Sheet AI101 - Add 01.pdf

PDF 327 KB Posted

Attached to
506-22-207 Facilities Maintenance Upgrades Federal contract opportunity
Solicitation number
36C25025B0027
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This document is a detailed architectural drawing (Sheet AI101) for the Ann Arbor VA Medical Center Facilities Maintenance Upgrades project, focusing on door and interior renovation specifications for the Surgical Suite in Building 1E. The drawing includes comprehensive schedules for room finishes, door specifications, and interior elevations, with key details such as:

Door Schedule: Includes 20 doors with specifications for width (3'-0" to 4'-0"), height (7'-0"), material (metal), and special requirements like lead lining and automatic operators. Many doors are designated as lead-lined, with various hardware sets and fire ratings. Door notes specify armor plating, painting requirements, and hardware set references. Room Finish Schedule covers multiple surgical and support spaces (e.g., Scrub Alcoves, Operating Rooms, Sub-Sterile areas) with resinous flooring (RF-1/RF-2) and existing finishes to remain. The document is part of bid documents dated 02/06/2025 with an addendum on 06/05/2025, prepared by FFE Engineering & Architecture for the VA Medical Center.

View the file

Other files for this federal contract opportunity

Show all 15

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NEW DOOR AUTOMATIC

OPERATOR WITH PUSH BUTTON.

REFER TO AI101 DOOR SCHEDULE

FOR OPERATOR INFORMATION.

DASHED LINE INDICATES AREA

FOR NEW AUTO OPERATOR - SEE

DOOR SCHEDULE AND PLAN.

RELOCATED ITEMS TO AVOID NEW AUTO

OPERATOR AND EXISTING LEAD LINING.

EXISTING HANDRAIL TO REMAIN -

REMOVE AND REINSTALL AS

NECESSARY FOR INSTALLATION

OF TEMPORARY CONSTRUCTION

BARRIERS.

EXISTING WALL BUMPER GUARD

TO REMAIN - REMOVE AND

REINSTALL AS NECESSARY FOR

INSTALLATION OF TEMPORARY

CONSTRUCTION BARRIERS.

NEW LEAD-LINED HOLLOW METAL

DOOR - SEE DOOR SCHEDULE.

EXISTING LEAD LINING AT OPERATING

ROOM INTERIOR FACE UP TO 7'-0" A.F.F.

SEE SCHEDULE

S E

E S

C H

E D

U L E

NOTES:

