PEN WEIGHT LEGEND
LIGHT FIXTURE TO BE REMOVED
EXISTING LIGHT FIXTURE TO REMAIN
NEW LIGHT FIXTURE
LINES ARE TO BE REMOVED.
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK DASHED
DUPLEX GROUNDED RECEPTACLE TO BE REMOVED
EXISTING DUPLEX GROUNDED RECEPTACLE TO REMAIN
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN LIGHT SOLID
LINES ARE EXISTING TO REMAIN.
LINES ARE NEW TO BE INSTALLED.
ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK SOLID
NEW DUPLEX GROUNDED RECEPTACLE
SYMBOL DESCRIPTION
LIGHTING FIXTURE SCHEDULE
MANUFACTURER
CATALOG NUMBER SEE NOTES VOLTS
LAMP TYPE
NO. REMARKS
DLWDESCRIPTION LENS\LOUVER\FINISH
CATALOG NUMBER
MANUFACTURERMANUFACTURER
CATALOG NUMBERCATALOG NUMBER
MANUFACTURER
LTR.
FIXT.
(P.E.C.)1 2 3 4
1 GENERAL CONTRACTOR SHALL PROVIDE FIREPROOFING AROUND RECESSED FIXTURES INSTALLED IN FIRE RATED CEILING PER U.L. REQUIREMENTS.
ELECTRICAL CONTRACTOR WILL COORDINATE.
2 MANUFACTURERS LISTED IN THIS SCHEDULE OR APPROVED BY WRITTEN ADDENDUM WILL BE THE ONLY APPROVED MANUFACTURERS TO BID THE LIGHTING FIXTURES FOR THIS PROJECT. CONTRACTORS AND SUPPLIERS USING PRICING FROM MANUFACTURERS NOT LISTED ON SCHEDULE OR BY
ADDENDUM DO SO AT THEIR OWN RISK.
LIGHT FIXTURE SELECTIONS ARE BASED ON THE MANUFACTURER IN THE LEFT MOST COLUMN AS LISTED IN THE SCHEDULE. FIXTURES APPROVED AS EQUALS IN THIS SCHEDULE OR BY ADDENDUM SHALL BE EQUAL TO THE UNIT SPECIFIED IN THE LEFT MOST COLUMN, IE: SPRING LOADED LATCHES, POST PAINTED FINISH, AND PHOTOMETRICS.
ALL LIGHT FIXTURES SHALL BE SECURED TO THE CEILING FRAMING SYSTEM BY MECHANICAL MEANS (SUCH AS BOLTS, SCREWS, OR RIVETS) OR BY CLIPS
IDENTIFIED FOR USE WITH THE TYPE OF CEILING FRAMING MEMBER AND LIGHT FIXTURE.
SHALL HAVE A BALLAST DISCONNECTING MEANS PROVIDED AND INSTALLED UNDER ANY OF THE FOLLOWING CONDITIONS:
TO COMPLY WITH NEC SECTION 410.130(G), ALL EXISTING OR RELOCATED FLUORESCENT LIGHT FIXTURES WITHOUT A BALLAST DISCONNECTING MEANS
a. WHEN AN EXISTING BALLAST IS REPLACED.
b. WHEN AN EXISTING LIGHT FIXTURE IS RELOCATED.
c. WHEN AN EXISTING LIGHT FIXTURE IS RECIRCUITED.
NO.
CIRC
V. A.
LOAD
TYPE
LOAD
SIZE
AMP
P. DESCRIPTION
LOAD
P H
A S
E
SIZE
AMP
P.DESCRIPTION
LOAD
TYPE
LOAD
V. A.
LOAD
NO.
CIRC
EQUIPMENT CONNECTION SCHEDULE
1 2
UNIT
VOLTAGE
UNIT
DESIG.
LOAD
H.P. FLA KVA
PANEL DEVICE
CIRCUIT
NUMBER
BKR.
AMPS
SW.
AMPS
FUSE
AMPS
P O L E
NEMA
START.
SIZE
BKR. SW.
AMPSAMPS AMPS
FUSE O
P
L
E SIZE
START.
