Marion testing 2.pdf

PDF 1 MB Posted

Attached to
H159--VANIHCS 3 Year Electrical Testing Marion and Fort Wayne
Solicitation number
36C25026Q0067
Issued by

About this file

This document is an engineering report by Premier Power Maintenance documenting transformer oil sampling performed at the Marion VA Medical Center on February 11, 2025. The report details oil testing for six transformers located at the facility, including dissolved gas analysis (DGA) and oil quality tests. The analysis was conducted by field technician Melvin Williams using standard procedures from organizations like NETA, NEC, and IEEE.

The report indicates that all tested transformers are considered serviceable, with most showing low volumes of combustible gases and acceptable water content levels. One transformer (TX3 Transformer) was noted to have potential overheating of cellulose insulation, with a recommendation to test for furanic compounds or methanol and ethanol. The sampling included transformers from various locations like Building 9, Building 51, Building 79, and Building 185, with capacities ranging from 0.3 to 1 MVA. Each transformer's dissolved gas and oil quality metrics were comprehensively documented, with a consistent recommendation of a 1-year resample frequency.

View the file

Other files

File Type Posted
36C25026Q0067 0004.pdf PDF
Marion testing.pdf PDF
36C25026Q0067 0003.pdf PDF
FTW Testing.pdf PDF
FTW Testing 2.pdf PDF
36C25026Q0067 0002.pdf PDF
36C25026Q0067 0001.pdf PDF
Sign-in-Marion.pdf PDF
Sign-in-Ft.-Wayne.pdf PDF
Attachment III - Wage Determination - Allen Co.pdf PDF
Attachment II - Wage Determination - Grant Co.pdf PDF
Attachment VII - marion dry type transformers.docx DOCX document
Attachment I - SOW Attachments.pdf PDF
Attachment IX - Important Information.docx DOCX document
Attachment VI - Marion panel boards.docx DOCX document
Attachment V - Fort Wayne Electrical test equipment list 08-05-25.xlsx XLSX spreadsheet
Attachment IV - Fort Wayne Electrical Panel 08-05-25.xlsx XLSX spreadsheet
Attachment VIII - Marion MCC.docx DOCX document
36C25026Q0067.docx DOCX document
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

“Integrity, Skill, Teamwork”

W W W . P R E M I E R P O W E R M A I N T E N A N C E . C O M

Engineering Report Marion VA Medical Center

Matt Schamber Oil Samples

Job Number: 240838 February 21, 2025

Premier Power Maintenance

4035 Championship Drive Indianapolis, IN 46268

T (317) 879-0660 www.premierpowermaintenance.com

February 21, 2025

Marion VA Medical Center 1700 E 38th St.

Marion, IN 46953

Attention: Matt Schamber

Subject: Maintenance Testing Project No. 240838

Dear Mr. Schamber, Thank you for the opportunity to provide services for you during this project. Our comprehensive report and recommendations are attached. They detail the work we performed, results obtained and provide recommendations for any corrective actions. Please let us know if you have any questions or need additional information.

As an independent third party electrical testing, maintenance and engineering services firm and full member of the InterNational Electrical Testing Association (NETA), Premier Power Maintenance prides itself in the quality of our services and skills of our people. Thanks again for the opportunity to provide you with electrical testing services. If there is anything more we can do for you, please don’t hesitate to contact us.

Sincerely, Premier Power Maintenance

Melvin Williams Field Service Specialist

1. Summary

• This project involved transformer oil sampling.

• Please refer to Section 5 for complete details regarding comments, deficiencies and recommendations.

2. Objectives

Oil Testing

• The oil in an oil filled transformer is intended to:

o Provide dielectric strength of the transformer insulation system o Provide efficient cooling o Protect the transformer core and coil assembly from chemical attack

• The oil quality screen (moisture, dielectric, interfacial tension, neutralization number, specific gravity, color and visual) is the standard testing means to determine if the oil is still capable of performing its intended function. While the degradation of oil is a natural process, early detection and remediation will extend the life of the transformer.

