08 11 13 Hollow Metal Doors and Frames - Add 01.pdf
PDF 80 KB Posted
- Attached to
- 506-22-207 Facilities Maintenance Upgrades Federal contract opportunity
- Solicitation number
- 36C25025B0027
About this file
This document is a technical specification section (Section 08 11 13) for Hollow Metal Doors and Frames, part of the Facilities Maintenance Upgrades project at the Lieutenant Colonel Charles S. Kettles VA Medical Center. The specification provides detailed requirements for standard and custom hollow metal doors, including interior and exterior door construction, materials, fabrication, installation, and finish standards. Key technical specifications include 1-3/4 inch doors with cold-rolled steel sheets, polystyrene or kraft-paper honeycomb cores, fire-rated and smoke control door options, and precise installation tolerances for non-fire-rated and fire-rated doors.
The document outlines comprehensive requirements for door manufacturers, including compliance with ANSI/SDI standards, fire protection ratings (up to 90-minute rating), and specific manufacturing processes. Acceptable manufacturers include CECO Door Products, Curries Company, and Steelcraft. The specification covers critical aspects such as hardware preparation, steel finishes (rust-inhibiting shop primer), edge reinforcement, hinge reinforcement, and field installation guidelines. The document emphasizes quality assurance, including SDI certification, fire-resistance testing, and detailed field inspection and punch list procedures to ensure proper door and frame installation and performance.
View the file
Other files for this federal contract opportunity
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Addendum #1 Lieutenant Colonel Charles S. Kettles VA Medical Center
06/05/2025 Facilities Maintenance Upgrades
Project Number 506-22-207
01-01-2021
081113 - 1
HOLLOW METAL DOORS AND FRAMES
SECTION 08 11 13
HOLLOW METAL DOORS AND FRAMES
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Standard and custom hollow metal doors.
2. Light frames and glazing installed in hollow metal doors.
1.2 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract and Division 01
Specification Sections, apply to this Section.
B. Related Sections:
1. Division 01 Section "General Conditions".
2. Division 08 Section "Glazing" for glass view panels in hollow metal doors.
3. Division 08 Section "Door Hardware".
4. Division 08 Section "Radiation Shielding Doors and Frames” for radiation protection at new hollow metal doors.
5. Division 09 Section "Interior Painting" for field painting hollow metal doors and frames.
1.3 APPLICABLE PUBLICATIONS
A. Codes and References: Comply with the version year adopted by the
Authority Having Jurisdiction.
1. ANSI/SDI A250.8 - Recommended Specifications for Standard Steel
Doors and Frames.
2. ANSI/SDI A250.4 - Test Procedure and Acceptance Criteria for
Physical Endurance for Steel Doors, Frames, Frames Anchors and
Hardware Reinforcing.
3. ANSI/SDI A250.6 - Recommended Practice for Hardware Reinforcing on
Standard Steel Doors and Frames.
4. ANSI/SDI A250.10 - Test Procedure and Acceptance Criteria for Prime
Painted Steel Surfaces for Steel Doors and Frames.
5. ANSI/SDI A250.11 - Recommended Erection Instructions for Steel
Frames.
6. ASTM A1008 - Standard Specification for Steel Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-
Alloy with Improved Formability.
Project Number 506-22-207
01-01-2021
081113 - 2
HOLLOW METAL DOORS AND FRAMES
7. ASTM A653 - Standard Specification for Steel Sheet, Zinc-Coated
(Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-
Dip Process.
8. ASTM A924 - Standard Specification for General Requirements for
Steel Sheet, Metallic-Coated by the Hot-Dip Process.
9. ASTM C 1363 - Standard Test Method for Thermal Performance of
Building Assemblies by Means of a Hot Box Apparatus.
10. ANSI/BHMA A156.115 - Hardware Preparation in Steel Doors and
Frames.
11. ANSI/SDI 122 - Installation and Troubleshooting Guide for Standard
Steel Doors and Frames.
12. ANSI/NFPA 80 - Standard for Fire Doors and Fire Windows; National
Fire Protection Association.
13. ANSI/NFPA 105: Standard for the Installation of Smoke Door
Assemblies.
14. NFPA 252 - Standard Methods of Fire Tests of Door Assemblies;
National Fire Protection Association.
15. UL 10C - Positive Pressure Fire Tests of Door Assemblies.
16. UL 1784 - Standard for Air Leakage Tests of Door Assemblies.
1.4 SUBMITTALS
A. Product Data: For each type of product indicated. Include construction details, material descriptions, core descriptions, hardware reinforcements, profiles, anchors, fire-resistance rating, and finishes.
