Text version

PEN WEIGHT LEGEND

LIGHT FIXTURE TO BE REMOVED

EXISTING LIGHT FIXTURE TO REMAIN

NEW LIGHT FIXTURE

LINES ARE TO BE REMOVED.

ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK DASHED

DUPLEX GROUNDED RECEPTACLE TO BE REMOVED

EXISTING DUPLEX GROUNDED RECEPTACLE TO REMAIN

ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN LIGHT SOLID

LINES ARE EXISTING TO REMAIN.

LINES ARE NEW TO BE INSTALLED.

ALL DEVICES, LIGHT FIXTURES, ETC., DRAWN IN DARK SOLID

NEW DUPLEX GROUNDED RECEPTACLE

SYMBOL DESCRIPTION

LIGHTING FIXTURE SCHEDULE

MANUFACTURER

CATALOG NUMBER SEE NOTES VOLTS

LAMP TYPE

NO. REMARKS

DLWDESCRIPTION LENS\LOUVER\FINISH

CATALOG NUMBER

MANUFACTURERMANUFACTURER

CATALOG NUMBERCATALOG NUMBER

MANUFACTURER

LTR.

FIXT.

(P.E.C.)1 2 3 4

1 GENERAL CONTRACTOR SHALL PROVIDE FIREPROOFING AROUND RECESSED FIXTURES INSTALLED IN FIRE RATED CEILING PER U.L. REQUIREMENTS.

ELECTRICAL CONTRACTOR WILL COORDINATE.

2 MANUFACTURERS LISTED IN THIS SCHEDULE OR APPROVED BY WRITTEN ADDENDUM WILL BE THE ONLY APPROVED MANUFACTURERS TO BID THE LIGHTING FIXTURES FOR THIS PROJECT. CONTRACTORS AND SUPPLIERS USING PRICING FROM MANUFACTURERS NOT LISTED ON SCHEDULE OR BY

ADDENDUM DO SO AT THEIR OWN RISK.

LIGHT FIXTURE SELECTIONS ARE BASED ON THE MANUFACTURER IN THE LEFT MOST COLUMN AS LISTED IN THE SCHEDULE. FIXTURES APPROVED AS EQUALS IN THIS SCHEDULE OR BY ADDENDUM SHALL BE EQUAL TO THE UNIT SPECIFIED IN THE LEFT MOST COLUMN, IE: SPRING LOADED LATCHES, POST PAINTED FINISH, AND PHOTOMETRICS.

ALL LIGHT FIXTURES SHALL BE SECURED TO THE CEILING FRAMING SYSTEM BY MECHANICAL MEANS (SUCH AS BOLTS, SCREWS, OR RIVETS) OR BY CLIPS

IDENTIFIED FOR USE WITH THE TYPE OF CEILING FRAMING MEMBER AND LIGHT FIXTURE.

SHALL HAVE A BALLAST DISCONNECTING MEANS PROVIDED AND INSTALLED UNDER ANY OF THE FOLLOWING CONDITIONS:

TO COMPLY WITH NEC SECTION 410.130(G), ALL EXISTING OR RELOCATED FLUORESCENT LIGHT FIXTURES WITHOUT A BALLAST DISCONNECTING MEANS

a. WHEN AN EXISTING BALLAST IS REPLACED.

b. WHEN AN EXISTING LIGHT FIXTURE IS RELOCATED.

c. WHEN AN EXISTING LIGHT FIXTURE IS RECIRCUITED.

NO.

CIRC

V. A.

LOAD

TYPE

LOAD

SIZE

AMP

P. DESCRIPTION

LOAD

P H

A S

E

SIZE

AMP

P.DESCRIPTION

LOAD

TYPE

LOAD

V. A.

LOAD

NO.

CIRC

EQUIPMENT CONNECTION SCHEDULE

1 2

UNIT

VOLTAGE

UNIT

DESIG.

LOAD

H.P. FLA KVA

PANEL DEVICE

CIRCUIT

NUMBER

BKR.

AMPS

SW.

AMPS

FUSE

AMPS

P O L E

NEMA

START.

SIZE

BKR. SW.

AMPSAMPS AMPS

FUSE O

P

L

E SIZE

START.