LX LEADED X-RAY SAFETY GLAZING

V1

SEE SCHEDULE

S E

E S

C H

E D

U L E

F

LX

SEE SCHEDULE

S E

E S

C H

E D

U L E

NL

LX

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /A n n

A rb o r

V A

F

M U p g ra d e s /F

F E

A n n

A rb o r

F

M U p g ra d e s B

E rv t

/5

/2

:3

:2

A

M

AI101

SCHEDULES AND INTERIOR

ELEVATION

05/14/2025 SS KT

FACILITY MAINTENANCE

UPGRADES

506-22-207

ANN ARBOR, MICHIGAN

BID DOCUMENTS

1E

ANN ARBOR VA

MEDICAL

CENTER Approved: Veteran's Affairs Medical Center

ROOM FINISH SCHEDULE

ROOM NAME ROOM NUMBER AREA FLOOR FINISH CEILING

WALL FINISH

WALL BASEN E S W

SCRUB ALCOVE C5-13A 94 SF RF-1 ETR ETR ETR ETR ETR RF-1

SCRUB ALCOVE C5-13B 99 SF RF-1 ETR ETR ETR ETR ETR RF-1

SCRUB ALCOVE C15-13F 100 SF RF-1 ETR ETR ETR ETR ETR RF-1

SCRUB ALCOVE C521A 51 SF RF-1 ETR ETR ETR ETR ETR RF-1

SCRUB ALCOVE C521B 46 SF RF-1 ETR ETR ETR ETR ETR RF-1

SUB-STERILE D505B 103 SF RF-1 ETR ETR ETR ETR ETR RF-1

SPECIAL OR NO 9 (ORTHO) D507 628 SF RF-1/2 ETR ETR ETR ETR ETR RF-1

STORAGE D507A 53 SF RF-1 ETR ETR ETR ETR ETR RF-1

ANESTHESIA WORKROOM D518 588 SF ETR ETR ETR ETR ETR ETR ETR

CONTROL ROOM D521B 74 SF RF-1 ETR ETR ETR ETR ETR RF-1

SUB-STERILE D523A 109 SF RF-1 ETR ETR ETR ETR ETR RF-1

STERILE SUPPLY D525A 85 SF RF-1 ETR ETR ETR ETR ETR RF-1

STERILE SUPPLY E507A 61 SF RF-1 ETR ETR ETR ETR ETR RF-1

GENERAL OR 1 E508 782 SF RF-1/2 ETR ETR ETR ETR ETR RF-1

GENERAL OR 2 E525 434 SF ETR ETR ETR ETR ETR ETR ETR

SUB STERILE E525C 62 SF ETR ETR ETR ETR ETR ETR ETR

CONTROL ROOM E525D 47 SF ETR ETR ETR ETR ETR ETR ETR

FINISH LEGEND

MARK DESCRIPTION BASIS OF DESIGN STYLE / COLOR COMMENTS

ETR EXISTING TO REMAIN - - -

P-1 NOT USED - - -

P-2 PAINT - TYPE 2 TBD HIGH BUILD GLAZED COATING (EPOXY)

RF-1 RESINOUS FLOORING STONHARD TBD INTEGRAL WALL BASE

RF-2 RESINOUS FLOORING STONHARD TBD INTEGRAL WALL BASE

WSF-1 WELDED SHEET FLOORING TBD INTEGRAL WALL BASE

DOOR SCHEDULE

DOOR NUMBER

NO. OF

DOORS WIDTH HEIGHT THICKNESS

DOOR

MATERIAL

DOOR

TYPE

FRAME

MATERIAL

DOOR

FINISH

FRAME

FINISH

HARDWARE

SET

LEAD

LINED FIRE RATED AUTO OPERATOR

E505AA 1 4' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 6.0 YES - EXISTING AUTO OPERATOR

E505FF 1 4' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 12.0 YES - EXISTING AUTO OPERATOR

E505G 2 3' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 7.0 YES - NEW AUTO OPERATOR

E505GG 1 4' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 14.0 YES - NEW AUTO OPERATOR

E505II 1 3' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 5.0 YES - -

E505L 2 3' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 7.0 YES - NEW AUTO OPERATOR

E505M 2 3' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 10.0 YES - EXISTING AUTO OPERATOR

NON-FUNCTIONING.

PROVIDE NEW AUTO

OPERATOR

E505N 2 3' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 10.0 YES - EXISTING AUTO OPERATOR

E505O 2 3' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 9.0 YES - NEW AUTO OPERATOR

E505OO 2 3' - 0" 7' - 0" 1 3/4" METAL NL ETR P-2 P-2 3.0 - 90MIN -

E505PP 2 3' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 9.0 YES - EXISTING AUTO OPERATOR

E505Q 1 4' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 5.0 YES - -

E505QQ 2 3' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 9.0 YES - EXISTING AUTO OPERATOR

E505S 1 4' - 0" 7' - 0" 1 3/4" METAL NL ETR P-2 P-2 1.0 - - -

E505V 1 4' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 14.0 YES - NEW AUTO OPERATOR

E505W 2 3' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 9.0 YES - NEW AUTO OPERATOR

E505X 2 3' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 9.0 YES - NEW AUTO OPERATOR

E505Z 1 4' - 0" 7' - 0" 1 3/4" METAL V1 ETR P-2 P-2 14.0 YES - NEW AUTO OPERATOR

1/4" = 1'-0"

INTERIOR ELEVATION AT TYPICAL CORRIDOR DOOR

1/4" = 1'-0"

DOOR ELEVATIONS

DOOR NOTES

1.) ALL NEW DOORS TO RECEIVE ARMOR PLATE ON THE PUSH SIDE AND A MOP PLATE ON THE PULL SIDE.

2.) PAINT BOTH SIDES OF ALL NEW HOLLOW METAL DOOR FRAMES.

3.) REFER TO SPECIFICATIONS FOR DOOR HARDWARE SETS.

No. Revisions: Date:

BID DOCUMENTS V.2 02/06/2025

1 ADDENDUM #1 06/05/2025

Sheets
AI101 - SCHEDULES AND INTERIOR ELEVATION

File details come from the government source that posted it. Updated .