B. Door hardware supplier is to furnish templates, template reference number and/or physical hardware to the steel door supplier in order to prepare the doors and frames to receive the finish hardware items.
C. Shop Drawings: Include the following:
1. Elevations of each door design.
2. Details of doors, including vertical and horizontal edge details and metal thicknesses.
3. Locations of reinforcement and preparations for hardware.
4. Details of anchorages, joints, field splices, and connections.
5. Details of accessories.
6. Details of moldings, removable stops, and glazing.
Project Number 506-22-207
01-01-2021
081113 - 3
HOLLOW METAL DOORS AND FRAMES
7. Details of conduit and preparations for power, signal, and control systems.
D. Samples for Verification:
1. Samples are only required by request of the architect and for manufacturers that are not current members of the Steel Door
Institute.
1.5 QUALITY ASSURANCE
A. Source Limitations: Obtain hollow metal doors through one source from a single manufacturer wherever possible.
B. Quality Standard: In addition to requirements specified, furnish SDI-
Certified manufacturer products that comply with ANSI/SDI A250.8, latest edition, "Recommended Specifications for Standard Steel Doors and Frames".
C. Fire-Rated Door Assemblies: Assemblies complying with NFPA 80 that are listed and labeled by a qualified testing agency, for fire-protection ratings indicated, based on testing at positive pressure according to
UL10C (neutral pressure at 40” above sill) or UL 10C.
1. Oversize Fire-Rated Door Assemblies Construction: For units exceeding sizes of tested assemblies, attach construction label certifying doors are built to standard construction requirements for tested and labeled fire rated door assemblies except for size.
2. Temperature-Rise Limit: Where indicated and at vertical exit enclosures (stairwell openings) and exit passageways, provide doors that have a maximum transmitted temperature end point of not more than 450 deg F (250 deg C) above ambient after 30 minutes of standard fire-test exposure.
3. Smoke Control Door Assemblies: Comply with NFPA 105.
a. Smoke "S" Label: Doors to bear “S” label, and include smoke and draft control gasketing applied to frame and on meeting stiles of pair doors.
D. Pre-Submittal Conference: Conduct conference in compliance with requirements in Division 01 Section "Project Meetings" with attendance by representatives of Supplier, Installer, and Contractor to review proper methods and procedures for installing hollow metal doors and to verify installation of electrical knockout boxes and conduit at frames with electrified or access control hardware.
Project Number 506-22-207
01-01-2021
081113 - 4
HOLLOW METAL DOORS AND FRAMES
1.6 DELIVERY, STORAGE, AND HANDLING
A. Deliver hollow metal work palletized, wrapped, or crated to provide protection during transit and Project site storage. Do not use non-vented plastic.
B. Store hollow metal work under cover at Project site. Place in stacks of five units maximum in a vertical position with heads up, spaced by blocking, on minimum 4-inch high wood blocking. Do not store in a manner that traps excess humidity.
1. Provide minimum 1/4-inch space between each stacked door to permit air circulation. Door to be stacked in a vertical upright position.
1.7 PROJECT CONDITIONS
A. Field Measurements: Verify actual dimensions of openings by field measurements before fabrication.
1.8 COORDINATION
A. Building Information Modeling (BIM) Support: Utilize designated BIM software tools and obtain training needed to successfully participate in the Project BIM processes. All technical disciplines are responsible for the product data integration and data reliability of their Work into the coordinated BIM applications.
1.9 WARRANTY
A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace doors that fail in materials or workmanship within specified warranty period.
B. Warranty includes installation and finishing that may be required due to repair or replacement of defective doors.
PART 2 - PRODUCTS
1.1 SYSTEM PERFORMANCE
A. Design hollow metal doors complying with specified performance:
1. Fire Doors: UL 10C; NFPA 80 labeled.
a. Fire Ratings: Door E505OO, Hardware Set 3.0 – 90 Min.
2. Smoke Control Doors: UL 1784; NFPA 80 labeled, maximum 0.15424 cubic meter/second/square meter (3.0 cubic feet/minute/square foot) at
24.9 Pa (0.10 inches water gauge) pressure differential.
2.1 MANUFACTURERS
A. Basis of Design Manufacturers: Subject to compliance with requirements, provide steel doors from an SDI Certified manufacturer:
Project Number 506-22-207
01-01-2021
081113 - 5
HOLLOW METAL DOORS AND FRAMES
1. CECO Door Products (C).
2. Curries Company (CU).
3. Steelcraft (S).
2.2 MATERIALS
A. Cold-Rolled Steel Sheet: ASTM A 1008/A 1008M, Commercial Steel (CS), Type B; suitable for exposed applications.
B. Metallic-Coated Steel Sheet: ASTM A 653/A 653M, Commercial Steel (CS), Type B; with minimum G60 (Z180) or A60 (ZF180) metallic coating.
