FTW Testing.pdf

PDF 14 MB Posted

Attached to
H159--VANIHCS 3 Year Electrical Testing Marion and Fort Wayne
Solicitation number
36C25026Q0067
Issued by

About this file

This document is a comprehensive electrical maintenance and testing report by Premier Power Maintenance for the VA Medical Center in Fort Wayne, Indiana, covering job number 220919 performed between February 21 and March 23, 2023. The report includes detailed inspections, tests, and recommendations for various electrical systems and equipment across multiple buildings and substations, including transformers, circuit breakers, switchboards, and electrical panels.

Key findings include multiple equipment deficiencies requiring attention, such as breakers with loose connections, temperature anomalies, corrosion signs, and trip unit performance issues. Specific recommendations include rechecking torque on load wires, replacing breakers with signs of wear or poor performance, investigating temperature increases in certain electrical components, and verifying proper load wire sizing. The testing was conducted using standards from organizations like NETA, NEC, and IEEE, and involved thermographic inspections, ground resistance testing, and low voltage power circuit breaker tests across different buildings and electrical systems.

View the file

Other files

File Type Posted
36C25026Q0067 0004.pdf PDF
Marion testing.pdf PDF
Marion testing 2.pdf PDF
FTW Testing 2.pdf PDF
36C25026Q0067 0003.pdf PDF
36C25026Q0067 0002.pdf PDF
Sign-in-Marion.pdf PDF
36C25026Q0067 0001.pdf PDF
Sign-in-Ft.-Wayne.pdf PDF
Attachment VII - marion dry type transformers.docx DOCX document
Attachment I - SOW Attachments.pdf PDF
Attachment VIII - Marion MCC.docx DOCX document
36C25026Q0067.docx DOCX document
Attachment III - Wage Determination - Allen Co.pdf PDF
Attachment II - Wage Determination - Grant Co.pdf PDF
Attachment IX - Important Information.docx DOCX document
Attachment VI - Marion panel boards.docx DOCX document
Attachment V - Fort Wayne Electrical test equipment list 08-05-25.xlsx XLSX spreadsheet
Attachment IV - Fort Wayne Electrical Panel 08-05-25.xlsx XLSX spreadsheet
Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

“Integrity, Skill, Teamwork”

W W W . P R E M I E R P O W E R M A I N T E N A N C E . C O M

Engineering Report VA Medical Center-Ft. Wayne

John Hendricks Maintenance Testing Job Number: 220919

April 10, 2023

Premier Power Maintenance

4035 Championship Drive Indianapolis, IN 46268

T (317) 879-0660 www.premierpowermaintenance.com

April 10, 2023

VA Medical Center –Ft. Wayne 2121 Lake Ave.

Ft. Wayne, IN 46805

Attention: John Hendricks

Subject: Maintenance Testing Project No. 220919

Dear Mr. Hendricks, Thank you for the opportunity to provide services for you during this project. Our comprehensive report and recommendations are attached. They detail the work we performed, results obtained and provide recommendations for any corrective actions. Please let us know if you have any questions or need additional information.

As an independent third party electrical testing, maintenance and engineering services firm and full member of the InterNational Electrical Testing Association (NETA), Premier Power Maintenance prides itself in the quality of our services and skills of our people. Thanks again for the opportunity to provide you with electrical testing services. If there is anything more we can do for you, please don’t hesitate to contact us.

Sincerely, Premier Power Maintenance

Melvin Williams Field Service Supervisor

1. Summary

• Maintenance tests and inspections of electrical equipment help assure proper and safe operation.

• This project involved air switches, oil-filled and dry type transformers, low and medium voltage breakers, switchboards, panel inspections and ground resistance.

• Please refer to Section 5 for complete details regarding comments, deficiencies and recommendations.

2. Objectives

Maintenance Testing

• The equipment and components listed in Section 3.0 of this report have been inspected and tested to help assure their proper and safe operation. Defective or marginal equipment can be identified, repaired, replaced or scheduled for future repairs without costly or unexpected interruptions during normal operating periods.

• The test results are particularly valuable when kept for comparison with past and future maintenance test results. This historic database enables one to predict the probability of equipment failure and thus schedule facility production and financial budgets to accommodate preventive maintenance or repair rather than breakdown maintenance.

Oil Testing

• The oil in an oil filled transformer is intended to:

o Provide dielectric strength of the transformer insulation system o Provide efficient cooling o Protect the transformer core and coil assembly from chemical attack

• The oil quality screen (moisture, dielectric, interfacial tension, neutralization number, specific gravity, color and visual) is the standard testing means to determine if the oil is still capable of performing its intended function. While the degradation of oil is a natural process, early detection and remediation will extend the life of the transformer.

Another valuable oil testing method for transformers is the dissolved gas analysis (DGA). This battery of tests, often called fault gas analysis, is the easiest method to determine the operating condition of the transformer itself. Some gases indicate overheating of the unit possibly due to overloading, while other gases indicate a fault type condition within the transformer. The proper monitoring of dissolved gas within the transformer with remediation can prolong the life of the unit. It can also be used as a warning for the need to replace the transformer prior to failure.

Thermographic Survey

• The purpose of infrared inspections is to provide information relative to the physical condition of the electrical distribution system. Loose and poor connections, unbalanced loads, and loose bus joints can be located. These conditions are characterized by increased resistance and accompanied by a temperature rise, which is detected by infrared scanning. The survey was performed while the system was loaded, representative of a “normal” workday.

3. Service Description

• This project was initiated by John Hendricks with VA Medical Center-Marion. All testing was performed by Premier Power Maintenance field technicians Melvin Williams, Tracy Stafford, Brandon Andrus, Austin Knight, Larry Jones and Austin Hudson from February 21, 2023 to March 23, 2023.

• For a list of equipment tested in this project, please see test sheets located in the Appendix.

4. Procedure

• All testing is performed in accordance with PPM’s standard procedures including, but not limited to, selected specifications from the following: InterNational Electrical Testing Association (NETA), National Electrical Code (NEC), National Fire Protection Association 70B-Electrical Equipment Maintenance (NFPA 70B), Institute of Electrical and Electronic Engineers (IEEE), American Society for Testing and Materials (ASTM), National Electrical Manufacturer’s Association (NEMA), manufacturer’s instruction manuals and/or project specifications, unless otherwise noted.

5. Results: Comments, Deficiencies and Recommendations

• The following is a list of problems discovered during this testing project along with any corrective action that was made by Premier Power Maintenance. Those corrections beyond the scope of the project that require your additional corrective action are in bolded text.

Based on the results of the inspections and tests performed, the equipment included in this project (see detailed test data in Appendix) is considered serviceable.

o BLDG 1 (399): PP-10- FOUND 1-3 PHASE BREAKER (POLE 2,4,6) TURNED ON. NO LOAD

WIRES. OPENED BREAKER. RECOMMEND INVESTIGATION.

o BLDG 1 MRI ENTRANCE WESTINGHOUSE: SPARE BREAKER 29 AND 30 STRUGGLED TO

CLOSE. RECOMMEND INVESTIGATION.

o BLDG 1-LP1M: UPPER RIGHT PLASTIC BACKING FOR THE CENTER COVER HAS BROKEN

OFF. WILL NEED TO BE REPLACED.

o BLDG1-TRAYLINE PNL: BREAKER #2 CONTINUITY TEST WAS INTERMITTING IN THE

CLOSED POSITION.

o BLDG1-EQ-KP-8: NEUTRAL BRACKET FOUND BROKEN. RECOMMEND REPAIR/REPLACE.

o BLDG1-PP-B: MARKED ONE OF THE SPARE BREAKERS AS BAD. DID NOT REMOVE FROM

PANEL.

o BLDG1-CR-1: TURNED OFF UNUSED BREAKERS. BREAKER #9 LOAD SIDE SCREW WAS

STRIPPED OUT. REPLACED WITH BREAKER #11.

o BLDG1-LP-1E: #19 BREAKER MANUAL TRIP FUNCTION DOES NOT WORK. RECOMMEND

INVESTIGATION.

o BLDG1-LP-B12: FOUND A FEW BREAKERS TO BE SLUGGISH. DID NOT REPLACE THEM AT

THIS TIME. PASSED CONTINUITY TESTS. RECOMMEND REPLACING IN THE FUTURE.

