This document is a Door Hardware specification (Section 08 71 00) for the Lieutenant Colonel Charles S. Kettles VA Medical Center's Facilities Maintenance Upgrades project, providing comprehensive technical requirements for door hardware installation. The specification covers detailed requirements for various hardware components, including hinges, continuous hinges, door closers, overhead stops, locks, electric strikes, armor plates, kick plates, flush bolts, door pulls, and thresholds, with specific guidelines for material finishes, installation heights, and compliance with accessibility and fire safety standards.
The document includes 14 detailed hardware sets specifying exact product types, manufacturers, and configurations for different door applications, such as fire-rated doors, office entries, and automatic operator doors. Key technical requirements include using BEST Great Grand Master Key System for cylinders, requiring anti-microbial coatings on hand-operated hardware, ensuring compliance with ABAAS accessibility standards, and specifying warranties ranging from 2 to 10 years depending on the hardware component. Manufacturers listed as basis of design include McKinney, Rixson, Rockwood, SARGENT, HES, Norton, Besam, and Securitron, with specific model numbers provided for each hardware set.
View the file
Other files for this federal contract opportunity
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum #1 Lieutenant Colonel Charles S. Kettles VA Medical Center
06/05/2025 Facilities Maintenance Upgrades
Project Number 506-22-207
05-01-2022
08 71 00-1
DOOR HARDWARE
SECTION 08 71 00
DOOR HARDWARE
PART 1 - GENERAL
1.1 DESCRIPTION
Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
Application of Hardware: Section 08 11 13, HOLLOW METAL DOORS AND
FRAMES.
Painting: Section 09 91 00, PAINTING.
Electrical: Division 26, ELECTRICAL.
1.3 GENERAL
All hardware shall comply with ABAAS, (Architectural Barriers Act
Accessibility Standard) unless specified otherwise.
Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).
Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.
Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.
The following items shall be of the same manufacturer, except as otherwise specified:
1. Mortise locksets.
2. Hinges for hollow metal and wood doors.
3. Surface applied overhead door closers.
4. Exit devices.
5. Floor closers.
Project Number 506-22-207
05-01-2022
08 71 00-2
DOOR HARDWARE
1.4 WARRANTY
Automatic door operators shall be subject to the terms of FAR Clause
52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:
1. Locks, latchsets, and panic hardware: 5 years.
2. Door closers and continuous hinges: 10 years.
1.5 MAINTENANCE MANUALS
In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled
"INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES. Submit 6 copies of the schedule per Section
01 33 23. Submit 2 final copies of the final approved schedules to VAMC
Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).
Hardware Schedule: AHC certified hardware consultant to prepare and submit hardware schedule in the following form:
Hardware
Item
Quantity Size Reference
Publication
Type No.
Finish Mfr.
Name and
Catalog
No.
Key
Control
Symbols
UL Mark
(if fire rated and listed)
ANSI/BHMA
Finish
Designation
Samples and Manufacturers' Literature:
1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers
Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.
2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.
Existing door frames must be surveyed, on site, to review existing hardware preparations and any conflicts with specified hardware
Project Number 506-22-207
05-01-2022
08 71 00-3
DOOR HARDWARE
components. Conduct site survey prior to submittal of door hardware schedule.
Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.
1.7 DELIVERY AND MARKING
Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to
COR for reference purposes. Tag shall identify items by Project
Specification number and manufacturer's catalog number. These items shall remain on file in COR's office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 PREINSTALLATION MEETING
Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Project Engineer and VA Locksmith, Hardware Consultant, and
Hardware Manufacturer’s Representative. Review the following:
1. Inspection of door hardware.
2. Job and surface readiness.
3. Coordination with other work.
4. Protection of hardware surfaces.
5. Substrate surface protection.
6. Installation.
7. Adjusting.
8. Repair.
9. Field quality control.
10. Cleaning.
Project Number 506-22-207
05-01-2022
08 71 00-4
DOOR HARDWARE
1.9 INSTRUCTIONS
Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols. Symbols for hardware sets consist a number. Each number designates a set of hardware items applicable to a door type.