NEMA

DEVICE AT UNIT

OTHER

S E T S

REMARKS

NOTES BELOW

FEEDER DESCRIPTION

OR SEE THE FEEDER SCHEDULE

OR SEE THE INDICATED

EXIST. PANEL: LPB-E4-120VC3

MECHANICAL EQUIPMENT CONNECTIONS

W

'FACP'

x-x x-x

J

'A'

A

F

A

WP

ELECTRICAL SHEET INDEX

DESCRIPTIONSHEET NO.

BRANCH CIRCUITS ARE INDICATED AS ONE CIRCUIT HOME

RUNS WITH INDIVIDUAL NEUTRALS. A MAXIMUM OF THREE

CIRCUITS (MAXIMUM OF THREE PHASE CONDUCTORS) MAY

BE GROUPED IN A SINGLE CONDUIT. WHERE MULTIPLE

CIRCUITS ARE LOCATED IN THE SAME RACEWAY, JUNCTION

BOX OR ENCLOSURE, NEUTRALS SHALL BE MARKED OR

LABELED TO INDICATE WHICH CIRCUIT THEY ARE

ASSOCIATED WITH. SEE SPECIFICATION SECTION "LOW

VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES"

FOR ADDITIONAL INFORMATION.

WHEN INCREASED CONDUCTOR SIZES ARE SHOWN ON THE

PLANS, THE LARGER CONDUCTOR SIZE SHALL BE USED

THROUGHOUT THE LENGTH OF THE CIRCUIT, INCLUDING

ALL ELECTRICAL WORK SHALL COMPLY WITH THE LATEST

EDITION OF THE NATIONAL ELECTRICAL CODE (NEC) &

SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED

WITH WIRING AND CONNECTION OF INTERLOCKING AND

CONDUIT RUN W/CONDUCTORS AS INDICATED & GROUND

WIRE SIZED PER N.E.C. 250.122. CONDUIT SIZE AS

REFER TO RELATED ARCHITECTURAL, MECHANICAL, AND

REFER TO THE SPECIFICATIONS FOR DATA NOT ON THE

ALL MOUNTING HEIGHTS TO CENTERLINE OF ITEM UNLESS

OTHERWISE NOTED. VERIFY ALL OUTLET LOCATIONS ON

9.

THE AMERICANS WITH DISABILITIES ACT (ADA).

NEUTRAL AND GROUND.

TO MINIMIZE CUTTING OF BRICK OR BLOCK.

THE JOB PRIOR TO ROUGH-IN.

E.C. SHALL REFER TO MECHANICAL DRAWINGS AND

CONTROLS OF MECHANICAL UNITS AND THERMOSTAT

STRUCTURAL DRAWINGS FOR RELATED INFORMATION.

COORDINATE OUTLET BOX LOCATIONS WITH MASONRY

2.

1.

3.

4.

LOCATIONS.

DRAWINGS.

6.

7.

8.

REQUIRED.

5.

10. LABEL THE FRONT OF EACH RECEPTACLE COVERPLATE

WITH PANEL DESIGNATION AND CIRCUIT NUMBER USING

CLEAR THERMAL TRANSFER (ELECTRONIC DYMO) LABELS

WITH 1/8" HIGH BLACK LETTERS (OR CONTRASTING

COLOR IF PLATES ARE BLACK OR BROWN). LABELS

SHALL BE SUITABLE FOR INDOOR/OUTDOOR USE. LABEL

THE BACK OF EACH LIGHT SWITCH COVERPLATE WITH

PANEL DESIGNATION AND CIRCUIT NUMBER USING A FINE

BLACK PERMANENT MARKER.

