Marion testing.pdf

PDF 18 MB Posted

Attached to
H159--VANIHCS 3 Year Electrical Testing Marion and Fort Wayne
Solicitation number
36C25026Q0067
Issued by

About this file

This document is a detailed electrical maintenance and testing report for the Marion VA Medical Center, performed by Premier Power Maintenance on job number 220919 from January 17 to February 16, 2023. The comprehensive report covers electrical system inspections and testing across multiple buildings and substations, including low voltage power circuit breakers, panel inspections, transformers, batteries, capacitors, and vacuum circuit breakers. The technicians identified numerous maintenance issues, such as breakers with loose connections, broken toggles, missing hardware, and thermal temperature variations, and made recommendations for repairs and replacements.

Key findings include deficiencies in various electrical components across buildings 124, 127, 138, 147, 15, 16, 172, 174, 175, and 185, with specific concerns like breaker continuity failures, thermal temperature increases, ground connection issues, and potential equipment degradation. The report encompasses detailed electrical testing results, including insulation resistance measurements, contact resistance tests, and dissolved gas analysis for transformers. The testing was performed by multiple technicians including Melvin Williams, Tracy Stafford, Brandon Andrus, Austin Knight, Andy Barnes, Andy Byrer, and Robert Stranzin, following standards from organizations like InterNational Electrical Testing Association (NETA), National Electrical Code, and IEEE.

View the file

Other files

File Type Posted
36C25026Q0067 0004.pdf PDF
Marion testing 2.pdf PDF
36C25026Q0067 0003.pdf PDF
FTW Testing.pdf PDF
FTW Testing 2.pdf PDF
36C25026Q0067 0002.pdf PDF
Sign-in-Marion.pdf PDF
Sign-in-Ft.-Wayne.pdf PDF
36C25026Q0067 0001.pdf PDF
Attachment VII - marion dry type transformers.docx DOCX document
Attachment I - SOW Attachments.pdf PDF
Attachment IX - Important Information.docx DOCX document
Attachment VI - Marion panel boards.docx DOCX document
Attachment V - Fort Wayne Electrical test equipment list 08-05-25.xlsx XLSX spreadsheet
Attachment IV - Fort Wayne Electrical Panel 08-05-25.xlsx XLSX spreadsheet
Attachment III - Wage Determination - Allen Co.pdf PDF
Attachment II - Wage Determination - Grant Co.pdf PDF
Attachment VIII - Marion MCC.docx DOCX document
36C25026Q0067.docx DOCX document
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

“Integrity, Skill, Teamwork”

W W W . P R E M I E R P O W E R M A I N T E N A N C E . C O M

Engineering Report VA Medical Center-Marion

John Hendricks Maintenance Testing Job Number: 220919

March 15, 2023

Premier Power Maintenance

4035 Championship Drive Indianapolis, IN 46268

T (317) 879-0660 www.premierpowermaintenance.com

March 15, 2023

VA Medical Center –Marion 1700 E. 38th St.

Marion, IN 46953

Attention: John Hendricks

Subject: Maintenance Testing Project No. 220919

Dear Mr. Hendricks, Thank you for the opportunity to provide services for you during this project. Our comprehensive report and recommendations are attached. They detail the work we performed, results obtained and provide recommendations for any corrective actions. Please let us know if you have any questions or need additional information.

As an independent third party electrical testing, maintenance and engineering services firm and full member of the InterNational Electrical Testing Association (NETA), Premier Power Maintenance prides itself in the quality of our services and skills of our people. Thanks again for the opportunity to provide you with electrical testing services. If there is anything more we can do for you, please don’t hesitate to contact us.

Sincerely, Premier Power Maintenance

Melvin Williams Field Service Supervisor

1. Summary

• Maintenance tests and inspections of electrical equipment help assure proper and safe operation.

• This project involved air switches, oil-filled and dry type transformers, low and medium voltage breakers, switchboards, panel inspections, relays and infrared inspections.

• Please refer to Section 5 for complete details regarding comments, deficiencies and recommendations.

2. Objectives

Maintenance Testing

• The equipment and components listed in Section 3.0 of this report have been inspected and tested to help assure their proper and safe operation. Defective or marginal equipment can be identified, repaired, replaced or scheduled for future repairs without costly or unexpected interruptions during normal operating periods.

• The test results are particularly valuable when kept for comparison with past and future maintenance test results. This historic database enables one to predict the probability of equipment failure and thus schedule facility production and financial budgets to accommodate preventive maintenance or repair rather than breakdown maintenance.

Thermographic Survey

• The purpose of infrared inspections is to provide information relative to the physical condition of the electrical distribution system. Loose and poor connections, unbalanced loads, and loose bus joints can be located. These conditions are characterized by increased resistance and accompanied by a temperature rise, which is detected by infrared scanning. The survey was performed while the system was loaded, representative of a “normal” workday.

Oil Testing

• The oil in an oil filled transformer is intended to:

o Provide dielectric strength of the transformer insulation system o Provide efficient cooling o Protect the transformer core and coil assembly from chemical attack

• The oil quality screen (moisture, dielectric, interfacial tension, neutralization number, specific gravity, color and visual) is the standard testing means to determine if the oil is still capable of performing its intended function. While the degradation of oil is a natural process, early detection and remediation will extend the life of the transformer.

Another valuable oil testing method for transformers is the dissolved gas analysis (DGA). This battery of tests, often called fault gas analysis, is the easiest method to determine the operating condition of the transformer itself. Some gases indicate overheating of the unit possibly due to overloading, while other gases indicate a fault type condition within the transformer. The proper monitoring of dissolved gas within the transformer with remediation can prolong the life of the unit. It can also be used as a warning for the need to replace the transformer prior to failure.

3. Service Description

• This project was initiated by John Hendricks with VA Medical Center-Marion. All testing was performed by Premier Power Maintenance field technicians Melvin Williams, Tracy Stafford, Brandon Andrus, Austin Knight, Andy Barnes, Andy Byrer and Robert Stranzin from January 17, 2023 to February 16, 2023.

• For a list of equipment tested in this project, please see test sheets located in the Appendix.

4. Procedure

• All testing is performed in accordance with PPM’s standard procedures including, but not limited to, selected specifications from the following: InterNational Electrical Testing Association (NETA), National Electrical Code (NEC), National Fire Protection Association 70B-Electrical Equipment Maintenance (NFPA 70B), Institute of Electrical and Electronic Engineers (IEEE), American Society for Testing and Materials (ASTM), National Electrical Manufacturer’s Association (NEMA), manufacturer’s instruction manuals and/or project specifications, unless otherwise noted.

5. Results: Comments, Deficiencies and Recommendations

• The following is a list of problems discovered during this testing project along with any corrective action that was made by Premier Power Maintenance. Those corrections beyond the scope of the project that require your additional corrective action are in bolded text.

Based on the results of the inspections and tests performed, the equipment included in this project (see detailed test data in Appendix) is considered serviceable.

o 124: 2AE NQOB-50416: HOLE IN FRONT OF PANEL NEEDS TO BE COVERED.

COVER IS BENT AND MISSING HARDWARE. RECOMMEND REPAIR/REPLACE.

o 124: 2CE NQOB-50416-26AA9: REPLACED BREAKER #30 o 124: 3B NQOB-50416-27881: BREAKER 31/33 WAS REPLACED. TIGHTENED LOOSE

WIRE.

o 124: PH2 5158C03G04: REPLACED BAD 2 PULL BREAKER WITH SPACERS, MISSING

SCREW IN PANEL.

o 124: 1CE NQOB-50416-26AA6: CONTINUITY CHECKS FAILED ON SPARE BREAKER(S).

REPLACED BREAKER 18 AND 20.

o 124: 1BE NQOB-50416-26AA: REPLACED ALL SPARE BREAKERS WHICH FAILED

CONTINUITY CHECKS.

o 138: L3B2 TX0B: #29 HAS A BROKEN TOGGLE. REPLACED #4 BREAKER.

o 138: L3B1 NQOB-50416-22V: REPLACED 3 BREAKERS.

o 138-DP2 42-50416-13: BREAKER 138 P3A IS BROKEN WON'T CLOSE. RECOMMEND

REPAIR.

o 138-DP-1 42-504160-12: 5 BREAKERS RING OUT IN OPEN POSITION. 138 LBB

BREAKER REPLACED WENT FROM 200A TO 150 AMP.

o 138-L3B2 TXOB: #29 BREAKER FOUND WITH BROKEN TOGGLE. REPLACED

# 4 BREAKER.

o 147: TN8 (XFMR): GROUND CABLE WAS LOOSE. TIGHTENED.

o 15: 1A NQ0B-50416-18R: NOTICED SEVERAL SPARE BREAKERS TURNED OFF.

