTRACTORE.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
NOT ALL SYMBOLS MAY APPLY.
MECHANICAL PHASING NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF PHASES. REFER TO
ARCHITECT'S INSTRUCTIONS FOR MORE DETAILS AND PHASING SCHEDULES AND FOR
CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT
THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY
DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF
THE PHASING CRITERIA.
2. REVIEW PROJECT PHASING PLANS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC.
WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE
ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF
PROJECT.
4. INSTALL TEMPORARY DUCTWORK, PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP
ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
6. BASIC TIMELINE OF WORK WOULD BE ALL LAB WORK FIRST, TEMPORARY AC9/PLATFORM
WORK; AC9 UNIT AND DENTAL UNIT WORK ONLY; ALL REMAINING DENTAL WORK; AC9
DUCTWORK MAINS TO FLOORS; THEN AC9 DUCTWORK FROM THE MAIN POINTS TO EACH
FLOOR TO THE END DEVICES.
7. TESTING AND BALANCING FOR ALL AFFECTED INLETS, OUTLETS, AND SYSTEMS SHALL
OCCUR AT THE COMPLETION OF EACH PHASE OF THE PROJECT. A COMPLETE SYSTEM TEST
AND BALANCE SHALL OCCUR AT THE COMPLETION OF THE PROJECT.
MECHANICAL GENERAL NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE
DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS.
DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC.,
AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE
INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING
CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM
ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR
PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE
CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO
VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO
VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES
OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING
WITH FABRICATION OR EQUIPMENT ORDERS.
4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE
REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER
ACCESS.
5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO
COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR
EXPENSE TO OTHERS.
6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL
CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF
DESIGN.
7. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY
AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING
MOUNTED DEVICES, OTHER THAN SPRINKLERS.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
9. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE
GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE
PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS
PANELS PRIOR TO BIDDING.
10. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING,
AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE
SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER
FOR OUTDOOR USE.
11. CAULK ALL PIPE AND DUCT PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL,
PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE
TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS
WITHIN ROOMS.
12. WHERE PIPES AND DUCTS ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED
OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL
RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
13. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT
MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND
REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS,
PIPING, DUCTWORK, ETC.
14. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES.
15. MAINTAIN A MINIMUM WORKING CLEARANCE OF 3’-6” IN FRONT OF ALL ELECTRICAL
EQUIPMENT REQUIRING MAINTENANCE, INSPECTION, AND TESTING INCLUDING BUT NOT
LIMITED TO PANELS, DISTRIBUTION PANELS, SWITCHBOARDS, MOTOR CONTROL CENTERS,
TRANSFORMERS, EQUIPMENT DISCONNECTS AND STARTERS.
16. MAINTAIN THE DEDICATED ELECTRICAL EQUIPMENT SPACE DEFINED BY THE WIDTH / DEPTH
OF ELECTRICAL EQUIPMENT MEASURED FROM THE FLOOR TO A HEIGHT 6’-0” ABOVE THE
EQUIPMENT OR THE STRUCTURAL CEILING, WHICHEVER IS LOWER. SYSTEMS FOREIGN TO
THE ELECTRICAL DISTRIBUTION SYSTEM ARE NOT ALLOWED IN THE DEDICATED
ELECTRICAL SPACE INCLUDING; DUCTWORK, PIPING, ETC.
17. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL
EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.
18. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE
CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
MECHANICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE PROTECTION, PLUMBING, VENTILATION, PIPING AND TEMPERATURE CONTROL.
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND
REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING DUCTWORK AND PIPING IS SHOWN. VERIFY EXISTING CONDITIONS
BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE
FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD
CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF THEIR WORK AND
SHALL NOTIFY THE ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE
REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO THEIR AREA OF WORK.
5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED
WITH THEIR WORK.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL
CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH
NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL
EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT
DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL
SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING
CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLATIONS THAT
REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY
REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW
SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR
TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND
CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY
DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT
THAT HAS BEEN REMOVED.
12. REMOVE ALL PIPING SHOWN TO BE REMOVED OR FOUND TO BE ABANDONED BACK TO THE
NEAREST MAIN AND CAPPED. NO DEAD LEGS SHALL BE PERMITTED.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR.
CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR
FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO
PLUMBING FIXTURES.
3. FOR CLARITY, NOT ALL VALVES HAVE BEEN SHOWN. PROVIDE SHUTOFF VALVES IN
DOMESTIC WATER PIPING SERVING EACH ROOM WITH FIXTURES. ANGLE STOPS SHALL NOT
BE CONSIDERED SHUTOFF VALVES.
4. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL
SCOPE OF ITEMS TO BE REMOVED. REFER TO SPECIFICATION SECTION 22 05 05 FOR
ADDITIONAL DEMOLITION INFORMATION.
5. P.C. SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK
UNLESS NOTED OTHERWISE. REFER TO SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL
INFORMATION.
PLUMBING GENERAL NOTES:
SMOKE PARTITION
FIRE / SMOKE BARRIER DESIGNATIONS
1-HOUR FIRE BARRIER
2-HOUR FIRE BARRIER
THE LINE TYPES SHOWN ARE FOR THE CONVENIENCE OF THE CONTRACTOR. THE CONTRACTOR
SHALL VERIFY RATINGS WITH THE LATEST SET OF ARCHITECTURAL PLANS AND FURNISH ALL
MATERIALS REQUIRED TO COMPLY WITH THOSE RATINGS WHETHER SHOWN OR NOT.
