AIR HANDLING UNIT SCHEDULE
MARK LOCATION
AREA AND/OR
BLDG SERVED
TYPE AIR FLOW
AIR FLOW
SUPPLY FAN
MARK
RETURN AIR FAN
MARK
EXHAUST FAN
MARK
PREFILTER MARK
AFTER
FILTER
MARK
FINAL
FILTER
MARK
HEAT RECOVERY
MARK
PREHEAT COIL
MARK
COOLING COIL
MARK
REHEAT COIL HUMIDIFIER MARK
REMARKSSUPPLY MIN OA RETURN
CFM [L/s] CFM [L/s] CFM [L/s]
AHU-30 A036 MECHANICAL ANIMAL RESEARCH INDOOR CUSTOM UNIT 100% OA 11,000 [5,190] 11,000 [5,190] 0 [0] 1-SF1 -- -- PF-1 AF-1 FF-1 1-HWC1 1-SHC1 1-DXC1 - 1-SH1 1, 2, 3
1.) THE FACTORY-MANUFACTURED, SITE-ASSEMBLED AHU WILL CONTAIN THE FOLLOWING SECTIONS: MERV 7 PRE-FILTER, MERV 14 AFTER-FILTER, HEAT RECOVERY HEATING WATER COIL, STEAM PREHEAT COIL, PLANT STEAM HUMIDIFIER, DX COOLING COIL, UV LIGHT, SUPPLY FANS (EACH FAN SHALL OPERATE AT 70-80% CAPACITY SIMULTANEOUSLY, EACH WITH A MOTOR OVERLOAD [PROVIDED BY MANUFACTURER] WITH A SINGLE VFD [PROVIDED BY E.C.], MERV 15
FINAL FILTER, AND DISCHARGE PLENUM.
2.) AIR HANDLER TO BE INSTALLED IN PHASE 1A. AIR HANDLER SHALL BE FULLY TESTED AND OPERATIONAL PRIOR TO BEGINNING FURTHER PHASE WORK.
3.) AIR HANDLER SHALL BE SHIPPED SUCH THAT ALL AHU COMPONENTS/SPLITS SHALL FIT THROUGH A 4'-0"W x 7'-0"H DOOR.
4.) AIR HANDLER SHALL BE ASSEMBLED ON-SITE WITHIN THE MECHANICAL ROOM. THE MAXIMUM AHU DIMENSIONS: 22'-9"L x 7'-0"W x 8'-6"H.
REMARKS
AIR FILTER SCHEDULE
MARK LOCATION
AREA AND/OR BLDG SERVED
SYSTEM AND/OR
SERVICE
MERV RATING AIR FLOW
APD
HOUSING TYPE
CARTRIDGES
INITIAL CHANGEOVER SIZE
ARRANGEMENT REMARKS
CFM [L/s] IN [mm] IN [mm] IN [mm]
1-PF1 AHU-30 ANIMAL RESEARCH 1-AHU-1 8 11,000 [5,190] 0.17 [4] 0.57 [15] FRAME 42"H x 24"W 1067 x 610 -- -----
1-AF1 AHU-30 ANIMAL RESEARCH 1-AHU-1 14 11,000 [5,190] 0.51 [13] 0.91 [23] FRAME 42"H x 24"W 1067 x 610 -- ----
1-FF1 AHU-30 ANIMAL RESEARCH 1-AHU-1 15 11,000 [5,190] 0.50 [13] 0.90 [23] FRAME 36"H x 24"W 915 x 610 -- ----
STEAM TRAP SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SERVICE
CAPACITY AT MIN DIFF PRESSURE
TRAP TYPE
MIN DIFF PRESSURE MIN INLET PRESSURE TRAP SIZE
REMARKS
PSI [kPa] PSI [kPa] IN [mm]
1-TP1 AHU-30 VESTIBULE AHU-30 / 1-SHC1
518 [235] 10 [34.5] 5 [34.5]
FLOAT AND
THERMOSTATIC
2 [50.8] 1.
LBS/HR [kg/HR]
REMARKS
1. STANDARD CONNECTION AND INTEGRAL VACUUM BREAKER.
REMARKS
1-TP2 AHU-30 VESTIBULE AHU-30 / 1-SH1
1594 [723] 10 [34.5] 5 [34.5]
FLOAT AND
THERMOSTATIC
4 [101.6] 1.