Keying: All cylinders shall be keyed into existing BEST Great Grand
Master Key System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset.
Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the COR.
1. Supply information regarding key control of cylinder locks to manufacturers of equipment having cylinder type locks. Notify COR immediately when and to whom keys or keying information is supplied.
Return all such keys to the COR.
1.10 APPLICABLE PUBLICATIONS
The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.
American National Standards Institute/Builders Hardware Manufacturers
Association (ANSI/BHMA):
A156.1-06...............Butts and Hinges
A156.3-08...............Exit Devices, Coordinators, and Auto Flush Bolts
A156.4-08...............Door Controls (Closers)
A156.5-14...............Cylinders and Input Devices for Locks.
A156.6-05...............Architectural Door Trim
A156.8-05...............Door Controls-Overhead Stops and Holders
A156.13-05..............Mortise Locks and Latches Series 1000
A156.14-07 .............Sliding and Folding Door Hardware
A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical
A156.16-08..............Auxiliary Hardware
A156.18-06..............Materials and Finishes
A156.21-09..............Thresholds
A156.22-05..............Door Gasketing and Edge Seal Systems
Project Number 506-22-207
05-01-2022
08 71 00-5
DOOR HARDWARE
A156.25-07 .............Electrified Locking Devices
A156.26-06..............Continuous Hinges
A156.28-07 .............Master Keying Systems
A156.31-07 .............Electric Strikes and Frame Mounted Actuators
A156.36-10..............Auxiliary Locks
A250.8-03...............Standard Steel Doors and Frames
National Fire Protection Association (NFPA):
80-10...................Fire Doors and Other Opening Protectives
101-09..................Life Safety Code
Underwriters Laboratories, Inc. (UL):
Building Materials Directory (2008)
PART 2 - PRODUCTS
2.1 BUTT HINGES
ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:
1. Exterior Doors: Type A2112/A5112 for doors 900 mm (3 feet) wide or less and Type A2111/A5111 for doors over 900 mm (3 feet) wide. Hinges for exterior outswing doors shall have non-removable pins. Hinges for exterior fire-rated doors shall be of stainless steel material.
2. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.
Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.
Provide quantity and size of hinges per door leaf as follows:
1. Doors up to 1210 mm (4 feet) high: 2 hinges.
2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.
3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.
4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm
(4-1/2 inches x 4-1/2 inches) hinges.
5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
Project Number 506-22-207
05-01-2022
08 71 00-6
DOOR HARDWARE
6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).
7. Provide heavy-weight hinges where specified.
8. At doors weighing 330 kg (150 pounds) or more, furnish 127 mm (5 inch) high hinges.
See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.
2.2 CONTINUOUS HINGES
ANSI/BHMA A156.26, Grade 1-600.
1. Listed under Category N in BHMA's "Certified Product Directory."
General: Minimum 14 gauge stainless steel, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete
Continuous, Pin and Barrel-Type Hinges: Hinge with knuckles formed around 0.187 inch minimum diameter stainless steel pin that extends entire length of hinge.
1. Base Metal for Exterior Hinges: Stainless steel.
2. Base Metal for Interior Hinges: Stainless steel.
3. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.
4. Provide with non-removable pin (hospital tip option) at lockable outswing doors.
5. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.
6. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.
7. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.
8. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.
Project Number 506-22-207
05-01-2022
08 71 00-7
DOOR HARDWARE
2.3 DOOR CLOSING DEVICES
Closing devices shall be products of one manufacturer for each type specified.
2.4 OVERHEAD CLOSERS
Conform to ANSI A156.4, Grade 1.
Closers shall conform to the following:
1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.
2. Where specified, closer shall have hold-open feature.
3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.
