Attach II - 092900 Gypsum Board.pdf

PDF 142 KB Posted

Attached to
Z1DA--Upgrade Fire Alarm System @ Cincinnati VAMC - Project # 539-22-101
Solicitation number
36C25025B0033
Issued by

About this file

This document is a technical specification (Section 09 29 00) for gypsum board installation at the Cincinnati Veterans Affairs Medical Center (VAMC) as part of a fire alarm system upgrade project. The specification provides detailed requirements for gypsum board products, including Type X gypsum board (5/8 inch thick), water-resistant gypsum backing board, and glass mat gypsum panels. Installation guidelines cover various aspects such as board placement, fastening techniques, finishing methods, and specific requirements for different construction types (single-ply, two-ply, and three-ply assemblies).

Key technical requirements include using post-consumer recycled paper for board facings, following ASTM standards for installation and finishing, and achieving a Level 4 finish for public-facing areas. The specification also addresses special considerations for acoustical, fire-rated, and sound-rated partitions, including sealing electrical box penetrations and maintaining construction integrity. The document is part of the bid documents for Project No. 539-22-101, with a focus on precise installation techniques and quality standards for gypsum board applications in the VA medical center renovation project.

View the file

Other files

File Type Posted
36C25025B0033 0008.docx DOCX document
36C25025B0033 0007.docx DOCX document
36C25025B0033 0006.docx DOCX document
Attach I - VAAR 852.219-75 VA NOTICE OF LIMITS ON SUBCONTRACTING_CERT OF COMPLIANCE FOR SERVICES AND CONSTRUCTION JAN 2023 DEV.docx DOCX document
36C25025B0033 0005.docx DOCX document
Attach III - Fire Watch Log.pdf PDF
Attach IV - Wage Determination 7.18.25.pdf PDF
Attach I - RFI 2 Responses.pdf PDF
36C25025B0033 0004.docx DOCX document
36C25025B0033 0003.docx DOCX document
Attach III - RFI 2 Addendum 1.doc DOC document
Attach II - Addendum 01 - 539-22-101.zip ZIP file
Attach I - RFI 1 Responses Revised 7.14.25.pdf PDF
36C25025B0033 0002.docx DOCX document
Attach I - RFI 1 Responses 7.3.2025.pdf PDF
36C25025B0033 0001.docx DOCX document
Sign In and Tour Info.pdf PDF
Attach VI - RFI 539-22-101.doc DOC document
Attach IV - VHA Directive 1192-01.pdf PDF
Attach II - Drawings BD 20250213.pdf PDF
Attach III - Specs 100-percent BD 20250213.pdf PDF
Attach I - Wage Determination 4.25.25.txt TXT text file
36C25025B0033_1.docx DOCX document
Attach V - Brand Name Justification.pdf PDF
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Cincinnati VAMC January 16, 2025

Upgrade Fire Alarm Bid Documents

Cincinnati, OH 45220-2637 Project No: 539-22-101

09 29 00 - 1

SECTION 09 29 00

GYPSUM BOARD

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies installation and finishing of gypsum board, including patching of existing walls at penetrations.

1.2 RELATED WORK

A. Acoustical Sealants: Section 07 92 00, JOINT SEALANTS.

1.3 TERMINOLOGY

A. Definitions and description of terms shall be in accordance with ASTM

C11, C840, and as specified.

B. "Yoked": Gypsum board cut out for opening with no joint at the opening

(along door jamb or above the door).

1.4 SUBMITTALS

A. Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT

DATA, AND SAMPLES.

B. Manufacturer's Literature and Data:

1. Finishing materials.

2. Laminating adhesive.

3. Gypsum board, each type.

C. Test Results:

1. Fire rating test, each fire rating required for each assembly.

D. Certificates: Certify that gypsum board types, gypsum backing board types, cementitious backer units, and joint treating materials do not contain asbestos material.