1-TP3
1-TP4
CORRIDOR CBA8* (EX) HUMIDIFIER
CORRIDOR CBA5 (EX) HUMIDIFIER
EXISTING HUMIDIFIER ABOVE CEILING DEMOLISHED IN PROJECT. CONTRACTOR TO SUPPLY STEAM TRAP AT END OF MAIN TO RETURN CONDENSATE BASED ON EXISTING CONDENSATE LOAD AT HUMIDIFIER.
EXISTING HUMIDIFIER ABOVE CEILING DEMOLISHED IN PROJECT. CONTRACTOR TO SUPPLY STEAM TRAP AT END OF MAIN TO RETURN CONDENSATE BASED ON EXISTING CONDENSATE LOAD AT HUMIDIFIER.
STEAM HEATING COIL SCHEDULE
MARK LOCATION
AREA AND/OR
BLDG SERVED
SYSTEM
AND/OR
SERVICE
APPLICATION
AIR FLOW
MAX FACE VELOCITY
APD
TEMPERATURES TOTAL MIN CAPACITY STEAM
REMARKSEAT LAT ENT CONT VALVE ENT COIL FLOW STEAM TRAP
CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] MBH [kW] PSIG [kPa] PSIG [kPa] LBS/HR [kg/HR] MARK LBS/HR [kg/HR]
1-SHC1 AHU-30 ANIMAL RESEARCH AHU-30 PREHEAT 11,000 [5,190] 638 [3.24] 0.34 [84.6] 28.3 [-2.1] 92.3 [33.5] 766.3 [244.6] 5 [34.5] 5 [34.5] 796.7 [361.4] 1-TP1 1594 [723] ----
STEAM HUMIDIFER SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SEVICE HUMIDIFIER TYPE
AIR FLOW # OF MANIFOLDS
EAT LAT
SOURCE
STEAM
CONTROL TYPE
TRAP
REMARKSDb Wb DEWPOINT DEWPOINT PRESS ENT VALVE PRESS ENT HEATER FLOW
MARK
CAPACITY
CFM [L/s] °F [°C] °F [°C] °F [°C] °F [°C] PSIG [kPa] PSIG [kPa] LBS/HR [kg/HR] LBS/HR [kg/HR]
1-SH1 AHU-30 ANIMAL RESEARCH PLANT STEAM 11,000 [5,190] 1 55 [--] 38.9 [--] 10.8 [--] 31.2 [--] PLANT STEAM 5 [35] 5 [35] 259 [--] MODULATING 1-TP2 518 [235]
1. HUMIDISTAT TO BE PROVIDED IN EXHAUST DUCTWORK AS SHOWN ON DRAWINGS. HUMIDIFIER TO BE SUPPLIED WITH LIVE PLANT STEAM.
SOUND ATTENUATING DEVICE SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SERVICE TYPE
AIRFLOW APD INLET SIZE LENGTH
DYNAMIC INSERTION LOSS DB OCTAVE BAND AND MID-FREQUENCY [CPS]
REMARKS63 125 250 500 1000 2000 4000 8000
CFM [L/s] IN WG [Pa] IN [mm] IN [mm] 1 2 3 4 5 6 7 8
1-SA1 AHU-30 [5,190] [125] [965 x 406] [1829] 1, 2
NOTES
1. BASED ON AIR HANDLER SUPPLY FAN OUTLET SOUND VALUES: 63HZ, 92dB; 125HZ, 95dB; 250HZ, 96dB; 500HZ, 98dB; 1000HZ, 94dB; 2000HZ, 88dB; 4000HZ, 84dB; 8000HZ, 81dB.
2. BASED ON MAXIMUM NOISE LEVEL OF NC-40 FOR RESEARCH LABORATORIES AND NC-45 FOR RESEARCH ANIMAL HOUSING AREAS, PER 2016 NATIONAL INSTITUTES OF HEALTH (NIH) DESIGN REQUIREMENTS MANUAL.
IN THE INLET SIZE COLUMN, WHEN ONE VALUE IS INDICATED, THE DUCT IS A ROUND DUCT. IF SIZE IS INDICATED AS ##" x ##," THE DUCT IS A RECTANGULAR DUCT WITH SPECIFICATIONS OF "DUCT WIDTH" BY "DUCT DEPTH."