4. Material of closer body shall be forged or cast.
5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.
6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.
7. Closers shall have full size metal cover; plastic covers will not be accepted.
8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.
9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.
10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.
11. Provide parallel arm closers with heavy duty rigid arm.
Project Number 506-22-207
05-01-2022
08 71 00-8
DOOR HARDWARE
12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.
13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
14. All closers shall have a 1 ½” (38mm) minimum piston diameter.
2.5 DOOR STOPS
Conform to ANSI A156.16.
Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use expansion shields for mounting door stops.
Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.
Provide floor stops (Type L02141 or L02161) in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.
Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.
Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.
Omit stops where floor mounted door holders are required and where automatic operated doors occur.
Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.
Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.
Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.
Project Number 506-22-207
05-01-2022
08 71 00-9
DOOR HARDWARE
Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.
Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).
2.6 OVERHEAD DOOR STOPS AND HOLDERS
Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.
2.7 LOCKS AND LATCHES
Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have not less than seven pins. Cylinders for all locksets shall be removable core type. Cylinder shall be removable by special key or tool. Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Great Grand Master Key System. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.
In addition to above requirements, locks and latches shall comply with following requirements:
1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 1. All locksets and latchsets, except on designated doors in Psychiatric (Mental Health) areas, shall have lever handles fabricated from cast stainless steel.
Provide sectional (sectional x lever) lever design matching Sargent
LNP. No substitute lever material shall be accepted. All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension.
Project Number 506-22-207
05-01-2022
08 71 00-10
DOOR HARDWARE
Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. All lock cases installed on lead lined doors shall be lead lined before applying final hardware finish. Furnish armored fronts for all mortise locks. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.
2.8 ELECTRIC STRIKES
ANSI/ BHMA A156.31 Grade 1.
General: Use fail-secure electric strikes at fire-rated doors.
2.9 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
Conform to ANSI Standard A156.6.
Provide protective plates and door edging as specified below:
1. Kick plates, mop plates and armor plates of metal, Type J100 series.
2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) ) high. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges
(B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates 25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.
3. Kick plates and/or mop plates are not required on following door sides:
a. Armor plate side of doors;
b. Exterior side of exterior doors;
c. Closet side of closet doors;
4. Armor plates for doors are listed under Article "Hardware Sets".
Armor plates shall be thickness as noted in the hardware set, 875 mm
(36 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all 4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail. On doors
Project Number 506-22-207
05-01-2022
08 71 00-11
DOOR HARDWARE
equipped with panic devices, extend armor plates to within 13 mm (1/2 inch) of panic bolt push bar.
5. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.
6. Provide stainless steel edge guards where so specified at wood doors.
Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.
2.10 FLUSH BOLTS (LEVER EXTENSION)
Conform to ANSI A156.16. Flush bolts shall be Type L24081 unless otherwise specified. Furnish proper dustproof strikes conforming to ANSI
A156.16, for flush bolts required on lower part of doors.
Lever extension manual flush bolts shall only be used at non-fire-rated pairs for rooms only accessed by maintenance personnel.
Face plates for cylindrical strikes shall be rectangular and not less than 25 mm by 63 mm (1 inch by 2-1/2 inches).
Friction-fit cylindrical dustproof strikes with circular face plate may be used only where metal thresholds occur.
Provide extension rods for top bolt where door height exceeds 2184 mm (7 feet 2 inches).
2.11 FLUSH BOLTS (AUTOMATIC)
Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI
A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).
At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than
Project Number 506-22-207
05-01-2022
08 71 00-12
DOOR HARDWARE
20 minutes; provide fire pins as required by auto flush bolt and door fire labels.
2.12 DOOR PULLS WITH PLATES
Conform to ANSI A156.6. Pull Type J401, 152 mm CTC (6 inches CTC) length by 19 mm (3/4 inches) diameter minimum with plate Type J302, 90 mm by
381 mm (3-1/2 inches by 15 inches), unless otherwise specified. Provide pull with projection of 57.2 mm (2 1/4 inches) minimum and a clearance of 38.1 mm (1 1/2 inches) minimum. Cut plates of door pull plate for cylinders, or turn pieces where required.