1.5 DELIVERY, IDENTIFICATION, HANDLING AND STORAGE

A. In accordance with the requirements of ASTM C840.

1.6 ENVIRONMENTAL CONDITIONS

A. In accordance with the requirements of ASTM C840.

1.7 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. American Society for Testing and Materials (ASTM):

C11-18b.................Terminology Relating to Gypsum and Related

Building Materials and Systems

C475/C475M-17(R2022)....Joint Compound and Joint Tape for Finishing

Gypsum Board

09 29 00 - 2

C840-23.................Application and Finishing of Gypsum Board

C919-22.................Sealants in Acoustical Applications

C954-22.................Steel Drill Screws for the Application of

Gypsum Board or Metal Plaster Bases to Steel

Stud from 0.033 in. (0.84mm) to 0.112 in.

(2.84mm) in thickness

C1002-22................Steel Self-Piercing Tapping Screws for the

Application of Gypsum Panel Products or Metal

Plaster Bases to Wood Studs or Steel Studs

C1047-19................Accessories for Gypsum Wallboard and Gypsum

Veneer Base

C1177/C1177M-17.........Glass Mat Gypsum Substrate for Use as

Sheathing

C1178/C1178M-18.........Specification for Coated Glass Mat Water

Resistant Backing Panel

C1658/C1658M-19(R2020)..Glass Mat Gypsum Panels

C1396/C1396M-17.........Gypsum Board

C. Underwriters Laboratories Inc. (UL):

Latest Edition..........(DIR) Online Certifications Directory

D. Inchcape Testing Services (ITS):

Latest Editions.........(DIR) Directory of Listed Products

PART 2 - PRODUCTS

2.1 GYPSUM BOARD

A. Gypsum Board: ASTM C1396, Type X, 16 mm (5/8 inch) thick unless shown otherwise.

B. Coreboard or Shaft Wall Liner Panels.

1. ASTM C1396, Type X.

2. ASTM C1658: Glass Mat Gypsum Panels,

3. Coreboard for shaft walls 300, 400, 600 mm (12, 16, or 24 inches) wide by required lengths 25 mm (one inch) thick with paper faces treated to resist moisture.

C. Water Resistant Gypsum Backing Board: ASTM C1178, Type X, 16 mm (5/8 inch) thick.

D. Paper facings shall contain 100 percent post-consumer recycled paper content.

09 29 00 - 3

2.2 ACCESSORIES

A. ASTM C1047, except form of 0.39 mm (0.015 inch) thick zinc coated steel sheet or rigid PVC plastic.

B. Flanges not less than 22 mm (7/8 inch) wide with punchouts or deformations as required to provide compound bond.

2.3 FASTENERS

A. ASTM C1002 and ASTM C840, except as otherwise specified.

B. ASTM C954, for steel studs thicker than 0.04 mm (0.33 inch).

C. Select screws of size and type recommended by the manufacturer of the material being fastened.

D. For fire rated construction, type and size same as used in fire rating test.

E. Clips: Zinc-coated (galvanized) steel; gypsum board manufacturer's standard items.

2.4 FINISHING MATERIALS AND LAMINATING ADHESIVE

A. ASTM C475 and ASTM C840. Free of antifreeze, vinyl adhesives, preservatives, biocides and other VOC. Adhesive shall contain a maximum VOC content of 50 g/l.

PART 3 - EXECUTION

3.1 INSTALLING GYPSUM BOARD

A. Coordinate installation of gypsum board with other trades and related work.

B. Install gypsum board in accordance with ASTM C840, except as otherwise specified.

C. Moisture and Mold–Resistant Assemblies: Provide and install moisture and mold-resistant glass mat gypsum wallboard products with moisture-resistant surfaces complying with ASTM C1658 where shown and in locations which might be subject to moisture exposure during construction.

D. Use gypsum boards in maximum practical lengths to minimize number of end joints.

E. Bring gypsum board into contact, but do not force into place.

F. Blow-Out Patches:

1. Holes over 3” diameter shall have patches screwed into stud framing. Provide supplemental framing as required.

09 29 00 - 4

2. Holes under 3” diameter may be laminated with full buttering of back of gypsum board and 6” minimum overlap of gypsum board at each side of opening. Use Type G screws to hold gypsum board patch in place.