Another valuable oil testing method for transformers is the dissolved gas analysis (DGA). This battery of tests, often called fault gas analysis, is the easiest method to determine the operating condition of the transformer itself. Some gases indicate overheating of the unit possibly due to overloading, while other gases indicate a fault type condition within the transformer. The proper monitoring of dissolved gas within the transformer with remediation can prolong the life of the unit. It can also be used as a warning for the need to replace the transformer prior to failure.

3. Service Description

• This project was initiated by Matt Schamber with Marion VA Medical Center. All testing was performed by Premier Power Maintenance field technician Melvin Williams on February 11, 2025.

• For a list of equipment tested in this project, please see test sheets located in the Appendix.

4. Procedure

• All testing is performed in accordance with PPM’s standard procedures including, but not limited to, selected specifications from the following: InterNational Electrical Testing Association (NETA), National Electrical Code (NEC), National Fire Protection Association 70B-Electrical Equipment Maintenance (NFPA 70B), Institute of Electrical and Electronic Engineers (IEEE), American Society for Testing and Materials (ASTM), National Electrical Manufacturer’s Association (NEMA), manufacturer’s instruction manuals and/or project specifications, unless otherwise noted.

5. Results: Comments, Deficiencies and Recommendations

• Based on the results of the inspections and tests performed, the equipment included in this project is considered serviceable.

APPENDIX

MARION VA MEDICAL CENTER

MARION VA MEDICAL CENTERCustomer

Plant

Table of Contents Job #240838

4035 Championship Drive Indianapolis, IN 46268

317-879-0660 www.premierpowermaintenance.com24 Hour Emergency Service REVISED 2/18/2008

OIL SAMPLESMARION VA FACILITIES

User

PagePositionSubstation Equipment

34567 - MEMO

PAGE

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

MATT SCHAMBER (765) 667-1207 x74390

1700 E 38TH ST.; MARION IN USA 46953

MARION VA MEDICAL CENTER

JOB # 240838

OWNER REPRESENTATIVE TELEPHONE

SUBSTATION MARION VA FACILITIES OIL SAMPLESPOSITION

EQPT. LOCATIONDATE 2/11/2025 AMBIENT TEMPERATURE HUMIDITY %°F °C

MARION VA MEDICAL CENTER MAINTENANCE PULLED 6 DGA OIL SAMPLES FROM THE FOLLOWING

OIL-FILLED TRANSFORMERS;

SWITCH T-TX3 TRANSFORMER

SWITCH J 500 KVA TRANSFORMER

SWITCH C-300 KVA TRANSFORMER

SWITCH B- 750 KVA TRANSFORMER

SWITCH B- 500KVA TRANSFORMER

SWITCH U- 750KVA TRANSFORMER

SAMPLES WERE COLLECTED FROM THE CUSTOMER ON 2/11/2025 BY MELVIN WILLIAMS.

APPARATUS DETAIL SAMPLING INFORMATION

Serial Number: 88V4406 Cooling: OA Temp Rise C: 45 Syringe No: GG895 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Gas Blanketed Misc. ID: Part Position: Bottom XFMR/TRN Name: T-CT Max MVA: 0.5 Liquid Type: Mineral Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: XFMR Volume: 245 Sample Date: 2025-02-11 Humidity:

Manufacturer Vantran Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-002 Serial Number: 88V4406 Misc Id:

Dissolved Gas Analysis

Sample Date: 2025-02-11 2023-01-20 Analysis Date: 2025-02-15 2023-02-23 Doble Sample Id: 313369-002 279833-021 Top Oil Temperature: 10 5

Hydrogen (H2) ASTM D3612 IEC 60567(ppm) ^ 4.0 15

Oxygen (O2) ASTM D3612 IEC 60567(ppm) ^ 14300 6310

Nitrogen (N2) ASTM D3612 IEC 60567(ppm) ^ 69900 71300

Methane (CH4) ASTM D3612 IEC 60567(ppm) ^ 15 19

Carbon Monox. (CO) ASTM D3612 IEC 60567(ppm) ^ 133 244

Ethane (C2H6) ASTM D3612 IEC 60567(ppm) ^ 28 27

Carbon Dioxide (CO2) ASTM D3612 IEC 60567(ppm) ^ 2070 2260

Ethylene (C2H4) ASTM D3612 IEC 60567(ppm) ^ 6.2 6.9

Acetylene (C2H2) ASTM D3612 IEC 60567(ppm) ^ 0 0

Total Gas (ppm) ^ 86456 80185

Comb. Gas (ppm) ^ 186 312

Est. TCG, % of Gas Space ^ 0.15 0.29

Ethylene-Acetylene Ratio ^ 0.00 0.00

H2+C2H2:TCG-CO Ratio 0.08 0.05

PPM/Day (ppm/day) ^ -0.2

CRITICALITY: Condition is of no immediate concern.