ALL FLOOR, FLOOR CEILING, AND ROOF CEILING ASSEMBLIES SHALL BE DESIGNATED AS 1, 2
HOUR FIRE /SMOKE, BARRIER(S), UNLESS NOTED OTHERWISE ON THE PLANS. RATINGS WERE
ACQUIRED FROM THE ARCHITECTURAL PLANS DATED 08/30/2024.
INSTALL AN ESCUTCHEON AROUND PIPES
EXPOSED IN FINISHED ROOMS. IN SUCH
INSTANCES WHERE AN ESCUTCHEON IS
REQUIRED AND THE PIPING IS INSULATED,
INSTALL A PLASTIC JACKET EXTENDING 6"
BEYOND THE WALL TO PROTECT INSULATION
FROM DAMAGE FROM THE ESCUTCHEON.
MAKE A SMOOTH ROUND OPENING IN
WALL SLIGHTLY LARGER THAN OUTSIDE
DIAMETER OF THE PIPE AND INSULATION.
ADD A BEAD OF NON-HARDENING
CAULK IN THE ANNULAR SPACE.
NOTES:
1. THIS DETAIL APPLIES TO ALL PIPES. THE INTENTION IS TO CONTINUE THE INSULATION AND
VAPOR BARRIER THROUGH ALL PENETRATIONS. PERMIT THERMAL EXPANSION WITHOUT
DAMAGING INSULATION, AND TO SEAL AIRTIGHT AROUND INSULATED AND UNINSULATED PIPES
FOR NOISE TRANSMISSION CONTROL.
2. SEE SPECIFICATION FOR ADDITIONAL INFORMATION.
3. FLOOR OPENINGS ARE SIMILAR, SEE SPECIFICATION FOR DIFFERENCES BETWEEN FLOOR AND
WALL PENETRATIONS.
FIRE SEALANT
FIRE SEALANT
NOTE 2
NOTE 3
PENETRATING ITEM
NOTE 4
NOTE 3
NOTE 4
PENETRATING ITEM
NOTE 2
NOTE 3
RATED WALL
(CONSTRUCTION
VARIES)
RATED FLOOR
(CONSTRUCTION
VARIES)
NOTES:
1. THIS GENERAL DETAIL APPLIES TO ALL ITEMS PENETRATING FIRE RATED WALLS OR FLOORS. THE INTENT IS TO MAINTAIN THE FIRE RATING AND TO ALLOW LONGITUDINAL MOVEMENT. REFER TO SPECIFICATION FOR SELECTION OF THROUGH
PENETRATION FIRE STOPPING.
2. SCHEDULE 5 PIPE SLEEVE EMBEDDED IN WALL OR FLOOR, OR SMOOTH CORE DRILL. EACH CONTRACTOR FURNISHES SLEEVE TO G.C., COORDINATES SLEEVE LOCATIONS AND DEBURS SLEEVE. G.C. BUILDS SLEEVE INTO WALL OR FLOOR ALLOWING NO GAP AROUND SLEEVE. IF SLEEVE IS NOT PROVIDED WHEN WALL OR FLOOR IS BUILT, CONTRACTOR SHALL INSTALL SLEEVE.
SLEEVE SIZE SHALL ALLOW ANNULAR SPACE REQUIRED BY THE SELECTED FIRE STOP SYSTEM.
3. INSTALL BACKING MATERIAL, SUCH AS MINERAL WOOL SAFING, AS REQUIRED FOR FIRE STOP SYSTEM. INSTALL IN ACCORDANCE WITH FIRE STOP SYSTEM APPLICATION LISTING. SECURE TO WALL OR FLOOR TO ALLOW LONGITUDINAL
MOVEMENT OF PENETRATING ITEM WITHOUT MOVEMENT OF FIRE BARRIER.
4. WATERTIGHT WELDED 1"x1" 20 GAUGE MINIMUM GALVANIZED SHEET METAL ANGLE FRAME, BY CONTRACTOR IN EQUIPMENT ROOMS FOR WATER STOP. PLACE A BEAD OF WATERPROOF SEALANT BETWEEN FLOOR AND BOTTOM OF ANGLE FRAME.
SECURE TO FLOOR WITH MASONRY ANCHORS IN CORNERS AND ON 12" MAXIMUM CENTERS. MULTIPLE PENETRATING ITEMS
MAY BE ENCLOSED IN ONE FRAME.
VENT PIPE
WATER CUTOFF MASTIC
PRE MOLDED PIPE SEAL
SPLICING CEMENT
LAP SEALANT
METAL ROOF DECK
INSULATION, SEE SPECIFICATIONS.CONCRETE ROOF
DECK
INSULATION
STAINLESS STEEL
CLAMPING RING
BALLAST
EPDM
MEMBRANE
NOTES:
1. VENT PIPE SHALL BE A MINIMUM OF 4" DIAMETER UNLESS NOTED LARGER
ON FLOOR PLANS. INCREASERS, IF REQUIRED TO TRANSITION TO THE
LARGER VTR SIZE, MUST BE INSTALLED AT LEAST 12 INCHES BELOW THE
THERMAL ENVELOPE OF THE BUILDING.