THERE WERE ALSO 3 OPENINGS WHICH WILL NEED BREAKER COVERS.

o 16: 1D: REPLACED BREAKER # 29 DUE TO POOR CONTINUITY CHECKS.

o 16: 1A NQOB-50416-23X1: TURNED OFF SPARE BREAKERS. BREAKER(S) # 34 AND 38

SPARE BREAKERS FAILED CONTINUITY CHECKS.

o 16: 3E: BREAKER # 8 NEEDS REPLACED. MEASURED 124VAC ON LOAD WIRE. TABS

BROKEN ON BREAKER(S) 4 AND 6.

o 172: 1HL2: NEUTRAL PLASTIC BLOCK FOUND BROKEN FROM PANEL. RECOMMEND

REPAIR/REPLACE.

o 172: HEDP1 APB2765A: SPARES IN SLOT 3 DO NOT OPERATE PROPERLY.

o 172: 1LN3B-N AQF3301MBX: INSTALL HOLE COVER FOR UNUSED BREAKER SECTION.

o 172: HDNP1 AUF3244MXB: UNUSED SPACE NEEDS BLANKS/UNUSED BREAKERS

TURNED OFF.

o 172: BHN1 AEF3301MXT: UNUSED BREAKERS TURNED OFF. SPARE BREAKER SNAPPED

FROM MOUNT. BREAKER REMOVED; FILLED OPENING.

o 172: 1HN3 AEF3302MBX: NEUTRAL MOUNTING PLATE BROKEN FROM BOX.

o 172: 1LN7-N AQF3302CTX: FOUND GROUND WIRE LOOSE. RE-TIGHTENED. OPENED UP

ALL SPARE BREAKERS FOUND IN THE 'ON' POSITION.

o 172-TN4 (XMFR): GROUNDS FOUND LOOSE. TIGHTENED.

o 172-TN2 (XFMR) 9T23Q3144: GROUND CONNECTIONS WERE FOUND LOOSE.

TIGHTENED.

o 172-1HN2-N AEF3302BTX: TURNED OFF SPARE BREAKERS. NEUTRAL BAR PLASTIC CLIP

FOUND BROKEN. STILL ISOLATED AND NO ISSUES.

o 172-2LN13 AQF3422CBX: INSTALLED NEW LATCH. TURNED OFF SPARE BREAKERS.

o MAIN BREAKER TX3: PT BLOCK UNDER BREAKER HAD BEEN REMOVED. IT WAS BACK IN

BEFORE RE-ENERGIZING. CUSTOMER WAS INFORMED THAT AFTER REPLACING THAT

FUSE BLOCK IT CAUSED THAT FEED TO DROP A PHASE. THE PT FUSE BLOCK WAS

REMOVED WHICH FIXED THE ISSUE. RECOMMEND REPLACING WITH GENERAL

ELECTRIC POWER METER.

o 175: MDSH2: INSTALLED BLANK o 51: MDP FUSED DISC 42-50416-6B: MISSING HARDWARE ON SIDE PANEL. NEEDS TWO

PHILLIPS HEAD SCREWS.

o 65: 1B NQOB-50416-257: TAPED AN EXPOSED WIRE THAT WAS DISCONNECTED.

o 65: B NQOB-3045-IN: REPLACED BREAKERS 22 AND 13.

o 65: 1A NQOB-50416-252: REPLACED BREAKER #9, REPLACED BRACKET FOR BREAKERS

11 AND 12.

o 65: B-65 3283-4M: COVER HELD ON WITH 1 SCREW AND ELECTRICAL TAPE. MISSING

BREAKER BLANKS.

o 79: 1B: 16 BAD BREAKERS, CUSTOMER SAID ANNOTATE AND MOVE ON. ENTIRE PANEL

NEEDS OVERHAULED.

o 79: 1C 41-32370-1A1: ENTIRE PANEL IS OFF. NONE OF THE BREAKERS RACK OUT AND

PANEL IS MISSING HARDWARE.

o 8-B2 P4260B3200CU: UNUSED HOLE IN BOTTOM RIGHT OF PANEL NEEDS FILLED WITH

BLANK.

o 97: PAINTHOUSE CDP-7: REPLACED BREAKER #3.

o PNL MDP52-BREAKER 52-B (CENTER FUSE/PHASE) SHOWS A THERMAL TEMPERATURE

INCREASE OF 6.2°C IN COMPARISON TO ADJACENT FUSE/PHASE. AT NEXT SCHEDULED

DOWNTIME, CHECK FUSE FOR PROPER SETTING OF FUSE BLADES. REMOVE AND

CLEAN IF NECESSARY (OR CHANGE OUT FUSE).

o BREAKER B-9 (A PHASE WIRE) HAS A THERMAL TEMPERATURE INCREASE OF 7.5°C IN

REFERENCE TO C-PHASE SAME BREAKER. AT NEXT SCHEDULED OUTAGE, CHECK WIRE

FOR DAMAGES/LOOSE CONNECTIONS. ALL BREAKERS WERE CHECKED FOR TORQUE,

TIGHTNESS, AND CONTINUITY ACROSS CLOSED CIRCUIT. MAY NEED TO RE-CHECK WIRE

AND INVESTIGATE LOAD END WHERE EQUIPMENT IS CONNECTED.

o PNL 9-1B BREAKER #11 SHOWS A THERMAL TEMPERATURE INCREASE OF 4.8°C IN

COMPARISON TO ADJACENT LOAD WIRES ON BREAKER #13. THIS BREAKER HAS 2 LOAD

WIRES. NEED TO VERIFY IF SECOND CIRCUIT CAN BE MOVED WITHIN THIS PANEL TO

TAKE LOAD OFF 20A BREAKER.

o MAIN SUBSTATION BATTERY CHARGER: BATTERY CHARGER WAS OFFLINE BECAUSE OF

THE OUTAGE TO PERFORM OTHER TESTING. BOTH POSITIVE AND NEGATIVE TO

GROUND INDICATE THERE IS A GROUND SOMEWHERE ON THE DC SYSTEM IN THE

MAIN SUB. FURTHER INVESTIGATION TO FIND EXACTLY WHERE.

o MAIN SUBSTATION EAST LOOP FEEDER #1: THIS IS A MAGNETIC-AIR BLAST STYLE

BREAKER. PISTOL GRIP WASN'T ABLE TO OPERATE BREAKER OPEN OR CLOSE. NEEDS

FURTHER INVESTIGATION OF UMBILICAL AND CONTROL WIRING.

o MAIN SUBSTATION FEEDER #3: REPLACED THE CLOSE LIGHT FOR PISTOL GRIP.

o MAIN SUBSTATION FEEDER #4: REPLACED LIGHT BULB FOR CLOSED LIGHT INDICATOR.

o MAIN SUBSTATION FEEDER #5: CLOSE LIGHT INDICATOR BULB WAS REPLACED.

o MAIN SUBSTATION WEST LOOP FEEDER #2: CLOSE BULB WAS REPLACED WITH NEW

BULB.

o SWITCH A SUBSTATION 225 kVA TRANSFORMER: RECOMMEND INSPECTIONS IN NEAR

FUTURE TO CHECK TO SEE IF THERE IS AN ACTIVE LEAK.

o SWITCH I SUBSTATION TRANSFORMER: WATER IN BOTTOM OF SWITCH. RECOMMEND

DRILLING A WEEP HOLE IN BOTTOM OF CABINET.

o SWITCH J SUBSTATION TRANSFORMER: OIL TEMPERATURE READS 5'C. RECOMMEND

CHECKING OIL LEVEL AGAIN ONCE TEMPERATURE REACHES 20'C OR ABOVE.

o SWITCH S SUBSTATION MAIN SWITCH: ALL ELECTRICAL TESTING WAS PERFORMED IN

COLD/SNOWY SUB ZERO CONDITONS. INSULATION RESISTANCE READINGS WERE

BELOW NETA STANDARDS. RECOMMEND RETESTING UNDER WARMER WEATHER

CONDITIONS TO CHECK FOR TRENDING.

