S06 - T002 - GENERAL RISER DIAGRAM AND DETAILS-revised.pdf
PDF 806 KB Posted
- Solicitation number
- 36C25222B0016
About this file
This document includes a general riser diagram and details for a project to renovate an electronic security system. The project involves upgrading the security systems at the Jesse Brown VA Medical Center in Chicago, Illinois, including installing an Avigilon access control management system and replacing door hardware. Key details of the project include connecting an Avigilon video management server to the existing VA network, installing card readers, door contacts, request to exit devices, and magnetic locks at doors. The document provides diagrams of typical device connections and locations as well as construction details for different door configurations. Bids for the project were due on April 7th, 2022, with an award date to be determined. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration VISN 12.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LP4502
LP4502
M R
M R
M R
M R
M R
M R
M R
M R
M R
D O
O R
D O
O R
CR
DC
D O
O R
TWO CARD READERS PER
DOOR TYPICAL
CONFIGURATION
ONE CARD READER PER
DOOR TYPICAL
CONFIGURATION
EXISTING LOCAL VA
NETWORK SWITCH
AVIGILON ACM
APPLIANCE (SERVER)
EXISTING LOCAL VA
NETWORK SWITCH
120V PWR
CAT 6
CAT 6
EXISTING VA
NETWORK
BACKBONE
CAT 6
1-PAIR SHIELDED 24AWG RS-485
CABLE WITH DRAIN WIRE
(TYPICAL)
1-PAIR SHIELDED 24AWG RS-485
CABLE WITH DRAIN WIRE
(TYPICAL)
MR52
TYPICAL
CONNECTIONS
- READER (2)
- INPUT (8)
- OUTPUT (6)
EL
REX
120V PWR 120V PWR
IDS
12V OR 24V
DC PWR
RS-485
COMM.
WIRE
CR
DC
LP4502
TYPICAL
CONNECTIONS
- READER (2)
- INPUT/OUTPUT (4)
EL
REX
12V OR 24V
DC PWR
CAT 6
NETWORK
WIRE
RS-485
COMM.
WIRE
FLEXPOWER
FP0150 UNIVERSAL
MOUNTING BOX
GEMINI RGM75 SERIES
RACK MOUNTED UNIT
EXPANSION BOX
(AS NEEDED)
DAMEN BUILDING
1A 7TH FLOOR
BIOMED SERVER
ROOM
TYPICAL TELECOM
ROOM
TYPICAL DOOR
LOCATIONS
TYPICAL TELECOM
ROOM
KEY:
CR = CARD READER
DC = DOOR CONTACT (POSITION SWITCH)
EL = ELECTRONIC LOCK (ELECTRIC STRIKE OR MAG LOCK)
REX = REQUEST TO EXIT DEVICE
IDS = INTRUSION DETECTION SYSTEM
IDS
IDS IDS
IDS COMPOSITE
CABLE
COMPOSITE CABLE (TYPICAL)
COMPOSITE CABLE (TYPICAL)
NOTE: THIS TOPOLOGY IS DIAGRAMMATIC IN NATURE INTENDED TO SHOW THE OVERALL SYSTEM CONNECTIVITY AND
DEVICES THAT CAN BE CONNECTED TO THE LP4502 AND MR52 CARDS. CONTRACTOR TO PROVIDE A SHOP DRAWING
OF A COMPLETE TOPOLOGY AND WIRING DIAGRAM SHOWING ACTUAL SYSTEM AND DEVICES TO BE INSTALLED.