LOCATED IN THE AREA BETWEEN 6 AND 10 DUCT EQUIVALENT

WHERE DUCT MOUNTED SMOKE DETECTORS ARE REQUIRED,

FIRE/SMOKE DAMPER, ETC.). DUCT DETECTORS SHOULD BE

DIAMETERS OF STRAIGHT, UNINTERRUPTED DUCTWORK. DUCT

DETECTORS FOR FIRE/SMOKE DAMPERS SHOULD BE LOCATED

BETWEEN THE LAST INLET OR OUTLET UPSTREAM OF THE

DAMPER AND THE FIRST INLET OR OUTLET DOWNSTREAM OF

PROVIDE 120V POWER AND FUSTAT FOR EACH FIRE/SMOKE

DAMPER. INTERLOCK WITH FIRE ALARM CONTROL PANEL TO

CLOSE FIRE/SMOKE DAMPER UPON ANY ALARM AT THE FIRE

WHERE MECHANICAL UNIT SHUTDOWN IS REQUIRED,

3 FEET OF THE FAN CONTROLS AND THE WIRING TO THE

RELAY SHALL BE MONITORED.

SMOKE DETECTORS (IE: RTU-1 SUPPLY, RTU-2 RETURN,

F1.

F2.

F3.

THE DAMPER.

ALARM CONTROL PANEL AND TO SHUTDOWN ASSOCIATED

F4.

MECHANICAL UNIT.

FIELD VERIFY LOCATION OF AREA SMOKE DETECTORS AND

HEAT DETECTORS. DO NOT LOCATE WITHIN 36" OF A

HVAC DIFFUSER (SUPPLY OR RETURN), IN A DIRECT AIR

FLOW, WITHIN 36" OF A SPRINKLER HEAD, OR WITHIN

36" OF THE TIP OF A CEILING FAN BLADE. SMOKE

DETECTORS FOR DOOR RELEASE SHALL BE LOCATED ON THE

CENTER LINE OF THE DOOR AND A MAXIMUM OF 5 FEET

FROM THE DOOR. THE MINIMUM DISTANCE FROM THE DOOR

IS THE DEPTH OF THE WALL SECTION ABOVE THE DOOR,

BUT NOT LESS THAN 12".

LABEL REMOTE ALARM INDICATOR FOR DUCT MOUNTED

FAN SHUTDOWN RELAY WIRING SHALL BE LOCATED WITHIN

WHERE FIRE/SMOKE DAMPERS EXIST WITHIN A FACILITY,

F5. FIRE ALARM DEVICES SHOWN INDICATE THE MINIMUM

REQUIRED. CONTRACTOR TO PROVIDE ALL ADDITIONAL

DEVICES REQUIRED BY CODE AND AUTHORITY HAVING

JURISDICTION.

11. EXISTING TELEMETRY AND CELL PHONE REPEATER ANTENNAS

TO REMAIN . PROTECT DEVICE AND CABLING DURING

CONSTRUCTION AND REINSTALL IN EXISTING LOCATIONS.

D

EXISTING FIXTURE

TO BE REMOVED

E

EXISTING FIXTURE

TO REMAIN 5

ALL EXISITNG FIXTURES TO REMAIN SHALL BE STORED/PROTECTED DURING CONSTRUCTION AND RE-INSTALLED IN EXACT SAME PLACE

N4 WILLIAMS

76-4-L32/835-WG7611-DRV

4' STRIP 3500K LED

UNV

WHITE

3200 LUMENS, 28 WATTS, 80+ CRI

PROVIDE WITH WIRE GUARD

208/120 VOLTS, 3 PHASE, 4 WIRE

225 AMP MLO, SURFACE MTD.

W/GRD. BUS

10000 AIC LABELED

1 EXISTING LOAD 1 20 A 2EXISTING LOAD220

3 EXISTING LOAD 1 20 B 4--------------------------------------------------------------------------------------------------|

5 EXISTING LOAD 1 20 C 6EXISTING LOAD120

7 EXISTING LOAD 1 20 A 8EXISTING LOAD120

9 EXISTING LOAD 2 20 B 10EXISTING LOAD120

11 ---------------- ---------------- -------------------------------------------------- ----------------| C 12EXISTING LOAD220

13 EXISTING LOAD 2 20 A 14--------------------------------------------------------------------------------------------------|

15 ---------------- ---------------- -------------------------------------------------- ----------------| B 16EXISTING LOAD120

17 EXISTING LOAD 2 20 C 18EXISTING LOAD120

19 ---------------- ---------------- -------------------------------------------------- ----------------| A 20EXISTING LOAD120