Resample Frequency: 1 year Comments: There is a low volume of combustible gases present.

Doble Indianapolis, 3902 Hanna Circle, Suite D, Indianapolis, IN, 46241, USA Page 1 of 2

Serial Number: 88V4406 Cooling: OA Temp Rise C: 45 Syringe No: GG895 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Gas Blanketed Misc. ID: Part Position: Bottom XFMR/TRN Name: T-CT Max MVA: 0.5 Liquid Type: Mineral Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: XFMR Volume: 245 Sample Date: 2025-02-11 Humidity:

Manufacturer Vantran Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-002 Serial Number: 88V4406 Misc Id:

Oil Quality Tests

Sample Date: 2025-02-11 2023-01-20 1998-06-18 Analysis Date: 2025-02-15 2023-02-23 2012-07-18 Doble Sample Id: 313369-002 279833-021 118901-001 Top Oil Temperature: 10 5

Water Content D1533 IEC 60814(ppm) ^ 8 4 30 *

Relative Saturation (%) ^ 22.3 14.1

Comments: The water content as reported in relative saturation is good to okay for in service oil.

Doble Indianapolis, 3902 Hanna Circle, Suite D, Indianapolis, IN, 46241, USA Page 2 of 2

Serial Number: 1250013119 Cooling: KNAN Temp Rise C: Syringe No: MM245 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Misc. ID: Part Position: Bottom XFMR/TRN Name: BUILDING 9 XFMR Max MVA: 0.3 Liquid Type: Natural Esters Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: TRN Volume: 192 Sample Date: 2025-02-11 Humidity:

Manufacturer Cooper Power Systems Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-003 Serial Number: 1250013119 Misc Id:

Dissolved Gas Analysis

Sample Date: 2025-02-11 2023-01-18 Analysis Date: 2025-02-15 2023-02-23 Doble Sample Id: 313369-003 279833-007 Top Oil Temperature: 10 21

Hydrogen (H2) ASTM D3612 IEC 60567(ppm) ^ 1.3 1.0

Oxygen (O2) ASTM D3612 IEC 60567(ppm) ^ 241 192

Nitrogen (N2) ASTM D3612 IEC 60567(ppm) ^ 69200 56800

Methane (CH4) ASTM D3612 IEC 60567(ppm) ^ 3.7 2.8

Carbon Monox. (CO) ASTM D3612 IEC 60567(ppm) ^ 15 13

Ethane (C2H6) ASTM D3612 IEC 60567(ppm) ^ 236 259

Carbon Dioxide (CO2) ASTM D3612 IEC 60567(ppm) ^ 1200 1280

Ethylene (C2H4) ASTM D3612 IEC 60567(ppm) ^ 5.3 4.8

Acetylene (C2H2) ASTM D3612 IEC 60567(ppm) ^ 0.1 0.1

Total Gas (ppm) ^ 70902 58556

Comb. Gas (ppm) ^ 261 281

Est. TCG, % of Gas Space ^ 0.03 0.04

Ethylene-Acetylene Ratio ^ 53.00 48.00

H2+C2H2:TCG-CO Ratio 0.01 0.00

PPM/Day (ppm/day) ^ 0.0

Serial Number: 1250013119 Cooling: KNAN Temp Rise C: Syringe No: MM245 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Misc. ID: Part Position: Bottom XFMR/TRN Name: BUILDING 9 XFMR Max MVA: 0.3 Liquid Type: Natural Esters Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: TRN Volume: 192 Sample Date: 2025-02-11 Humidity:

Manufacturer Cooper Power Systems Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-003 Serial Number: 1250013119 Misc Id:

Oil Quality Tests

Sample Date: 2025-02-11 2023-01-18 Analysis Date: 2025-02-15 2023-02-23 Doble Sample Id: 313369-003 279833-007 Top Oil Temperature: 10 21

Water Content D1533 IEC 60814(ppm) ^ 35 23

Relative Saturation (%) ^ 4.5 2.3

Comments: The water content as reported in relative saturation is excellent for in-service oil.

