AIR HANDLING UNIT SCHEDULE

MARK LOCATION

AREA AND/OR

BLDG SERVED

TYPE AIR FLOW

AIR FLOW

SUPPLY FAN

MARK

RETURN AIR FAN

MARK

EXHAUST FAN

MARK

PREFILTER MARK

AFTER

FILTER

MARK

FINAL

FILTER

MARK

HEAT RECOVERY

MARK

PREHEAT COIL

MARK

COOLING COIL

MARK

REHEAT COIL HUMIDIFIER MARK

REMARKSSUPPLY MIN OA RETURN

CFM [L/s] CFM [L/s] CFM [L/s]

AHU-30 A036 MECHANICAL ANIMAL RESEARCH INDOOR CUSTOM UNIT 100% OA 11,000 [5,190] 11,000 [5,190] 0 [0] 1-SF1 -- -- PF-1 AF-1 FF-1 1-HWC1 1-SHC1 1-DXC1 - 1-SH1 1, 2, 3

1.) THE FACTORY-MANUFACTURED, SITE-ASSEMBLED AHU WILL CONTAIN THE FOLLOWING SECTIONS: MERV 7 PRE-FILTER, MERV 14 AFTER-FILTER, HEAT RECOVERY HEATING WATER COIL, STEAM PREHEAT COIL, PLANT STEAM HUMIDIFIER, DX COOLING COIL, UV LIGHT, SUPPLY FANS (EACH FAN SHALL OPERATE AT 70-80% CAPACITY SIMULTANEOUSLY, EACH WITH A MOTOR OVERLOAD [PROVIDED BY MANUFACTURER] WITH A SINGLE VFD [PROVIDED BY E.C.], MERV 15

FINAL FILTER, AND DISCHARGE PLENUM.

2.) AIR HANDLER TO BE INSTALLED IN PHASE 1A. AIR HANDLER SHALL BE FULLY TESTED AND OPERATIONAL PRIOR TO BEGINNING FURTHER PHASE WORK.

3.) AIR HANDLER SHALL BE SHIPPED SUCH THAT ALL AHU COMPONENTS/SPLITS SHALL FIT THROUGH A 4'-0"W x 7'-0"H DOOR.

4.) AIR HANDLER SHALL BE ASSEMBLED ON-SITE WITHIN THE MECHANICAL ROOM. THE MAXIMUM AHU DIMENSIONS: 22'-9"L x 7'-0"W x 8'-6"H.

REMARKS

AIR FILTER SCHEDULE

MARK LOCATION

AREA AND/OR BLDG SERVED

SYSTEM AND/OR

SERVICE

MERV RATING AIR FLOW

APD

HOUSING TYPE

CARTRIDGES

INITIAL CHANGEOVER SIZE

ARRANGEMENT REMARKS

CFM [L/s] IN [mm] IN [mm] IN [mm]

1-PF1 AHU-30 ANIMAL RESEARCH 1-AHU-1 8 11,000 [5,190] 0.17 [4] 0.57 [15] FRAME 42"H x 24"W 1067 x 610 -- -----

1-AF1 AHU-30 ANIMAL RESEARCH 1-AHU-1 14 11,000 [5,190] 0.51 [13] 0.91 [23] FRAME 42"H x 24"W 1067 x 610 -- ----

1-FF1 AHU-30 ANIMAL RESEARCH 1-AHU-1 15 11,000 [5,190] 0.50 [13] 0.90 [23] FRAME 36"H x 24"W 915 x 610 -- ----

STEAM TRAP SCHEDULE

MARK LOCATION

SYSTEM AND/OR

SERVICE

CAPACITY AT MIN DIFF PRESSURE

TRAP TYPE

MIN DIFF PRESSURE MIN INLET PRESSURE TRAP SIZE

REMARKS

PSI [kPa] PSI [kPa] IN [mm]

1-TP1 AHU-30 VESTIBULE AHU-30 / 1-SHC1

518 [235] 10 [34.5] 5 [34.5]

FLOAT AND

THERMOSTATIC

2 [50.8] 1.

LBS/HR [kg/HR]

REMARKS

1. STANDARD CONNECTION AND INTEGRAL VACUUM BREAKER.

REMARKS

1-TP2 AHU-30 VESTIBULE AHU-30 / 1-SH1

1594 [723] 10 [34.5] 5 [34.5]

FLOAT AND

THERMOSTATIC

4 [101.6] 1.