NEMA
DEVICE AT UNIT
OTHER
S E T S
REMARKS
NOTES BELOW
FEEDER DESCRIPTION
OR SEE THE FEEDER SCHEDULE
OR SEE THE INDICATED
EXIST. PANEL: LPB-E4-120VC3
MECHANICAL EQUIPMENT CONNECTIONS
W
'FACP'
x-x x-x
J
'A'
A
F
A
WP
ELECTRICAL SHEET INDEX
DESCRIPTIONSHEET NO.
BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME
RUNS WITH INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE
CIRCUITS (MAXIMUM OF THREE PHASE CONDUCTORS) MAY
BE GROUPED IN A SINGLE CONDUIT. WHERE MULTIPLE
CIRCUITS ARE LOCATED IN THE SAME RACEWAY, JUNCTION
BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR
LABELED TO INDICATE WHICH CIRCUIT THEY ARE
ASSOCIATED WITH. SEE SPECIFICATION SECTION "LOW
VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES"
FOR ADDITIONAL INFORMATION.
WHEN INCREASED CONDUCTOR SIZES ARE SHOWN ON THE
PLANS, THE LARGER CONDUCTOR SIZE SHALL BE USED
THROUGHOUT THE LENGTH OF THE CIRCUIT, INCLUDING
ALL ELECTRICAL WORK SHALL COMPLY WITH THE LATEST
EDITION OF THE NATIONAL ELECTRICAL CODE (NEC) &
SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED
WITH WIRING AND CONNECTION OF INTERLOCKING AND
CONDUIT RUN W/CONDUCTORS AS INDICATED & GROUND
WIRE SIZED PER N.E.C. 250.122. CONDUIT SIZE AS
REFER TO RELATED ARCHITECTURAL, MECHANICAL, AND
REFER TO THE SPECIFICATIONS FOR DATA NOT ON THE
ALL MOUNTING HEIGHTS TO CENTERLINE OF ITEM UNLESS
OTHERWISE NOTED. VERIFY ALL OUTLET LOCATIONS ON
9.
THE AMERICANS WITH DISABILITIES ACT (ADA).
NEUTRAL AND GROUND.
TO MINIMIZE CUTTING OF BRICK OR BLOCK.
THE JOB PRIOR TO ROUGH-IN.
E.C. SHALL REFER TO MECHANICAL DRAWINGS AND
CONTROLS OF MECHANICAL UNITS AND THERMOSTAT
STRUCTURAL DRAWINGS FOR RELATED INFORMATION.
COORDINATE OUTLET BOX LOCATIONS WITH MASONRY
2.
1.
3.
4.
LOCATIONS.
DRAWINGS.
6.
7.
8.
REQUIRED.
5.
10. LABEL THE FRONT OF EACH RECEPTACLE COVERPLATE
WITH PANEL DESIGNATION AND CIRCUIT NUMBER USING
CLEAR THERMAL TRANSFER (ELECTRONIC DYMO) LABELS
WITH 1/8" HIGH BLACK LETTERS (OR CONTRASTING
COLOR IF PLATES ARE BLACK OR BROWN). LABELS
SHALL BE SUITABLE FOR INDOOR/OUTDOOR USE. LABEL
THE BACK OF EACH LIGHT SWITCH COVERPLATE WITH
PANEL DESIGNATION AND CIRCUIT NUMBER USING A FINE
BLACK PERMANENT MARKER.
LOCATED IN THE AREA BETWEEN 6 AND 10 DUCT EQUIVALENT
WHERE DUCT MOUNTED SMOKE DETECTORS ARE REQUIRED,
FIRE/SMOKE DAMPER, ETC.). DUCT DETECTORS SHOULD BE
DIAMETERS OF STRAIGHT, UNINTERRUPTED DUCTWORK. DUCT
DETECTORS FOR FIRE/SMOKE DAMPERS SHOULD BE LOCATED
BETWEEN THE LAST INLET OR OUTLET UPSTREAM OF THE
DAMPER AND THE FIRST INLET OR OUTLET DOWNSTREAM OF
PROVIDE 120V POWER AND FUSTAT FOR EACH FIRE/SMOKE
DAMPER. INTERLOCK WITH FIRE ALARM CONTROL PANEL TO
CLOSE FIRE/SMOKE DAMPER UPON ANY ALARM AT THE FIRE
WHERE MECHANICAL UNIT SHUTDOWN IS REQUIRED,
3 FEET OF THE FAN CONTROLS AND THE WIRING TO THE
RELAY SHALL BE MONITORED.