Serial Number: 1350009809 Cooling: OA Temp Rise C: 40 Syringe No: RR536 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Misc. ID: Part Position: Bottom XFMR/TRN Name: BUILDING 51 XFMR Max MVA: 0.5 Liquid Type: Natural Esters Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: TRN Volume: 171 Sample Date: 2025-02-11 Humidity:

Manufacturer Cooper Power Systems Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-005 Serial Number: 1350009809 Misc Id:

Dissolved Gas Analysis

Sample Date: 2025-02-11 2023-01-23 Analysis Date: 2025-02-15 2023-02-27 Doble Sample Id: 313369-005 279833-019 Top Oil Temperature: 10 10

Hydrogen (H2) ASTM D3612 IEC 60567(ppm) ^ 54 22

Oxygen (O2) ASTM D3612 IEC 60567(ppm) ^ 166 354

Nitrogen (N2) ASTM D3612 IEC 60567(ppm) ^ 69900 59100

Methane (CH4) ASTM D3612 IEC 60567(ppm) ^ 5.2 4.2

Carbon Monox. (CO) ASTM D3612 IEC 60567(ppm) ^ 56 60

Ethane (C2H6) ASTM D3612 IEC 60567(ppm) ^ 323 408

Carbon Dioxide (CO2) ASTM D3612 IEC 60567(ppm) ^ 958 1060

Ethylene (C2H4) ASTM D3612 IEC 60567(ppm) ^ 3.2 3.3

Acetylene (C2H2) ASTM D3612 IEC 60567(ppm) ^ 0.2 0.2

Total Gas (ppm) ^ 71466 61011

Comb. Gas (ppm) ^ 442 498

Est. TCG, % of Gas Space ^ 0.22 0.17

Ethylene-Acetylene Ratio ^ 16.00 16.50

H2+C2H2:TCG-CO Ratio 0.14 0.04

PPM/Day (ppm/day) ^ -0.1

Serial Number: 1350009809 Cooling: OA Temp Rise C: 40 Syringe No: RR536 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Misc. ID: Part Position: Bottom XFMR/TRN Name: BUILDING 51 XFMR Max MVA: 0.5 Liquid Type: Natural Esters Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: TRN Volume: 171 Sample Date: 2025-02-11 Humidity:

Manufacturer Cooper Power Systems Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-005 Serial Number: 1350009809 Misc Id:

Oil Quality Tests

Sample Date: 2025-02-11 2023-01-23 Analysis Date: 2025-02-15 2023-02-27 Doble Sample Id: 313369-005 279833-019 Top Oil Temperature: 10 10

Water Content D1533 IEC 60814(ppm) ^ 48 16

Relative Saturation (%) ^ 6.1 1.9

Comments: The water content as reported in relative saturation is good for in-service oil.

Serial Number: C4201911 Cooling: OA Temp Rise C: Syringe No: RR566 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Gas Blanketed Misc. ID: Part Position: Bottom XFMR/TRN Name: BUILDING 79 XFMR Max MVA: 0.75 Liquid Type: Mineral Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: XFMR Volume: 610 Sample Date: 2025-02-11 Humidity:

Manufacturer Ohio Transformer Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-004 Serial Number: C4201911 Misc Id:

Dissolved Gas Analysis

Sample Date: 2025-02-11 2023-01-23 Analysis Date: 2025-02-15 2023-02-23 Doble Sample Id: 313369-004 279833-002 Top Oil Temperature: 10