2. EXTEND VENT PIPE AT LEAST 7 FEET ABOVE ROOF LEVEL WHEN ROOF
AREA IS INTENDED TO BE USED BY THE GENERAL PUBLIC. THIS INCLUDES
PROMENADES, OBSERVATION DECKS, ETC. THIS IS NOT REQUIRED FOR
ROOFS THAT ARE ACCESSIBLE BY MAINTENANCE PERSONEL ONLY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
657A4-21-800REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATON, AND
AIR CONDITIONING
BID DOCUMENTS
JOHN J. PERSHING VETERANS' ADMINISTRATION
MEDICAL CENTER 1500 N. WESTWOOD BLVD. POPLAR
BLUFF, MO 63901-3318
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
A u to d e s k D o c s /2
-1
A
-2
-3
V A
P o p la r B lu ff
R e m o v e a n d R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.M
E P
T
R
.1
R e p l L a b A
H U
A
H U
C .r v t
/1
/2
:4
:4
A
M
PL000
PLUMBING COVERSHEET
GORPAT BHAACH
08/30/2024
NO SCALE
WALL PENETRATION - NON-FIRE RATED
1 NO SCALE
FLOOR/WALL PENETRATION - RATED FIRE BARRIER
NO SCALE
VENT PIPE FLASHING
P-709 EMERGENCY EYE WASH [ ] 0.75 [ 19 ] 0.75 [ 19 ] 4 N/A NO PEDESTAL/DECK MOUNTED
P-707
FREE STANDING EMERGENCY
SHOWER/EYE/FACE WASH
2 [ 50 ] 1.5 [ 38 ] 0.75 [ 19 ] 0.75 [ 19 ] 3 4 N/A NO
P-528 EXAM SINK 2 [ 50 ] 1.5 [ 38 ] 0.75 [ 19 ] 0.75 [ 19 ] 3 4 NO NO FOOT CONTROL WITH GOOSENECK SPOUT.
P-527 BREAK ROOM SINK 2 [ 50 ] 1.5 [ 38 ] 0.75 [ 19 ] 0.75 [ 19 ] 3 4 YES NO WRIST BLADES HANDLE WITH GOOSENECK SPOUT FAUCET
IN [mm] IN [mm] IN [mm] IN [mm]
MARK DESCRIPTION
WASTE PIPE VENT PIPE COLD WATER HOT WATER WASTE
FIXTURE
UNITS
WATER
FIXTURE
UNITS
WRIST BLADE
HANDLES
ELECTRIC
SENSOR
REMARKS
PLUMBING FIXTURE SCHEDULE
Revisions: Date:
Addendum No.1 13 MAR 25
1 1
T
CORRIDOR
GE-C01
STORAGE
GE-068
LAUNDRY
GE-066
STAFF RESTROOM
GE-065
LAUNDRY
GE-070
OFFICE
GE-063
RM
GE-064
CORRIDOR
GE-C02
OFFICE
GE-068A
SUPPLY
GA-059
CORRIDOR
GA-C02
CLOSET
GA-058
MORGUE
GA-072
LOCKER RM., M
GA-056
REST ROOM
GA-075 EMS
GA-073
STORAGE
GA-076
RESTROOM/SHOWER, M
GA-055
LINEN CHUTE
GA-078
RESTROOM/SHOWER, F
GA-079
RESTROOM, F
GA-079A
CREDIT UNION
GA-080 ELECTRICAL ROOM
GA-081
LOCKER RM F
GA-077
OFFICE
GE-062
SERVER ROOM
GA-054
STAIR E
1E-S01
OFFICE
GA-077A
"V
A C
2"VAC
2" VAC
1 1/2"SAN
4"SAN
2 1/2"V
2"CW
1 1/2"HW
3/4"HWC
1 1/2"V
2"SAN
3/4"CW
3/4"HWC
1"HW
2"CW
2 1/2"V
3/4"HWC
1 1/4"HW
2"CW
2 1/2"V
4"SAN
1 1/2"CW
4"SAN
2"V
2"SAN
3/4"CW
3/4"HW
3/4"HWC
2"SAN
3/4"CW
3/4"CW
3/4"HW
3/4"HWC
4"SAN
4"SAN
3/4"VAC3/4"VAC
4"ST
3"ST
"S
T
4"ST
3/4"CW
4"ST
4"ST
3"ST
2"CW
1 1/2"HW
3/4"HWC
4"SAN
2"V
3/4"CW
3/4"CW
1/2"CW
1/2"HW
1 1/2"SAN
1/2"CW
1/2"HW
1 1/2"SAN
1 1/2"V
4"ST
4"ST
4"ST
4"ST
2"V
2"V
3"V
3" V UP TO
VTR
4" V UP TO VTR
4"V
"V
3"V
EWC-E
SK-E
2"V
3/4"CW
3/4"HW
4" V UP TO VTR
3/4"V
P-89-E
P-66-E
P-1-E P-35-E
P-39-E
P-66-E
P-69-E
P-69-E
VS-10-E
P-82-E
P-35-E
P-35-E
P-1-E
P-1-E P-66-E
P-66-E
P-1-E
P-1-E
P-35-E
P-66-E
P-66-E
P-89-E
P-89-E
P-66-E
P-66-E
P-1-E
P-1-E
P-1-E
P-35-E
P-35-E
P-30-E
4"ST
3/4"V
3/4"CW
2"V
4"ST
4"SAN
4"ST
1 1/2"HWC
3/4"HW
3/4"CW
1"CW
1"HW
3/4"HWC
3"SAN
2"V
4"SAN
3/4"HWC
1 1/2"HW
2"CW
3/4"HWC
3/4"HW
1 1/2"CW
2"VAC
4"SAN
2"V
2"CW
1"HW
3/4"HWC
2"V
2"V
WC-E
3/4"HWC
1"HW
/2
"A V
3"V
REMOVE PIPING IN GROUND FLOOR
CEILING PLENUM FROM WITHIN 6" OF
SLAB ABOVE TO APPROXIMATELY 6"
ABOVE CEILING. PIPING TO BE
RELOCATED AS REQUIRED FOR DUCT
INSTALLATION. COORDINATE WITH
MECHANICAL CONTRACTOR.