2.3 HOLLOW METAL DOORS
A. General: Provide 1-3/4 inch doors of design indicated, not less than thickness indicated; fabricated with smooth surfaces, without visible joints or seams on exposed faces unless otherwise indicated. Comply with ANSI/SDI A250.8 and ANSI/NAAMM HMMA 867.
B. Interior Doors: Face sheets fabricated of commercial quality cold rolled steel that complies with ASTM A 1008/A 1008M. Provide doors complying with requirements indicated below by referencing
ANSI/SDI A250.8 for level and model and ANSI/SDI A250.4 for physical performance level:
1. Design: Flush panel.
2. Core Construction: Manufacturer's standard kraft-paper honeycomb, or one-piece polystyrene core, securely bonded to both faces.
a. Fire Door Core: As required to provide fire-protection and temperature-rise ratings indicated.
3. Level/Model: Level 3 and Physical Performance Level A (Extra
Heavy Duty), minimum 16 gauge (0.053-inch - 1.3-mm) thick steel, Model 2.
4. Vertical Edges: Vertical edges to have the face sheets spot welded and filled full height with an epoxy filler. Welds are to be ground, filled and dressed smooth. Beveled Lock Edge, 1/8 inch in 2 inches (3 mm in 50 mm).
5. Top and Bottom Edges: Reinforce tops and bottoms of doors with a continuous steel channel not less than 16 gauge, extending the full width of the door and welded to the face sheet.
6. Hinge Reinforcement: Minimum 7 gauge (3/16") plate 1-1/4" x 9" or minimum 14 gauge continuous channel with pierced holes, drilled and tapped.
Project Number 506-22-207
01-01-2021
081113 - 6
HOLLOW METAL DOORS AND FRAMES
7. Hardware Reinforcements: Fabricate according to ANSI/SDI A250.6 with reinforcing plates from same material as door face sheets.
C. Manufacturers Basis of Design:
1. Curries Company (CU) - Polystyrene Core - 707 Series.
2.4 LIGHT OPENINGS AND GLAZING
A. Stops and Moldings: Provide stops and moldings around glazed lites where indicated. Form corners of stops and moldings with butted or mitered hairline joints at fabricator’s shop. Fixed and removable stops to allow multiple glazed lites each to be removed independently.
Coordinate frame rabbet widths between fixed and removable stops with the type of glazing and installation indicated.
B. Moldings for Glazed Lites in Doors and Loose Stops for Glazed Lites in
Frames: Minimum 20 gauge thick, fabricated from same material as door face sheet in which they are installed.
C. Fixed Frame Moldings: Formed integral with hollow metal frames, a minimum of 5/8 inch (16 mm) high unless otherwise indicated. Provide fixed frame moldings and stops on outside of exterior and on secure side of interior doors and frames.
D. Preformed Metal Frames for Light Openings: Manufacturer's standard frame formed of 0.048-inch-thick, cold rolled steel sheet; with baked enamel or powder coated finish; and approved for use in doors of fire protection rating indicated. Match pre-finished door paint color where applicable.
2.5 ACCESSORIES
A. Mullions and Transom Bars: Join to adjacent members by welding or rigid mechanical anchors.
B. Grout Guards: Formed from same material as frames, not less than 0.016 inches thick.
2.6 FABRICATION
A. Fabricate hollow metal work to be rigid and free of defects, warp, or buckle. Accurately form metal to required sizes and profiles, with minimum radius for thickness of metal. Where practical, fit and assemble units in manufacturer's plant. When shipping limitations so dictate, frames for large openings are to be fabricated in sections for splicing or splining in the field by others.
B. Tolerances: Fabricate hollow metal work to tolerances indicated in
ANSI/SDI A250.8.
Project Number 506-22-207
01-01-2021
081113 - 7
HOLLOW METAL DOORS AND FRAMES
C. Hollow Metal Doors:
1. Exterior Doors: Provide optional weep-hole openings in bottom of exterior doors to permit moisture to escape where specified.
2. Glazed Lites: Factory cut openings in doors with applied trim or kits to fit. Factory install glazing where indicated.