1-TP3

1-TP4

CORRIDOR CBA8* (EX) HUMIDIFIER

CORRIDOR CBA5 (EX) HUMIDIFIER

EXISTING HUMIDIFIER ABOVE CEILING DEMOLISHED IN PROJECT. CONTRACTOR TO SUPPLY STEAM TRAP AT END OF MAIN TO RETURN CONDENSATE BASED ON EXISTING CONDENSATE LOAD AT HUMIDIFIER.

EXISTING HUMIDIFIER ABOVE CEILING DEMOLISHED IN PROJECT. CONTRACTOR TO SUPPLY STEAM TRAP AT END OF MAIN TO RETURN CONDENSATE BASED ON EXISTING CONDENSATE LOAD AT HUMIDIFIER.

STEAM HEATING COIL SCHEDULE

MARK LOCATION

AREA AND/OR

BLDG SERVED

SYSTEM

AND/OR

SERVICE

APPLICATION

AIR FLOW

MAX FACE VELOCITY

APD

TEMPERATURES TOTAL MIN CAPACITY STEAM

REMARKSEAT LAT ENT CONT VALVE ENT COIL FLOW STEAM TRAP

CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] MBH [kW] PSIG [kPa] PSIG [kPa] LBS/HR [kg/HR] MARK LBS/HR [kg/HR]

1-SHC1 AHU-30 ANIMAL RESEARCH AHU-30 PREHEAT 11,000 [5,190] 638 [3.24] 0.34 [84.6] 28.3 [-2.1] 92.3 [33.5] 766.3 [244.6] 5 [34.5] 5 [34.5] 796.7 [361.4] 1-TP1 1594 [723] ----

STEAM HUMIDIFER SCHEDULE

MARK LOCATION

SYSTEM AND/OR

SEVICE HUMIDIFIER TYPE

AIR FLOW # OF MANIFOLDS

EAT LAT

SOURCE

STEAM

CONTROL TYPE

TRAP

REMARKSDb Wb DEWPOINT DEWPOINT PRESS ENT VALVE PRESS ENT HEATER FLOW

MARK

CAPACITY

CFM [L/s] °F [°C] °F [°C] °F [°C] °F [°C] PSIG [kPa] PSIG [kPa] LBS/HR [kg/HR] LBS/HR [kg/HR]

1-SH1 AHU-30 ANIMAL RESEARCH PLANT STEAM 11,000 [5,190] 1 55 [--] 38.9 [--] 10.8 [--] 31.2 [--] PLANT STEAM 5 [35] 5 [35] 259 [--] MODULATING 1-TP2 518 [235]

1. HUMIDISTAT TO BE PROVIDED IN EXHAUST DUCTWORK AS SHOWN ON DRAWINGS. HUMIDIFIER TO BE SUPPLIED WITH LIVE PLANT STEAM.

SOUND ATTENUATING DEVICE SCHEDULE

MARK LOCATION

SYSTEM AND/OR

SERVICE TYPE

AIRFLOW APD INLET SIZE LENGTH

DYNAMIC INSERTION LOSS DB OCTAVE BAND AND MID-FREQUENCY [CPS]

REMARKS63 125 250 500 1000 2000 4000 8000

CFM [L/s] IN WG [Pa] IN [mm] IN [mm] 1 2 3 4 5 6 7 8

1-SA1 AHU-30 [5,190] [125] [965 x 406] [1829] 1, 2

NOTES

1. BASED ON AIR HANDLER SUPPLY FAN OUTLET SOUND VALUES: 63HZ, 92dB; 125HZ, 95dB; 250HZ, 96dB; 500HZ, 98dB; 1000HZ, 94dB; 2000HZ, 88dB; 4000HZ, 84dB; 8000HZ, 81dB.

2. BASED ON MAXIMUM NOISE LEVEL OF NC-40 FOR RESEARCH LABORATORIES AND NC-45 FOR RESEARCH ANIMAL HOUSING AREAS, PER 2016 NATIONAL INSTITUTES OF HEALTH (NIH) DESIGN REQUIREMENTS MANUAL.

IN THE INLET SIZE COLUMN, WHEN ONE VALUE IS INDICATED, THE DUCT IS A ROUND DUCT. IF SIZE IS INDICATED AS ##" x ##," THE DUCT IS A RECTANGULAR DUCT WITH SPECIFICATIONS OF "DUCT WIDTH" BY "DUCT DEPTH."