o BLDG1-CR-1: TURNED OFF UNUSED BREAKERS. BREAKER #9 LOAD SIDE SCREW WAS

STRIPPED OUT. REPLACED WITH BREAKER #11.

o BLDG1-LP-3D: FOUND BREAKER BAD. REPLACED BREAKER.

o BLDG1-LP-3E: PANEL COVER BOLT FOUND BROKEN . INSTALLED NEW BOLT.

o BLDG1-DP-1E: BREAKER #22 (REMOVED LOTO FROM OTHER CONTRACTOR PER

CUSTOMER).

o BLDG1-CR-OIT-2: BREAKERS #1 WIRE WAS FOUND LOOSE. TIGHTENED.

o BLDG1-CR-OIT-1: BREAKER #1 WAS FOUND LOOSE. TIGHTENED.

o BLDG1-EMP: 5/16 BOLT ON PRIMARY INCOMING BUS (BLACK PHASE) WAS FOUND

STRIPPED. HARDWARE HAS BEEN REPLACED.

o BLDG 17 PNL A (MRI): BREAKER #7 RUNG OUT WITH BREAKER IN THE OPEN POSITION.

REPLACED WITH NEW BREAKER.

o BLDG2-B-EQ-DP-1: B PHASE CABLE ON EQ-HPP-4 FOUND LOOSE. IT WAS TIGHTENED.

o BLDG2-PNL LVA: REPLACED 1-20A BREAKER. ALSO, REPLACED 2 BLANKS.

o BLDG3-B3A2: FOUND 3 SPARES WHICH TESTED BAD. BREAKER #2 SHOWED SIGNS OF

CORROSION. RECOMMEND REPLACE.

o BLDG6-PPE-3: FOUND EACH PRIMARY LUG TO BUS LOOSE. RETIGHTENED.

o BLDG6-PP1: BREAKER 21/23 SHOWING SIGNS OF CORROSION. BREAKER 25 SHOWING

SIGNS OF OVERHEATING. RECOMMEND REPLACE.

o BLDG6-B6-208V SW: FOUND A PHASE LOOSE. RETIGHTENED. (FUSETRON FUS-FRN-R-

350).

o BLDG7-PP-7A: SPARE BREAKER #1 AND 3 FOUND BAD. RECOMMEND REPLACE.

o BLDG7-B7-A: FOUND BREAKER #13 OF DOUBLE-POLE TO BE BAD. UNABLE TO

ESTABLISH CONTINUITY.

o MAIN SUBSTATION 1500kVA EAST PADMOUNT TRANSFORMER: UNABLE TO REMOVE

H3A LOADBREAK CONNECTION FROM TRANSFORMER. PERFORMED ALL TESTING WITH

CABLE INCLUDED IN RESULTS. RECOMMEND REMOVAL OF LOADBREAK AND INSERT.

REPLACE BOTH WITH NEW ONES. PICTURE(S) INCLUDED OF CONNECTION AND CABLE

INFO.

o MAIN SUBSTATION 1500kVA WEST PADMOUNT TRANSFORMER: UNABLE TO REMOVE

ARRESTERS ON HIGH SIDE. RECOMMEND OUTAGE TO CUT BACK/REMOVE ALL 3

ARRESTERS FROM BUSHING AND REPLACE THEM WITH COOPER RTE LPC215 8.3 /

14.4kV LOADBREAK ARRESTERS. PICTURES INCLUDED WITH TEST SHEET.

o MAIN SUBSTATION 500 kVA EAST PADMOUNT TRANSFORMER: UNABLE TO REMOVE

ARRESTERS ON HIGH SIDE. RECOMMEND OUTAGE TO CUT BACK/REMOVE ALL 3

ARRESTERS FROM BUSHING AND REPLACE THEM WITH COOPER RTE LPC215 8.3 /

14.4kV LOADBREAK ARRESTERS. PICTURES INCLUDED WITH TEST SHEET.

o HAZMAT PANEL: FOUND LOOSE LOAD WIRES ON BREAKER 28/30. TIGHTENED WIRES.

o T6-3: TIGHTENED MAIN LUGS.

o T4-2: BREAKER #13 HOLD CONTINUITY WHILE IN THE OPEN POSITION.

o T5-3: LOOSE NEUTRAL WIRE TIGHTENED.

o RM 42 BREAKERS BOILER PLANT: SHORT TIME DELAY OUT OF TOLERANCE ON TIME.

RECOMMEND INVESTIGATION.

o RM 42 BREAKERS SOUTH MAIN: SHORT TIME AND GROUND FAULT DELAYS FOUND TO

BE OUT OF TOLERANCE. RECOMMEND REPLACING TRIP UNIT.

APPENDIX

FT WAYNE VA MEDICAL CENTER

FT WAYNE VA MEDICAL CENTERCustomer

Plant

Table of Contents Job #220919

4035 Championship Drive Indianapolis, IN 46268

317-879-0660 www.premierpowermaintenance.com24 Hour Emergency Service REVISED 2/18/2008

PANEL INSPECTIONSBUILDING # 1

User

PagePositionSubstation Equipment

50955 - PANEL INSPECTION RESULTS_R01-23

PANEL INSPECTIONS-2BUILDING # 1 50955 - PANEL INSPECTION RESULTS_R01-23 (2)

PANEL INSPECTIONS-3BUILDING # 1 50955 - PANEL INSPECTION RESULTS_R01-23 (3)

PANEL INSPECTIONS-4BUILDING # 1 50955 - PANEL INSPECTION RESULTS_R01-23 (4)

PANEL INSPECTIONS-5BUILDING # 1 50955 - PANEL INSPECTION RESULTS_R01-23 (5)

PANEL INSPECTIONS-6BUILDING # 1 50955 - PANEL INSPECTION RESULTS_R01-23 (6)

PANEL INSPECTIONS-7BUILDING # 1 50955 - PANEL INSPECTION RESULTS_R01-23 (7)

PANEL INSPECTIONSBUILDING # 16 50955 - PANEL INSPECTION RESULTS_R01-23 (3)

PANEL INSPECTIONSBUILDING # 17 50955 - PANEL INSPECTION RESULTS_R01-23

CB/201BUILDING # 2 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

PANEL INSPECTIONSBUILDING # 2 50955 - PANEL INSPECTION RESULTS_R01-23 (2)

PANEL INSPECTIONSBUILDING # 3 50955 - PANEL INSPECTION RESULTS_R01-23 (2)

PANEL INSPECTIONSBUILDING # 4 50955 - PANEL INSPECTION RESULTS_R01-23 (2)

PANEL INSPECTIONSBUILDING # 5 50955 - PANEL INSPECTION RESULTS_R01-23 (2)

PANEL INSPECTIONSBUILDING # 6 50955 - PANEL INSPECTION RESULTS_R01-23 (2)

PANEL INSPECTIONSBUILDING # 7 50955 - PANEL INSPECTION RESULTS_R01-23 (2)

1500kVA EAST PADMOUNT XFMRMAIN SUBSTATION 56750 - XFMR MAINTENANCE AND INSP_R05-23 (2)

1500KVA EAST PADMOUNT XFMRMAIN SUBSTATION 57130 - TRANSFORMER LIQUID COOLANT TRENDING

1500KVA WEST PADMOUNT XFMRMAIN SUBSTATION 56750 - XFMR MAINTENANCE AND INSP_R05-23

1500KVA WEST PADMOUNT XFMRMAIN SUBSTATION 57130 - TRANSFORMER LIQUID COOLANT TRENDING

1500KVA XFMR (EAST) SWITCHMAIN SUBSTATION 29000 - LOADBREAK DISCONNECT_R02-23 (4)

500KVA EAST PADMOUNT XFMRMAIN SUBSTATION 56750 - XFMR MAINTENANCE AND INSP_R04-23 (2)