21 EXISTING LOAD 1 20 B 22EXISTING LOAD120

23 EXISTING LOAD 1 20 C 24EXISTING LOAD120

25 EXISTING LOAD 1 20 A 26EXISTING LOAD120

27 EXISTING LOAD 1 20 B 28EXISTING LOAD120

29 EXISTING LOAD 1 20 C 30EXISTING LOAD120

31 EXISTING LOAD 1 20 A 32EXISTING LOAD120

33 EXISTING LOAD 1 20 B 34EXISTING LOAD120

35 EXISTING LOAD 1 20 C 36EXISTING LOAD120

37 1200 POWR AHU-30-1L LTS & REC 1 20 A2 38600RCPTREC - MECH RM A036/A038120 2

39 1080 P/P 1-TU- B1-B6, B17-B19 1 20 B2 40SPACE

41 1080 P/P 1-TU- B7-B16 1 20 C2 42SPACE

1 EXISTING SQUARE D NQ PANELBOARD. ALL EXISTING LOADS TO REMAIN UNLESS OTHERWISE NOTED.

2 PROVIDE AND INSTALL CIRCUIT BREAKER INDICATED IN EXISTING BLANK SPACE. BREAKER SHALL MATCH

MAKE, MODEL, AND MAX AIC RATING OF EXISTING BREAKERS WITHIN PANEL. VERIFY ALL REQUIREMENTS PRIOR TO

INSTALLATION, AND UPDATE PANEL SCHEDULE ACCORDINGLY.

1SF 480/3 20 54.0 44.87 MCCB-G14-VQ: 80 3 VFD100 70100 70 33 1 3 #3 AWG THWN; #8 AWG GRD; 1-1/4" C. FANS346

1L 120/1 10.0 1.200 LPB-E4-120VC3:37 20 1 FUSTAT 1 2 #12 AWG THWN; #12 AWG GRD; 1/2" C. LIGHTS AND RECEPTACLE5

30 480/3 64.3A 149.5 124.2 MCCB-G14-VQ: 225 3 200 175200 175 NEMA-3R33 1 3 #4/0 AWG THWN; #4 AWG GRD; 2-1/2" C.6

1 ALL CONNECTIONS AND ELECTRICAL EQUIPMENT LISTED IN SCHEDULE SHALL BE PROVIDED AND INSTALLED BY THE ELECTRICAL

CONTRACTOR. FIELD VERIFY CONNECTION REQUIREMENTS AND EQUIPMENT PROVIDED BY OTHERS PRIOR TO ROUGH-IN.

2 REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED WITH WIRING AND CONNECTIONS OF

INTERLOCKING, THERMOSTAT LOCATIONS, EXHAUST FAN CONTROL SWITCHES, AND OTHER CONTROLS OF MECHANICAL EQUIPMENT.

3 PROVIDE DUCT MOUNTED SMOKE DETECTORS IN THE SUPPLY AND RETURN DUCTS. VERIFY THE REQUIRED QUANTITY OF DUCT

SMOKE DETECTORS FOR EACH UNIT WITH THE FINAL INSTALLED DUCTWORK LAYOUT TO MEET NFPA REQUIREMENTS. PROVIDE FAN

SHUT DOWN RELAY TO SHUT DOWN MECHANICAL UNIT UPON ANY ALARM AT THE FIRE ALARM CONTROL PANEL.

4 VFD PROVIDED AND INSTALLED BY EC. MOTOR OVERLOADS PROVIDED BY AHU SUPPLIER INTEGRAL TO UNIT.

5 LED LIGHT FIXTURES AND GFCI RECEPTACLE PROVIDED AND INSTALLED WITH UNIT. EC TO PROVIDE 120V CIRCUIT AND TOGGLE

SWITCH AS REQUIRED.

6 CONNECT TO SPARE BUCKET IN EXISTING GE EVOLUTION SERIES E9000 MOTOR CONTROL CENTER. REMOVE EXISTING CIRCUIT BREAKER

AND/OR PLUG WITHIN SPARE BUCKET, AND PROVIDE CIRCUIT BREAKER AND/OR PLUG TO MEET AMPACITY INDICATED IN SCHEDULE. BREAKER SHALL

MATCH MAKE, MODEL, AND MAX AIC RATING OF OTHER CIRCUIT BREAKERS WITHIN EXISTING MOTOR CONTROL CENTER BUCKETS.