SA DUCT 11,000 0.5 38 x 16 72 2.0 7.0 19.0 22.0 19.0 20.0 13.0 11.0
REACTIVE,
FIBER-FREE
HOT WATER HEATING PREHEAT COIL SCHEDULE
MARK LOCATION
AREA AND/OR BLDG
SERVED
SYSTEM AND/OR
SERVICE
AIR FLOW
MAX FACE VELOCITY
APD
EAT LAT
TOTAL CAPACITY
HEATING HOT WATER
REMARKSDb Db FLOW EWT LWT WPD
CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] MBH [kW] GPM [L/s] °F [°C] °F [°C] FT [M]
1-HWC1 AHU-30 ANIMAL RESEARCH AHU-30 11,000 [5,190] 401 [--] 0.37 [--] 1.3 [--] 35.8 [--] 204.8 [--] 70 [--] 48.4 [--] 36.1 [--] 8.03 [--] 1
NOTE
THE COOLING COIL FIN SPACING SHALL NOT EXCEED 132 FINS PER FOOT [400 FINS PER METER].
% GLYCOL
1. BASED ON (2) COILS WITHIN THE AHU, EACH 5,500 CFM AND 35 GPM.
FIRE DAMPER SCHEDULE
MARK
1-FD-1
LOCATION
MECH RM
REMARKS
FAN
SYSTEM
AHU-30
SYSTEM /
SERVICE
INTAKE AIR [ 1219 x 559 ]
[ mm ]
48 x 22
IN
DUCT SIZE
[ 498 ]
[ Pa ]
2"
IN WG
DUCT PRESSURE CLASS
1-HR FIRE WALL
1-FD-2
1-FD-3
1-FD-4
MECH RM AHU-30
MECH RM AHU-30
MECH RM AHU-30
SUPPLY AIR
SUPPLY AIR
SUPPLY AIR
10 DIA
10 DIA
38 x 16
[ 498 ]2"
[ 498 ]2"
[ 498 ]2"
1-HR FIRE WALL
1-HR FIRE WALL
1-HR FIRE WALL
[ 254 DIA ]
[ 965 x 406 ]
[ 254 DIA ]
DX COOLING COIL SCHEDULE
MARK LOCATION
AREA AND/OR BLDG
SERVED
SYSTEM AND/OR
SERVICE
AIR FLOW MAX FACE VELOCITY APD
EAT LAT
TOTAL CAPACITY
REMARKSDb Db
CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] MBH [kW]
1-DXC1 AHU-30 ANIMAL RESEARCH AHU-30 11,000 [5,190] 429 [2.18] 1.07 [267] 86.1 [30.0] 49.6 [9.8] 867 [254] ----
NOTE
THE COOLING COIL FIN SPACING SHALL NOT EXCEED 132 FINS PER FOOT [400 FINS PER METER].
SENSIBLE CAPACITY
MBH [kW]
436 [128]
Wb
°F [°C]
73.8 [23.2]
Wb
°F [°C]
49.3 [9.6] R-410A
REFRIGERANT
SATURATED SUCTION
TEMP
42 [5.6]
°F [°C]
AIR COOLED CONDENSING UNIT SCHEDULE
MARK LOCATION
AREA AND/OR BLDG
SERVED
SYSTEM AND/OR
SERVICE
MIN TOTAL
REFRIGERATION
MAX SUCTION TEMP @
COMP
OA TEMP
COMPRESSOR MOTOR
REMARKS
MBH [kW] F [C] F [C]
# COMP
CU-30 NUC MED ROOF ANIMAL RESEARCH AHU-30 867 [3,000] 42 [6] 105 [41] 2 MCA = 165, MOCP = 225
NOTE
UL-RATED STARTERS SHALL BE FURNISHED BY MANUFACTURER OF EQUIPMENT.
NOMINAL
POWER
RLA
64.3
REFRIGERANT
R-410a
MIN EER
10.0
IPLV
PHASE
VOLT
CONDENSER FAN MOTOR
# FANS
NOMINAL
POWER
HP
1.5
PHASE
VOLT
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Columbia, Missouri
Addendum 1 08/22/2018
M-601
MECHANICAL SCHEDULES
INSTALL ANIMAL RESEARCH AIR HANDLER # 589A4-17-181
06/22/2018 BOH AR
BID DEDUCT OPTIONS:
1. MAINTAIN HEAT RECOVERY COIL IN AIR HANDLER AND REMOVE THE HEAT RECOVERY LOOP PIPING.