APPENDIX

MARION VA MEDICAL CENTER

MARION VA MEDICAL CENTERCustomer

Plant

Table of Contents Job #220919

4035 Championship Drive Indianapolis, IN 46268

317-879-0660 www.premierpowermaintenance.com24 Hour Emergency Service REVISED 2/18/2008

User

PagePositionSubstation Equipment

00100 - ENGINEERING REPORT CHECKLIST

MAIN BREAKERBUILDING #124 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

PANEL INSPECTIONS-1BUILDING #124 50955 - PANEL INSPECTION RESULTS_R01-23

MAIN BREAKERBUILDING #127 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

PANEL INSPECTIONSBUILDING #127 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #137 50955 - PANEL INSPECTION RESULTS_R01-23

DP1BUILDING #138 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

EEDP-A MAINBUILDING #138 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

PANEL INSPECTIONS-1BUILDING #138 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-2BUILDING #138 50955 - PANEL INSPECTION RESULTS_R01-23 (2)

SWBD MDP 2BUILDING #138 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

SWDB 138 MAINBUILDING #138 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

PANEL INSPECTIONSBUILDING #147 50955 - PANEL INSPECTION RESULTS_R01-23

MAIN BREAKERBUILDING #15 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

PANEL INSPECTIONS-1BUILDING #15 50955 - PANEL INSPECTION RESULTS_R01-23

MAIN BREAKERBUILDING #16 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

PANEL INSPECTIONS-1BUILDING #16 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #17 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #172 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-2BUILDING #172 50955 - PANEL INSPECTION RESULTS_R01-23 (3)

PANEL INSPECTIONS-3BUILDING #172 50955 - PANEL INSPECTION RESULTS_R01-23 (2)

PANEL INSPECTIONS-4BUILDING #172 50955 - PANEL INSPECTION RESULTS_R01-23 (3)

PANEL INSPECTIONS-5BUILDING #172 50955 - PANEL INSPECTION RESULTS_R01-23 (4)

1 HE6-E MAINBUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

ATS#5 ELEVATOR & EM PNL #1BUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

CHILLER #3BUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

CHILLER 174.CCU2BUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

CHILLER 174-CCU-1BUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

MAIN BREAKER FOR LNDP1BUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

MAIN BREAKER FOR MDAPFBUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

MAIN BREAKER TX 4BUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

MAIN BREAKER TX3BUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

MCC HEBUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

MCC HNBUILDING #174 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

PANEL INSPECTIONS-1BUILDING #174 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-2BUILDING #174 50955 - PANEL INSPECTION RESULTS_R01-23 (2)

ATS #1 HDSCBUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

ATS #2BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

Table of Contents Job #220919

4035 Championship Drive Indianapolis, IN 46268

317-879-0660 www.premierpowermaintenance.com24 Hour Emergency Service REVISED 2/18/2008

PagePositionSubstation Equipment

ATS #3BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

ATS #6 ELEV. EM PANEL #2BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

ATS #7 ELEV EM PANEL #3BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

ATS #8 - 1HRGBUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

EHDS 1 ATS #1BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

EHDS 1 ATS #3BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

EHDS 1 MAIN BREAKERBUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

EHDS 2 ATS #2BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

EHDS 2 ATS #8BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

EHDS 2 MAIN BREAKERBUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

EHDS 2 TE 16BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

ELDS 1 EXISTING ATS BLDG 138 EEDPABUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

ELDS 1 EXISTING ATS BLDG 138 EMDPBUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

ELDS 1 EXISTING EM SWBD BLDG 124BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

ELDS 1 MAIN BREAKERBUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

GEN #1 BREAKERBUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

GEN #2 BREAKERBUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

GEN #3 BREAKERBUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

MAIN BREAKER MDSH5 FROM TX6BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

MAIN BREAKER MDSH6 FROM TX7BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

MAIN BREAKER TX 1BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

MAIN BREAKER TX 2BUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

PANEL INSPECTIONS-1BUILDING #175 50955 - PANEL INSPECTION RESULTS_R01-23

TE 16 MAIN BREAKERBUILDING #175 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

TE16 XFMRBUILDING #175 56750 - XFMR MAINTENANCE AND INSP_R03-23

MLEDP MAIN BREAKERBUILDING #185 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST (2)

MLNDP MAIN BREAKERBUILDING #185 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

PANEL INSPECTIONS-1BUILDING #185 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONSBUILDING #2 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #3 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #4 50955 - PANEL INSPECTION RESULTS_R01-23

MDP-47BUILDING #47 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

PANEL INSPECTIONS-1BUILDING #47 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #5 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #51 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #52 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #53 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #54 50955 - PANEL INSPECTION RESULTS_R01-23

55-MDPBUILDING #55 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

PANEL INSPECTIONS-1BUILDING #55 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #6 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #65 50955 - PANEL INSPECTION RESULTS_R01-23

4035 Championship Drive Indianapolis, IN 46268

317-879-0660 www.premierpowermaintenance.com24 Hour Emergency Service REVISED 2/18/2008

PagePositionSubstation Equipment

BASEMENT DRY CORE XFMRBUILDING #79 57130 - TRANSFORMER LIQUID COOLANT TRENDING

PANEL INSPECTIONS-1BUILDING #79 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #8 50955 - PANEL INSPECTION RESULTS_R01-23 (4)

MDP 9 MAIN 1200A BREAKERBUILDING #9 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

PANEL INSPECTIONS -1BUILDING #9 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-1BUILDING #97 PAINTHOUSE 50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONSBUILDINGS (UNIDENTIFIED) 50955 - PANEL INSPECTION RESULTS_R01-23 (3)

INFRARED SURVEY-1CAMPUS IR SURVEY 52000 - THERMOGRAPHIC INSPECTION

INFRARED SURVEY-2CAMPUS IR SURVEY 52000 - THERMOGRAPHIC INSPECTION

INFRARED SURVEY-3CAMPUS IR SURVEY 52000 - THERMOGRAPHIC INSPECTION (2)

BATTERIESMAIN SUBSTATION 10151 - BATTERY INSPECTION

BATTERY CHARGERMAIN SUBSTATION 10200 - BATTERY CHARGER INSPECTION

CAPACITORSMAIN SUBSTATION 61611 - CAPACITOR BANK TESTS

CONTROL POWER TRANSFORMERMAIN SUBSTATION 27450 - CONTROL POWER TRANSFORMER TEST

EAST LOOP FEEDER #1MAIN SUBSTATION 16100 - VACUUM CIRCUIT BREAKER_R01-23

EAST LOOP FEEDER #1MAIN SUBSTATION 45000 - OVERCURRENT RELAY(2)

FEEDER #3MAIN SUBSTATION 16100 - VACUUM CIRCUIT BREAKER_R01-23

FEEDER #3MAIN SUBSTATION 45000 - OVERCURRENT RELAY(2)

FEEDER #4MAIN SUBSTATION 16100 - VACUUM CIRCUIT BREAKER_R01-23

FEEDER #4MAIN SUBSTATION 45000 - OVERCURRENT RELAY(3)

FEEDER #5MAIN SUBSTATION 16100 - VACUUM CIRCUIT BREAKER_R01-23

FEEDER #5MAIN SUBSTATION 45000 - OVERCURRENT RELAY(4)

MAIN BREAKER 52 AMAIN SUBSTATION 16100 - VACUUM CIRCUIT BREAKER_R01-23

MAIN BREAKER 52 AMAIN SUBSTATION 34567 - MEMO

MAIN BREAKER 52 AMAIN SUBSTATION 45000 - OVERCURRENT RELAY(5)

MAIN BREAKER 52 PMAIN SUBSTATION 16100 - VACUUM CIRCUIT BREAKER_R01-23

MAIN BREAKER 52 PMAIN SUBSTATION 34567 - MEMO

MAIN BREAKER 52 PMAIN SUBSTATION 45000 - OVERCURRENT RELAY(4)

PT DRAWER EASTMAIN SUBSTATION 27200 - VOLTAGE TRANSFORMER TEST (2)

PT DRAWER WESTMAIN SUBSTATION 27200 - VOLTAGE TRANSFORMER TEST

WEST LOOP FEEDER #2MAIN SUBSTATION 16100 - VACUUM CIRCUIT BREAKER_R01-23

WEST LOOP FEEDER #2MAIN SUBSTATION 45000 - OVERCURRENT RELAY(3)

MAIN SWITCHPACT AREA 15600 - FUSED DISCONNECTED INSP

MAIN TRANSFORMERPACT AREA 56750 - XFMR MAINTENANCE AND INSP_R03-23

MAIN TRANSFORMERPACT AREA 57130 - TRANSFORMER LIQUID COOLANT TRENDING

PANEL INSPECTIONS-1PACT AREA 50955 - PANEL INSPECTION RESULTS_R01-23

XFMR BREAKERPACT AREA 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST

225 KVA TRANSFORMERSWITCH A 57130 - TRANSFORMER LIQUID COOLANT TRENDING

500 KVA TRANSFORMERSWITCH A 56750 - XFMR MAINTENANCE AND INSP_R03-23

500 KVA TRANSFORMERSWITCH A 57130 - TRANSFORMER LIQUID COOLANT TRENDING (2)

MAIN SWITCHSWITCH A 15600 - FUSED DISCONNECTED INSP (2)