(TYPICAL)
4"V
1/2"HW
1/2"CW
REMOVE PIPE AS INDICATED
AND PREPARE FOR NEW
CONNECTION.
REMOVE PIPE AS INDICATED
AND PREPARE FOR NEW
CONNECTION.
FD-E
FD-E
FD-E
WMF-E WMF-E
EE-E
FD-EFD-E FS-E
L-E
FD-E
REMOVE AS INDICATED AND
PREPARE FOR NEW
CONNECTION (TYPICAL)
2" V DN
FD-E
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
657A4-21-800REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATON, AND
AIR CONDITIONING
BID DOCUMENTS
JOHN J. PERSHING VETERANS' ADMINISTRATION
MEDICAL CENTER 1500 N. WESTWOOD BLVD. POPLAR
BLUFF, MO 63901-3318
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
E
Aw
F
D
Ac Ae
C
B
KEY PLAN
A u to d e s k D o c s /2
-1
A
-2
-3
V A
P o p la r B lu ff
R e m o v e a n d R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.M
E P
T
R
.1
R e p l L a b A
H U
A
H U
C .r v t
/1
/2
:4
:3
A
M
PD100
GROUND FLOOR - PLUMBING
DEMOLITION
GORPAT BHAACH
08/30/2024
N O R
HT
1/8" = 1'-0"
GROUND FLOOR - PLUMBING DEMOLITION
Revisions: Date:
DENTAL LABORATORY
1E-129
OFFICE
1E-116
TREATMENT ROOM
1E-130A
ORAL SURGERY
1E-114
DENTAL TREATMENT
1E-113
TREATMENT ROOM
1E-130
DENTAL IMAGING
1E-131
DENTAL IMAGING
1E-132
CLERKS OFFICE
1E-111
BREAK ROOM
1E-112
DENTAL WAITING ROOM
1E-110
ELECTRICAL CLOSET
1E-110B
COMPRESSOR
1A-109
EXAM ROOM/DOCTOR OFFICE
1A-108
MY HEALTH VET OFFICE
1A-107
BREAK ROOM
1A-106 BUSINESS
1A-105
BUSINESS
1A-104 PATIENT REP QM
1A-103
RELEASE OF INFORMATION
1A-102
MEDICAL RECORDS
1A-101
ADMISSIONS
1A-142
PATIENT EDUCATION
1A-144
SOILED LINEN/CLSOET
1A-147
RESTROOM, F
1F-149
ELECTRICAL CLOSET
1A-1
MEDICATION ROOM
1F-150 EXAM
1F-167
RESTROOM, M
1F-169
CLOSET
1F-168
HOLDING AREA
1A-170
OFFICE OF PATIENT ADVOCATE
1A-171 VETERANS EXPERIENCE OFFICER
1A-172
MAIL ROOM
1A-173
CORRIDOR E
1E-C01
CLOSET
1E-115A
CLOSET
1E-115
STAIR E
1E-S01
STAIRWELL 3
1A-S03
WEST ENTRY EMPLOYEE ENTRANCE
VESTIBULE
1A-C05A
WEST ENTRY PUBLIC ENTRANCE
VESTIBULE
1A-C05
3/4"CW
3/4"CW
3/4"V
4"SAN
4"ST
4"SAN
4"ST
4"ST
2"SAN
3/4"CW
3/4"HW
3/4"HWC
2"VAC3/4"HWC
1"HW
1 1/2"CW
4"SAN
2"V
4"ST
4"SAN
2"V
1 1/2"SAN
4"SAN
3/4"CW
3/4"CW
1 1/2"V
2"SAN
2 1/2"V
4"ST
2"CW
1 1/2"HW
3/4"HWC
4"ST
2 1/2"V
1/2"HW
1/2"CW
3/4"CW
1 1/2"SAN
1/2"CW
1/2"HW
3/4"CW
3/4"CW
2"CW
1 1/2"HW
3/4"HWC
4"SAN
2"V
2"V
3"ST
4"ST
4"ST
4"ST
P-66-E P-58-E P-1-E
P-1-E
3/4"HWC
3/4"HW
3/4"CW
2"SAN
1"CW
1"HW
3/4"HWC
3"SAN
3"ST
2"CW
1 1/2"HW
3/4"HWC
4"SAN
2"V
3/4"HW
3/4"CW
4"ST
4"SAN
2 1/2"V
4"ST
2"CW
1 1/4"HW
3/4"HWC
2"SAN
3/4"HW
1"G
P-66-E P-89-E
P-1-E
4"SAN
3/4"HWC
1 1/2"HW
2"CW
4"ST
2 1/2"V
3/4"V
P-1-EP-1-E
P-89-E P-66-E
P-66-E
3/4"HWC
1"HW
2"CW
4"ST
3/4"VAC
4"V
P-1-E
P-89-E
P-66-E 1 1/2"V
3" VTR
2"CW
1"HW
3/4"HWC
3/4"CW
3/4"HWC
3/4"HW
3/4"CW
2"SAN
REMOVE PIPING FROM WITHIN 6" OF
SLAB ABOVE TO APPROXIMATELY 6"
ABOVE CEILING. PIPING TO BE
RELOCATED AS REQUIRED FOR DUCT
INSTALLATION. COORDINATE WITH
MECHANICAL CONTRACTOR.