G. Ceilings:

1. For single-ply construction, use perpendicular application.

2. For two-ply assembles:

a. Use perpendicular application.

b. Apply face ply of gypsum board so that joints of face ply do not occur at joints of base ply with joints over framing members.

H. Walls:

1. When gypsum board is installed parallel to framing members, space fasteners 300 mm (12 inches) on center in field of the board, and

200 mm (8 inches) on center along edges.

2. When gypsum board is installed perpendicular to framing members, space fasteners 300 mm (12 inches) on center in field and along edges.

3. Stagger screws on abutting edges or ends.

4. For single-ply construction, apply gypsum board with long dimension either parallel or perpendicular to framing members as required to minimize number of joints except gypsum board shall be applied vertically over "Z" furring channels.

5. For two-ply gypsum board assemblies, apply base ply of gypsum board to assure minimum number of joints in face layer. Apply face ply of wallboard to base ply so that joints of face ply do not occur at joints of base ply with joints over framing members.

6. For three-ply gypsum board assemblies, apply plies in same manner as for two-ply assemblies, except that heads of fasteners need only be driven flush with surface for first and second plies. Apply third ply of wallboard in same manner as second ply of two-ply assembly, except use fasteners of sufficient length enough to have the same penetration into framing members as required for two-ply assemblies.

7. No offset in exposed face of walls and partitions will be permitted because of single-ply and two-ply or three-ply application requirements.

I. Acoustical or Sound Rated Partitions, Fire and Smoke Partitions:

09 29 00 - 5

1. Cut gypsum board for a space approximately 3 mm to 6 mm (1/8 to 1/4 inch) wide around partition perimeter.

2. Coordinate for application of caulking or sealants to space prior to taping and finishing.

3. For sound rated partitions, use sealing compound (ASTM C919) to fill the annular spaces between all receptacle boxes and the partition finish material through which the boxes protrude to seal all holes and/or openings on the back and sides of the boxes. STC minimum values as shown.

J. Electrical and Telecommunications Boxes:

1. Seal annular spaces between electrical and telecommunications receptacle boxes and gypsum board partitions.

K. Accessories:

1. Set accessories plumb, level and true to line, neatly mitered at corners and intersections, and securely attach to supporting surfaces as specified.

2. Install in one piece, without the limits of the longest commercially available lengths.

3.2 FINISHING OF GYPSUM BOARD

A. Finish joints, edges, corners, and fastener heads in accordance with

ASTM C840. Use Level 4 finish for al finished areas open to public view.

B. Before proceeding with installation of finishing materials, assure the following:

1. Gypsum board is fastened and held close to framing or furring.

2. Fastening heads in gypsum board are slightly below surface in dimple formed by driving tool.

C. Finish joints, fasteners, and all openings, including openings around penetrations, on that part of the gypsum board extending above suspended ceilings to seal surface of non-decorated smoke barrier, fire rated, and sound rated gypsum board construction. After the installation of hanger rods, hanger wires, supports, equipment, conduits, piping and similar work, seal remaining openings and maintain the integrity of the smoke barrier, fire rated, and sound rated construction/ Sanding is not required of non-decorated surfaces.

09 29 00 - 6

3.3 REPAIRS

A. After taping and finishing has been completed, and before decoration, repair all damaged and defective work, including nondecorated surfaces.

B. Patch holes or openings 13 mm (1/2 inch) or less in diameter, or equivalent size, with a setting type finishing compound or patching plaster.

C. Repair holes or openings over 13 mm (1/2 inch) diameter, or equivalent size, with 16 mm (5/8 inch) thick gypsum board secured in such a manner as to provide solid substrate equivalent to undamaged surface.

D. Tape and refinish scratched, abraded or damaged finish surfaces including cracks and joints in non-decorated surface to provide smoke tight construction fire protection equivalent to the fire rated construction and STC equivalent to the sound rated construction.

- - - E N D - - -