500 kVA TRANSFORMERSWITCH B 56750 - TRANS. MAINTENANCE AND INSP_r1

4035 Championship Drive Indianapolis, IN 46268

317-879-0660 www.premierpowermaintenance.com24 Hour Emergency Service REVISED 2/18/2008

PagePositionSubstation Equipment

500 KVA TRANSFORMERSWITCH B 57130 - TRANSFORMER LIQUID COOLANT TRENDING

750 KVA TRANSFORMERSWITCH B 56750 - TRANS. MAINTENANCE AND INSP_r1

750 KVA TRANSFORMERSWITCH B 57130 - TRANSFORMER LIQUID COOLANT TRENDING

MAIN SWITCHSWITCH B 15600 - FUSED DISCONNECTED INSP

225 KVA TRANSFORMERSWITCH C 56750 - TRANS. MAINTENANCE AND INSP_r1

225 KVA TRANSFORMERSWITCH C 57130 - TRANSFORMER LIQUID COOLANT TRENDING

300 KVA TRANSFORMERSWITCH C 56750 - TRANS. MAINTENANCE AND INSP_r1

300 KVA TRANSFORMERSWITCH C 57130 - TRANSFORMER LIQUID COOLANT TRENDING

MAIN SWITCHSWITCH C 15600 - FUSED DISCONNECTED INSP

50 KVA SINGLE PHASE TRANSFORMERSWITCH H 56750 - TRANS. MAINTENANCE AND INSP_r1

50 KVA SINGLE PHASE TRANSFORMERSWITCH H 57130 - TRANSFORMER LIQUID COOLANT TRENDING

MAIN SWITCHSWITCH H 15600 - FUSED DISCONNECTED INSP

112.5 KVA TRANSFORMERSWITCH I 56750 - TRANS. MAINTENANCE AND INSP_r1

112.5 KVA TRANSFORMERSWITCH I 57130 - TRANSFORMER LIQUID COOLANT TRENDING

250KVA TRANSFORMERSWITCH I 56750 - TRANS. MAINTENANCE AND INSP_r1 (2)

250KVA TRANSFORMERSWITCH I 57130 - TRANSFORMER LIQUID COOLANT TRENDING

MAIN SWITCHSWITCH I 15600 - FUSED DISCONNECTED INSP

1000 KVA TRANSFORMERSWITCH J 56750 - TRANS. MAINTENANCE AND INSP_r1

1000 KVA TRANSFORMERSWITCH J 57130 - TRANSFORMER LIQUID COOLANT TRENDING

500 KVA TRANSFORMERSWITCH J 56750 - TRANS. MAINTENANCE AND INSP_r1

500 KVA TRANSFORMERSWITCH J 57130 - TRANSFORMER LIQUID COOLANT TRENDING

MAIN SWITCHSWITCH J 15600 - FUSED DISCONNECTED INSP

225 KVA XFMRSWITCH M 56750 - XFMR MAINTENANCE AND INSP_R03-23

225 KVA XFMRSWITCH M 57130 - TRANSFORMER LIQUID COOLANT TRENDING

MAIN SWITCHSWITCH M 15600 - FUSED DISCONNECTED INSP (2)

500 KVA TRANSFORMERSWITCH O 56750 - TRANS. MAINTENANCE AND INSP_r1

500 KVA TRANSFORMERSWITCH O 57130 - TRANSFORMER LIQUID COOLANT TRENDING

MAIN SWITCHSWITCH O 15600 - FUSED DISCONNECTED INSP (3)

MAIN SWITCHSWITCH P 15600 - FUSED DISCONNECTED INSP (3)

XFMR # TX5SWITCH P 56750 - TRANS. MAINTENANCE AND INSP_r1 (2)

XFMR # TX5SWITCH P 57130 - TRANSFORMER LIQUID COOLANT TRENDING (2)

MAIN SWITCHSWITCH Q 15600 - FUSED DISCONNECTED INSP (2)

XFMR # TX4SWITCH Q 56750 - TRANS. MAINTENANCE AND INSP_r1

XFMR # TX4SWITCH Q 57130 - TRANSFORMER LIQUID COOLANT TRENDING

MAIN SWITCHSWITCH R 15600 - FUSED DISCONNECTED INSP

XFMR TX-1SWITCH R 56750 - TRANS. MAINTENANCE AND INSP_r1

XFMR TX-1SWITCH R 57130 - TRANSFORMER LIQUID COOLANT TRENDING

XFMR TX-2SWITCH R 56750 - TRANS. MAINTENANCE AND INSP_r1 (2)

XFMR TX-2SWITCH R 57130 - TRANSFORMER LIQUID COOLANT TRENDING (2)

MAIN SWITCHSWITCH S 15600 - FUSED DISCONNECTED INSP

XFMR TX-6SWITCH S 56750 - TRANS. MAINTENANCE AND INSP_r1 (2)

XFMR TX-6SWITCH S 57130 - TRANSFORMER LIQUID COOLANT TRENDING (2)

4035 Championship Drive Indianapolis, IN 46268

317-879-0660 www.premierpowermaintenance.com24 Hour Emergency Service REVISED 2/18/2008

PagePositionSubstation Equipment

XFMR TX-7SWITCH S 56750 - TRANS. MAINTENANCE AND INSP_r1 (3)

XFMR TX-7SWITCH S 57130 - TRANSFORMER LIQUID COOLANT TRENDING (3)

MAIN SWITCHSWITCH T 15600 - FUSED DISCONNECTED INSP (2)

XFMR # TX3SWITCH T 56750 - TRANS. MAINTENANCE AND INSP_r1

XFMR # TX3SWITCH T 57130 - TRANSFORMER LIQUID COOLANT TRENDING

XFMR # TX8SWITCH T 56750 - TRANS. MAINTENANCE AND INSP_r1

XFMR # TX8SWITCH T 57130 - TRANSFORMER LIQUID COOLANT TRENDING

750 KVA TRANSFORMERSWITCH U 56750 - TRANS. MAINTENANCE AND INSP_r1

750 KVA TRANSFORMERSWITCH U 57130 - TRANSFORMER LIQUID COOLANT TRENDING

MAIN SWITCHSWITCH U 15600 - FUSED DISCONNECTED INSP

D.O.BREAKER TYPE

TRIP UNIT TYPE

122480

CUBICLE CODE

SN / SO NO.GENERAL ELECTRIC

TS32LSIG

NA

1600/2500POWER BREAK

FUSE CAT. NO.

RMS-9 MICROVERSATRIP

SENSOR TAPS

NA

TRIP UNIT CAT #

MANUFACTURER

Test Amps

% of Setting

Performance Tolerance

Pole 1 Pole 2 Pole 3 Targets

Found/Left Found/Left

Trip Unit SettingTest Criteria

LongTime PU

Long Time Delay

Short Time PU

Short Time Delay

Instant PU

Instant Delay

GRD Fault PU

GRD Fault Delay

NA

NA

NA NA NA

Found/Left

NA

NA NA NA NA

NA NA NA NA

NA NA NA NA

NA NA

NA NA NA NA

NA NA NA NA

NA NA NA NANA

NA

NA NA

NA

NA

NA

NA

Primary/Secondary Current Performance Tests

NANA

2.872.87

NA

0.12

NA

NA

0.135

NA

0.12

NA

NA

0.135

0.135 0.132 0.132

931 931

NANA

NA

0.12

NA

2.87

NA

NA

0.12

NA

2.87

NA

0.135

919 919

NANA

NA NA

0.120.12

NA

2.87

NA

NA

2.87

NA

0.37

0.37

MIN

MIN

A

AA

X

A

A

A

A = A

10,640

1,600 1,520

1,520

1,520

1,520

0.13

0.13

A

X 1,600

SENSOR TAP

DELAY

0.13

0.13

RATING PLUG

SENSOR TAP

RATING PLUG

I2T

OUT

OUT

ADDI INFO

MIN

MIN

GRD. FLT.

INST.

SHORT

LONG

FUNCTION

SHORT

LONG

0.95

0.95

Setting

OUT6,080-

INST.

GRD. FLT.