500KVA EAST PADMOUNT XFMRMAIN SUBSTATION 57130 - TRANSFORMER LIQUID COOLANT TRENDING

500KVA WEST PADMOUNT XFMRMAIN SUBSTATION 56750 - XFMR MAINTENANCE AND INSP_R04-23

500KVA WEST PADMOUNT XFMRMAIN SUBSTATION 57130 - TRANSFORMER LIQUID COOLANT TRENDING

500KVA XFMR (WEST) SWITCHMAIN SUBSTATION 29000 - LOADBREAK DISCONNECT_R02-23 (3)

ANTHONY-WABASH SWITCHMAIN SUBSTATION 27200 - VOLTAGE TRANSFORMER TEST (2)

ANTHONY-WABASH SWITCHMAIN SUBSTATION 29000 - LOADBREAK DISCONNECT_R02-23 (2)

METERING PTsMAIN SUBSTATION 27200 - VOLTAGE TRANSFORMER TEST

SPYRUN DISCONNECT SWITCHMAIN SUBSTATION 27200 - VOLTAGE TRANSFORMER TEST

SPYRUN DISCONNECT SWITCHMAIN SUBSTATION 29000 - LOADBREAK DISCONNECT_R02-23

PANEL INSPECTIONSMDP-TRAILERS 50955 - PANEL INSPECTION RESULTS_R01-23

208-120 TIERM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

AMBULATORY CARERM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

ATS-1 #1RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

ATS-10 #8RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

ATS-2 #15RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

ATS-3 #14RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

Table of Contents Job #220919

4035 Championship Drive Indianapolis, IN 46268

317-879-0660 www.premierpowermaintenance.com24 Hour Emergency Service REVISED 2/18/2008

PagePositionSubstation Equipment

ATS-4 #6RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

ATS-8 #7RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

ATS-9 #11RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

BEQH2RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

BOILER PLANT (4)RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

DP-1 #2RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

DP-10 #13RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

DP-2 #5RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

DP-3 #12RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

DP-4 #10RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

DP-5 #4RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

DP9 #16RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

FIRE PUMP #17RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

GENERATOR 1RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

GENERATOR 2 SPARERM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

GENERATOR 3RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

MDP-OR #9RM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

NORTH MAINRM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

NORTH MAIN 208 GEARRM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

SOUTH MAINRM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

SOUTH MAIN 208 GEARRM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

TIERM 42 BREAKERS 15200 - LOW VOLTAGE POWER CIRCUIT BREAKER TEST_R01-23

FALL OF POTENTIAL TESTINGVARIOUS AREAS 34567 - MEMO

GROUND RESISTANCE TESTINGVARIOUS AREAS 24210 - GROUND RESISTANCE TWO TERMINAL

GROUND RESISTANCE TESTING (2)VARIOUS AREAS 24210 - GROUND RESISTANCE TWO TERMINAL

INFRARED SURVEYVARIOUS AREAS 52000 - THERMOGRAPHIC INSPECTION

EQPT. LOCATION

PAGE

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 1 PANEL INSPECTIONSPOSITION

2/27/2023 AMBIENT TEMPERATURE 20 °C HUMIDITY 45 %

B. ANDRUS / A. KNIGHT / L. JONES / T. STAFFORDTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

PRL3A250A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

EATON

CATALOG #

EZB2090R

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

DT-375KVABLDG 1: S. BRKR XFM EATON V48M28T756CULS47

DRY TYPE TRANSFORMER

NAB400ABLDG 1 (399): PP-10 GE NA

FOUND 1 - 3PHASE BREAKER (POLE 2,4,6) TURNED ON. NO

LOAD WIRES. OPENED BREAKER.

NQB100ABLDG 1(399): PP-10A WESTINGHOUSE FY-37632

FOUND BREAKER 1 LOAD WIRE LOOSE. TIGHTENED

MODEL 36B150KVABLDG1(XFMR 105) FPI T204H150E

QL150KVABLDG1 (XFMR 104) GE 9T23Q9876

NA600ABLDG1(DISC.104XF) GE NA

FUSED DISCONNECT 240VAC; EQUIPPED WITH FLNR 600A ID

FUSES CHECKED GOOD.

NA400ABLDG1(DISC SWB 19) GE NA

NO FUSES

NA600ABLDG1 (DISC DS 103) GE NA

EQUIPPED WITH FLNR 400 ID FUSES. CHECKED OK.

QL150KVABLDG1 (XFMR T-103) GE 9T23Q9876

GCB600ABLDG 1 (DP-5) GE BJ10141

4 SPARES FOUND WITHIN PANEL. MISSING HARDWARE ON

TOP CENTER PLATE.

WEB31CIR100ABLDG 1 (LP-BF) WESTINGHOUSE TE-40910

NQOD100ABLDG 1 (LP IH) SQUARE D NQOD430M100

NANABLDG 1 (DIMMING) LITHONIA CNTRL SYS NA

LITHONIA LIGHTING CONTROL PANEL. 6 BREAKERS.

HDP400ABLDG 1 (EQ HDP-B) GE EQ-HDP-B

BLDG 1 RM 250. REPLACED BREAKER HDP-2 WITH USED

BREAKER. (ORIGINAL BREAKER WOULD NOT CLOSE) 225A PL

PRL1C125ABLDG1 CR4B-SEC 1 EATON EZB2048R

PRL1A225ABLDG1 CR4B-SEC 2 EATON EZB2036R

PRL1A125ABLDG1 CR4C EATON EZB2036R

PRL1A225ABLDG1 CR4A-SEC2 EATON E2B2042R

BREAKERS TO BUS FOUND LOOSE. TIGHTENED.

PRL1C125ABLDG1 CR4A-SEC1 EATON E2B1048R

UNUSED BREAKERS TURNED OFF (4 TOTAL)

TYPE 1100ABLDG 1- DP-6 WESTINGHOUSE YS2042

WLA42CIR225ABLDG 1 MRI ENTRANC WESTINGHOUSE TE-4091D

SPARE BREAKER 29 AND 30 STRUGGLED TO CLOSE

NANABLDG1 EQ-HDP-B SQUARE D NA

CT SCANNER DISCONNECT

NF225ABLDG1 EQ-HDP-2 SQUARE D 1228435189

NF125ABLDG1 1HE1 CRITICA SQUARE D 123381495300

NQ100ABLDG1 EQ-USP SQUARE D N218L2C

AXB7150ABLDG1 EQ-PP-B GE AQF3242CBX

QL45KVABLDG1-T-102 XFMR GE 9T23Q9873

OOB400ABLDG 1 EQ-PP-11 GE NA

NA225ABLDG 1 LP-OR 3217 GE AQF3302MGX

TABS FOR BREAKER(S) 3,27, AND 27 FOUND BROKEN.

REPLACED BREAKERS.

NA225ABLDG 1 MDP-OR GE AQF3362CBX

CTL225ABLDG1 RM 536 LP-5A WESTINGHOUSE B2SS140

1225ABLDG1 LP-3-A EATON EZB2060R

1225ABLDG1 LP-3-B EATON EZB2060R

BLDG 1: CRDP1

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 1 PANEL INSPECTIONS-2POSITION

2/28/2023 AMBIENT TEMPERATURE 15 °C HUMIDITY 45 %

B. ANDRUS / T. STAFFORDTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

NA100A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

WESTINGHOUSE

CATALOG #

NA

COMMENTS

UNUSED BREAKERS WERE OPENED.

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

WCA42CIR225ABLDG1 LP-2A WESTINGHOUSE TE-40910

CTL225ABLDG1 LP-2BA WESTINGHOUSE TE-40910

UNUSED BREAKERS WERE OPENED.

CTL225ABLDG1 LP-2B WESTINGHOUSE TE-40910

UNUSED BREAKERS WERE OPENED.

B10R18CIR100ABLDG1 PP-CA WESTINGHOUSE TE-43220

UNUSED BREAKERS WERE OPENED.

