S06 - T002 - GENERAL RISER DIAGRAM AND DETAILS-revised.pdf

PDF 806 KB Posted

Attached to
Z1DA--537-19-125 Renovate Electronic Security System (VA-22-00034826)
Solicitation number
36C25222B0016
Issued by

About this file

This document includes a general riser diagram and details for a project to renovate an electronic security system. The project involves upgrading the security systems at the Jesse Brown VA Medical Center in Chicago, Illinois, including installing an Avigilon access control management system and replacing door hardware. Key details of the project include connecting an Avigilon video management server to the existing VA network, installing card readers, door contacts, request to exit devices, and magnetic locks at doors. The document provides diagrams of typical device connections and locations as well as construction details for different door configurations. Bids for the project were due on April 7th, 2022, with an award date to be determined. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration VISN 12.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

LP4502

LP4502

M R

M R

M R

M R

M R

M R

M R

M R

M R

D O

O R

D O

O R

CR

DC

D O

O R

TWO CARD READERS PER

DOOR TYPICAL

CONFIGURATION

ONE CARD READER PER

DOOR TYPICAL

CONFIGURATION

EXISTING LOCAL VA

NETWORK SWITCH

AVIGILON ACM

APPLIANCE (SERVER)

EXISTING LOCAL VA

NETWORK SWITCH

120V PWR

CAT 6

CAT 6

EXISTING VA

NETWORK

BACKBONE

CAT 6

1-PAIR SHIELDED 24AWG RS-485

CABLE WITH DRAIN WIRE

(TYPICAL)

1-PAIR SHIELDED 24AWG RS-485

CABLE WITH DRAIN WIRE

(TYPICAL)

MR52

TYPICAL

CONNECTIONS

- READER (2)

- INPUT (8)

- OUTPUT (6)

EL

REX

120V PWR 120V PWR

IDS

12V OR 24V

DC PWR

RS-485

COMM.

WIRE

CR

DC

LP4502

TYPICAL

CONNECTIONS

- READER (2)

- INPUT/OUTPUT (4)

EL

REX

12V OR 24V

DC PWR

CAT 6

NETWORK

WIRE

RS-485

COMM.

WIRE

FLEXPOWER

FP0150 UNIVERSAL

MOUNTING BOX

GEMINI RGM75 SERIES

RACK MOUNTED UNIT

EXPANSION BOX

(AS NEEDED)

DAMEN BUILDING

1A 7TH FLOOR

BIOMED SERVER

ROOM

TYPICAL TELECOM

ROOM

TYPICAL DOOR

LOCATIONS

TYPICAL TELECOM

ROOM

KEY:

CR = CARD READER

DC = DOOR CONTACT (POSITION SWITCH)

EL = ELECTRONIC LOCK (ELECTRIC STRIKE OR MAG LOCK)

REX = REQUEST TO EXIT DEVICE

IDS = INTRUSION DETECTION SYSTEM

IDS

IDS IDS

IDS COMPOSITE

CABLE

COMPOSITE CABLE (TYPICAL)

COMPOSITE CABLE (TYPICAL)

NOTE: THIS TOPOLOGY IS DIAGRAMMATIC IN NATURE INTENDED TO SHOW THE OVERALL SYSTEM CONNECTIVITY AND

DEVICES THAT CAN BE CONNECTED TO THE LP4502 AND MR52 CARDS. CONTRACTOR TO PROVIDE A SHOP DRAWING

OF A COMPLETE TOPOLOGY AND WIRING DIAGRAM SHOWING ACTUAL SYSTEM AND DEVICES TO BE INSTALLED.

CARD READER /

KEYPAD COMBO

DOUBLE GANG

DOOR STRIKE

(BEYOND)

DOOR CONTACT (BEYOND)

UNSECURED SIDE OF DOORSECURED SIDE OF DOOR

DOOR STRIKE

CARD READER /

KEYPAD COMBO

DOUBLE GANG

DOOR CONTACT

3/4" CCONDUIT TO RUN

UNDERGROUND

UNSECURED SIDE OF DOORSECURED SIDE OF DOOR

PANIC

EXITING DEVICE

DOOR STRIKE

SURFACE MTD. DOOR STRIKE

(BEYOND)

1/2" FLEX C

DOOR CONTACT

3/4" C

CARD READER /

KEYPAD COMBO

DOUBLE GANG

1/2" FLEX C

6"

3' -6

3' -4

REQUEST TO

EXIT (MOTION)

SINGLE GANG BB

J-BOX(RECESSED)

4"x4"x2 1/8"