VERIFY ALL REQUIREMENTS PRIOR TO INSTALLATION. PROVIDE UPDATED MCC BUCKET LABEL.

A

A

A

A

A

GENERAL NOTESFIRE ALARM NOTES SYMBOL LIST

DUPLEX GROUNDED RECEPTACLE

EMERGENCY CIRCUIT CEIL./WALL

SWITCH LEGS (#12 UON)

GROUND CONDUCTOR (#12 UON)

CONDUIT RUN PARTIAL CIRCUIT. 2#12

CONDUIT RUN 2#12 & 1#12 GRD.-

CONDUIT HOME RUN, 2 CIRCUITS

PHASE CONDUCTORS (#12 UON)

NEUTRAL CONDUCTOR (#12 UON)

CEIL./WALL

ELECTRICAL DISTRIBUTION EQUIPMENT

BRANCH CIRCUIT PANEL & PANEL DESIG.

SPECIAL DEVICE (AS NOTED)

FUSTAT BUSS #SSY

JUNCTION BOX

72" TO TOP

SPECIAL OUTLET (SEE SCHEDULE OR AS NOTED)

GROUND FAULT DUPLEX RECEPTACLE

DOUBLE DUPLEX GROUNDED RECEPTACLE

AFF

NL NIGHT LIGHT-WIRE AHEAD OF CONTROLS

ABOVE FINISHED FLOOR

WEATHERPROOF

EXIT LIGHT (SHADING DENOTES EXIT FACE SIDE) CEIL./WALL

SYMBOL

LIGHT FIXTURE & FIXTURE LETTER

LIGHT FIXTURE & FIXTURE LETTER

LIGHT FIXTURE & FIXTURE LETTER

DESCRIPTION

CEILING

CEILING

WALL

CEILING

MOUNTING

UON UNLESS OTHERWISE NOTED

CEIL./WALL

FLOOR/WALL

STRIP LIGHT FIXTURE & FIXTURE LETTER

EM LIGHT FIXTURE ON EMERGENCY POWER

18"AFF

18"AFF

18"AFF

1/2"C.

GROUND FAULT DOUBLE DUPLEX RECEPTACLE 18"AFF

& 1#12 GRD. 1/2"C.

CEIL./WALL

CEIL./WALLCONDUIT HOME RUN, 1 CIRCUIT. 2#12

& 1#12 GRD. 1/2"C.

CEIL./WALLCONDUIT HOME RUN, 1 CIRCUIT. 2#10

& 1#10 GRD. GEN. NOTE 7 & 8#10

EQUIPMENT - SEE EQUIPMENT

CONNECTION SCHEDULE

WALL

CLG

CCTV CAMERA - FIXED

CCTV CAMERA - FIXED

46"AFFFIRE ALARM MANUAL STATION

FIRE ALARM VISUAL SIGNAL

FIRE ALARM SPEAKER

FIRE ALARM CONTROL PANEL WALL

80" TO BOTTOM

COMB. F.A. SPEAKER & VISUAL SIGNAL

80" TO BOTTOM

80" TO BOTTOM

E-001 ELECTRICAL SYMBOLS AND SCHEDULES

E-101 PARTIAL ELECTRICAL FLOOR PLANS

E-102

E-103

E-104

E-105

E-501 ELECTRICAL DETAILS

PARTIAL ELECTRICAL FLOOR PLANS

PARTIAL ELECTRICAL FLOOR PLANS

PARTIAL ELECTRICAL FLOOR PLANS

PARTIAL ELECTRICAL FLOOR PLANS

AHU-30 AIR HANDLING UNIT

CU CONDENSING UNIT

Drawing Title

Approved: Project Director

Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Dwg.Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Columbia, Missouri

E-001

ELECTRICAL SYMBOLS AND

SCHEDULES

INSTALL ANIMAL RESEARCH AIR HANDLER # 589A4-17-181

06/22/2018 BMW JLW

ADDENDUM 1 8/22/2018

Sheets
E-001 - ELECTRICAL SYMBOLS AND SCHEDULES
E-501 - ELECTRICAL DETAILS