NA250A BLDG1 2H12 EAST HL SQUARE D LE36225LSG

NA250ABLDG1 CHILLER CH-1 SQUARE D LE36225LSG

NA400ABLDG1 SPARE SQUARE D LE36400LSG

NA400ABLDG1 PP-A SQUARE D LE36400LSG

NA400ABLDG1 WEST POWER SQUARE D LE36400LSG

NA150ABLDG1 ATS-11 SQUARE D AL150HD

PRL4B400ABLDG1 PP-A CUTLER HAMMER PRL4

NANABLDG1 PP-AA GE NA

NA400ABLDG1 N-H3 RISER SQUARE D LE36400LSG

NA400ABLDG1N-ATS-6 SQUARE D LE36400LSG

NA400ABLDG 1 N-BLDG 5,6,7 SQUARE D LE36300LSG

NA250ABLDG 1 N-PP-B SQUARE D LE36250LSG

NA400ABLDG1 N- H2-RISER SQUARE D LE36400LSG

NA400ABLDG1 N-3H1,4H1,5H1 SQUARE D LE36400LSG

NA400ABLDG1 N- ATS 13 SQUARE D LJA36400CU44Y

NA400ABLDG1 N-BEQHI RM49 SQUARE D LJA36400CU44Y

NANABLDG1 N -ESS-P NA NA

NA400ABLDG1 N--ATS-7 SQUARE D LE36400LSG

NA250ABLDG1 N-SPARE SQUARE D LE36100LSG

NA250ABLDG1 N-NEW CHLR SQUARE D AL250JD

NQ100ABLDG1 LP1B (NORM) SQUARE D 12338149530010001

NQ100ABLDG1 LP-1A(NORM) SQUARE D 12338149530010001

HCA-42-CIR225ABLDG1-LP-BA WESTINGHOUSE TE-40910

NQ100ABLDG1-LP-BA-A SQUARE D NQ430L

NANABLDG1-DP-4 WESTINGHOUSE NA

HCA-42-CIR100ABLDG1-EM-2 WESTINGHOUSE TE-40910

NQOD100ABLDG1-PNL BASE A1 SQUARE D NQOD12L100CU

S25KVABLDG1 XFMR 269 SQUARE D 25S3HF

NANABLDG1-A1 (RM 305) SQUARE D NA

NA400ABLDG1- EQ-DP-B GE AQF3124MTX

RM 42.

BLDG1 PP 2BA

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 1 PANEL INSPECTIONS-3POSITION

3/8/2023 AMBIENT TEMPERATURE 20 °C HUMIDITY 45 %

M Williams / A. Hudson / T. Stafford / B. AndrusTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

NA600A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

SQUARE D

CATALOG #

MODEL 6

COMMENTS

ALL FUSES CHECKED GOOD.

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

QL30KVABLDG1- TS-202 XFMR GE 9T23Q9872

EQ-1A225ABLDG1-EQ-1A GE AF495

CDP-7225ABLDG1-PP-REF ITE SERIES 8

FUSED600ABLDG1-AMB CARE DIS SQUARE D H326NR

TR500R FUSES. ALL CHECKED GOOD

NANABLDG1-AMB XFMR FPI NA

NAMEPLATE HAS BEEN REMOVED

NA150KVABLDG1 XFMR DP SQUARE D 150T3H

1250ABLDG 1-MDP SQUARE D HC4250DB

RM A155

E1400ABLDG 1-DP SQUARE D 12107016971

NQOD225ABLDG 1-LP1N SQUARE D NQOD442L225CU

NQOD225ABLDG 1-LP1M SQUARE D NQOD442L225CU

UPPER RIGHT PLASTIC BACKING FOR THE CENTER COVER

HAS BROKEN OFF. WILL NEED REPAIRED

PRLA225ABLDG 1-LP4C1-SEC2 EATON 1C96649G06

PRL1A100ABLDG1-LP4E EATON EZB2036R

SEVERAL SPARES WITHIN PANEL.

NA225ABLDG1-LP4C1-SEC1 EATON 1C96649G06

PRLA225ABLDG1-LP4C2 EATON EZB2060R

WCA-42-CIR225ABLDG1-LP-5B WESTINGHOUSE TE-40910

WCA-42-CIR225ABLDG1-LP-3C WESTINGHOUSE TE-40910

GCB600ABLDG1-DP-2 GE NA

1 SPARE BREAKER (11,13,15) WOULD NOT RESET.

NA225ABLDG1-LP-BE WESTINGHOUSE TE-40910

KITCHEN AREA-ROOM 2

NA400ABLDG1-CR-DP-B GE AQF3184MBX

ROOM 42 (LOCATED BEHIND 208 SWITCHGEAR/ LV

BREAKERS.

PRL1A200ABLDG1-CR-OIT-5 EATON 1C96649G06

5TH FLOOR

1100ABLDG1-CR-OIT-4 SIEMENS P122481100CU

PRL1A200ABLDG1-CR-OIT-3 EATON 1C96649G02

NA225ABLDG1-LP-BC WESTINGHOUSE BZ56344

CUSTOMER REMOVED 4 LOTO FROM OTHER CONTRACTOR

FOR PANEL. PPM REMOVED LOAD WIRES AND TAPED OFF.

WEB15-CIR100ABLDG1-EM-1 WESTINGHOUSE TE-40910

1ST FLOOR/ RM 176

SERIES E2100ABLDG1-EM1A SQUARE D DQDD12LI

1ST FLOOR / RM A155 MECH ROOM

CTL100ABLDG1-EM-5 WESTINGHOUSE BV220216

5TH FLOOR

WEB15-CIR100ABLDG1-EM-13 WESTINGHOUSE TE-40910

FOIUND BREAKER # 18 LOOSE. TIGHTENED.

NQ100ABLDG1-BLSL2 SQUARE D 4536773271

WEB15-CIR100A BLDG1-LP-E2 WESTINGHOUSE TE-40910

1100ABLDG1-BLRL2 SQUARE D 453677327100S0001

NQOD100ABLDG1-CR1A SQUARE D NQOD431

NQOD100ABLDG1-CR1B SQUARE D NQOD431

BLDG1-MCC1

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 1 PANEL INSPECTIONS-4POSITION

3/9/2023 AMBIENT TEMPERATURE 18 °C HUMIDITY 45 %

MELVIN WILLIAMSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

WEB15-CIR100A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

WESTINGHOUSE

CATALOG #

TE-40910

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

PRL1A225ABLDG1-CRP CUTLER-HAMMER FJ727559

BIOB24-CIR100ABLDG1-DP-3A WESTINGHOUSE 5217-969

A100ABLDG1-CR-OIT-AMB EATON EZB2042R

PRL1A100ABLDG1-CR-OIT-2 EATON EZB2042R

BREAKER # 1 WIRE FOUND LOOSE. TIGHTENED.

PRL1A100ABLDG1-CR-OIT-B EATON EZB2042R

1100ABLDG1-CR-OIT-1 EATON EZB2042R

BREAKER # 1 FOUND LOOSE. TIGHTENED.

1NABLDG1-CR-2C SQUARE D NC385HR

USUSED BREAKERS TURNED OFF

1NABLDG1-CR-2D SQUARE D NC38SHR

PRL1A100ABLDG1-LPE1 CUTLER HAMMER YS204B

UNUSED BREAKERS TURNED OFF.

PRL1A225ABLDG1-EMP CUTLER HAMMER NA

5/16 BOLT ON PRIMARY INCOMING BUS (BLACK PHASE) WAS

FOUND STRIPPED. HARDWARE HAS BEEN REPLACED.

QL112.5KVABLDG1-T-101 XFMR GE 9T23Q9875

10200ABLDG1-DS-101 GE THN3364

NA100ABLDG1-TRAYLINE PNL SQUARE D QOC24US

BREAKER # 2 CONTINUITY TEST WAS INTERMITTING IN THE

CLOSED POSITION.

175KVABLDG1-CR1DA XFMR SQUARE D 12338149S300S0001

PRL1A225ABLDG1-PP-1 CUTLER HAMMER 1C96649G01

WEB15-CIR100ABLDG1-EQ-B WESTINGHOUSE TE-40910

BIOB23-CIR100ABLDG1-DP-3A WESTINGHOUSE 5217-969

1NABLDG1-TELE-C XFMR SQUARE D NCSOSHR

A100ABLDG1-CR1D SQUARE D 12338149530020001

NANABLDG1-CR-3 WESTINGHOUSE TE-40910

NA100ABLDG1-CR3-B EATON EZB2060R

NA125ABLDG1-CR-3A GE AQF3241CBX

NA15KVABLDG1-TELE-A XFMR GE 9T22B3091G03

NA225ABLDG1-2H1 SQUARE D 1210377300005

NA125ABLDG1-CR-5 GE AQF3301AT

NA100ABLDG1-CR-2 WESTINGHOUSE TE-40910

NA60ABLDG1-PP-DISHMAC WESTINGHOUSE IN74370

NA225ABLDG1-PP-4 CUTLER HAMMER YSZ049

NA100ABLDG1-EQ-5 WESTINGHOUSE TE-60910

NA100ABLDG1-EQ-4 EATON EZB2036R

NA100ABLDG1-EQ-3 WESTINGHOUSE TE-40910

NA225ABLDG1-LP-2CA WESTINGHOUSE TE-40310

FOUND A BAD SPARE BREAKER WITHIN PANEL.