2.13 PUSH PLATES
Conform to ANSI A156.6. Metal, Type J302, 203 mm (8 inches) wide by
406.4 mm (16 inches) high. Provide metal Type J302 plates 102 mm (4 inches) wide by 406.4 mm (16 inches) high where push plates are specified for doors with stiles less than 203 mm (8 inches) wide. Cut plates for cylinders, and turn pieces where required.
2.14 COMBINATION PUSH AND PULL PLATES
Conform to ANSI 156.6. Type J303, stainless steel 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with 38 mm (1-1/2 inch) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.
2.15 COORDINATORS
Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.
2.16 THRESHOLDS
Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be
Project Number 506-22-207
05-01-2022
08 71 00-13
DOOR HARDWARE
installed in a bed of sealant with ¼-20 stainless steel machine screws and expansion shields. In new construction, embed aluminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for the full width of the openings.
For thresholds at elevators entrances see other sections of specifications.
At exterior doors and any interior doors exposed to moisture, provide threshold with non-slip abrasive finish.
Provide with miter returns where threshold extends more than 12 mm (0.5 inch) beyond face of frame.
2.17 AUTOMATIC DOOR BOTTOM SEAL AND RUBBER GASKET FOR LIGHT PROOF OR SOUND
CONTROL DOORS
Conform to ANSI A156.22. Provide mortise or under-door type, except where not practical. For mortise automatic door bottoms, provide type specific for door construction (wood or metal).
2.18 FINISHES
Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING.
626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.
Miscellaneous Finishes:
1. Hinges --interior doors: 630.
2. Pivots: Match door trim.
3. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.
4. Thresholds: Mill finish aluminum.
5. Cover plates for floor hinges and pivots: 630.
6. Other primed steel hardware: 600.
Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests.
Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.
Project Number 506-22-207
05-01-2022
08 71 00-14
DOOR HARDWARE
2.19 BASE METALS
Apply specified U.S. Standard finishes on different base metals as following:
Finish Base Metal
652 Steel
626 Brass or bronze
630 Stainless steel
PART 3 - EXECUTION
3.1 HARDWARE HEIGHTS
For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA COR for approval.
Hardware Heights from Finished Floor:
1. Exit devices centerline of strike (where applicable) 1024 mm (40-5/16 inches).
2. Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches).
3. Deadlocks centerline of strike 1219 mm (48 inches).
4. Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket.
5. Centerline of door pulls to be 1016 mm (40 inches).
6. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.
7. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.
8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.
3.2 INSTALLATION
Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Where closers are mounted on doors they shall be mounted with hex nuts and bolts; foot shall be fastened to frame with machine screws.
Hinge Size Requirements:
Door Thickness Door Width Hinge Height
45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)
Project Number 506-22-207
05-01-2022
08 71 00-15
DOOR HARDWARE
Door Thickness Door Width Hinge Height
45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)
125 mm (5 inches)
35 mm (1-3/8 inch)
(hollow core wood doors)
Not over 1200 mm (4 feet) 113 mm (4-1/2 inches)
Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.
Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by
COR. Existing hinges shall not be reused on door openings having new doors and new frames. Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.
Hinges Required Per Door:
Door Description Number butts
Doors over 1500 mm (5 ft) high and not over 2280 mm
(7 ft 6 in) high
3 butts
Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted. All fastenings exposed to weather shall be of nonferrous metal.
After locks have been installed; show in presence of COR that keys operate their respective locks in accordance with keying requirements.
(All keys, Master Key level and above shall be sent Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the COR for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.