SETTINGS AS FOUND

A

2,500 OUT

SETTINGS AS LEFT FUNCTION Setting DELAY I2T ADDI INFO

10640=

925=

X

X

X

A

A

A

PAGE

USER

ADDRESS

CUSTOMER

LOW VOLTAGE POWER CIRCUIT BREAKER TEST 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

(765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

JOHN HENDRICKS

DATE

SUBSTATION BUILDING #124

2/7/2023 AMBIENT TEMPERATURE 21 17 %

POSITION

ASSET #: OUTDOOR GEAR TOP LEFT

MAIN BREAKER

HUMIDITY°C

COUNTER END

ANDY BARNESTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service 15200, REVISED 2/24/2023

NA

INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE

C/L

NA

NA

C

NA

C

Description

ARC CHUTES

AUXILIARY DEVICES

GROUND CONNECTION

Description

CUBICLE AND RACKING DEVICES

CONTACT FINGERS

LOADING AND ARCING CONTACTS

OVERCURRENT DEV. BATTERY CTRIP UNIT

GOOD

GOOD

NA

NA NA

GOOD

NA

NA

NA

ELECTRICALLY OPERATED

MOUNTING

COUNTER BEGINNING

B.I.

NA

NOYES

FRAME SIZE AMPS V2,500

Insulation Resistance

POLE TO FRAME

10,620

10,320

11,151

10,836

181,335

5,520

4,480

109,600

4,704

115,080

8,380

11,910

151,000

8,799

12,505.5

158,550

5,796

LINE TO LOAD 172,700

EQUIPMENT TEMPERATURE TEMPERATURE CORRECTION FACTOR TO 20 °C

21 1.05°CV °C1,000

POLE 1 (M©) (P1-P2) POLE 2 (M©) (P2-P3)

TEST VOLTAGE

POLE 3 (M©) (P3-P1)

POLE TO POLE

READINGREADING 20°C20°CREADING 20°C

POLE 3

39.029.0 42.0

POLE 2POLE 1

POLE RESISTANCE (µ©)

COMMENTS: TOOK COVER OFF BREAKER BECAUSE HEARD SOMETHING RATTLING AND FOUND A BROKEN METAL FLANGE, DOESN'T SEEM TO AFFECT OPERATION OF BREAKER. CHARGING INDICTOR STICKER FELL OFF OF BREAKER TOO.

DEFICIENCIES:

EQPT. LOCATION

PAGE

USER

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

JOHN HENDRICKS (765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

DATE

SUBSTATION BUILDING #124 PANEL INSPECTIONS-1POSITION

2/9/2023 AMBIENT TEMPERATURE °C HUMIDITY %

ROBERT STRANZINTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

NQ225A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

SQUARE D

CATALOG #

NQ442L2C

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

PRL1100A124: P1 CUTLER HAMMER 5158C03G02

2 UNUSED HOLES IN BOTTOM OF PANEL, MISSING 1 PANEL

COVER SCREW

AA45 KVA124: P1 (XFMR) CUTLER HAMMER V45226

VISIBLE HEAT DAMAGE ON WHAT LOOKS LIKE PAPER COVERING-

CONNECTION POINT LOOKS GOOD.

NQOB225A124: 2AE SQUARE D NQOB-50416

HOLE IN FRONT OF PANEL NEEDS TO BE COVERED.

COVER IS BENT AND MISSING HARDWARE.

NQOB225A124: 2CE SQUARE D NQOB-50416-26AA9

REPLACED BREAKER #30

NQOB225A124: 3AE SQUARE D NQOB-50416-26AA10

NQ200A124: 1 SQUARE D 12253383120020001

NQOB225A124: 3B SQUARE D NQOB-50416-27881

BREAKER 31/33REPLACED, TIGHTENED LOOSE WIRE,

UNUSED HOLE IN BOTTOM OF PANEL

PRL1225A124: PH2 CUTLER HAMMER 5158C03G04

REPLACED BAD 2 PULL BREAKER WITH SPACERS, MISSING

SCREW IN PANEL

NQOB225A124: 2B PANEL SQUARE D NQOB-50416-26AA10

NQOB100A124: B1 SQUARE D NQOB-50416-28AA

NQ225A124: 2C PANEL SQUARE D NQ442L2C

NQOB225A124: 1AE SQUARE D NQOD-50416-26AA5

Y448125A124: 1HL7-L GE AEF3181BTX

TURNED OFF SPARE BREAKERS.

Y448125A124: 1LN13-N GE AQF3301CTX

TURNED OFF SPARE BREAKERS

Y448125A124: 1HN9-N GE AEF3301BTX

Y448125A124:1HE7-E GE AEF3181BTX

NA2000A124: EM SWBD SQUARE D 50416-11

TURNED 2 SPARE BREAKERS OFF

QL15KVA124: TE-11 (XFMR) GE 9T23Q3141

Y448125A124: 1LE7-E GE AQF3121CTX

QL30KVA124: TN-15 (XFMR) GE 9T23Q3142

NQOB225A124: 1CE SQUARE D NQOB-50416-26AA6

CONTINUITY CHECKS FAILED ON SPARE BREAKER(S)

REPLACED BREAKER 18 AND 20.

NQOB225A124: 1BE SQUARE D NQOB-50416-26AA

REPLACED ALL SPARE BREAKERS WHICH FAILED

CONTINUITY CHECKS.

124: 3CE

NA

CUBICLE CODE

SN / SO NO.GENERAL ELECTRIC

TS20LSIG

NA

800/1200HI BREAK

FUSE CAT. NO.

RMS-9 MICROVERSATRIP

SENSOR TAPS

NA

TRIP UNIT CAT #

MANUFACTURER

Test Amps

% of Setting

Performance Tolerance

Pole 1 Pole 2 Pole 3 Targets

Found/Left Found/Left

Trip Unit SettingTest Criteria

LongTime PU

Long Time Delay

Short Time PU

Short Time Delay

Instant PU

Instant Delay

GRD Fault PU

GRD Fault Delay

NA

NA

NA NA NA

Found/Left

NA

NA NA NA NA

NA NA NA NA

NA NA NA NA

NA NA

NA NA NA NA

NA NA NA NA

NA NA NA NANA

NA

NA NA

NA

NA

NA

NA

Primary/Secondary Current Performance Tests

411411

2.872.87

NA

0.12

NA

NA

0.156

NA

0.12

NA

NA

0.156

0.153 0.15 0.15

254 254

NANA

NA

0.12

NA

2.87

NA

0.12

NA

2.87

0.153

258 258

NANA

NA NA

0.120.12

NA

2.87

NA

2.87

0.2

0.2

MIN

MIN

A

AA

X

A

A

A

A = A

2,800

800 400

0.13

0.13

A

X 800

SENSOR TAP

DELAY

0.13

0.13

RATING PLUG

SENSOR TAP

RATING PLUG

I2T

OUT

OUT

ADDI INFO

MIN

MIN

GRD. FLT.

INST.

SHORT

LONG

FUNCTION

SHORT

LONG

0.5

0.5

Setting

OUT1,600-

INST.

GRD. FLT.

SETTINGS AS FOUND

A

1,200 OUT

SETTINGS AS LEFT FUNCTION Setting DELAY I2T ADDI INFO

2800=

240=

X

X

X

A

A

A

PAGE

USER

ADDRESS

CUSTOMER

LOW VOLTAGE POWER CIRCUIT BREAKER TEST 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

(765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

JOHN HENDRICKS

DATE

SUBSTATION BUILDING #127

2/7/2023 AMBIENT TEMPERATURE %

POSITION

ASSET #: OUTDOOR SWITCHGEAR BOTTOM RIGHT

MAIN BREAKER

HUMIDITY°C

COUNTER END

ANDY BARNESTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service 15200, REVISED 2/24/2023

NA

INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE

C/L

NA

NA

C

NA

C

Description

ARC CHUTES

AUXILIARY DEVICES

GROUND CONNECTION

Description

CUBICLE AND RACKING DEVICES

CONTACT FINGERS

LOADING AND ARCING CONTACTS

OVERCURRENT DEV. BATTERY CTRIP UNIT

GOOD

GOOD

NA

NA NA

GOOD

NA

NA

GOOD

ELECTRICALLY OPERATED

MOUNTING

COUNTER BEGINNING

B.I.

NOYES

FRAME SIZE AMPS V1,200

Insulation Resistance

POLE TO FRAME

1,310

1,611,000

1,375.5

1,691,550

2,352,000

1,675

1,461,000

3,000,000

1,534,050

3,150,000

1,018

1,207,000

3,000,000

1,068.9

1,267,350

3,150,000

1,758.75

LINE TO LOAD 2,240,000

EQUIPMENT TEMPERATURE TEMPERATURE CORRECTION FACTOR TO 20 °C

21 1.05°CV °C1,000

POLE 1 (M©) (P1-P2) POLE 2 (M©) (P2-P3)

TEST VOLTAGE

POLE 3 (M©) (P3-P1)

POLE TO POLE

READINGREADING 20°C20°CREADING 20°C

POLE 3

36.940.3 36.9

POLE 2POLE 1

POLE RESISTANCE (µ©)

COMMENTS: TRIP UNIT FLAG WAS OUT ON GROUND FAULT BEFORE REMOVED FROM TEST CELL.