NA225ABLDG1-LP-2C WESTINGHOUSE TE-40310

BLDG1-CR-B

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 1 PANEL INSPECTIONS-5POSITION

3/10/2023 AMBIENT TEMPERATURE 18 °C HUMIDITY 45 %

A. HUDSON / A. KNIGHT / L. JONES / B. ANDRUSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

NA225A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

CUTLER HAMMER

CATALOG #

YS204B

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

NA225ABLDG1-LP-1C WESTINGHOUSE TE-40910

NA225ABLDG1-LP-1F WESTINGHOUSE TE-40910

NA400ABLDG1-BEQH-1 SQUARE D 44367732710020031

NA400ABLDG1-BEHQ-3 SQUARE D 29436891020040001

NA225ABLDG1-DP-TELE-A GE AQF3242CTX

NA225ABLDG1-DP-TELE-B GE NA

NA125ABLDG1-DP-TELE GE A331

NA125ABLDG1-CR-2B GE AQF3241MBX

NA225ABLDG1-CR-2A GE AQF3422MBX

NA125ABLDG1-CR-1C GE AQF3241MBX

NA400ABLDG1-LP1K SQUARE D NQOD442L400CU

NA225ABLDG1-LP1L SQUARE D NQOD442L225CU

PANEL FOUND BROKEN IN A FEW AREAS.

NA100ABLDG1-EM2 WESTINGHOUSE TY40910

NA100ABLDG1-EM-4 EATON 1C96646001

NA225ABLDG1-EQ-KP-8 GE AQF3242MBX

NEUTRAL BRACKET FOUND BROKEN

NA100ABLDG1-4H2 SQUARE D 121037730012

NA100ABLDG1-3H2 SQUARE D 1210377300009

NA100ABLDG1-2H2 SQUARE D 1210377300006

NA225ABLDG1-EQ-2A GE AQF3362CBX

NA200ABLDG1-10S POWER SQUARE D 5H1S2100-FA

NA100ABLDG1-5H2 SQUARE D 1210377300015

NA100ABLDG1-1H2 SQUARE D 12103773000003

WCA42-CIR225ABLDG1-LP-ID WESTINGHOUSE TE-40910

NA125ABLDG1-PP-OR GE AQF3301MBX

NQO100ABLDG1-RM 311 SQUARE D 5H152100-FA

2A225ABLDG1-PP-B GE AR-243606

MARKED ONE OF THE SPARE BREAKERS AS BAD. DID NOT

REMOVE FROM PANEL.

I-LINE100ABLDG1-5H1 SQUARE D 1210377300014

I-LINE150ABLDG1-4H1 SQUARE D 1210377300011

E1125ABLDG1-2H3 SQUARE D 121377300007

NH1B225ABLDG1-5H3 SQUARE D 46612-2A

OPENED UNUSED SPARE BREAKERS.

PRL2A200ABLDG1-3H1 EATON EZB2048R

NA200ABLDG1-OR ROOM 313 SQUARE D 5H152100-FE

MISSING DEAD FRONT BOLT

E1100ABLDG1-1H3 SQUARE D 1210377300-004

E1125ABLDG1-3H3 SQUARE D 1210377300010

BLDG1-PP-XRAY

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 1 PANEL INSPECTIONS-6POSITION

3/9/2023 AMBIENT TEMPERATURE 18 °C HUMIDITY 45 %

MELVIN WILLIAMSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

WEB15-CIR100A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

WESTINGHOUSE

CATALOG #

TE-40910

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

NQO100ABLDG1-OR PANEL SQUARE D Q020-40504

NANABLDG1-OR RM 303 NA NA

PRL4B400ABLDG1-EQP CUTLER HAMMER BX3673

WEB15-CIR100ABLDG1-EQ-1 WESTINGHOUSE TE-40910

NLAB225ABLDG1-LP-IJ GE BR23910B

TURNED OFF UNUSED BREAKERS

WEB15-CIR100ABLDG1-CR-1 WESTINGHOUSE TE-40910

TURNED OFF UNUSED BREAKERS. BKR # 9 LOAD SIDE

SCREW WAS STRIPPED OUT. REPLACED WITH BRK # 11

PRL1A225ABLDG1-PP-9 CUTLER HAMMER YS2060

BREAKER FOR 208 CHARGING RECEPTACLE FOUND

TRIPPED. RESET BREAKER.

N/P30KVABLDG1-DOC XFMR FPI T20LH42-3

WCE 42 CIR225ABLDG1-LP2E WESTINGHOUSE TE-40910

WEB 24 CIR100ABLDG1-LP-3DA WESTINGHOUSE TE-40910

WCA 42 CIR225ABLDG1-LP-3D WESTINGHOUSE TE-40910

FOUND BREAKER BAD. REPLACED BREAKER

WCA 42 CIR225ABLDG1-LP-3E WESTINGHOUSE TE-40910

PANEL COVER BOLT FOUND BROKEN. INSTALLED NEW

BOLT.

PRL1A225ABLDG1-LP-4D SEC1 EATON NA

PRL1A225ABLDG1-LP4D1-SEC2 EATON NA

PRL1A225ABLDG1-LP4D1-SEC1 EATON NA

WCA 42 CIR225ABLDG1-LP-5C WESTINGHOUSE TE-40910

NQOB225ABLDG1-LP-5D SQUARE D 46612-3P

PRL1A225ABLDG1-LP4D2-SEC2 EATON NA

NQBNABLDG1-PP-6B WESTINGHOUSE FY35005

PRL1A225ABLDG1-PP-6 CUTLER-HAMMER YS2048

1400ABLDG1-DP-9 SQUARE D HC42S9TSHR

NQOD225ABLDG1-LP-2H SQUARE D NA

UNUSED BREAKERS OPENED.

PRL1A225ABLDG1-LP-2G CUTLER HAMMER YS2048

PRL1A225ABLDG1-PP-3 CUTLER HAMMER YS2060

WCA 42 CIR225ABLDG1-LP-1E WESTINGHOUSE TE-40910

#19 BREAKER MANUAL TRIP FUNCTION DOES NOT WORK.

WCA 42 CIR225ABLDG1-LP-1EA WESTINGHOUSE TE-40910

WCA 42 CIR225ABLDG1-LP-2D WESTINGHOUSE TE-40910

CGB600ABLDG1-DP-1 GE NA

THIS SWITCHBOARD IS EQUIPPED WITH 1-50A BREAKER

WCA 42 CIR225ABLDG1-LP-B12 WESTINGHOUSE TE-40910

FOUND A FEW BREAKERS TO BE SLUGGISH. DID NOT

REPLACE THEM AT THIS TIME. PASSED CONTINUITY TESTS

NLAB200ABLDG1-DP-1E GE NA

BREAKER # 22 (REMOVED LOTO FROM OTHER CONTRACTOR

PER CUSTOMER)

NQ225ABLDG1-BNL2-1 SQUARE D NC38SHR

NQ225ABLDG1-BNL2-2 SQUARE D NC38SHR

NQ225ABLDG-BEQL2 SQUARE D NC38SHR

BLDG1-EQ-2

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 1 PANEL INSPECTIONS-7POSITION

3/9/2023 AMBIENT TEMPERATURE 18 °C HUMIDITY 45 %

MELVIN WILLIAMSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

NLAB225A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

GE

CATALOG #

NA

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

PRL4B800ABLDG1-DP-3 CUTLER HAMMER NA

NQOB100ABLDG1-MED-REC SQUARE D NQOB-204

PRL1A225ABLDG1-LPL CUTLER HAMMER NA

NA400ABLDG1-ATS#14 SQUARE D LJA36400CU44X

NA250ABLDG1-ACC3 KIT CON SQUARE D LX36200

NA250ABLDG1-ACC2 LAB CO SQUARE D LX38175

BLDG1-PP-2

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 16 PANEL INSPECTIONSPOSITION

3/9/2023 AMBIENT TEMPERATURE 16 °C HUMIDITY 45 %

Melvin WilliamsTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

PRL3A400A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

CUTLER HAMMER

CATALOG #

YS2072

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

NANABLDG 16-B16-A WESTINGHOUSE NA

#8 BREAKER RINGS THROUGH IN THE OPEN POSITION.

