FTW Testing 2.pdf

PDF 105 KB Posted

Attached to
H159--VANIHCS 3 Year Electrical Testing Marion and Fort Wayne
Solicitation number
36C25026Q0067
Issued by

About this file

This laboratory analysis report by Doble Engineering details dissolved gas and oil quality tests for four transformers located at the Veteran Affairs substation, owned by Premier Power Maintenance Co. The tests were conducted on samples collected on 03/16/2023 and analyzed on 03/24/2023, with each transformer (1500 West, 1500 East, 500 West, and 500 East) having similar mineral oil characteristics and Cooper Power Systems manufacturing.

The analysis reveals consistent findings across the transformers: all samples show a "Condition is of no immediate concern" with a recommended resample frequency of 1 year. The common comment for each transformer is "Overheating of cellulose," though water content and relative saturation levels are noted as excellent for in-service oil. The transformers have similar specifications, including 12.47 max KV, OA cooling, and volumes between 284-627 gallons. Each transformer's dissolved gas analysis shows trace amounts of hydrogen, oxygen, nitrogen, methane, carbon monoxide, and other gases, with total gas levels ranging from approximately 75,000 to 77,000 ppm.

View the file

Other files

File Type Posted
36C25026Q0067 0004.pdf PDF
Marion testing.pdf PDF
Marion testing 2.pdf PDF
36C25026Q0067 0003.pdf PDF
FTW Testing.pdf PDF
36C25026Q0067 0002.pdf PDF
Sign-in-Marion.pdf PDF
Sign-in-Ft.-Wayne.pdf PDF
36C25026Q0067 0001.pdf PDF
Attachment VII - marion dry type transformers.docx DOCX document
Attachment I - SOW Attachments.pdf PDF
Attachment IX - Important Information.docx DOCX document
Attachment VI - Marion panel boards.docx DOCX document
Attachment V - Fort Wayne Electrical test equipment list 08-05-25.xlsx XLSX spreadsheet
Attachment IV - Fort Wayne Electrical Panel 08-05-25.xlsx XLSX spreadsheet
Attachment VIII - Marion MCC.docx DOCX document
36C25026Q0067.docx DOCX document
Attachment III - Wage Determination - Allen Co.pdf PDF
Attachment II - Wage Determination - Grant Co.pdf PDF
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Laboratory Analysis Report

280849

Premier Power Maintenance Co.

REPORT AUTHORIZATIONORDER INFORMATIONCUSTOMER INFORMATION

Address:

Date Report Issued:

Authorization Signature:

Email:

Authorized By:

Report Revision:

Date Received:

Submitter Ref:

Purchase Order:

Thank you for using Doble Engineering analytical laboratory services, we greatly appreciate the opportunity to serve you and value your business. In accordance with your request, we have performed testing on the sample(s) provided. If the sampling date is not provided, the sample receipt date is used to provide chronological information. Should you have any comments, suggestions or questions please feel free to contact us at the Email listed above.

Primary Email:

Primary Contact:

220919-03162023

03/16/2023

03/26/2023

Lamilla Rosemin lamila.rosemin@premierpower.us

Premier Power Maintenance Co.

4035 Championship Drive

Indianapolis, IN 46268

Campbell, Charis

CCampbell@doble.com

Samples Requiring Immediate Attention

Sample Id Apparatus Type Serial No Miscellaneous Id

Doble Engineering and Morgan Schaffer Laboratories are ISO/IEC 17025 Accredited

The analyses contained in this report are based upon material and information supplied by the customer. Doble Engineering/ Morgan Schaffer do not imply that the contents of the sample received are the same as all such material in the environment from which the sample was taken. Our test results only relate to the sample(s) tested. Doble Engineering/ Morgan Schaffer assume no responsibility and makes no warranty or representation as provided in the Doble Terms and Conditions Revision 030232020. This report must not be reproduced, unless in its entirety, without the written consent of Doble Engineering.

(^Accredited Tests (from the start date of each lab's accreditation), Ŧ Subcontracted Tests, *Non-Doble/MS Imported Test Results).