USER

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

JOHN HENDRICKS (765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

DATE

SUBSTATION BUILDING #127 PANEL INSPECTIONSPOSITION

2/9/2023 AMBIENT TEMPERATURE °C HUMIDITY %

MELVIN WILLIAMSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

CDP-7225A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

ITE

CATALOG #

86-70105-508-2

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

NQOB100A127-1E SQUARE D NQOB

CDP-7225A127-OP ITE 87-70105-508-1

TURNED OFF UNUSED SPARE BREAKERS.

127-PP2

USER

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

JOHN HENDRICKS (765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

DATE

SUBSTATION BUILDING #137 PANEL INSPECTIONS-1POSITION

2/10/2023 AMBIENT TEMPERATURE °C HUMIDITY %

ROBERT STRANZINTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

NQOB50A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

SQUARE D

CATALOG #

NQOB-50416-21U

COMMENTS

MAIN BREAKER WIRE LOOSE, TURNED OFF SPARES.

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

137: 1

561004837369001

CUBICLE CODE

SN / SO NO.GE

GB216L3XXXFXXXX

NA

1600POWER BREAK 2

FUSE CAT. NO.

ENTELIGAURD TU

SENSOR TAPS

NA

TRIP UNIT CAT #

MANUFACTURER

Test Amps

% of Setting

Performance Tolerance

Pole 1 Pole 2 Pole 3 Targets

Found/Left Found/Left

Trip Unit SettingTest Criteria

LongTime PU

Long Time Delay

Short Time PU

Short Time Delay

Instant PU

Instant Delay

GRD Fault PU

GRD Fault Delay

0.5

800 NA NA

Found/Left

NA

4800 NA 1.61-2.45 NA

1200 NA NA NA

1800 NA NA NA

NA NA

4800 NA 0.0-0.05 NA

NA NA NA NA

NA NA NA NANA

NA

2 3200

NA

2.25

1.5

Primary/Secondary Current Performance Tests

NANA

2.362.36

0.085

NA

0.044

NA

NA

0.085

NA

0.044

NA

NA

NA NA NA

NA NA

0.0350.035

NA

0.085

2.3

NA

NA

0.085

2.3

NA

NA

NA NA

0.0450.045

NA NA

0.0950.095

2.36

NA

2.36

NA

1.5

1.5

A

AA

X

A

A

A = A1,600

3,200

1,600 800

1,600

2.45

0.06

X 1,600

SENSOR TAP 1,600

DELAY

2.45

0.06

1,600

RATING PLUG

SENSOR TAP

RATING PLUG

I2T ADDI INFO

GRD. FLT.

INST.

SHORT

LONG

FUNCTION

SHORT

LONG

0.5

0.5

Setting

1,200-

INST.

GRD. FLT.

SETTINGS AS FOUND

1,600

A

SETTINGS AS LEFT FUNCTION Setting DELAY I2T ADDI INFO

3200=

X

X

X

A

A

A

PAGE

USER

ADDRESS

CUSTOMER

LOW VOLTAGE POWER CIRCUIT BREAKER TEST 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

(765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

JOHN HENDRICKS

DATE

SUBSTATION BUILDING #138

1/19/2023 AMBIENT TEMPERATURE %

POSITION

ASSET #: BUILDING 138 SWBD

DP1

HUMIDITY°C

COUNTER END

ANDY BYRERTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service 15200, REVISED 2/24/2023

NA

INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE

NA

NA

NA

C

NA

NA

Description

ARC CHUTES

AUXILIARY DEVICES

GROUND CONNECTION

Description

CUBICLE AND RACKING DEVICES

CONTACT FINGERS

LOADING AND ARCING CONTACTS

OVERCURRENT DEV. BATTERY CTRIP UNIT

NA

NA

NA

GOOD C

GOOD

NA

NA

GOOD

ELECTRICALLY OPERATED

MOUNTING

COUNTER BEGINNING

B.I.

NOYES

FRAME SIZE AMPS V1,600

Insulation Resistance

POLE TO FRAME

3,000,000

3,000,000

3,000,000

3,000,000

3,000,000

3,000,000

3,000,000

3,000,000

3,000,000

3,000,000

2,470,000

3,000,000

3,000,000

2,470,000

3,000,000

3,000,000

3,000,000

LINE TO LOAD 3,000,000

EQUIPMENT TEMPERATURE TEMPERATURE CORRECTION FACTOR TO 20 °C

20 1°CV °C1,000

POLE 1 (M©) (P1-P2) POLE 2 (M©) (P2-P3)

TEST VOLTAGE

POLE 3 (M©) (P3-P1)

POLE TO POLE

READINGREADING 20°C20°CREADING 20°C

POLE 3

36.035.0 34.0

POLE 2POLE 1

POLE RESISTANCE (µ©)

COMMENTS:

NA

CUBICLE CODE

SN / SO NO.GENERAL ELECTRIC

NA

NA

800HI-BREAK

FUSE CAT. NO.

NA

SENSOR TAPS

NA

TRIP UNIT CAT #

MANUFACTURER

Test Amps

% of Setting

Performance Tolerance

Pole 1 Pole 2 Pole 3 Targets

Found/Left Found/Left

Trip Unit SettingTest Criteria

LongTime PU

Long Time Delay

Short Time PU

Short Time Delay

Instant PU

Instant Delay

GRD Fault PU

GRD Fault Delay

NA

NA

NA NA NA

Found/Left

NA

NA NA NA NA

NA NA NA NA

NA NA NA NA

NA NA

NA NA NA NA

NA NA NA NA

NA NA NA NANA

NA

NA NA

NA

NA

NA

NA

Primary/Secondary Current Performance Tests

NANA

NANA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA NA NA

NA NA

NANA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA NA

NANA

NA NA

NANA

NA

NA

NA

NA

NA

NA

= AA

X A = A

X

SENSOR TAP

DELAY

RATING PLUG

SENSOR TAP

RATING PLUG

I2T ADDI INFO

GRD. FLT.

INST.

SHORT

LONG

FUNCTION

SHORT

LONG

Setting

INST.

GRD. FLT.

SETTINGS AS FOUND

SETTINGS AS LEFT FUNCTION Setting DELAY I2T ADDI INFO

X

X

X

A

A

A

PAGE

USER

ADDRESS

CUSTOMER

LOW VOLTAGE POWER CIRCUIT BREAKER TEST 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

(765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

JOHN HENDRICKS

DATE

SUBSTATION BUILDING #138

2/10/2023 AMBIENT TEMPERATURE %

POSITION

ASSET #:

EEDP-A MAIN

HUMIDITY°C

COUNTER END

ROBERT STRANZINTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service 15200, REVISED 2/24/2023

NA

INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE

NA

NA

NA

NA

NA

NA

Description

ARC CHUTES

AUXILIARY DEVICES

GROUND CONNECTION

Description

CUBICLE AND RACKING DEVICES

CONTACT FINGERS

LOADING AND ARCING CONTACTS

OVERCURRENT DEV. BATTERY NATRIP UNIT

NA

NA

NA

GOOD C

NA

NA

NA

NA

ELECTRICALLY OPERATED

MOUNTING

COUNTER BEGINNING

B.I.