REMOVED BREAKER. LOAD CABLE RINGS THROUGH BUS

NA15KVABLDG 16-XFMR 16-A SQUARE D 15T3H

BLDG 16-PP-16

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 17 PANEL INSPECTIONSPOSITION

3/7/2023 AMBIENT TEMPERATURE 18 °C HUMIDITY 35 %

Melvin WilliamsTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

NQ225A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

SQUARE D

CATALOG #

NQ442L2C

COMMENTS

BREAKER # 7 RUNG OUT WITH BREAKER IN THE OPEN

POSITION. REPLACED WITH NEW BREAKER.

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

HCM400ABLDG 17: MDP (MRI) SQUARE D HCM91TSD

THIS PANEL WAS EQUIPPED WITH A MAIN 400A BREAKER.

REMOVED LUG SHIELD. SCREWS WERE STRIPPED OUT.

330KVABLDG 17: XFMR (MRI) SQUARE D EE30T3H

BLDG 17: PNL A (MRI)

D.O.

ELECTRICALLY OPERATED

BREAKER TYPE

TRIP UNIT TYPE

SGHA36AT0600

CUBICLE CODE

SN / SO NO.

MOUNTING

GE

NA

NA

600SPECTRA RMS

FUSE CAT. NO.

TCLK265

SENSOR TAPS

CB/201

TRIP UNIT CAT #

MANUFACTURER

INSPECTED CONDITION CLEAN/LUBE INSPECTED CONDITION CLEAN/LUBE

C

NA

C

C

NA

C

Description

ARC CHUTES

AUXILIARY DEVICES

GROUND CONNECTION

Description

CUBICLE AND RACKING DEVICES

CONTACT FINGERS

LOADING AND ARCING CONTACTS

OVERCURRENT DEV. BATTERY CTRIP UNIT

COUNTER BEGINNING

PAGE

ADDRESS

CUSTOMER

LOW VOLTAGE POWER CIRCUIT BREAKER TEST 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

(765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

JOHN HENDRICKSOWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 2

3/7/2023 AMBIENT TEMPERATURE 19 30 %

POSITION

ASSET #:

CB/201

HUMIDITY°C

AUSTIN KNIGHTTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service 15200, REVISED 3/23/2023

NA

B.I.

NA

NOYES

GOOD

NA

GOOD

GOOD C

GOOD

GOOD

NA

GOOD

FRAME SIZE AMPS V600600

COUNTER END

= AA

600X 600

SENSOR TAP

DELAY

RATING PLUG

I2T

NA

NA

ADDI INFO

GRD. FLT.

INST.

SHORT

LONG

FUNCTION

SettingSETTINGS AS FOUND

A

X

X

X

5,400 A

A

A

9 -

X

A

A = A

5,400

600 600RATING PLUG

SENSOR TAP

NA

NA

SHORT

LONG 1

INST.

GRD. FLT.

SETTINGS AS LEFT FUNCTION Setting DELAY I2T ADDI INFO

Test Amps

% of Setting

Performance Tolerance

Pole 1 Pole 2 Pole 3 Targets

Found/Left Found/Left

Trip Unit SettingTest Criteria

Found/Left

Primary/Secondary Current Performance Tests

Long Time Delay

1 600 100 NA NA

1800 300 NA NA

NANA

34.334.3 /

36.2

NA

36.2

NA

34.9

NA

34.9

NA

/LongTime PU

Instant Delay

NA NA

8100 150 0/0.07 NA

9 5400 100 5419

0.01

0.01 /

0.010.01

5450 5450/

/0.030.03

5270 5270/

Instant PU

Insulation Resistance

POLE TO FRAME

2,680,000

3,000,000

2,578,160

2,886,000

2,886,000

3,000,000

3,000,000

3,000,000

2,886,000

2,886,000

2,700,000

3,000,000

3,000,000

2,597,400

2,886,000

2,886,000

2,886,000

LINE TO LOAD 3,000,000

EQUIPMENT TEMPERATURE TEMPERATURE CORRECTION FACTOR TO 20 °C

0.962°CV °C1,000

POLE 1 (M©) (P1-P2) POLE 2 (M©) (P2-P3)

TEST VOLTAGE

POLE 3 (M©) (P3-P1)

POLE TO POLE

READINGREADING 20°C20°CREADING 20°C

POLE RESISTANCE (µ©)

POLE 3

110.7106.7 100.6

POLE 2POLE 1

COMMENTS: UNABLE TO PERFORM LONGTIME PICKUP FOR THIS MODEL UNIT

DEFICIENCIES:

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 2 PANEL INSPECTIONSPOSITION

3/9/2023 AMBIENT TEMPERATURE 18 °C HUMIDITY 45 %

MELVIN WILLIAMSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

NQ225A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

SQUARE D

CATALOG #

NQ442L2C

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

NF250ABLDG2-EQ-HPP-4 SQUARE D NF430L2C

SO75KVABLDG2-TS-203 XFMR SQUARE D EXN76T3H

SERIES E2225ABLDG2-A SQUARE D NQODQ2

NQOD100ABLDG2-A1 SQUARE D NQOD424

CTLNABLDG2-B2-A2 WESTINGHOUSE NA

NQ100ABLDG2-A3 SQUARE D NQ430L1U

NA225ABLDG2-EQ-HPP-3 GE AEF3362MBX

APNBNABLDG2-B-EQ-DP-1 GE NA

B PHASE CABLE ON EQ--HPP-4 FOUND LOOSE. TIGHTENED.

QL112.5KVABLDG2-TS 201 XFMR GE 9T23Q9875

MCC600ABLDG2-MAIN MCC GE 481X0476L01

NLAB225ABLDG2-LP PNL LVA GE NA

NLAB225ABLDG2-PNL LVA GE NA

REPLACED 1-20A BREAKER. ALSO, REPLACED 2 BLANKS.

BLDG2-EQ-LLP-4

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 3 PANEL INSPECTIONSPOSITION

3/9/2023 AMBIENT TEMPERATURE 189 °C HUMIDITY 45 %

MELVIN WILLIAMSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

DT-375KVA

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

NA

CATALOG #

V48M28T7516CU

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

NANABLDG3-DISC TS-BLD3 EATON NA

PRL1A225ABLDG3-B3A1 CUTLER-HAMMER Y32048

NANABLDG3-B3A2 EATON NA

FOUND 3 SPARES WHICH TESTED BAD. BREAKER #2

SHOWED SIGNS OF CORROSION. RECOMMEND REPLACING

PRL1A225ABLDG3-B3A EATON YS2048

BLDG3-TS-BLD3 XFM

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 4 PANEL INSPECTIONSPOSITION

2/21/2023 AMBIENT TEMPERATURE 18 °C HUMIDITY 45 %

MELVIN WILLIAMSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

NA100A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

WESTINGHOUSE

CATALOG #

TY43727

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

BLDG4-B4-A

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 5 PANEL INSPECTIONSPOSITION

3/9/2023 AMBIENT TEMPERATURE 18 °C HUMIDITY 45 %

MELVIN WILLIAMSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

1NA

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

SQUARE D

CATALOG #

QOL24U

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

WEHB-15-CIR150ABLDG5- B5-A WESTINGHOUSE FY-43313

B1OB-18-CIR150ABLDG5-PP-5 WESTINGHOUSE FY-43313

S25KVABLDG5-T-B5A XFMR SQUARE D EE2553H

MP-230KVABLDG5-B5B XFMR SQUARE D PMP2-CTYPE 3R

THIS IS A PANEL/XFMR COMBINATION. UNABLE TO ACCESS

TRANSFORMER PICTURE.