MOUNTED ABOVE CEILING

(VERIFY IN FIELD w/ EC)

3/4" C AND RS-485

AND 18/2 CABLES

TO CARD

READER

CONTROLLER

TO CARD

READER

CONTROLLER 3/4" C AND RS-485

AND 18/2 CABLES

SECURED CONCEALED VERTICAL RODS UNSECURED CONCEALED VERTICAL RODS

RIGHT HAND REVERSE(RHRB) DOOR

PANIC EXITING DEVICE

WITH CONCEALED

VERTICAL ROD AND

MONITOR SWITCH

SEE PLAN FOR

CONDUIT SIZE

J-BOX(RECESSED) 4"x4"x2 1/8"

MOUNTED ABOVE CEILING

(VERIFY IN FIELD W/ EC)

1/2" FLEX C 1/2" FLEX C

DOOR CONTACT

3/4" C3/4" C

CONCELAED

ELECTRIC POWER

TRANSFER

3/8" CHANNEL

3/4" C

CARD READER / KEYPAD

COMBO SINGLE GANG BB

(VERTICAL)

CONCEALED

ELECTRIC POWER

TRANSFER

3' -6

3' -4

6" 6"

SECURED SIDE OF THE DOOR UNSECURED SIDE OF THE DOOR

J-BOX(RECESSED)

4"x4"x2 1/8"

MOUNTED ABOVE CEILING

(VERIFY IN FIELD w/ EC)

1/2" FLEX C 1/2" FLEX C

DOOR CONTACT

3/4" C

3' -6

3' -4

DOUBLE

MAGNETIC

LOCK

1/2" FLEX C

REQUEST TO

EXIT (MOTION)

SINGLE GANG BB

3/4" C AND RS-485

AND 18/2 CABLES

TO CARD

READER

CONTROLLER

TO CARD

READER

CONTROLLER

3/4" C AND RS-485

AND 18/2 CABLES

1/2" FLEX C

CARD READER /

KEYPAD COMBO

DOUBLE GANG BB

(VERTICAL)

UNSECURED SIDE OF DOORSECURED SIDE OF DOOR

PANIC

EXITING DEVICE

DOOR STRIKE

SURFACE MTD. DOOR STRIKE

(BEYOND)

1/2" FLEX C

DOOR CONTACT

3/4" C

CARD READER /

KEYPAD COMBO

DOUBLE GANG

1/2" FLEX C

6"

3' -6

3' -4

REQUEST TO

EXIT (MOTION)

SINGLE GANG BB

J-BOX(RECESSED)

4"x4"x2 1/8"

MOUNTED ABOVE CEILING

(VERIFY IN FIELD w/ EC)

3/4" C AND RS-485

AND 18/2 CABLES

TO CARD

READER

CONTROLLER

TO CARD

READER

CONTROLLER 3/4" C AND RS-485 AND

18/2 CABLES

MAGNETIC

LOCK

1/2" FLEX C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseArchitect/Engineer of Record StampConsultant

321 4 5 6 7 8 9 10

Sprinkler Status

AE Works, LTD.

418 Beaver Street

Sewickley, PA 15143

Phone: 412-287-7333 www.aeworks.com

B

IM

/V J E

S -0

R e n o v a te E le c tr o n ic S e c u ri ty

S y s te m /J e s s e

B ro w n

V A

M e d ic a l C e n te r M a in

C a m p u s

M E

P

.r v t

/7

/2

:1

:0

A M

T002

GENERAL RISER DIAGRAM AND

DETAILS

RENOVATE ELECTRONIC

SECURITY SYSTEM

820 S. Damen Ave. Chicago, IL 60612

537-19-125

12.21.2021 BK BF

ISSUED FOR BID AND

CONSTRUCTION

NOT TO SCALE

AVIGILON ACM SYSTEM TOPOLOGY

NOT TO SCALE

DOOR ASSEMBLY - GATE DOOR - ELECTRIC STRIKE

NOT TO SCALE

DOOR ASSEMBLY - SINGLE DOOR

NOT TO SCALE

DOOR ASSEMBLY - CONCEALED VERTICAL RODS

NOT TO SCALE

DOOR ASSEMBLY - DOUBLE DOOR - MAGNETIC LOCK

NOT TO SCALE

DOOR ASSEMBLY - SINGLE DOOR - MAGNETIC LOCK

# Revisions Date

1 Addendum 1 04/07/22

ACCOMPANYING 36C25222B0016 0005

Sheets
T002 - GENERAL RISER DIAGRAM AND DETAILS

File details come from the government source that posted it. Updated .