SMOKE DETECTORS (IE: RTU-1 SUPPLY, RTU-2 RETURN,
F1.
F2.
F3.
THE DAMPER.
ALARM CONTROL PANEL AND TO SHUTDOWN ASSOCIATED
F4.
MECHANICAL UNIT.
FIELD VERIFY LOCATION OF AREA SMOKE DETECTORS AND
HEAT DETECTORS. DO NOT LOCATE WITHIN 36" OF A
HVAC DIFFUSER (SUPPLY OR RETURN), IN A DIRECT AIR
FLOW, WITHIN 36" OF A SPRINKLER HEAD, OR WITHIN
36" OF THE TIP OF A CEILING FAN BLADE. SMOKE
DETECTORS FOR DOOR RELEASE SHALL BE LOCATED ON THE
CENTER LINE OF THE DOOR AND A MAXIMUM OF 5 FEET
FROM THE DOOR. THE MINIMUM DISTANCE FROM THE DOOR
IS THE DEPTH OF THE WALL SECTION ABOVE THE DOOR,
BUT NOT LESS THAN 12".
LABEL REMOTE ALARM INDICATOR FOR DUCT MOUNTED
FAN SHUTDOWN RELAY WIRING SHALL BE LOCATED WITHIN
WHERE FIRE/SMOKE DAMPERS EXIST WITHIN A FACILITY,
F5. FIRE ALARM DEVICES SHOWN INDICATE THE MINIMUM
REQUIRED. CONTRACTOR TO PROVIDE ALL ADDITIONAL
DEVICES REQUIRED BY CODE AND AUTHORITY HAVING
JURISDICTION.
11. EXISTING TELEMETRY AND CELL PHONE REPEATER ANTENNAS
TO REMAIN . PROTECT DEVICE AND CABLING DURING
CONSTRUCTION AND REINSTALL IN EXISTING LOCATIONS.
D
EXISTING FIXTURE
TO BE REMOVED
E
EXISTING FIXTURE
TO REMAIN 5
ALL EXISITNG FIXTURES TO REMAIN SHALL BE STORED/PROTECTED DURING CONSTRUCTION AND RE-INSTALLED IN EXACT SAME PLACE
N4 WILLIAMS
76-4-L32/835-WG7611-DRV
4' STRIP 3500K LED
UNV
WHITE
3200 LUMENS, 28 WATTS, 80+ CRI
PROVIDE WITH WIRE GUARD
208/120 VOLTS, 3 PHASE, 4 WIRE
225 AMP MLO, SURFACE MTD.
W/GRD. BUS
10000 AIC LABELED
1 EXISTING LOAD 1 20 A 2EXISTING LOAD220
3 EXISTING LOAD 1 20 B 4--------------------------------------------------------------------------------------------------|
5 EXISTING LOAD 1 20 C 6EXISTING LOAD120
7 EXISTING LOAD 1 20 A 8EXISTING LOAD120
9 EXISTING LOAD 2 20 B 10EXISTING LOAD120
11 ---------------- ---------------- -------------------------------------------------- ----------------| C 12EXISTING LOAD220
13 EXISTING LOAD 2 20 A 14--------------------------------------------------------------------------------------------------|
15 ---------------- ---------------- -------------------------------------------------- ----------------| B 16EXISTING LOAD120
17 EXISTING LOAD 2 20 C 18EXISTING LOAD120
19 ---------------- ---------------- -------------------------------------------------- ----------------| A 20EXISTING LOAD120