Hydrogen (H2) ASTM D3612 IEC 60567(ppm) ^ 62 9.7

Oxygen (O2) ASTM D3612 IEC 60567(ppm) ^ 27300 29900

Nitrogen (N2) ASTM D3612 IEC 60567(ppm) ^ 64500 58500

Methane (CH4) ASTM D3612 IEC 60567(ppm) ^ 4.3 1.1

Carbon Monox. (CO) ASTM D3612 IEC 60567(ppm) ^ 83 19

Ethane (C2H6) ASTM D3612 IEC 60567(ppm) ^ 0.8 0.2

Carbon Dioxide (CO2) ASTM D3612 IEC 60567(ppm) ^ 1160 617

Ethylene (C2H4) ASTM D3612 IEC 60567(ppm) ^ 25 2.2

Acetylene (C2H2) ASTM D3612 IEC 60567(ppm) ^ 0 0

Total Gas (ppm) ^ 93135 89049

Comb. Gas (ppm) ^ 175 32

Est. TCG, % of Gas Space ^ 0.22 0.04

Ethylene-Acetylene Ratio ^ 0.00 0.00

H2+C2H2:TCG-CO Ratio 0.67 0.31

PPM/Day (ppm/day) ^ 0.2

Serial Number: C4201911 Cooling: OA Temp Rise C: Syringe No: RR566 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Gas Blanketed Misc. ID: Part Position: Bottom XFMR/TRN Name: BUILDING 79 XFMR Max MVA: 0.75 Liquid Type: Mineral Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: XFMR Volume: 610 Sample Date: 2025-02-11 Humidity:

Manufacturer Ohio Transformer Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-004 Serial Number: C4201911 Misc Id:

Oil Quality Tests

Sample Date: 2025-02-11 2023-01-23 1998-06-18 1998-06-18 Analysis Date: 2025-02-15 2023-02-23 2012-07-18 2012-07-18 Doble Sample Id: 313369-004 279833-002 118580-001 118580-002 Top Oil Temperature: 10

Water Content D1533 IEC 60814(ppm) ^ 12 9 33 * 34 *

Relative Saturation (%) ^ 33.5 Need Data

Comments: The water content as reported in relative saturation is okay for in-service oil.

Serial Number: PED0415 Cooling: OA Temp Rise C: Syringe No: IBP612 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Misc. ID: Part Position: Bottom XFMR/TRN Name: BUILDING 185 XFMR Max MVA: 0.75 Liquid Type: Mineral Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: TRN Volume: 173 Sample Date: 2025-02-11 Humidity:

Manufacturer Siemens Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-006 Serial Number: PED0415 Misc Id:

Dissolved Gas Analysis

Sample Date: 2025-02-11 2023-01-24 Analysis Date: 2025-02-15 2023-02-23 Doble Sample Id: 313369-006 279833-020 Top Oil Temperature: 10 8

Hydrogen (H2) ASTM D3612 IEC 60567(ppm) ^ 3.7 7.3

Oxygen (O2) ASTM D3612 IEC 60567(ppm) ^ 19800 19400

Nitrogen (N2) ASTM D3612 IEC 60567(ppm) ^ 65900 62400

Methane (CH4) ASTM D3612 IEC 60567(ppm) ^ 4.1 4.1

Carbon Monox. (CO) ASTM D3612 IEC 60567(ppm) ^ 204 265

Ethane (C2H6) ASTM D3612 IEC 60567(ppm) ^ 1.0 1.3

Carbon Dioxide (CO2) ASTM D3612 IEC 60567(ppm) ^ 2550 2120

Ethylene (C2H4) ASTM D3612 IEC 60567(ppm) ^ 0.9 0.8

Acetylene (C2H2) ASTM D3612 IEC 60567(ppm) ^ 0.1 0

Total Gas (ppm) ^ 88464 84201

Comb. Gas (ppm) ^ 214 279

Est. TCG, % of Gas Space ^ 0.21 0.30

Ethylene-Acetylene Ratio ^ 9.00 0.00

H2+C2H2:TCG-CO Ratio 0.38 0.03

PPM/Day (ppm/day) ^ -0.1

Serial Number: PED0415 Cooling: OA Temp Rise C: Syringe No: IBP612 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Misc. ID: Part Position: Bottom XFMR/TRN Name: BUILDING 185 XFMR Max MVA: 0.75 Liquid Type: Mineral Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: TRN Volume: 173 Sample Date: 2025-02-11 Humidity:

Manufacturer Siemens Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-006 Serial Number: PED0415 Misc Id:

Oil Quality Tests

Sample Date: 2025-02-11 2023-01-24 Analysis Date: 2025-02-15 2023-02-23 Doble Sample Id: 313369-006 279833-020 Top Oil Temperature: 10 8