NA

NOYES

FRAME SIZE AMPS V800

Insulation Resistance

POLE TO FRAME

LINE TO LOAD

EQUIPMENT TEMPERATURE TEMPERATURE CORRECTION FACTOR TO 20 °C

°CV °C

POLE 1 (M©) (P1-P2) POLE 2 (M©) (P2-P3)

TEST VOLTAGE

POLE 3 (M©) (P3-P1)

POLE TO POLE

READINGREADING 20°C20°CREADING 20°C

POLE 3

67.065.0 61.0

POLE 2POLE 1

POLE RESISTANCE (µ©)

COMMENTS: CONTACT RESISTANCE ONLY. BREAKER WAS NOT REMOVED,

USER

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

JOHN HENDRICKS (765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

DATE

SUBSTATION BUILDING #138 PANEL INSPECTIONS-1POSITION

2/9/2023 AMBIENT TEMPERATURE °C HUMIDITY %

A. KNIGHT, A. BARNES, R. STRANZINTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

PRL1A100A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

EATON

CATALOG #

IC966466

COMMENTS

4TH FLOOR AREA

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

NQ100A138: PE SQUARE D 2944242910030001

NEW PANEL (INSTALLED 2-2-2023)

NA225A138: L3A 120/280 SQUARE D NQOB-50416-27BB5

NA225A138: RCU1 GE BR-12055

TURNED SPARE BREAKER OFF (NO LOAD WIRING)

NA225A138: RCU GE BR-32054

BKR # 29 SPARE FOUND TURNED ON. TURNED OFF

NLAB225A138: L3B2 GE TX0B

#29 HAS A BROKEN TOGGLE. REPLACED #4 BREAKER

NDP100A138: E3B FPE BZ-162968

REMOVED SPARE BREAKER FROM BOTTOM OF PANEL

NA100A138: E4A EATON EZ-82048R

A SERIES II600A138: EMDP PANEL GE AQF3306MBX

MISSING COVER HARDWARE

NA400A138: EMI SQUARE D 12-3619176BO

OPENED SPARE BREAKERS

NQOD225A138: EM-2 SQUARE D NQ0D430M225

OPENED ALL SPARE BREAKERS

NA100A138: PNL 138 E2 B SQUARE D NA

NA100A138: PNL 138-E2C SQUARE D MHC-15

1800A138: EEDP-A GE APB4089

BREAKER 138 PE WAS LOCKED OUT- CONTINUITY WAS UNABLE

TO BE TESTED

1400A138: EQXP GE D2006331T

CT SCAN BREAKER (NO CABLES LANDED) TOGGLE HAS A PIECE

BROKEN OFF. TURNED OFF BREAKER.

PRL1A100A138: L4A EATON 1C966401503

PRL1A225A138: P4D EATON 1C96640603

PRL1A225A138: P4A EATON 1C96640G03

NQOB200A138: L3B1 SQUARE D NQOB-50416-22V

REPLACED 3 BREAKERS.

NQOB100A138: 3B3 SQUARE D NQOB-244M

NQ225A138: P1 SQUARE D 29420271440030001

NQOD225A138: L1C2 SQUARE D NQOD442M225

NQOD225A138: L1A SQUARE D NQOB-50416-30GG9

BREAKER 20 WAS MISSING HARDWARE

NQOB100A138: P1A SQUARE D NQOB-50416-27BB

BREAKER 3 WAS TRIPPED, MISSING 1 BREAKER BLANK.

NQOB200A138: L1B1 SQUARE D NQOB-50416-22V

MISSING COVER AND PANEL HARDWARE

NQOB100A138: L1B2 SQUARE D NQOB-50416-22V

NQOB200A138: L2C SQUARE D NQOB-50416-22V

NQOD100A138: P2C SQUARE D NA

SPARES TURNED OFF.

NQOB225A138: P2A SQUARE D NQOB-50416-30GG7

MISSING PANEL HARDWARE.

NQOB225A138: L2A SQUARE D NQOB-50416-30GG8

TURNED OFF SPARES

NA80A138: L3C1A GE NA

NAB225A138: L3C2 GE BR-31508

NQOB100A138: L3C1 SQUARE D NQOB-50416-22V1

TWO OPEN UNUSED HOLES IN BOTTOM OF PANEL.

NQOB200A138: L2B SQUARE D NQOB-50416-22V

NQOB225A138: L3A SQUARE D NQOB-50416-27BB5

TURNED OFF SPARES

138: E48

USER

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

JOHN HENDRICKS (765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

DATE

SUBSTATION BUILDING #138 PANEL INSPECTIONS-2POSITION

2/10/2023 AMBIENT TEMPERATURE 20 °C HUMIDITY 34 %

ANDY BARNESTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

THQB225

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

GENERAL ELECTRIC

CATALOG #

THQB

COMMENTS

SEVERAL SPARE, UNWIRED BREAKERS WERE TURNED OFF

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

NQOB200PNL: 138-LBB SQUARE D NQOB-50416-27BB

SEVERAL SPARE, UNWIRED BREAKERS WERE TURNED OFF

MODEL 5600138-MCC1 SQUARE D H668018

TOP 2 BREAKERS ARE SPARES, P-7 ON, P-1 OFF, P-2 OFF

NQOB225138-LBA SQUARE D NQOB-50416-30GG10

SWBD600SWBD 138 MDP-2 SQUARE D 3619176AD

SWBD 138 MDP-2(CB-13) FULL NAME

NQOB100138-LBC2 SQUARE D NQOB-50416-22V

6 SPARE BREAKER TURNED OFF

NQOB225138-PSA SQUARE D NQOB-50416-30GG11

ONLY TWO BREAKERS IN PANEL ARE BEING USED ALL

OTHERS ARE SPARES

NQOB225138-LBC SQUARE D NQOB-50416-30GG12

BREAKER #11 AND 18 ARE SPARES AND WERE TURNED OFF

NQOB225138-LBC 1 SQUARE D NQOB-50416-30GG13

7 SPARE BREAKERS WERE ON AND WE TURNED THEM OFF

481600138-DP2 SQUARE D 42-50416-13

BREAKER 138 P3A IS BROKEN WON'T CLOSE

421600138-DP3 SQUARE D 50416-14

481600138-DP-1 SQUARE D 42-504160-12

5 BREAKERS RING OUT IN OPEN POSITION, 138 LBB

BREAKER REPLACED WENT FROM 200A TO 150 AMP.

NQOB225138-P3A SQUARE D NQOB-50416-27BB4

SEVERAL SPARE BREAKERS ON, TURNED OFF AFTER

INSPECTION

NANA138-P2-BE NA NA

UNABLE TO PERFORM INSPECTIONS AND TESTING.

PANEL WAS ENERGIZED.

NANA138-L1 NA NA

UNABLE TO PERFORM INSPECTIONS AND TESTING.

PANEL WAS ENERGIZED.

NA100A138-E2B SQUARE D NA

NA120A138-E2C SQUARE D MHC-15

PRL1A100A138-E48 EATON 1C96640G01

NQ100A138 (PENTHOUSE) PE SQUARE D 29443429

NEW PANEL. INSTALLED 2-2-2023.

NA225A138-L3A SQUARE D NQ0B-50416-27BB5

NA225A138-RCUI GE BR-12055

TURNED SPARE BREAKERS OFF

NA200A138-RCU GE BR-32054

TURNED OFF SPARE BREAKERS

NLAB225A138-L3B2 GE TXOB

NDP100A138-E3B FPE B2-162968

FOUND SPARE BREAKER IN BOTTOM OF PANEL.

NA100A138-E4A EATON EZ-82048R

SERIES II600A138-EMDP PANEL GE AQF3306MBX

MISSING COVER HARDWARE

NA400A138-EMI SQUARE D 12-3619176B0

TURNED OFF SPARE BREAKERS

NQ0D225A138-EM-2 SQUARE D NQ0D430M225

TURNED OFF SPARE BREAKERS

NA225A138: P48 EATON E2B2072R

NA225A138: PH3 EAST EATON NA

NQOD100A138: E1A SQUARE D NQOD43OL100

NQOD225A138: EBB SQUARE D NQOD442M225

FOUND 10 SPARE BREAKERS IN BOTTOM OF THE PANEL.

NA225A138: P4C EATON E282072R

PNL:138 BBB

NA

CUBICLE CODE

SN / SO NO.SQUARE D

MH36600

NA

600BOLT-IN

FUSE CAT. NO.

THERMAL MAG TRIP

SENSOR TAPS

NA

TRIP UNIT CAT #

MANUFACTURER

Test Amps

% of Setting

Performance Tolerance

Pole 1 Pole 2 Pole 3 Targets

Found/Left Found/Left

Trip Unit SettingTest Criteria

LongTime PU

Long Time Delay

Short Time PU

Short Time Delay

Instant PU

Instant Delay

GRD Fault PU

GRD Fault Delay

NA

NA NA NA

Found/Left

NA

3000 100 NA GOOD

NA NA NA NA

NA NA NA NA

NA NA

NA NA NA NA

NA NA NA NA

NA NA NA NANA

NA

NA NA

NA

NA

NA

NA

Primary/Secondary Current Performance Tests

NANA

5.55.5

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA

NA NA NA

NA NA

NANA

NA

NA

NA

5.5

NA

NA

NA

NA

5.5

NA

NA

NA NA

NANA

NA NA

NANA

NA

5.5

NA

NA

5.5

NA

= AA

X A = A600 600 3,000

3,000X 600

SENSOR TAP 600

DELAY

RATING PLUG

SENSOR TAP

RATING PLUG

I2T ADDI INFO

GRD. FLT.

INST.

SHORT

LONG

FUNCTION

SHORT

LONG

Setting

INST.

GRD. FLT.