CARD READER /
KEYPAD COMBO
DOUBLE GANG
DOOR STRIKE
(BEYOND)
DOOR CONTACT (BEYOND)
UNSECURED SIDE OF DOORSECURED SIDE OF DOOR
DOOR STRIKE
CARD READER /
KEYPAD COMBO
DOUBLE GANG
DOOR CONTACT
3/4" CCONDUIT TO RUN
UNDERGROUND
UNSECURED SIDE OF DOORSECURED SIDE OF DOOR
PANIC
EXITING DEVICE
DOOR STRIKE
SURFACE MTD. DOOR STRIKE
(BEYOND)
1/2" FLEX C
DOOR CONTACT
3/4" C
CARD READER /
KEYPAD COMBO
DOUBLE GANG
1/2" FLEX C
6"
3' -6
3' -4
REQUEST TO
EXIT (MOTION)
SINGLE GANG BB
J-BOX(RECESSED)
4"x4"x2 1/8"
MOUNTED ABOVE CEILING
(VERIFY IN FIELD w/ EC)
3/4" C AND RS-485
AND 18/2 CABLES
TO CARD
READER
CONTROLLER
TO CARD
READER
CONTROLLER 3/4" C AND RS-485
AND 18/2 CABLES
SECURED CONCEALED VERTICAL RODS UNSECURED CONCEALED VERTICAL RODS
RIGHT HAND REVERSE(RHRB) DOOR
PANIC EXITING DEVICE
WITH CONCEALED
VERTICAL ROD AND
MONITOR SWITCH
SEE PLAN FOR
CONDUIT SIZE
J-BOX(RECESSED) 4"x4"x2 1/8"
MOUNTED ABOVE CEILING
(VERIFY IN FIELD W/ EC)
1/2" FLEX C 1/2" FLEX C
DOOR CONTACT
3/4" C3/4" C
CONCELAED
ELECTRIC POWER
TRANSFER
3/8" CHANNEL
3/4" C
CARD READER / KEYPAD
COMBO SINGLE GANG BB
(VERTICAL)
CONCEALED
ELECTRIC POWER
TRANSFER
3' -6
3' -4
6" 6"
SECURED SIDE OF THE DOOR UNSECURED SIDE OF THE DOOR
J-BOX(RECESSED)
4"x4"x2 1/8"
MOUNTED ABOVE CEILING
(VERIFY IN FIELD w/ EC)
1/2" FLEX C 1/2" FLEX C
DOOR CONTACT
3/4" C
3' -6
3' -4
DOUBLE
MAGNETIC
LOCK
1/2" FLEX C
REQUEST TO
EXIT (MOTION)
SINGLE GANG BB
3/4" C AND RS-485
AND 18/2 CABLES
TO CARD
READER
CONTROLLER
TO CARD
READER
CONTROLLER
3/4" C AND RS-485
AND 18/2 CABLES
1/2" FLEX C
CARD READER /
KEYPAD COMBO
DOUBLE GANG BB
(VERTICAL)
UNSECURED SIDE OF DOORSECURED SIDE OF DOOR
PANIC
EXITING DEVICE
DOOR STRIKE
SURFACE MTD. DOOR STRIKE
(BEYOND)
1/2" FLEX C
DOOR CONTACT
3/4" C
CARD READER /
KEYPAD COMBO
DOUBLE GANG
1/2" FLEX C
6"
3' -6
3' -4
REQUEST TO
EXIT (MOTION)
SINGLE GANG BB
J-BOX(RECESSED)
4"x4"x2 1/8"
MOUNTED ABOVE CEILING
(VERIFY IN FIELD w/ EC)
3/4" C AND RS-485
AND 18/2 CABLES
TO CARD
READER
CONTROLLER
TO CARD
READER
CONTROLLER 3/4" C AND RS-485 AND
18/2 CABLES
MAGNETIC
LOCK
1/2" FLEX C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseArchitect/Engineer of Record StampConsultant
321 4 5 6 7 8 9 10
Sprinkler Status
AE Works, LTD.
418 Beaver Street
Sewickley, PA 15143
Phone: 412-287-7333 www.aeworks.com
B
IM
/V J E
S -0
R e n o v a te E le c tr o n ic S e c u ri ty
S y s te m /J e s s e
B ro w n
V A
M e d ic a l C e n te r M a in
C a m p u s
M E
P
.r v t
/7
/2
:1
:0
A M
T002
GENERAL RISER DIAGRAM AND
DETAILS
RENOVATE ELECTRONIC
SECURITY SYSTEM
820 S. Damen Ave. Chicago, IL 60612
537-19-125
12.21.2021 BK BF
ISSUED FOR BID AND
CONSTRUCTION
NOT TO SCALE
AVIGILON ACM SYSTEM TOPOLOGY
NOT TO SCALE
DOOR ASSEMBLY - GATE DOOR - ELECTRIC STRIKE
NOT TO SCALE
DOOR ASSEMBLY - SINGLE DOOR
NOT TO SCALE
DOOR ASSEMBLY - CONCEALED VERTICAL RODS
NOT TO SCALE
DOOR ASSEMBLY - DOUBLE DOOR - MAGNETIC LOCK
NOT TO SCALE
DOOR ASSEMBLY - SINGLE DOOR - MAGNETIC LOCK
# Revisions Date
1 Addendum 1 04/07/22
ACCOMPANYING 36C25222B0016 0005
| Sheets |
| T002 - GENERAL RISER DIAGRAM AND DETAILS |
File details come from the government source that posted it. Updated .