Doble Engineering Company - 3902 Hanna Circle Suite D, Indianapolis, IN 46241 USA

Design Rev: 210112-01

APPARATUS DETAIL SAMPLING INFORMATION

Serial Number: 976000795

Equipment No: Preservation: Gas Blanketed

Temp Rise C:

XFMR/TRN Name: 1500 WEST

Substation: VETERAN AFFAIRS

Syringe No: 1069

Manufacturer: Cooper Power Systems

Year Made:

Cooling: OA

Max KV: 12.47

Max MVA: 1.5

XFMR/TRN Type: Transformer

Design Type:

1 or 3 Phase: N

Volume: 627

Liquid Type: Mineral

Limit Set: Doble

Vol Units: Gallons

Misc. ID:

Work Order:

Sample Date: 03/16/2023

Sample Time:

Sampling Reason:

Sampled By:

Sample Point: Bottom

Top Oil Temp C: 30

Humidity:

Amb Temp C:

TRANSFORMER

3/16/2023

3/24/2023

280849-001

Hydrogen (H2) ASTM D3612 IEC 60567 (ppm ) ^ 8.9

Oxygen (O2) ASTM D3612 IEC 60567 (ppm ) ^ 8120

Nitrogen (N2) ASTM D3612 IEC 60567 (ppm ) ^ 65600

Methane (CH4) ASTM D3612 IEC 60567 (ppm ) ^ 11.2

Carbon Monox. (CO) ASTM D3612 IEC 60567 (ppm ) ^ 935

Ethane (C2H6) ASTM D3612 IEC 60567 (ppm ) ^ 1.3

Carbon Dioxide (CO2) ASTM D3612 IEC 60567 (ppm ) ^ 2612

Ethylene (C2H4) ASTM D3612 IEC 60567 (ppm ) ^ 26.3

Acetylene (C2H2) ASTM D3612 IEC 60567 (ppm ) ^ 0.0

Total Gas (ppm ) ^ 77315

Comb. Gas (ppm ) ^ 983

Est. TCG, % of Gas Space ^ 1.03

Ethylene-Acetylene Ratio ^ 0.00

PPM/Day (ppm/day ) ^ 0.0

Dissolved Gas Analysis

Sample Id: 280849-001 Serial Number: 976000795 Misc Id:

Sample Date:

Analysis Date:

Doble Sample Id:

Top Oil Temperature:

^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 10/29/2019)

*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined

CRITICALITY: Condition is of no immediate concern.

Resample Frequency: 1 year

Comments: Overheating of cellulose.

3/16/2023

3/24/2023

280849-001

Water Content D1533 IEC 60814 (ppm ) ^ 1

Relative Saturation (% ) ^ 1.2

Color D1500 D1500 ^ 1.0

Dielectric, D 1816, 1mm gap D1816 (kV ) ^ 43

Interfacial Tension D971 (mN/m ) ^ 27.7

Neut. Number D974 (mgKOH/g ) ^ 0.01

Power Factor @ RT D924 (% ) ^ 0.046

Specific Gravity By D4052 D4052 (60/60 ) ^ 0.8733

Visual Examination D1524 ^ C&B

Oil Quality Tests

Sample Id: 280849-001 Serial Number: 976000795 Misc Id:

Sample Date:

Analysis Date:

Doble Sample Id:

Top Oil Temperature:

^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 10/29/2019)

*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined

Comments: The water content as reported in relative saturation is excellent for in-service oil. Other results are acceptable.

Serial Number: 976000796

Equipment No: Preservation: Gas Blanketed

Temp Rise C:

XFMR/TRN Name: 1500 EAST

Substation: VETERAN AFFAIRS

Syringe No: IBP551

Manufacturer: Cooper Power Systems

Year Made:

Cooling: OA

Max KV: 12.47

Max MVA: 1.5

XFMR/TRN Type: Transformer

Design Type:

1 or 3 Phase: N

Volume: 627

Liquid Type: Mineral

Limit Set: Doble

Vol Units: Gallons

Misc. ID:

Work Order:

Sample Date: 03/16/2023

Sample Time:

Sampling Reason:

Sampled By:

Sample Point: Bottom

Top Oil Temp C: 30

Humidity:

Amb Temp C:

