TYPICAL RECEPTACLE MOUNTING DETAIL
NO SCALE
METAL STUD
CONDUITS
RECEPTACLE
EQUIPMENT GROUND
CONDUCTOR
GROUND SCREW ON
WIRING DEVICE
GROUND SCREW IN
OUTLET BOX
CONDUIT
4 SQUARE OUTLET BOX
DRYWALL
PLASTER RING
PLASTER RING
RECEPTACLE
OUTLET BOX SECURED
TO BOX SUPPORT
GROUND SCREW IN
OUTLET BOX
WIRE NUT (TYP.)
STUD TO STUD BOX
SUPPORT, B-LINE #BB2
SERIES OR EQUAL.
NEUTRAL
CONDUCTORS
HOT CONDUCTORS
TYPICAL NAME PLATES
SERIES RATED
BRANCH CIRCUIT/DISTRIBUTION PANELBRANCH CIRCUIT/DISTRIBUTION PANEL
DISCONNECT SWITCH
CONTROL CENTER BREAKER/SWITCH
SWITCHBOARD/DISTRIBUTION PANEL/MOTOR
F.A. DEVICE MOUNTING DETAIL
NO SCALE
NO SCALE
NOTE:
WHERE DEVICES ARE INDICATED TO BE INSTALLED IN
EXISTING WALLS, WALLS SHALL BE CUT AND PATCHED AS
REQUIRED TO INSTALL STUD-TO-STUD SUPPORTS.
PANEL K
PHASE B: RED
PHASE C: BLUE
PHASE A: BLACK
42,000 A.I.C. WITH
120/208V.,3∅,4W.
1/4"
1/8"
1/8" 1/8"
1/4"
3/8"
GROUND: GREEN
NEUTRAL: WHITE
ISO.GRD.: GRN/YEL
22KA BREAKERS AND1/4"
CLASS 'J' FUSES1/4"
CAUTION - SERIES1/4"
RATED SYSTEM.1/4"
FED FROM DP:**1/4"
1/8"
1/4"
1/4"
PANEL K
PHASE B: RED
PHASE C: BLUE
PHASE A: BLACK
10,000 A.I.C.
120/208V.,3∅,4W.
1/4"
1/8"
1/8" 1/8"
1/4"
3/8"
GROUND: GREEN
NEUTRAL: WHITE
RTU #1
LPJ 200AMP
SERVES
1/8"
1/4" RTU-1
SERVES
ISO.GRD.: GRN/YEL
FED FROM DP:**1/4"
FED FROM DP:**1/4"
CRITICAL BRANCH1/4"
1/4" CRITICAL BRANCH
CRITICAL BRANCH1/4"
6"(MIN.)
48" AFF
DEVICE SHALL NOT BE MORE THAN
46" AFF TO CENTERLINE, TOP OF
SPECIFICATIONS.
WITH HARDWARE
OPEN. COORDINATE
OR CLOSURE/HOLD
MAGNETIC HOLD OPEN
(TYP.)
DETECTOR
SMOKE
FIRE ALARM DEVICE MOUNTING CRITERIA
SPECIFIED OTHERWISE ON THE DRAWINGS.
UNLESS MOUNTING HEIGHTS HAVE BEEN
THESE GUIDELINES SHALL BE USED
AUDIO/VISUAL
GENERAL NOTE
PULL STATION
REFER TO THE VISUAL UNIT.
AUDIO/VISUAL UNIT
AUDIO UNIT
VISUAL UNIT
ACCEPTABLE HERE
TOP OF DETECTOR
IN THIS AREA
DO NOT PLACE DETECTOR
AND AIR DIFFUSER/REGISTER/GRILL
MAINTAIN 36" BETWEEN SMOKE DETECTOR
STATION
PULL
12" 4"
90"
80"
46"
80" TO BOTTOM
AUDIO ONLY
6"(MIN.)
6"(MIN.)
90" TO TOP
AUDIO ONLYVISUAL ONLY
80" TO BOTTOM
FINISH FLOOR
CEILING
MAX. OF 5'-0", MIN. OF "d"
BUT NOT LESS THAN 12"
DETECTORS ON ONE SIDE
OR BOTH SIDES OF DOOR
AS REQUIRED BY NFPA 72.
DOOR HEADER "d"
HEIGHT OF
AIR DIFFUSER
TOP OF DEVICE 90 INCHES ABOVE
HIGHEST FLOOR LEVEL OR 6 INCHES
BELOW CEILING WHICH EVER IS LOWER.
BOTTOM OF DEVICE 80 INCHES ABOVE
HIGHEST FLOOR LEVEL OR 6 INCHES
BELOW CEILING WHICH EVER IS LOWER.
4"
12" MAX
AHU-30 AND CU-30
LOCATIONS
LOCATION OF MCCB-G14-VQ. ROUTE FEEDERS
FOR MECHANICAL EQUIPMENT UNDER SLAB IN
PIPE BASEMENT TO MECHANICAL ROOM A038.
ELECTRICAL ROOM
D022
MECH ROOM
A038
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Columbia, Missouri
E-501
ELECTRICAL DETAILS
INSTALL ANIMAL RESEARCH AIR HANDLER # 589A4-17-181
06/22/2018 BMW JLW
1/16" = 1'-0" A
ELECTRICAL LOWER LEVEL OVERALL FLOOR PLAN
N
8' 16' 32'
1/16" = 1'-0"
0'
PLAN INCLUDED FOR REFERENCE ONLY
ADDENDUM 1 8/22/2018
| Sheets |
| E-001 - ELECTRICAL SYMBOLS AND SCHEDULES |
| E-501 - ELECTRICAL DETAILS |