3. Astragals: Provide overlapping astragals as noted in door hardware sets in Division 08 Section "Door Hardware" on one leaf of pairs of doors where required by NFPA 80 for fire-performance rating or where indicated. Extend minimum 3/4 inch beyond edge of door on which astragal is mounted.
4. Continuous Hinge Reinforcement: Provide welded continuous 12 gauge strap for continuous hinges specified in hardware sets in Division
08 Section "Door Hardware".
D. Hardware Preparation: Factory prepare hollow metal work to receive template mortised hardware; include cutouts, reinforcement, mortising, drilling, and tapping according to the Door Hardware Schedule and templates furnished as specified in Division 08 Section "Door
Hardware."
1. Locate hardware as indicated, or if not indicated, according to
ANSI/SDI A250.8.
2. Reinforce doors and frames to receive non-template, mortised and surface mounted door hardware.
3. Comply with applicable requirements in ANSI/SDI A250.6 and
ANSI/DHI A115 Series specifications for preparation of hollow metal work for hardware.
4. Coordinate locations of conduit and wiring boxes for electrical connections with Division 26 Sections.
2.7 STEEL FINISHES
A. Prime Finishes: Doors and frames to be cleaned, and chemically treated to insure maximum finish paint adhesion. Surfaces of the door and frame exposed to view to receive a factory applied coat of rust inhibiting shop primer.
1. Shop Primer: Manufacturer's standard, fast-curing, lead and chromate free primer complying with ANSI/SDI A250.10 acceptance criteria; recommended by primer manufacturer for substrate; and compatible with substrate and field-applied coatings.
Project Number 506-22-207
01-01-2021
081113 - 8
HOLLOW METAL DOORS AND FRAMES
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.
B. General Contractor to verify the accuracy of dimensions given to the steel door manufacturer for existing openings or existing frames
(strike height, hinge spacing, hinge back set, etc.).
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Remove welded in shipping spreaders installed at factory. Restore exposed finish by grinding, filling, and dressing, as required to make repaired area smooth, flush, and invisible on exposed faces.
B. Tolerances shall comply with SDI-117 "Manufacturing Tolerances
Standard Steel Doors and Frames."
C. Drill and tap doors and frames to receive non-template, mortised, and surface-mounted door hardware.
3.3 INSTALLATION
A. General: Install hollow metal work plumb, rigid, properly aligned, and securely fastened in place; comply with Drawings and manufacturer's written instructions.
B. Hollow Metal Doors: Fit hollow metal doors accurately in frames, within clearances specified below. Shim as necessary.
1. Non-Fire-Rated Standard Steel Doors:
a. Jambs and Head: 1/8 inch plus or minus 1/16 inch.
b. Between Edges of Pairs of Doors: 1/8 inch plus or minus 1/16 inch.
c. Between Bottom of Door and Top of Threshold: Maximum 3/8 inch.
d. Between Bottom of Door and Top of Finish Floor (No
Threshold): Maximum 3/4 inch.
2. Fire-Rated Doors: Install doors with clearances according to
NFPA 80.
C. Field Glazing: Comply with installation requirements in Division 08
Section "Glazing" and with hollow metal manufacturer's written instructions.
Project Number 506-22-207
01-01-2021
081113 - 9
HOLLOW METAL DOORS AND FRAMES
3.4 ADJUSTING AND CLEANING
A. Final Adjustments: Check and readjust operating hardware items immediately before final inspection. Leave work in complete and proper operating condition. Remove and replace defective work, including hollow metal work that is warped, bowed, or otherwise unacceptable.
B. Remove grout and other bonding material from hollow metal work immediately after installation.
C. Prime-Coat and Painted Finish Touchup: Immediately after erection, sand smooth rusted or damaged areas of prime coat, or painted finishes, and apply touchup of compatible air drying, rust-inhibitive primer, zinc rich primer (exterior and galvanized openings) or finish paint.
3.5 FIELD QUALITY CONTROL
A. Field Inspection (Punch Report): Reference Division 01 Sections
“Closeout Procedures”. Produce project punch report for each installed door opening indicating compliance with approved submittals and verification hardware is properly installed, operating and adjusted.
Include list of items to be completed and corrected, indicating the reasons or deficiencies causing the Work to be incomplete or rejected.
1. Organization of List: Include separate Door Opening and
Deficiencies and Corrective Action Lists organized by Mark, Opening Remarks and Comments, and related Opening Images and
Video Recordings.
- - - END - - -