TRANSFORMER

3/16/2023

3/24/2023

280849-002

Hydrogen (H2) ASTM D3612 IEC 60567 (ppm ) ^ 9.6

Oxygen (O2) ASTM D3612 IEC 60567 (ppm ) ^ 8100

Nitrogen (N2) ASTM D3612 IEC 60567 (ppm ) ^ 63900

Methane (CH4) ASTM D3612 IEC 60567 (ppm ) ^ 11.4

Carbon Monox. (CO) ASTM D3612 IEC 60567 (ppm ) ^ 932

Ethane (C2H6) ASTM D3612 IEC 60567 (ppm ) ^ 1.2

Carbon Dioxide (CO2) ASTM D3612 IEC 60567 (ppm ) ^ 2573

Ethylene (C2H4) ASTM D3612 IEC 60567 (ppm ) ^ 24.0

Acetylene (C2H2) ASTM D3612 IEC 60567 (ppm ) ^ 0.0

Total Gas (ppm ) ^ 75551

Comb. Gas (ppm ) ^ 978

Est. TCG, % of Gas Space ^ 1.05

Ethylene-Acetylene Ratio ^ 0.00

PPM/Day (ppm/day ) ^ 0.1

Dissolved Gas Analysis

Sample Id: 280849-002 Serial Number: 976000796 Misc Id:

Sample Date:

Analysis Date:

Doble Sample Id:

Top Oil Temperature:

^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 10/29/2019)

*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined

CRITICALITY: Condition is of no immediate concern.

Resample Frequency: 1 year

Comments: Overheating of cellulose.

280849-002

Water Content D1533 IEC 60814 (ppm ) ^ 1

Relative Saturation (% ) ^ 1.2

Color D1500 D1500 ^ L1.5

Dielectric, D 1816, 1mm gap D1816 (kV ) ^ 42

Interfacial Tension D971 (mN/m ) ^ 27.5

Neut. Number D974 (mgKOH/g ) ^ 0.01

Power Factor @ RT D924 (% ) ^ 0.045

Specific Gravity By D4052 D4052 (60/60 ) ^ 0.8731

Visual Examination D1524 ^ C&B

Oil Quality Tests

Sample Id: 280849-002 Serial Number: 976000796 Misc Id:

Sample Date:

Analysis Date:

Doble Sample Id:

Top Oil Temperature:

^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 10/29/2019)

*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined

Comments: The water content as reported in relative saturation is excellent for in-service oil. Other results are acceptable.

Serial Number: 979003984

Equipment No: Preservation: Gas Blanketed

Temp Rise C:

XFMR/TRN Name: 500 WEST

Substation: VETERAN AFFAIRS

Syringe No: EE426

Manufacturer: Cooper Power Systems

Year Made:

Cooling: OA

Max KV: 12.47

Max MVA: 0.5

XFMR/TRN Type: Transformer

Design Type:

1 or 3 Phase: N

Volume: 284

Liquid Type: Mineral

Limit Set: Doble

Vol Units: Gallons

Misc. ID:

Work Order:

Sample Date: 03/16/2023

Sample Time:

Sampling Reason:

Sampled By:

Sample Point: Bottom

Top Oil Temp C: 10

Humidity:

Amb Temp C:

TRANSFORMER

3/16/2023

3/24/2023

280849-003

Hydrogen (H2) ASTM D3612 IEC 60567 (ppm ) ^ 90.7

Oxygen (O2) ASTM D3612 IEC 60567 (ppm ) ^ 735

Nitrogen (N2) ASTM D3612 IEC 60567 (ppm ) ^ 69500

Methane (CH4) ASTM D3612 IEC 60567 (ppm ) ^ 22.3

Carbon Monox. (CO) ASTM D3612 IEC 60567 (ppm ) ^ 761

Ethane (C2H6) ASTM D3612 IEC 60567 (ppm ) ^ 3.2

Carbon Dioxide (CO2) ASTM D3612 IEC 60567 (ppm ) ^ 4897

Ethylene (C2H4) ASTM D3612 IEC 60567 (ppm ) ^ 20.3

Acetylene (C2H2) ASTM D3612 IEC 60567 (ppm ) ^ 0.0

Total Gas (ppm ) ^ 76030

Comb. Gas (ppm ) ^ 898

Est. TCG, % of Gas Space ^ 1.04

Ethylene-Acetylene Ratio ^ 0.00

PPM/Day (ppm/day ) ^ 0.0

Dissolved Gas Analysis

Sample Id: 280849-003 Serial Number: 979003984 Misc Id:

Sample Date:

Analysis Date:

Doble Sample Id:

Top Oil Temperature:

^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 10/29/2019)

*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined

CRITICALITY: Condition is of no immediate concern.

Resample Frequency: 1 year

Comments: Overheating of cellulose.