SETTINGS AS FOUND

SETTINGS AS LEFT FUNCTION Setting DELAY I2T ADDI INFO

X

X

X

A

A

A

PAGE

USER

ADDRESS

CUSTOMER

LOW VOLTAGE POWER CIRCUIT BREAKER TEST 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

(765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

JOHN HENDRICKS

DATE

SUBSTATION BUILDING #138

1/18/2023 AMBIENT TEMPERATURE 14 45 %

POSITION

ASSET #: BUILDING 138 PANEL

SWBD MDP 2

HUMIDITY°C

COUNTER END

ANDY BARNESTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service 15200, REVISED 2/24/2023

NA

INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE

NA

NA

NA

C

NA

C

Description

ARC CHUTES

AUXILIARY DEVICES

GROUND CONNECTION

Description

CUBICLE AND RACKING DEVICES

CONTACT FINGERS

LOADING AND ARCING CONTACTS

OVERCURRENT DEV. BATTERY CTRIP UNIT

NA

NA

NA

GOOD C

GOOD

GOOD

NA

GOOD

ELECTRICALLY OPERATED

MOUNTING

COUNTER BEGINNING

B.I.

NOYES

FRAME SIZE AMPS V600

Insulation Resistance

POLE TO FRAME

317,000

2,230,000

317,000

2,230,000

954,000

584,400

879,000

10,070

879,000

10,070

1,072,000

799,000

1,767,000

1,072,000

799,000

1,767,000

584,400

LINE TO LOAD 954,000

EQUIPMENT TEMPERATURE TEMPERATURE CORRECTION FACTOR TO 20 °C

20 1°CV °C1,000

POLE 1 (M©) (P1-P2) POLE 2 (M©) (P2-P3)

TEST VOLTAGE

POLE 3 (M©) (P3-P1)

POLE TO POLE

READINGREADING 20°C20°CREADING 20°C

POLE 3

166.0153.0 138.0

POLE 2POLE 1

POLE RESISTANCE (µ©)

561004837362001

CUBICLE CODE

SN / SO NO.GENERAL ELECTRIC

GB530LXXXFXXXX

NA

3000BOLT-IN

FUSE CAT. NO.

ENTELLIGUARD TU

SENSOR TAPS

NA

TRIP UNIT CAT #

MANUFACTURER

Test Amps

% of Setting

Performance Tolerance

Pole 1 Pole 2 Pole 3 Targets

Found/Left Found/Left

Trip Unit SettingTest Criteria

LongTime PU

Long Time Delay

Short Time PU

Short Time Delay

Instant PU

Instant Delay

GRD Fault PU

GRD Fault Delay

0.5

1500 NA NA

Found/Left

NA

9000 NA NA NA

2250 NA NA NA

3375 NA NA NA

NA NA

9000 NA NA NA

NA NA NA NA

NA NA NA NANA

NA

2 6000

NA

NA

NA

1.5

Primary/Secondary Current Performance Tests

15351535

NANA

0.083

NA

NA

NA

0.083

NA

NA

NA

NA NA NA

NA NA

NANA

0.091

NA

0.091

NA

NA

NA NA

NANA

6060 6060

0.0910.091

NA

NA

1.5

1.5

A

AA

X

A

A

A = A3,000

6,000

3,000 1,500

3,000

1,500

1,500

0.113

0.06

X 3,000

SENSOR TAP 3,000

DELAY

0.113

0.06

3,000

RATING PLUG

SENSOR TAP

RATING PLUG

I2T ADDI INFO

GRD. FLT.

INST.

SHORT

LONG

FUNCTION

SHORT

LONG

0.5

0.5

Setting

2,250-

INST.

GRD. FLT.

SETTINGS AS FOUND

3,000

A

SETTINGS AS LEFT FUNCTION Setting DELAY I2T ADDI INFO

6000=

X

X

X

A

A

A

PAGE

USER

ADDRESS

CUSTOMER

LOW VOLTAGE POWER CIRCUIT BREAKER TEST 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

(765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

JOHN HENDRICKS

DATE

SUBSTATION BUILDING #138

1/19/2023 AMBIENT TEMPERATURE 20 44 %

POSITION

ASSET #: MAIN BREAKER

SWDB 138 MAIN

HUMIDITY°C

COUNTER END

ANDY BYRERTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service 15200, REVISED 2/24/2023

INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE

NA

NA

NA

C

NA

NA

Description

ARC CHUTES

AUXILIARY DEVICES

GROUND CONNECTION

Description

CUBICLE AND RACKING DEVICES

CONTACT FINGERS

LOADING AND ARCING CONTACTS

OVERCURRENT DEV. BATTERY CTRIP UNIT

NA

NA

NA

GOOD C

GOOD

NA

NA

GOOD

ELECTRICALLY OPERATED

MOUNTING

COUNTER BEGINNING

B.I.

NA

NOYES

FRAME SIZE AMPS V3,000

Insulation Resistance

POLE TO FRAME

910,000

916,000

910,000

916,000

1,795,000

838,000

995,000

2,140,000

995,000

2,140,000

746,000

1,164,000

1,667,000

746,000

1,164,000

1,667,000

838,000

LINE TO LOAD 1,795,000

EQUIPMENT TEMPERATURE TEMPERATURE CORRECTION FACTOR TO 20 °C

20 1°CV °C1,000

POLE 1 (M©) (P1-P2) POLE 2 (M©) (P2-P3)

TEST VOLTAGE

POLE 3 (M©) (P3-P1)

POLE TO POLE

READINGREADING 20°C20°CREADING 20°C

POLE 3

34.038.5 36.2

POLE 2POLE 1

POLE RESISTANCE (µ©)

USER

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

JOHN HENDRICKS (765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

DATE

SUBSTATION BUILDING #147 PANEL INSPECTIONSPOSITION

2/9/2023 AMBIENT TEMPERATURE 10 °C HUMIDITY 45 %

Melvin WilliamsTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

Y441400A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

GE

CATALOG #

AQF330FCTX

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

Y442125A147: 2LN11-N GE AQF3301MBX

TURNED OFF SPARE BREAKERS

Y441225A147: 2HN4-N GE AEF3302BBX

NA125A147: 2HN7-N GE AEF3301BBX

TURNED OFF SPARE BREAKERS

Y433125A147: 2HN8-N GE AEF3301BBX

NANA147: TN8 (XFMR) EGS NA

GROUND CABLE WAS LOOSE. TIGHTENED.

147: 2LN10-N

NA

CUBICLE CODE

SN / SO NO.GENERAL ELECTRIC

TS20LSIG

NA

800/1200HI BREAK

FUSE CAT. NO.

RMS-9 MICROVERSATRIP

SENSOR TAPS

NA

TRIP UNIT CAT #

MANUFACTURER

Test Amps

% of Setting

Performance Tolerance

Pole 1 Pole 2 Pole 3 Targets

Found/Left Found/Left

Trip Unit SettingTest Criteria

LongTime PU

Long Time Delay

Short Time PU

Short Time Delay

Instant PU

Instant Delay

GRD Fault PU

GRD Fault Delay

NA

NA

NA NA NA

Found/Left

NA

NA NA NA NA

NA NA NA NA

NA NA NA NA

NA NA

NA NA NA NA

NA NA NA NA

NA NA NA NANA

NA

NA NA

NA

NA

NA

NA

Primary/Secondary Current Performance Tests

408408

2.872.87

NA

0.12

NA

NA

0.155

NA

0.12

NA

NA

0.155

0.153 0.156 0.156

242 242

NANA

NA

0.12

NA

2.87

NA

0.12

NA

2.87

0.153

248 248

NANA

NA NA

0.120.12

NA

2.87

NA

2.87

0.2

0.2

MIN

MIN

A

AA

X

A

A

A

A = A

2,800

800 400

0.13

0.13

A

X 800

SENSOR TAP

DELAY

0.13

0.13

RATING PLUG

SENSOR TAP

RATING PLUG

I2T

OUT

OUT

ADDI INFO

MIN

MIN

GRD. FLT.

INST.

SHORT

LONG

FUNCTION

SHORT

LONG

0.5

0.5

Setting

OUT1,600-

INST.

GRD. FLT.

SETTINGS AS FOUND

A

1,200 OUT

SETTINGS AS LEFT FUNCTION Setting DELAY I2T ADDI INFO

2800=

240=

X

X

X

A

A

A

PAGE

USER

ADDRESS

CUSTOMER

LOW VOLTAGE POWER CIRCUIT BREAKER TEST 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

OWNER REPRESENTATIVE TELEPHONE

MARION VA MEDICAL CENTER; 1700 E 38TH ST.; MARION IN USA 46953

(765) 674-3321 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 220919

JOHN HENDRICKS

DATE

SUBSTATION BUILDING #15

2/7…