(TYPICAL)
4" VTR
4" VTR
4" VTR
REMOVE 4" VTR AND REFER TO
PL101 SHEET FOR NEW LOCATION.
REFER TO ARCHITECTURAL FOR
PATCHING.
REMOVE 4" VTR AND REFER TO
PL101 SHEET FOR NEW LOCATION.
REFER TO ARCHITECTURAL FOR
PATCHING.
REMOVE PIPING FROM WITHIN 6" OF
SLAB ABOVE TO APPROXIMATELY 6"
ABOVE CEILING. PIPING TO BE
RELOCATED AS REQUIRED FOR DUCT
INSTALLATION. COORDINATE WITH
MECHANICAL CONTRACTOR. (TYPICAL)
REMOVE PIPING FROM WITHIN 6" OF
SLAB ABOVE TO APPROXIMATELY 6"
ABOVE CEILING. PIPING TO BE
RELOCATED AS REQUIRED FOR DUCT
INSTALLATION. COORDINATE WITH
MECHANICAL CONTRACTOR. (TYPICAL)
1 1/2"HWC
2"SAN
2"SAN
3/4"HWC
2"HW
2"CW
2"V
4"SAN
PATIENT EDUCATION
1A-144
SOILED LINEN/CLSOET
1A-147
RESTROOM, F
1F-149
MEDICATION ROOM
1F-150
BUSINESS OFFICE
1F-152
EXAM
1F-153
EXAM
1F-154
OEF/OIF CASE MANAGER
1F-155
CHECK IN/WAITING
1F-156
EXAM
1F-157
RESTROOM, F
1F-158
EXAM
1F-159
STAFF WORK ROOM
1F-160
STERILE
1F-161 RESTROOM
1F-162
CAREGIVER SUPPORT/RN ASSESSOR
1F-165
WAITING ROOM
1F-166
EXAM
1F-167
CLOSET
1F-168
HOLDING AREA
1A-170
C&P CHECK IN
1F-163
ELEC. CLOSET
1F-166A
BUSINESS OFFICE
1F-151
CORRIDOR F
1F- CC
STAIRWELL F
1F-S01
STAIRWELL
1F-S02
4"SAN
1 1/2"CW
1"HW
3/4"HWC
4"SAN
1 1/2"CW
3/4"HWC
3/4"HW
4"ST
1 1/2"CW
3/4"HW
3/4"HWC
4"SAN
4"ST
3/4"V
3/4"HWC
1"HW
1 1/4"CW
4"SAN
4"ST
3/4"HWC
P-65-E
P-1-E
1"HW
1 1/4"CW
2"V
4"SAN
4"SAN
1 1/4"CW
1"HW
3/4"HWC
3/4"V
3"ST
3"ST
4"ST
2 1/2"V
3/4"HWC
1"HW
2"CW
3/4"HWC
1"HW
1 1/2"CW
4"SAN
3/4"V
4"ST
4"SAN
3/4"HWC
1"HW
1 1/4"CW
REMOVE PIPING FROM WITHIN 6" OF
SLAB ABOVE TO APPROXIMATELY 6"
ABOVE CEILING. PIPING TO BE
RELOCATED AS REQUIRED FOR DUCT
INSTALLATION. COORDINATE WITH
MECHANICAL CONTRACTOR. (TYPICAL)
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
657A4-21-800REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATON, AND
AIR CONDITIONING
BID DOCUMENTS
JOHN J. PERSHING VETERANS' ADMINISTRATION
MEDICAL CENTER 1500 N. WESTWOOD BLVD. POPLAR
BLUFF, MO 63901-3318
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
E
Aw
F
D
Ac Ae
C
B
KEY PLAN
A u to d e s k D o c s /2
-1
A
-2
-3
V A
P o p la r B lu ff
R e m o v e a n d R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.M
E P
T
R
.1
R e p l L a b A
H U
A
H U
C .r v t
/1
/2
:4
:3
A
M
PD101
FIRST FLOOR - PLUMBING
DEMOLITION
GORPAT BHAACH
08/30/2024
N O R
HT
1/8" = 1'-0"
FIRST FLOOR - PLUMBING DEMOLITION
N O R
HT
1/8" = 1'-0"
FIRST FLOOR SOUTH WEST - PLUMBING DEMOLITION
TT
CORRIDOR
GE-C01
STORAGE
GE-068
LAUNDRY
GE-066
STAFF RESTROOM
GE-065
LAUNDRY
GE-070
OFFICE
GE-063
RM
GE-064
CORRIDOR
GE-C02
OFFICE
GE-068A
SUPPLY
GA-059
CORRIDOR
GA-C02
CLOSET
GA-058
MORGUE
GA-072
LOCKER RM., M
GA-056
REST ROOM
GA-075 EMS
GA-073
STORAGE
GA-076
RESTROOM/SHOWER, M
GA-055
LINEN CHUTE
GA-078
RESTROOM/SHOWER, F
GA-079
RESTROOM, F
GA-079A
CREDIT UNION
GA-080 ELECTRICAL ROOM
GA-081
LOCKER RM F