Project Number 506-22-207
05-01-2022
08 71 00-16
DOOR HARDWARE
3.3 FINAL INSPECTION
Installer to provide letter to VA Resident/Project Engineer that upon completion, installer has visited the Project and has accomplished the following:
1. Re-adjust hardware.
2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.
3. Identify items that have deteriorated or failed.
4. Submit written report identifying problems.
3.4 DEMONSTRATION
Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of COR and VA Locksmith.
3.5 HARDWARE SETS
Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.
Existing door frames must be surveyed, on site, to review existing hardware preparations and any conflicts with specified hardware components. Conduct site survey prior to submittal of door hardware schedule.
Manufacturers listed in hardware sets below represent the Basis of Design.
1. MK - McKinney
2. RF - Rixson
3. RO - Rockwood
4. SA - SARGENT
5. HS - HES
6. NO - Norton
7. BM - Besam
8. OT - Other
9. SU - Securitron
Hardware Sets
Project Number 506-22-207
05-01-2022
08 71 00-17
DOOR HARDWARE
Set: 1.0
3 Hinge, Full Mortise TA2314xNRP 5" x 4-1/2" US32D MK
1 Keypad Cylindrical Lock 70 KP10G77 LL US26D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Surf Overhead Stop 9-X36 x lead lined thru-bolts
630 RF
1 Surface Closer 8501 M MLL 689 NO
1 Armor Plate K1050 36" high SA BEV US32D RO
1 Kick Plate K1050 8" high SA BEV US32D RO
Set: 2.0
3 Hinge, Full Mortise TA2314 x NRP US32D MK
1 Classroom Lock 70 74 8237 ALP US32D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Surface Closer 7500H M - pull side mount
(H.O.)
689 NO
1 Armor Plate K1050 36" high SA BEV US32D RO
1 Wall Stop 409 US32D RO
Notes: Latch bolt by paddle either side unless outside paddle is locked by key outside. Outside paddle remains locked unless unlocked by key. Inside paddle always free for egress.
Set: 3.0 – Fire Rated Door – 90 min
6 Hinge, Full Mortise TA2314 x NRP US32D MK
2 Manual Flush Bolt 555 US26D RO
1 Dust Proof Strike 570 US26D RO
1 Keypad Cylindrical Lock 70 KP10G77 LL US26D SA
Project Number 506-22-207
05-01-2022
08 71 00-18
DOOR HARDWARE
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
2 Surf Overhead Stop 9-X36 x lead lined thru-bolts
630 RF
1 Surface Closer 8501 M MLL 689 NO
2 Armor Plate K1050 36" high SA BEV US32D RO
2 Kick Plate K1050 8" high SA BEV US32D RO
1 Astragal (R0Y634) 357C PE
Adhesive Gasketing
(R0Y154)
S88BL PE
Set: 4.0
3 Hinge (heavy weight) T4A3786 (NRP) US26D MK
1 Mortise Deadlock 70 74 4875 x LB thrumb turn
US26D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Pull Plate BF 125x70B CFC x lead lined thru-bolts
US32D RO
1 Push Pull 91-RKW CFC SA US32D RO
1 Surface Closer 7500 M MLL - pull side mount
689 NO
1 Armor Plate K1050 36" high SA BEV US32D RO
Notes: ** Coordinate hinge temple with lead lining in hollow metal door.
Dead bolt projected and retracted by both key outside and thumb turn inside.
Set: 5.0
1 Pivot Set L147 630 RF
Project Number 506-22-207
05-01-2022
08 71 00-19
DOOR HARDWARE
1 Intermediate Pivot ML19 630 RF
1 Office/Entry Lock 70 74 8205 ALP US32D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Surface Closer CPS7500T M MLL 689 NO
Notes: Latch operated by paddle either side, unless outside paddle is locked or unlocked by key outside or thumb turn inside. Outside paddle is unlocked by key outside or thumb turn inside. Latch is retracted by key outside when outside paddle is locked. Inside paddle always free for egress.