BLDG5- 5-LP

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 6 PANEL INSPECTIONSPOSITION

3/9/2023 AMBIENT TEMPERATURE 18 °C HUMIDITY 45 %

MELVIN WILLIAMSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

PRL2A225A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

EATON

CATALOG #

EZB2042R

COMMENTS

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

NQ225ABLDG6-PPE-3 SQUARE D NQ442L2C

FOUND EACH PRMARY LUG TO BUSS LOOSE. RETIGHTENED.

PRL1A400ABLDG6-PP1 EATON EZB2060R

BREAKER 21/23 SHOING SIGNS OF CORROSION. BREAKER 25

SHOWING SIGNS OF OVERHEATING.

1225ABLDG6-PP1A EATON EZB2042R

AA112.5KVABLDG6-TS-6 XFMR EATON V48M28T12CU

3R400ABLDG6-B6-208V SW EATON DG325NRK

FOUND A PHASE LOOSE. RETIGHTENED. (FUSETRON FUS

FRN-R-350).

3R100ABLDG6-PP3 DISC. SQUARE D H323NRB

BUSSMAN- FUSE NON-100

N200ABLDG6-480V SWITCH EATON NA

LITTLE FUSE-FLSR 200ID

BLDG6-PP2

ADDRESS

CUSTOMER

4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION BUILDING # 7 PANEL INSPECTIONSPOSITION

3/9/2023 AMBIENT TEMPERATURE 18 °C HUMIDITY 45 %

Melvin WilliamsTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service REVISED 3/16/2023

G =

P =

C =

ITEMS REQUIRING IMMEDIATE CORRECTIVE ACTIONSITEMS FOUND IN POOR CONDITION AND REQUIRE FUTURE CORRECTIVE ACTION

ITEMS FOUND IN SATISFACTORY CONDITION ITEMS FOUND OR CORRECTED AND LEFT IN SATISFACTORY CONDITION

G P C I

WEHB15-CIR100A

CURRENT

RATING TYPE

RESULTS

LOCATION / PANEL ID MANUFACTURE

WESTINGHOUSE

CATALOG #

FY43313

COMMENTS

SPARE BREAKER # 1 AND 3 FOUND BAD.

PANEL INSPECTION

I =

CONDITIONS - (OVERALL , TORQUE CHECK, CLEANLINESS, CONTINUITY CHECKS)

WEHB15-CIR100ABLDG7-PP-7B WESTINGHOUSE FY43313

B10B18-CIR150ABLDG7-B7-B WESTINGHOUSE FY43313

QO50ABLDG7-A1 SQUARE D QOC16W

QO50ABLDG7-B7-B1 SQUARE D QOC16W

B10818-CIR150ABLDG7-B7-A WESTINGHOUSE FY43313

FOUND BREAKER #13 OF DOUBLE-POLE TO BE BAD. UNABLE

TO ESTABLISH CONTINUITY.

BLDG7-PP-7A

ADDRESS

CUSTOMER

TRANSFORMER MAINTENANCE AND INSPECTION 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION MAIN SUBSTATION 1500kVA EAST PADMOUNT XFMRPOSITION

3/1/2023 AMBIENT TEMPERATURE 15 °C HUMIDITY 45 %

TANK TYPE

5.9

NAMEPLATE DATA

976000796SERIAL NO.

D E

12,780

COOPER YR MFR 1997

KVA

IMPEDANCE //OA

WINDING MATERIAL °CALUMINUM

B

CLASS

B.I.L. RATING

PRIMARY V

TAP SETTING

/ 65

DISTRIB

MANUFACTURER

DELTA

/ 3095

WYE EXPOSED NEUTRAL - X0

11807627CAPACITY

TEMPERATURE RISE

LBSGAL WEIGHT TYPE

MFR LOCATION

INSULATING MEDIUM

0.277

12.470

12,470

277.12

13,090 12,780 12,470 12,160 11,850

A

V

WAUKESHA WI

SEALED

TAP VOLTAGES

TAP POSITION B

MINERAL OIL

CONSERVATOR

/1,500

SECONDARY V

C0.480

HIGH SIDE TAP LOW SIDE TAP

T. STAFFORD / B. ANDRUSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service 56750, REVISED 4/10/2023

NA YES 25'C NA YES

OIL C/ MAX WIND C/ MAX

POWER FACTOR

RESET LEVEL PRESSUREDATE OIL/DGA SAMPLE TAKEN

3/1/2023 30/50

EXTERNAL DOCUMENTS

ATTACHED TO REPORT

INSPECT PHYSICAL AND MECHANICAL CONDITION VERIFY FANS OPERATEPASS

NOTES

ROUTINEREASON FOR INSPECTION

Description NOTES

PASS

NA

Description

INSPECT ANCHORAGE, ALIGNMENT AND GROUNDING

VISUAL AND MECHANICAL INSPECTION

SECONDARY TO

GROUND

1.95

10,410

5,350

4,650

PRIMARY TO

SECONDARY

1.72

20,200

11,730

9,993

PRIMARY TO

GROUND

P. I. (10min/1min)

Test kV

0.50

1.00

10.00

MINUTES

10,640

6,710

1.59

INSULATION RESISTANCE (M©)

6,050

ELECTRICAL TESTS

20TEST AMPS20

WINDING RESISTANCE TEST (m©)

APPARATUS TEMP. (°C)

CORRECTED CORRECTEDMeasured CORRECTEDMeasured

CORRECTED CORRECTEDMeasured CORRECTEDMeasured

784.80 800.82 781.00 796.94 807.45 823.93

0.482 0.468 0.4670.472 0.458 0.458

H3-H1 H1-H2 H2-H3

X0-X1 X0-X2 X0-X3

Measured

Measured

TRANSFORMER TURN RATIO TEST

PHASE B PHASE CTAP CALC PHASE A

46.129 46.130B

ERROR 0.032% 0.026% 0.028%

46.117 46.132

COMMENTS:

DEFICIENCIES: UNABLE TO REMOVE H3A LOADBREAK CONNECTION FROM TRANSFORMER. PERFORMED ALL TESTING WITH CABLE INCLUDED IN RESULTS.

RECOMMEND REMOVAL OF LOADBREAK AND INSERT; REPLACE BOTH WITH NEW ONES. PICTURE(S) INCLUDED OF CONNECTION AND CABLE INFO.

IM

G

_7938 (H 3A

-1500K V

A ).jpg

IMG_7939 (H3A-1500KVA).jpg

976000796_X2 (1500KVA EAST)

TwoWindingTransformerReport Source

3/1/2023 8:01:08 PMSession Test Date

Nameplate - Two-winding Transformer Company PREMIER POWER MAINTENANCE Serial Number 976000796

Location VA-FORT WAYNE IN Special ID 1500KVA EAST XFMR

Division INDIANAPOLIS Circuit Designation

Manufacturer Cooper Power Systems Configuration D_Y

Year Manufactured 1997 Tank Type Sealed

Mfr Location WAUKESHA WI Coolant Oil

Phases Three Class OA

Oil Volume 627 UG BIL 95 kV

Weight 11807 LB kV 12.47, 0.48 VA Rating 1500, *, *, *, kVA

Administration Test Date 3/1/2023 Test Time: 8:01 PM Weather Night

Air Temperature 13.6°C Apparatus Temperature

30°C Humidity 53.748 %

Tester TRACY STAFFORD Work Order 220919 Date Last Tested

Verified BRANDON ANDRUS Test Set Type M4100 Date Retested

Verification Date 3/2/2023 Set Top Serial # 69400229 Reason Routine

Last Sheet # Test Set Model M4100 Travel Time

Purchase Order Ins. Book # Duration

Copies Sheet # Crew Size 3

Excitation Current & Losses Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume

DETC 5 * * 2 2 *

H1 H3 H2 H1 H2 H3

Winding :

Tap Position

(s)

Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual

HV: 2 10 75.730 575.601 L 29.485 227.850 L 78.636 577.315 L Good

Report generated on 3/2/2023 12:45:32 AM 1 - 1

TOP / BOTTOM VALVES

BUSHING OIL LEVEL PRI / SEC

GROUNDS

RESET GAUGES

OXYGEN CONTENT %

PRESSURE PSI

OIL LEVEL

#2 WINDING C / MAX

#1 WINDING C / MAX

EQPT. LOCATION

PAGE

ADDRESS

CUSTOMER

TRANSFORMER LIQUID COOLANT TRENDING 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION MAIN SUBSTATION 1500KVA EAST PADMOUNT XFMRPOSITION

3/1/2023 AMBIENT TEMPERATURE 15 °C HUMIDITY 45 %

DELTA

DELTA

WYE

NA 1,500 DISTRIB OA

°C 5.9

NA

1,804

CAPACITY

WINDING MATERIAL ALUMINUM

LBS627

NAMEPLATE DATA

MANUFACTURER 976000796SERIAL NO.