GA-077
OFFICE
GE-062
SERVER ROOM
GA-054
STAIR E
1E-S01
OFFICE
GA-077A
2" VAC
1 1/2"SAN
4"SAN
2 1/2"V
2"CW
1 1/2"HW
3/4"HWC
1 1/2"V
2"SAN
3/4"CW
2 1/2"V
3/4"HWC
1 1/4"HW
2"CW
2 1/2"V
4"SAN
1 1/2"CW
4"SAN
2"V
2"SAN
3/4"CW
3/4"HW
3/4"HWC
2"SAN
3/4"CW
3/4"CW
3/4"HW
3/4"HWC
4"SAN
4"SAN
3/4"VAC
4"ST
3"ST
4"ST
3/4"CW
4"ST
4"ST
3"ST
2"CW
1 1/2"HW
3/4"HWC
4"SAN
2"V
3/4"CW
3/4"CW
1/2"CW
1/2"HW
1 1/2"SAN
1/2"CW
1/2"HW
1 1/2"SAN
1 1/2"V
4"ST
4"ST
4"ST
4"ST
3" V UP TO
VTR
4" V UP TO VTR
4"V
"V
3"V
3/4"CW
3/4"HW
3/4"V
P-89-E
P-66-E
P-1-E P-35-E
P-39-E
P-66-E
P-69-E
P-69-E
VS-10-E
P-82-E
P-35-E
P-35-E
P-1-E
P-1-E P-66-E
P-66-E
P-1-E
P-1-E
P-35-E
P-66-E
P-66-E
P-89-E
P-89-E
P-66-E
P-66-E
P-1-E
P-1-E
P-1-E
P-35-E
P-35-E
P-30-E
4"ST
3/4"V
3/4"CW
2"V
4"ST
4"SAN
4"ST
1 1/2"HWC
3/4"HW
3/4"CW
1"CW
1"HW
3/4"HWC
3"SAN
2"V
4"SAN
3/4"HWC
1 1/2"HW
2"CW
3/4"HWC
3/4"HW
1 1/2"CW
2"VAC
4"SAN
2"V
2"CW
1"HW
3/4"HWC
2"V
WC-E
3/4"HWC
1"HW
3"V2"V
"V
2"V
4"V
1/2"HW
1/2"CW
"V
"V
3"ST
3/4"HWC
1"HW
2"CW
WMF-E WMF-E
EE-E
L-E
FD-E
FD-EFS-EFD-E
FD-E
EWC-E
SK-E
FD-E
FD-E FD-E
/2
"A V
2" V DN
2"V
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
657A4-21-800REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATON, AND
AIR CONDITIONING
BID DOCUMENTS
JOHN J. PERSHING VETERANS' ADMINISTRATION
MEDICAL CENTER 1500 N. WESTWOOD BLVD. POPLAR
BLUFF, MO 63901-3318
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
E
Aw
F
D
Ac Ae
C
B
KEY PLAN
A u to d e s k D o c s /2
-1
A
-2
-3
V A
P o p la r B lu ff
R e m o v e a n d R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.M
E P
T
R
.1
R e p l L a b A
H U
A
H U
C .r v t
/1
/2
:4
:4
A
M
PL100
GROUND FLOOR - PLUMBING
GORPAT BHAACH
08/30/2024
N O R
HT
1/8" = 1'-0"
GROUND FLOOR - PLUMBING
DENTAL LABORATORY
1E-129
OFFICE
1E-116
TREATMENT ROOM
1E-130A
ORAL SURGERY
1E-114
DENTAL TREATMENT
1E-113
TREATMENT ROOM
1E-130
DENTAL IMAGING
1E-131
DENTAL IMAGING
1E-132
CLERKS OFFICE
1E-111
BREAK ROOM
1E-112
DENTAL WAITING ROOM
1E-110
ELECTRICAL CLOSET
1E-110B
COMPRESSOR
1A-109
EXAM ROOM/DOCTOR OFFICE
1A-108
MY HEALTH VET OFFICE
1A-107
BREAK ROOM
1A-106 BUSINESS
1A-105
BUSINESS
1A-104 PATIENT REP QM
1A-103
RELEASE OF INFORMATION
1A-102
MEDICAL RECORDS
1A-101
ADMISSIONS
1A-142
PATIENT EDUCATION
1A-144
SOILED LINEN/CLSOET
1A-147
RESTROOM, F
1F-149
ELECTRICAL CLOSET
1A-1
RESTROOM, M
1F-169
CLOSET
1F-168
HOLDING AREA
1A-170
OFFICE OF PATIENT ADVOCATE
1A-171 VETERANS EXPERIENCE OFFICER
1A-172
MAIL ROOM
1A-173
CORRIDOR E
1E-C01
CLOSET
1E-115A
CLOSET
1E-115
STAIR E
1E-S01
STAIRWELL 3
1A-S03
WEST ENTRY EMPLOYEE ENTRANCE
VESTIBULE
1A-C05A
WEST ENTRY PUBLIC ENTRANCE
VESTIBULE
1A-C05
4"SAN
4"ST
4" VTR
4"SAN
4"ST
4"ST
2"SAN
3/4"CW
3/4"HW
3/4"HWC
3/4"HWC
1"HW
1 1/2"CW
4"SAN
2"V
4"ST
4"SAN
2"V
1 1/2"SAN
4"SAN
3/4"CW
3/4"CW
1 1/2"V
2"SAN
2 1/2"V
4"ST
2"CW
1 1/2"HW
3/4"HWC
4"ST