Set: 6.0
1 Intermediate Pivot ML19 630 RF
1 Office/Entry Lock 70 74 8205 ALP US32D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Surf Overhead Stop 9-X36 x lead lined thru-bolts
630 RF
1 Reuse Existing Automatic Operator and
Accessories
OT
Notes: Latch operated by paddle either side, unless outside paddle is locked or unlocked by key outside or thumb turn inside. Outside paddle is unlocked by key outside or thumb turn inside. Latch is retracted by key outside when outside paddle is locked. Inside paddle always free for egress.
Set: 7.0
2 Pivot Set L147 630 RF
1 Intermediate Pivot ML19 630 RF
1 Electrified Inter Pivot EML19 626 RF
Project Number 506-22-207
05-01-2022
08 71 00-20
DOOR HARDWARE
1 Auto. Flush Bolt Set 2845 US26D RO
1 Dust Proof Strike 570 US26D RO
1 Dormitory Lock 70 8245 ALP US32D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Electric Strike 1600-CDB-DLMS 630 HS
1 SMART Pac Bridge Rectifier 2005M3 HS
2 Surf Overhead Stop 9-X36 x lead lined thru-bolts
630 RF
Automatic Operator (double door)
Besam SW200i - push side mount
BM
2 Armor Plate K1050 36" high SA BEV US32D RO
2 Kick Plate K1050 8" high SA BEV US32D RO
1 Door Switch 505 (6" x 6") NO
1 Power Supply AQL4-R8E1 SU
Notes: Door normally closed and locked. Key outside and thumb turn inside both project and retract deadbolt.
Paddle outside is locked by toggle on lock edge or by projecting deadbolt.
Paddle outside is unlocked by toggle only.
Key outside retracts both latch bolt and deadbolt, outside paddle remains locked.
Paddle inside always retracts latch bolt and deadbolt simultaneously, paddle outside remains locked.
Activation of automatic operator switch shall cycle automatic operators if deadbolt of lockset is retracted (may utilize deadbolt lock monitor switch in electric strike for this function). Must time doors such that electric strike releases first, active leaf begins cycle second, and inactive leaf cycle opens last.
Set: 8.0
Project Number 506-22-207
05-01-2022
08 71 00-21
DOOR HARDWARE
1 Intermediate Pivot ML19 630 RF
1 Dormitory Lock 70 8245 ALP US32D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Electric Strike 1600-CDB-DLMS 630 HS
1 SMART Pac Bridge Rectifier 2005M3 HS
Automatic Operator (single door)
Besam SW200i - push side mount
BM
1 Armor Plate K1050 36" high SA BEV US32D RO
1 Kick Plate K1050 8" high SA BEV US32D RO
1 Door Switch 505 (6" x 6") NO
1 Power Supply AQL4-R8E1 SU
Notes: Door normally closed and locked. Key outside and thumb turn inside both project and retract deadbolt.
Paddle outside is locked by toggle on lock edge or by projecting deadbolt.
Paddle outside is unlocked by toggle only.
Key outside retracts both latch bolt and deadbolt, outside paddle remains locked.
Paddle inside always retracts latch bolt and deadbolt simultaneously, paddle outside remains locked.
Activation of automatic operator switch shall cycle automatic operator if deadbolt of lockset is retracted (may utilize deadbolt lock monitor switch in electric strike for this function).
Set: 9.0
2 Intermediate Pivot ML19 630 RF
1 Auto. Flush Bolt Set 2845 US26D RO
1 Dust Proof Strike 570 US26D RO
1 Mortise Deadlock 70 74 4875 x LB thumb turn US26D SA
Project Number 506-22-207
05-01-2022
08 71 00-22
DOOR HARDWARE
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Pull Plate BF 125x70B CFC x lead lined thru-bolts
US32D RO
1 Pull Plate BF 125x70B x lead lined thru-bolts
US32D RO
1 Push Pull 91-RKW CFC SA US32D RO
1 Push Pull 91-RKW SA US32D RO
1 Surf Overhead Stop 9-X36 x lead lined thru-bolts
630 RF
Automatic Operator (double door)
Besam SW200i - push side mount
BM
2 Armor Plate K1050 36" high SA BEV US32D RO
2 Kick Plate K1050 8" high SA BEV US32D RO
2 Door Switch 505 (6" x 6") NO
Notes: Dead bolt projected and retracted by both key outside and thumb turn inside.