Water Content D1533 IEC 60814(ppm) ^ 3 3

Relative Saturation (%) ^ 8.4 9.2

Powered by TCPDF (www.tcpdf.org) http://www.tcpdf.org

Serial Number: Q112693TSH Cooling: OA Temp Rise C: Syringe No: IBP218 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Misc. ID: Part Position: Bottom XFMR/TRN Name: TX3 TRANSFORMER Max MVA: 1 Liquid Type: Mineral Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: TRN Volume: 324 Sample Date: 2025-02-11 Humidity:

Manufacturer General Electric Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-001 Serial Number: Q112693TSH Misc Id:

Dissolved Gas Analysis

Sample Date: 2025-02-11 2023-01-31 Analysis Date: 2025-02-15 2023-02-23 Doble Sample Id: 313369-001 279833-014 Top Oil Temperature: 10 5

Hydrogen (H2) ASTM D3612 IEC 60567(ppm) ^ 2.9 3.8

Oxygen (O2) ASTM D3612 IEC 60567(ppm) ^ 10300 7500

Nitrogen (N2) ASTM D3612 IEC 60567(ppm) ^ 70900 65600

Methane (CH4) ASTM D3612 IEC 60567(ppm) ^ 32 35

Carbon Monox. (CO) ASTM D3612 IEC 60567(ppm) ^ 1070 1310

Ethane (C2H6) ASTM D3612 IEC 60567(ppm) ^ 3.2 3.4

Carbon Dioxide (CO2) ASTM D3612 IEC 60567(ppm) ^ 5680 5260

Ethylene (C2H4) ASTM D3612 IEC 60567(ppm) ^ 0.7 0.8

Acetylene (C2H2) ASTM D3612 IEC 60567(ppm) ^ 0.1 0.1

Total Gas (ppm) ^ 87989 79714

Comb. Gas (ppm) ^ 1109 1354

Est. TCG, % of Gas Space ^ 1.06 1.42

Ethylene-Acetylene Ratio ^ 7.00 8.00

H2+C2H2:TCG-CO Ratio 0.08 0.00

PPM/Day (ppm/day) ^ -0.3

Comments: Overheating of cellulose. Because of the high amounts of carbon oxides it is recommended that this oil be tested for furanic compounds or methanol and ethanol to determine the condition of the cellulose if it has not yet been done.

Doble Indianapolis, 3902 Hanna Circle, Suite D, Indianapolis, IN, 46241, USA Page 2 of 3

Serial Number: Q112693TSH Cooling: OA Temp Rise C: Syringe No: IBP218 Sampled By:

Equipment No.: Max KV: 12.47 Preservation: Misc. ID: Part Position: Bottom XFMR/TRN Name: TX3 TRANSFORMER Max MVA: 1 Liquid Type: Mineral Work Order: Top Oil Temp C: 10 Substation: VETERAN AFFAIRS XFMR/TRN Type: TRN Volume: 324 Sample Date: 2025-02-11 Humidity:

Manufacturer General Electric Design Type: Vol Units: Gallons Sample Time: Amb Temp C:

Year Made: 1 or 3 Phase: No Report Type: XFMR-Bottom

Sample Id: 313369-001 Serial Number: Q112693TSH Misc Id:

Oil Quality Tests

Sample Date: 2025-02-11 2023-01-31 Analysis Date: 2025-02-15 2023-02-23 Doble Sample Id: 313369-001 279833-014 Top Oil Temperature: 10 5

Water Content D1533 IEC 60814(ppm) ^ 2 4

Relative Saturation (%) ^ 5.6 14.1

Doble Indianapolis, 3902 Hanna Circle, Suite D, Indianapolis, IN, 46241, USA Page 3 of 3

240838 Marion VA Medical Center
Results: Comments, Deficiencies and Recommendations
Table of Contents
MARION VA FACILITIES OIL SAMPLES
T-CT 88V4406
BUILDING 9 TRANSFORMER 1250013119
BUILDING 51 TRANSFORMER 1350009809
BUILDING 79 TRANSFORMER C4201911
BUILDING 185 TRANSFORMER PRD0415
TX3 TRANSFORMER Q112693TSH

File details come from the government source that posted it. Updated .