2 1/2"V
1/2"HW
1/2"CW
3/4"CW
1 1/2"SAN
1/2"CW
1/2"HW
3/4"CW
3/4"CW
2"CW
1 1/2"HW
3/4"HWC
4"SAN
2"V
2"V
3"ST
4"ST
4"ST
4"ST
P-66-E P-58-E P-1-E
P-1-E
3/4"HWC
3/4"HW
3/4"CW
2"SAN
1"CW
1"HW
3/4"HWC
3"SAN
3"ST
2"CW
1 1/2"HW
3/4"HWC
4"SAN
2"V
3/4"HW
3/4"CW
4"ST
4"SAN
2 1/2"V
4"ST
2"CW
1 1/4"HW
3/4"HWC
2"SAN
3/4"HW
1"G
P-66-E P-89-E
P-1-E
4"SAN
3/4"HWC
1 1/2"HW
2"CW
4"ST
2 1/2"V
3/4"V
P-1-EP-1-E
P-89-E P-66-E
P-66-E
3/4"HWC
1"HW
2"CW
P-1-E
P-89-E
P-66-E 1 1/2"V
3" VTR
2"CW
1"HW
3/4"HWC
3/4"CW
4"ST
3/4"VAC
4"V
4" VTR
AREA
DRAIN
2"SAN
2"SAN
2"CW
1 1/2"HW
3/4"HWC
4"SAN
2"V
3/4"HWC
2"HW
2"CW
2"V
4"SAN
3/4"V
3/4"CW
3/4"CW
3/4"HWC
3/4"HW
3/4"CW
2"SAN
3"SAN
3"SAN
1"CW
3/4"HW
SOILED LINEN/CLSOET
1A-147
RESTROOM, F
1F-149
MEDICATION ROOM
1F-150
BUSINESS OFFICE
1F-152
EXAM
1F-153
EXAM
1F-154
OEF/OIF CASE MANAGER
1F-155
CHECK IN/WAITING
1F-156
EXAM
1F-157
RESTROOM, F
1F-158
EXAM
1F-159
STAFF WORK ROOM
1F-160
STERILE
1F-161 RESTROOM
1F-162
CAREGIVER SUPPORT/RN ASSESSOR
1F-165
WAITING ROOM
1F-166
EXAM
1F-167
CLOSET
1F-168
HOLDING AREA
1A-170
C&P CHECK IN
1F-163
ELEC. CLOSET
1F-166A
BUSINESS OFFICE
1F-151
CORRIDOR F
1F- CC
STAIRWELL F
1F-S01
STAIRWELL
1F-S02
4"SAN
1 1/2"CW
1"HW
3/4"HWC
4"SAN
1 1/2"CW
3/4"HWC
3/4"HW
4"ST
1 1/2"CW
3/4"HW
3/4"HWC
4"SAN
4"ST
3/4"V
3/4"HWC
1"HW
1 1/4"CW
4"SAN
4"ST
3/4"HWC
P-65-E
P-1-E
1"HW
1 1/4"CW
2"V
4"SAN
4"SAN
1 1/4"CW
1"HW
3/4"HWC
3/4"V
3"ST
3"ST
4"ST
2 1/2"V
3/4"HWC
1"HW
2"CW
3/4"HWC
1"HW
1 1/2"CW
4"SAN
3/4"V
4"ST
4"SAN
3/4"HWC
1"HW
1 1/4"CW
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
657A4-21-800REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATON, AND
AIR CONDITIONING
BID DOCUMENTS
JOHN J. PERSHING VETERANS' ADMINISTRATION
MEDICAL CENTER 1500 N. WESTWOOD BLVD. POPLAR
BLUFF, MO 63901-3318
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
E
Aw
F
D
Ac Ae
C
B
KEY PLAN
A u to d e s k D o c s /2
-1
A
-2
-3
V A
P o p la r B lu ff
R e m o v e a n d R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.M
E P
T
R
.1
R e p l L a b A
H U
A
H U
C .r v t
/1
/2
:4
:5
A
M
PL101
FIRST FLOOR - PLUMBING
GORPAT BHAACH
08/30/2024
N O R
HT
1/8" = 1'-0"
FIRST FLOOR - PLUMBING
N O R
HT
1/8" = 1'-0"
FIRST FLOOR SOUTH WEST - PLUMBING
RECORDS/SUPPLY STORAGE
2A-036
LAB SUPPLY ROOM
2A-037
CULTURE ROOM
2A-038
BLOOD BANK / HISTOLOGY
2A-037A MICROBIOLOGY
2A-037B
LAB SUPERVISOR OFFICE
2C-041
LAB INFORMATION OFFICE
2C-042
RESTROOM, M/F
2C-043
BREAK ROOM
2C-044
SPECIMEN & REAGENT STORAGE
2C-045
CHEMISTRY
2C-046
CLOSET
2C-042A
HEMATOLOGY
2C-048
ANCILLARY OFFICE
2C-051
HOUSEKEEPING CLOSET
2C-052
HOUSEKEEPING CLOSET
2C-053
REAGENT / SUPPLIES ROOM
2C-054
RESTROOM, M/F
2C-055A
PHLEBOTOMY
2A-055
LAB COAT CLOSET
2C-054A
WAITING ROOM RADIOLOGY/LAB
2A-057
CORRIDOR C
2C-C01
WAITING ROOM RAIOLOGY/LAB
2A-058
ELEVATOR ROOM
2C-047
ELECTRICAL CLOSET
2A-035
RESTROOM, M