21 EXISTING LOAD 1 20 B 22EXISTING LOAD120
23 EXISTING LOAD 1 20 C 24EXISTING LOAD120
25 EXISTING LOAD 1 20 A 26EXISTING LOAD120
27 EXISTING LOAD 1 20 B 28EXISTING LOAD120
29 EXISTING LOAD 1 20 C 30EXISTING LOAD120
31 EXISTING LOAD 1 20 A 32EXISTING LOAD120
33 EXISTING LOAD 1 20 B 34EXISTING LOAD120
35 EXISTING LOAD 1 20 C 36EXISTING LOAD120
37 1200 POWR AHU-30-1L LTS & REC 1 20 A2 38600RCPTREC - MECH RM A036/A038120 2
39 1080 P/P 1-TU- B1-B6, B17-B19 1 20 B2 40SPACE
41 1080 P/P 1-TU- B7-B16 1 20 C2 42SPACE
1 EXISTING SQUARE D NQ PANELBOARD. ALL EXISTING LOADS TO REMAIN UNLESS OTHERWISE NOTED.
2 PROVIDE AND INSTALL CIRCUIT BREAKER INDICATED IN EXISTING BLANK SPACE. BREAKER SHALL MATCH
MAKE, MODEL, AND MAX AIC RATING OF EXISTING BREAKERS WITHIN PANEL. VERIFY ALL REQUIREMENTS PRIOR TO
INSTALLATION, AND UPDATE PANEL SCHEDULE ACCORDINGLY.
1SF 480/3 20 54.0 44.87 MCCB-G14-VQ: 80 3 VFD100 70100 70 33 1 3 #3 AWG THWN; #8 AWG GRD; 1-1/4" C. FANS346
1L 120/1 10.0 1.200 LPB-E4-120VC3:37 20 1 FUSTAT 1 2 #12 AWG THWN; #12 AWG GRD; 1/2" C. LIGHTS AND RECEPTACLE5
30 480/3 64.3A 149.5 124.2 MCCB-G14-VQ: 225 3 200 175200 175 NEMA-3R33 1 3 #4/0 AWG THWN; #4 AWG GRD; 2-1/2" C.6
1 ALL CONNECTIONS AND ELECTRICAL EQUIPMENT LISTED IN SCHEDULE SHALL BE PROVIDED AND INSTALLED BY THE ELECTRICAL
CONTRACTOR. FIELD VERIFY CONNECTION REQUIREMENTS AND EQUIPMENT PROVIDED BY OTHERS PRIOR TO ROUGH-IN.
2 REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED WITH WIRING AND CONNECTIONS OF
INTERLOCKING, THERMOSTAT LOCATIONS, EXHAUST FAN CONTROL SWITCHES, AND OTHER CONTROLS OF MECHANICAL EQUIPMENT.
3 PROVIDE DUCT MOUNTED SMOKE DETECTORS IN THE SUPPLY AND RETURN DUCTS. VERIFY THE REQUIRED QUANTITY OF DUCT
SMOKE DETECTORS FOR EACH UNIT WITH THE FINAL INSTALLED DUCTWORK LAYOUT TO MEET NFPA REQUIREMENTS. PROVIDE FAN
SHUT DOWN RELAY TO SHUT DOWN MECHANICAL UNIT UPON ANY ALARM AT THE FIRE ALARM CONTROL PANEL.
4 VFD PROVIDED AND INSTALLED BY EC. MOTOR OVERLOADS PROVIDED BY AHU SUPPLIER INTEGRAL TO UNIT.
5 LED LIGHT FIXTURES AND GFCI RECEPTACLE PROVIDED AND INSTALLED WITH UNIT. EC TO PROVIDE 120V CIRCUIT AND TOGGLE
SWITCH AS REQUIRED.
6 CONNECT TO SPARE BUCKET IN EXISTING GE EVOLUTION SERIES E9000 MOTOR CONTROL CENTER. REMOVE EXISTING CIRCUIT BREAKER
AND/OR PLUG WITHIN SPARE BUCKET, AND PROVIDE CIRCUIT BREAKER AND/OR PLUG TO MEET AMPACITY INDICATED IN SCHEDULE. BREAKER SHALL
MATCH MAKE, MODEL, AND MAX AIC RATING OF OTHER CIRCUIT BREAKERS WITHIN EXISTING MOTOR CONTROL CENTER BUCKETS.