SPECIFICATION NO. TYPE CLASS

PHASE IMPEDANCE %

TOTAL WEIGHT 11807 LBS

K FACTOR NA

RATED CURRENT

RATED CURRENT

AMPERES

AMPERES/

TAP VOLTAGES 13,090 12,780 12,470 12,160 11,850

A B C D E

TAP SETTING B 12,780 Volts INTERNAL EXTERNAL DRY TYPE

12,470

TAP CHANGER:# FANS 0

COOPER

3 65TEMPERATURE RISE KV SEC.30B.I.L. RATING 95 KV PRI.

COOLANT MINERAL OIL

WINDING POLARITY

PRIMARY VOLTAGE

SECONDARY VOLTAGE

TAP CONNECTIONS

277 WYE

KVA

3/1/2023

OIL C / MAX

RADIATORS AND FANS

CONSERVATOR

AUTO GAS CYLINDER

RAPID RISE RELAY

SUDDEN PRESSURE RELIEF

PRI / SEC BUSHING VISUAL

30/50

NA

NA

25'C

NA

NT

YES

OK

NA

OK

NA

OK

OK/NA

NA

NA

NA

OK

TEST DATE

VISUAL INSPECTION

DOBLE ENGINEERINGSAMPLED BY: TESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service 57130, REVISED 1/31/2023

MELVIN WILLIAMS

PV SYSTEM

COMMENTS:

ADDRESS

CUSTOMER

TRANSFORMER MAINTENANCE AND INSPECTION 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121 LAKE AVE; FORT WAYNE IN USA 46805

FT WAYNE VA MEDICAL CENTER

JOB # 220919

OWNER REPRESENTATIVE TELEPHONE

DATE

SUBSTATION MAIN SUBSTATION 1500KVA WEST PADMOUNT XFMRPOSITION

3/1/2023 AMBIENT TEMPERATURE 15 °C HUMIDITY 45 %

TANK TYPE

5.9

NAMEPLATE DATA

976000795SERIAL NO.

D E

12,780

COOPER YR MFR 1997

KVA

IMPEDANCE //OA

WINDING MATERIAL °CALUMINUM

B

CLASS

B.I.L. RATING

PRIMARY V

TAP SETTING

/ 65

DISTRIB

MANUFACTURER

DELTA

/ 3095

WYE EXPOSED NEUTRAL - X0

11807627CAPACITY

TEMPERATURE RISE

LBSGAL WEIGHT TYPE

MFR LOCATION

INSULATING MEDIUM

0.277

12.470

12,470

277.12

13,090 12,780 12,470 12,160 11,850

A

V

WAUKESHA WI

SEALED

TAP VOLTAGES

TAP POSITION B

MINERAL OIL

CONSERVATOR

/1,500

SECONDARY V

C0.480

HIGH SIDE TAP LOW SIDE TAP

T. STAFFORD / B. ANDRUSTESTED BY:

www.premierpowermaintenance.com24 Hour Emergency Service 56750, REVISED 4/10/2023

NA YES 25'C NA YES

OIL C/ MAX WIND C/ MAX

POWER FACTOR

RESET LEVEL PRESSUREDATE OIL/DGA SAMPLE TAKEN

3/1/2023 30/50

EXTERNAL DOCUMENTS

ATTACHED TO REPORT

INSPECT PHYSICAL AND MECHANICAL CONDITION VERIFY FANS OPERATEPASS

NOTES

ROUTINEREASON FOR INSPECTION

Description NOTES

PASS

NA

Description

INSPECT ANCHORAGE, ALIGNMENT AND GROUNDING

VISUAL AND MECHANICAL INSPECTION

SECONDARY TO

GROUND

1.78

9,190

5,150

4,500

PRIMARY TO

SECONDARY

1.79

27,900

15,590

13,350

PRIMARY TO

GROUND

P. I. (10min/1min)

Test kV

0.50

1.00

10.00

MINUTES

22,300

13,340

1.67

INSULATION RESISTANCE (M©)

11,150

ELECTRICAL TESTS

20TEST AMPS20

WINDING RESISTANCE TEST (m©)

APPARATUS TEMP. (°C)

CORRECTED CORRECTEDMeasured CORRECTEDMeasured

CORRECTED CORRECTEDMeasured CORRECTEDMeasured

789.45 805.56 787.60 803.67 778.20 794.08

0.478 0.467 0.4670.469 0.458 0.457

H3-H1 H1-H2 H2-H3

X0-X1 X0-X2 X0-X3

Measured

Measured

TRANSFORMER TURN RATIO TEST

PHASE B PHASE CTAP CALC PHASE A

46.129 46.134B

ERROR 0.034% 0.026% 0.037%

46.117 46.133

COMMENTS:

DEFICIENCIES: UNABLE TO REMOVE ARRESTERS ON HIGH SIDE. RECOMMEND OUTAGE TO CUT BACK/REMOVE ALL 3 ARRESTERS FROM BUSHING AND REPLACE THEM WITH

COOPER RTE LPC215 8.3 / 14.4KV LOADBREAK ARRESTERS. PICTURES INCLUDED WITH TEST SHEET.

IMG_7944 (1500KVA W-ARRESTERS).jpg

IMG_7943 (1500KVA W-ARRESTERS).jpg

976000795_X2 (1500KVA WEST)

3/1/2023 7:56:08 PMSession Test Date

Nameplate - Two-winding Transformer Company PREMIER POWER MAINTENANCE Serial Number 976000795

Location VA-FORT WAYNE IN Special ID 1500KVA XFMR (WEST)

Division INDIANAPOLIS Circuit Designation

Manufacturer Cooper Power Systems Configuration D_Y

Year Manufactured 1997 Tank Type Sealed

Mfr Location WAUKESHA WI Coolant Oil

Phases Three Class OA

Oil Volume 627 UG BIL 95 kV

Weight 11807 LB kV 12.47, 0.48 VA Rating 1500, *, *, *, kVA

Administration Test Date 3/1/2023 Test Time: 7:56 PM Weather Night

Air Temperature 13.6°C Apparatus Temperature

30°C Humidity 53.138 %

Tester TRACY STAFFORD Work Order 220919 Date Last Tested

Verified BRANDON ANDRUS Test Set Type M4100 Date Retested

Verification Date 3/2/2023 Set Top Serial # 69400229 Reason Routine

Last Sheet # Test Set Model M4100 Travel Time

Purchase Order Ins. Book # Duration

Copies Sheet # Crew Size 3

Excitation Current & Losses Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume

DETC 5 * * 2 2 *

H1 H3 H2 H1 H2 H3

Winding :

Tap Position

(s)

Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual

HV: 2 10 76.703 578.358 L 30.238 221.700 L 78.789 575.115 L Good

Report generated on 3/2/2023 12:44:37 AM 1 - 1

GROUNDS

RESET GAUGES

OXYGEN CONTENT %

PRESSURE PSI

OIL LEVEL

#2 WINDING C / MAX

#1 WINDING C / MAX

EQPT. LOCATION

PAGE

ADDRESS

CUSTOMER

TRANSFORMER LIQUID COOLANT TRENDING 4035 Championship Drive Indianapolis, IN 46268

317-879-0660

JOHN HENDRICKS (765) 674-3321 x74390

2121…