2A-009
CT CONTROL ROOM
2A-007
LINEN CHUTE/HK CLOSET
2A-008
EQUIPMENT
2B-034
STORAGE
2B-010
RESTROOM, F
2B-011
X-RAY IMAGING ROOM
2B-033
NUCLEAR MEDICINE IMAGING ROOM
2A-002
STAIR A1
2A-S01
3"ST
RDRD
2"V
3/4"CW
3/4"HW
3/4"HWC
4"SAN
/4
"V /4
"V
4"SAN
2"V
3/4"CW
3/4"HW
3/4"HWC
4"SAN
2"V
3/4"CW
3/4"HW
3/4"HWC
1 1/2"AV
2"AV
4"ST
4"AV
3/4"G
2"AV
2"AV
1 1/2"AV
4"ST
4"ST
3/4"CW
3/4"HW
3/4"HWC
3"SAN
4"V
4"SAN
3/4"HWC
3/4"HW
3/4"CW
4"ST
1"HWC
1"HW
1"CW
1 1/2"V
1"HWC
1"HW
1"CW
1 1/2"V
4"SAN
3/4"HWC
3/4"HW
3/4"CW
CONNECT TO EXISTING
3/4 CW LINE FOR
EXISTING HOSE BIBB.
2" VTR
4"SAN
4"V
1"CW
1"HW
1"HWC
1"HWC
1"HW
1"CW
2"V
3/4"HWC
3/4"HW
3/4"CW
2"V
4"SAN
CONNECT TO PIPING FROM WITHIN 6"
OF SLAB ABOVE TO APPROXIMATELY 6"
ABOVE CEILING. PIPING TO BE
RELOCATED AS REQUIRED FOR DUCT
INSTALLATION. COORDINATE WITH
MECHANICAL CONTRACTOR. (TYPICAL)
HB
PROVIDE NEW FIXTURES AND CONNECT TO
EXISTING PIPING CONNECTIONS WITHIN
CASEWORK. COORDINATE EXACT LOCATION
OF FIXTURE AND TRIM WITH ARCHITECTURAL.
COORDINATE LOCATION OF FIXTURE AND
ASSOCIATED MIXING VALVES, ACCESSORIES,
COMPONENTS WITH ARCHITECTURAL.
(TYPICAL)
REINSTALL EXISTING PVC
STANDPIPE SYSTEM AND
CONNECT TO EXISTING
SYSTEM.
CONTRACTOR SHALL TEMPORARILY SUPPORT
EMERGENCY FIXTURE AND REMOVE FOOT FOR
FLOORING REMOVAL. REINSTALL FOOT ONCE
FLOORING WORK IN THE IMMEDIATE AREA IS
COMPLETED.
CONTRACTOR SHALL TEMPORARILY SUPPORT
EMERGENCY FIXTURE AND REMOVE FOOT FOR
FLOORING REMOVAL. REINSTALL FOOT ONCE
FLOORING WORK IN THE IMMEDIATE AREA IS
COMPLETED.
P-528
P-528
P-527
P-528
P-528
P-528
P-707
P-709
P-707
P-709
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
657A4-21-800REMOVE AND REPLACE END OF
LIFE HEATING, VENTILATON, AND
AIR CONDITIONING
BID DOCUMENTS
JOHN J. PERSHING VETERANS' ADMINISTRATION
MEDICAL CENTER 1500 N. WESTWOOD BLVD. POPLAR
BLUFF, MO 63901-3318
Alesia Architecture P.C.
3705 North 200th Street Elkhorn, Nebraska 68022 Phone: (402) 291-6941
Shaffer, Stevens & Schaap 1070 Howard Street Omaha, Nebraska 68102 Phone: (402) 455-7698
AMI Environmental Inc 8802 S 135th Street Omaha, NE 68138 Phone: (402) 397-5001
IMEG Corp.
15 Sunnen Drive, Suite 104 St. Louis, MO 63143 Phone: (314) 645-1132
E
Aw
F
D
Ac Ae
C
B
KEY PLAN
A u to d e s k D o c s /2
-1
A
-2
-3
V A
P o p la r B lu ff
R e m o v e a n d R e p la c e
L a b A
H U a n d A
H U
/6
A
-2
-3
.B
.M
E P
T
R
.1
R e p l L a b A
H U
A
H U
C .r v t
/1
/2
:4
:0
A
M
PL102
SECOND FLOOR - PLUMBING
GORPAT BHAACH
08/30/2024
N O R
HT
1/8" = 1'-0"
SECOND FLOOR - PLUMBING
| Sheets |
| PL000 - PLUMBING COVERSHEET |
| PD100 - GROUND FLOOR - PLUMBING DEMOLITION |
| PD101 - FIRST FLOOR - PLUMBING DEMOLITION |
| PL100 - GROUND FLOOR - PLUMBING |
| PL101 - FIRST FLOOR - PLUMBING |
| PL102 - SECOND FLOOR - PLUMBING |
File details come from the government source that posted it. Updated .