Activation of either door switch shall cycle automatic operators only when deadbolt is in retracted position.
Set: 10.0
2 Intermediate Pivot ML19 630 RF
1 Auto. Flush Bolt Set 2845 US26D RO
1 Dust Proof Strike 570 US26D RO
1 Mortise Deadlock 70 74 4875 x LB thumb turn US26D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
Project Number 506-22-207
05-01-2022
08 71 00-23
DOOR HARDWARE
1 Pull Plate BF 125x70B CFC x lead lined thru-bolts
US32D RO
1 Pull Plate BF 125x70B x lead lined thru-bolts
US32D RO
1 Push Pull 91-RKW CFC SA US32D RO
1 Push Pull 91-RKW SA US32D RO
2 Surf Overhead Stop 9-X36 x lead lined thru-bolts
630 RF
1 Reuse Existing Automatic Operator and
Accessories
OT
2 Armor Plate K1050 36" high SA BEV US32D RO
2 Kick Plate K1050 8" high SA BEV US32D RO
2 Wall Stop 409 US32D RO
Set: 11.0
1 Intermediate Pivot ML19 630 RF
1 Mortise Deadlock 70 74 4875 x LB thumb turn US26D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Pull Plate BF 125x70B x lead lined thru-bolts
US32D RO
1 Push Pull 91-RKW CFC SA US32D RO
1 Surface Closer 7500 M MLL - pull side mount
689 NO
Project Number 506-22-207
05-01-2022
08 71 00-24
DOOR HARDWARE
1 Armor Plate K1050 36" high SA BEV US32D RO
Set: 12.0
1 Intermediate Pivot ML19 630 RF
1 Mortise Deadlock 70 74 4875 x LB thumb turn US26D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Pull Plate BF 125x70B CFC x lead lined thru-bolts
US32D RO
1 Push Pull 91-RKW CFC SA US32D RO
1 Surf Overhead Stop 9-X36 x lead lined thru-bolts
630 RF
1 Reuse Existing Automatic Operator and
Accessories
OT
1 Armor Plate K1050 36" high SA BEV US32D RO
1 Kick Plate K1050 8" high SA BEV US32D RO
Set: 13.0
Project Number 506-22-207
05-01-2022
08 71 00-25
DOOR HARDWARE
1 Pivot Set L147 630 RF
1 Intermediate Pivot ML19 630 RF
1 Mortise Deadlock 70 74 4875 x LB thumb turn US26D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Pull Plate BF 125x70B x lead lined thru-bolts
US32D RO
1 Push Pull 91-RKW CFC SA US32D RO
1 Surface Closer CPS7500T M MLL 689 NO
Set: 14.0
1 Intermediate Pivot ML19 630 RF
1 Mortise Deadlock 70 74 4875 x LB thumb turn US26D SA
Permanent Interchangeable
Core
- to match Owner's existing SFIC key system
1 Pull Plate BF 125x70B CFC x lead lined thru-bolts
US32D RO
1 Push Pull 91-RKW CFC SA US32D RO
1 Surf Overhead Stop 9-X36 x lead lined thru-bolts
630 RF
Automatic Operator (single door)
Besam SW200i - push side mount
BM
1 Armor Plate K1050 36" high SA BEV US32D RO
Project Number 506-22-207
05-01-2022
08 71 00-26
DOOR HARDWARE
- - - END - - -