VERIFY ALL REQUIREMENTS PRIOR TO INSTALLATION. PROVIDE UPDATED MCC BUCKET LABEL.
A
A
A
A
A
GENERAL NOTESFIRE ALARM NOTES SYMBOL LIST
DUPLEX GROUNDED RECEPTACLE
EMERGENCY CIRCUIT CEIL./WALL
SWITCH LEGS (#12 UON)
GROUND CONDUCTOR (#12 UON)
CONDUIT RUN PARTIAL CIRCUIT. 2#12
CONDUIT RUN 2#12 & 1#12 GRD.-
CONDUIT HOME RUN, 2 CIRCUITS
PHASE CONDUCTORS (#12 UON)
NEUTRAL CONDUCTOR (#12 UON)
CEIL./WALL
ELECTRICAL DISTRIBUTION EQUIPMENT
BRANCH CIRCUIT PANEL & PANEL DESIG.
SPECIAL DEVICE (AS NOTED)
FUSTAT BUSS #SSY
JUNCTION BOX
72" TO TOP
SPECIAL OUTLET (SEE SCHEDULE OR AS NOTED)
GROUND FAULT DUPLEX RECEPTACLE
DOUBLE DUPLEX GROUNDED RECEPTACLE
AFF
NL NIGHT LIGHT-WIRE AHEAD OF CONTROLS
ABOVE FINISHED FLOOR
WEATHERPROOF
EXIT LIGHT (SHADING DENOTES EXIT FACE SIDE) CEIL./WALL
SYMBOL
LIGHT FIXTURE & FIXTURE LETTER
LIGHT FIXTURE & FIXTURE LETTER
LIGHT FIXTURE & FIXTURE LETTER
DESCRIPTION
CEILING
CEILING
WALL
CEILING
MOUNTING
UON UNLESS OTHERWISE NOTED
CEIL./WALL
FLOOR/WALL
STRIP LIGHT FIXTURE & FIXTURE LETTER
EM LIGHT FIXTURE ON EMERGENCY POWER
18"AFF
18"AFF
18"AFF
1/2"C.
GROUND FAULT DOUBLE DUPLEX RECEPTACLE 18"AFF
& 1#12 GRD. 1/2"C.
CEIL./WALL
CEIL./WALLCONDUIT HOME RUN, 1 CIRCUIT. 2#12
& 1#12 GRD. 1/2"C.
CEIL./WALLCONDUIT HOME RUN, 1 CIRCUIT. 2#10
& 1#10 GRD. GEN. NOTE 7 & 8#10
EQUIPMENT - SEE EQUIPMENT
CONNECTION SCHEDULE
WALL
CLG
CCTV CAMERA - FIXED
CCTV CAMERA - FIXED
46"AFFFIRE ALARM MANUAL STATION
FIRE ALARM VISUAL SIGNAL
FIRE ALARM SPEAKER
FIRE ALARM CONTROL PANEL WALL
80" TO BOTTOM
COMB. F.A. SPEAKER & VISUAL SIGNAL
80" TO BOTTOM
80" TO BOTTOM
E-001 ELECTRICAL SYMBOLS AND SCHEDULES
E-101 PARTIAL ELECTRICAL FLOOR PLANS
E-102
E-103
E-104
E-105
E-501 ELECTRICAL DETAILS
PARTIAL ELECTRICAL FLOOR PLANS
PARTIAL ELECTRICAL FLOOR PLANS
PARTIAL ELECTRICAL FLOOR PLANS
PARTIAL ELECTRICAL FLOOR PLANS
AHU-30 AIR HANDLING UNIT
CU CONDENSING UNIT
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Dwg.Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1
B
A
C
D
E
F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Columbia, Missouri
E-001
ELECTRICAL SYMBOLS AND
SCHEDULES
INSTALL ANIMAL RESEARCH AIR HANDLER # 589A4-17-181
06/22/2018 BMW JLW
ADDENDUM 1 8/22/2018
| Sheets |
| E-001 - ELECTRICAL SYMBOLS AND SCHEDULES |
| E-501 - ELECTRICAL DETAILS |