280849-003

Water Content D1533 IEC 60814 (ppm ) ^ 1

Relative Saturation (% ) ^ 2.8

Color D1500 D1500 ^ L1.5

Dielectric, D 1816, 1mm gap D1816 (kV ) ^ 46

Interfacial Tension D971 (mN/m ) ^ 27.4

Neut. Number D974 (mgKOH/g ) ^ 0.01

Power Factor @ RT D924 (% ) ^ 0.053

Specific Gravity By D4052 D4052 (60/60 ) ^ 0.8717

Visual Examination D1524 ^ C&B

Oil Quality Tests

Sample Id: 280849-003 Serial Number: 979003984 Misc Id:

Sample Date:

Analysis Date:

Doble Sample Id:

Top Oil Temperature:

^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 10/29/2019)

*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined

Comments: The water content as reported in relative saturation is excellent for in-service oil. Other results are acceptable.

Serial Number: 979003985

Equipment No: Preservation: Gas Blanketed

Temp Rise C:

XFMR/TRN Name: 500 EAST

Substation: VETERAN AFFAIRS

Syringe No: FM395

Manufacturer: Cooper Power Systems

Year Made:

Cooling: OA

Max KV: 12.47

Max MVA: 0.5

XFMR/TRN Type: Transformer

Design Type:

1 or 3 Phase: N

Volume: 284

Liquid Type: Mineral

Limit Set: Doble

Vol Units: Gallons

Misc. ID:

Work Order:

Sample Date: 03/16/2023

Sample Time:

Sampling Reason:

Sampled By:

Sample Point: Bottom

Top Oil Temp C: 10

Humidity:

Amb Temp C:

TRANSFORMER

3/16/2023

3/24/2023

280849-004

Hydrogen (H2) ASTM D3612 IEC 60567 (ppm ) ^ 108.3

Oxygen (O2) ASTM D3612 IEC 60567 (ppm ) ^ 809

Nitrogen (N2) ASTM D3612 IEC 60567 (ppm ) ^ 70500

Methane (CH4) ASTM D3612 IEC 60567 (ppm ) ^ 24.2

Carbon Monox. (CO) ASTM D3612 IEC 60567 (ppm ) ^ 820

Ethane (C2H6) ASTM D3612 IEC 60567 (ppm ) ^ 3.2

Carbon Dioxide (CO2) ASTM D3612 IEC 60567 (ppm ) ^ 4710

Ethylene (C2H4) ASTM D3612 IEC 60567 (ppm ) ^ 20.6

Acetylene (C2H2) ASTM D3612 IEC 60567 (ppm ) ^ 0.0

Total Gas (ppm ) ^ 76995

Comb. Gas (ppm ) ^ 976

Est. TCG, % of Gas Space ^ 1.14

Ethylene-Acetylene Ratio ^ 0.00

PPM/Day (ppm/day ) ^ 0.0

Dissolved Gas Analysis

Sample Id: 280849-004 Serial Number: 979003985 Misc Id:

Sample Date:

Analysis Date:

Doble Sample Id:

Top Oil Temperature:

^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 10/29/2019)

*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined

CRITICALITY: Condition is of no immediate concern.

Resample Frequency: 1 year

Comments: Overheating of cellulose.

280849-004

Water Content D1533 IEC 60814 (ppm ) ^ 2

Relative Saturation (% ) ^ 5.6

Color D1500 D1500 ^ L1.5

Dielectric, D 1816, 1mm gap D1816 (kV ) ^ 49

Interfacial Tension D971 (mN/m ) ^ 26.6

Neut. Number D974 (mgKOH/g ) ^ 0.01

Power Factor @ RT D924 (% ) ^ 0.037

Specific Gravity By D4052 D4052 (60/60 ) ^ 0.8717

Visual Examination D1524 ^ C&B

Oil Quality Tests

Sample Id: 280849-004 Serial Number: 979003985 Misc Id:

Sample Date:

Analysis Date:

Doble Sample Id:

Top Oil Temperature:

^These samples were performed under the Doble and Morgan Schaffer laboratories ISO 17025 accreditation. (Accreditation Date: 10/29/2019)

*Imported results from non-Doble or Morgan Schaffer sources, the accuracy of the results cannot be determined

Comments: The water content as reported in relative saturation is excellent for in-service oil. Other results are acceptable.