SA DUCT 11,000 0.5 38 x 16 72 2.0 7.0 19.0 22.0 19.0 20.0 13.0 11.0

REACTIVE,

FIBER-FREE

HOT WATER HEATING PREHEAT COIL SCHEDULE

MARK LOCATION

AREA AND/OR BLDG

SERVED

SYSTEM AND/OR

SERVICE

AIR FLOW

MAX FACE VELOCITY

APD

EAT LAT

TOTAL CAPACITY

HEATING HOT WATER

REMARKSDb Db FLOW EWT LWT WPD

CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] MBH [kW] GPM [L/s] °F [°C] °F [°C] FT [M]

1-HWC1 AHU-30 ANIMAL RESEARCH AHU-30 11,000 [5,190] 401 [--] 0.37 [--] 1.3 [--] 35.8 [--] 204.8 [--] 70 [--] 48.4 [--] 36.1 [--] 8.03 [--] 1

NOTE

THE COOLING COIL FIN SPACING SHALL NOT EXCEED 132 FINS PER FOOT [400 FINS PER METER].

% GLYCOL

1. BASED ON (2) COILS WITHIN THE AHU, EACH 5,500 CFM AND 35 GPM.

FIRE DAMPER SCHEDULE

MARK

1-FD-1

LOCATION

MECH RM

REMARKS

FAN

SYSTEM

AHU-30

SYSTEM /

SERVICE

INTAKE AIR [ 1219 x 559 ]

[ mm ]

48 x 22

IN

DUCT SIZE

[ 498 ]

[ Pa ]

2"

IN WG

DUCT PRESSURE CLASS

1-HR FIRE WALL

1-FD-2

1-FD-3

1-FD-4

MECH RM AHU-30

MECH RM AHU-30

MECH RM AHU-30

SUPPLY AIR

SUPPLY AIR

SUPPLY AIR

10 DIA

10 DIA

38 x 16

[ 498 ]2"

[ 498 ]2"

[ 498 ]2"

1-HR FIRE WALL

1-HR FIRE WALL

1-HR FIRE WALL

[ 254 DIA ]

[ 965 x 406 ]

[ 254 DIA ]

DX COOLING COIL SCHEDULE

MARK LOCATION

AREA AND/OR BLDG

SERVED

SYSTEM AND/OR

SERVICE

AIR FLOW MAX FACE VELOCITY APD

EAT LAT

TOTAL CAPACITY

REMARKSDb Db

CFM [L/s] FPM [M/s] IN WG [Pa] °F [°C] °F [°C] MBH [kW]

1-DXC1 AHU-30 ANIMAL RESEARCH AHU-30 11,000 [5,190] 429 [2.18] 1.07 [267] 86.1 [30.0] 49.6 [9.8] 867 [254] ----

NOTE

THE COOLING COIL FIN SPACING SHALL NOT EXCEED 132 FINS PER FOOT [400 FINS PER METER].

SENSIBLE CAPACITY

MBH [kW]

436 [128]

Wb

°F [°C]

73.8 [23.2]

Wb

°F [°C]

49.3 [9.6] R-410A

REFRIGERANT

SATURATED SUCTION

TEMP

42 [5.6]

°F [°C]

AIR COOLED CONDENSING UNIT SCHEDULE

MARK LOCATION

AREA AND/OR BLDG

SERVED

SYSTEM AND/OR

SERVICE

MIN TOTAL

REFRIGERATION

MAX SUCTION TEMP @

COMP

OA TEMP

COMPRESSOR MOTOR

REMARKS

MBH [kW] F [C] F [C]

# COMP

CU-30 NUC MED ROOF ANIMAL RESEARCH AHU-30 867 [3,000] 42 [6] 105 [41] 2 MCA = 165, MOCP = 225

NOTE

UL-RATED STARTERS SHALL BE FURNISHED BY MANUFACTURER OF EQUIPMENT.

NOMINAL

POWER

RLA

64.3

REFRIGERANT

R-410a

MIN EER

10.0

IPLV

PHASE

VOLT

CONDENSER FAN MOTOR

# FANS

NOMINAL

POWER

HP

1.5

PHASE

VOLT

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

Addendum 1 08/22/2018

M-601

MECHANICAL SCHEDULES

INSTALL ANIMAL RESEARCH AIR HANDLER # 589A4-17-181

06/22/2018 BOH AR

BID DEDUCT OPTIONS:

1. MAINTAIN HEAT RECOVERY COIL IN AIR HANDLER AND REMOVE THE HEAT RECOVERY LOOP PIPING.

Sheets
M-601 - MECHANICAL SCHEDULES