539-21-210 Addendum 0006 - 7.19.2021.pdf

PDF 1 MB Posted

Attached to
Z1DA--Reconfigure 2nd Floor Waiting and Check-In - 539-21-210
Solicitation number
36C25021B0038
Issued by

About this file

This is a solicitation for project 539-21-210 to reconfigure the second floor waiting and check-in areas at the Department of Veterans Affairs Medical Center in Cincinnati, Ohio. Work includes general construction, alterations, plumbing, mechanical and electrical systems to construct a new radiology check-in, renovate portions of the existing radiology waiting area and create a new office, reading room and greeter station. An unfinished room will be renovated into a shared breakroom. Corridor remodel finish work will occur during off hours. The existing nuclear medicine area will be renovated to share a check-in area for nuclear medicine and cardiology. Various rooms will be remodeled and repurposed as shown in the drawings. Bidding materials consisting of drawings, specifications and contract forms, along with any amendments, are available at beta.SAM.gov by searching for solicitation number 36C25021B0038. This is the only official location for the bid documents. No hard copy materials are provided.

View the file

Other files

File Type Posted
36C25021B0038 0008.docx DOCX document
Final RFI Responses.pdf PDF
36C25021B0038 0007.docx DOCX document
36C25021B0038 0006.docx DOCX document
36C25021B0038 0005.docx DOCX document
36C25021B0038 0004.docx DOCX document
RFI 3 Received 6-29-21 02.pdf PDF
RFI 21 - Received 6-29-21.pdf PDF
2nd Floor Reconfiguration Asbestos Report.pdf PDF
RFI 17 - Received 6-29-21.pdf PDF
RFI 5 - Received 6-29-21.pdf PDF
RFI 29 - Received 6-29-21.pdf PDF
RFI 6 - Received 6-29-21.pdf PDF
RFI 15 - Received 6-29-21.pdf PDF
36C25021B0038 0003.docx DOCX document
RFI 3 Received 6-29-21.pdf PDF
RFI 1 Received 6-29-21.pdf PDF
2nd Floor Reconfiguration Lead Based Paint Report.pdf PDF
RFI 25 - Received 6-29-21.pdf PDF
RFI 2 - Received 6-29-21.pdf PDF
RFI 4 - Received 6-29-21.pdf PDF
RFI 11 - Received 6-29-21.pdf PDF
RFI 16 - Received 6-29-21.pdf PDF
RFI 8 - Received 6-29-21.pdf PDF
RFI 7 - Received 6-29-21.pdf PDF
RFI 30 - Received 6-29-21.pdf PDF
RFI 9 - Received 6-29-21.pdf PDF
RFI 10 - Received 6-29-21.pdf PDF
Sign in Sheet.pdf PDF
RFI 28 - Received 6-29-21.pdf PDF
RFI 26 - Received 6-29-21.pdf PDF
RFI 24 - Received 6-29-21.pdf PDF
36C25021B0038 0002.docx DOCX document
Drawings 11-04-2020.pdf PDF
Specifications - 11-04-2020.pdf PDF
36C25021B0038 0001.docx DOCX document
RFI Form.docx DOCX document
539-21-210 Bid Dwgs_2020-10-30.pdf PDF
539-21-210 Bid Specs_2020-10-30.pdf PDF
36C25021B0038.docx DOCX document
Contractor EMR Certification Form.docx DOCX document
Wage Determination OH20210082 5-21-21.pdf PDF
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum No. 0006

Date: July 19, 2021

Project: 539-21-210

Reconfigure 2nd Floor Waiting & Check-In

Cincinnati VA Medical Center

3200 Vine Street

Cincinnati, OH 45220

To: Yvonne Demorest, VA CO

This Addendum supplements and amends the original Drawings and Specifications for the above referenced project. This Addendum shall be forwarded to all Prime Bidders and all appropriate building code authorities. This Addendum shall be taken into account in the preparation of bids and shall become a part of the Contract Documents.

Receipt of this Addendum must be acknowledged on the Bid Form.

This addendum consists of the following items:

Drawings

1. Sheet A611 – Door Schedule, Window Types & Details – Reissued.

a. Revised Door Hardware for Reading Room door #C201.

2. Sheet TA101 – Second Floor Plan - New Work - Technology – Reissued.

a. Added plan note #6 to clarify scope of installing new Valcom paging speaker.

Specifications

1. Section 08 71 00 – Door Hardware – Reissued.

a. A new hardware set has been added to reflect the lockset revision to

Reading Room door #C201.

2. Section 22 11 00 – Facility Water Distribution – Reissued.

a. Updated specification section to most current VA master specification which prohibits the use of mechanical press-connect fittings.

3. Section 23 09 23 – Direct-Digital Control System for HVAC – Reissued.

a. Updated specification section to clarify new controller and graphics requirements.

Clarifications

1. Mechanical press connect fittings are not acceptable for Division 23 work.

End of Addendum No. 0006

SEE PLANSEE PLAN

1/2" 1/2"

1/2"1/2"

H1

J1

8.02

9.21

9.80

8.02

9.09

9.21

9.80

8.08

9.21

9.80

8.08

9.09

9.21

9.80

8.04

S1 H1

J1

9.08

7.82 7.82

9.08

7.82 1/2" 1/2"

7.82

1/2" 1/2"

2"

SEE

SCHED. 2"

S E

E S

C H

E D

U L E

3 1/4" SEE SCHEDULE 3 1/4"

/4

S E

E S

C H

E D

U L E

SEE SCHED.

S E

E S

C H

E D

U L E

F

4' - 6"

A611

A611

A611

Finish Floor

A

PLAN

SEE

Check-In

7.83

9.08

6.08

8.26

8.51

P L A

N

S E

E

Check-In

6.08

7.83

8.51

8.26

1/2"

1/2"

Check-In

8.26

8.51

7.83

9.34

6.08

PLAN

SEE

3' - 0"

B

A611

A611

A611

E

3/8"See Plan1/8"

A611

Open

Open

6.27

2"

8.63

8.51

9.21

PLAN

SEE

A611

2' - 0"

C

A611

A611

D

2' - 0"

A611

A611

A611

6.08

9.28

7.83

8.26

8.55 2' - 0"

P L A

N

S E

E

7.83

8.26 8.55

8.24

8.26

7.83

8.26

/2

A611

3/8"See Plan1/8"

Open

Open

F

6.27

2.092.09

2.11

2.10

8.50

A611 9.34

2.10

2.09

1/2"

9.34

2.09

8.508.50

6.08

2.04

2.03

PLAN

SEE

2.09

9.60

/4

7.89

J O H N

A

P O E

IO

H O

F O

E T A T

S

R EG

IS

E T

R E D

R A

C H

TI

E

CT

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

SD 35% SCHEMATIC DESIGN 07.24.2020

DD 65% DESIGN DEVELOPMENT 09.02.2020

CD 95% CONSTUCTION DOCUMENTS 10.02.2020

CD 100% CONSTUCTION DOCUMENTS 10.30.2020

BID 100% CONSTUCTION DOCUMENTS 11.04.2020

/2

/2

:2

:2

A

M

Reconfigure 2nd Floor Waiting & Check-In

11/04/2020

DOOR SCHEDULE, WINDOW TYPES

& DETAILS

A611

CVKR

20003.00

539-21-210

Cincinnati VA

JOSH SCHNEIDER - COR

100% CONSTRUCTION

DOCUMENTS

DOOR SCHEDULE

WT

BETWEEN DOOR DESCRIPTION FRAME DESCRIPTION

FIRE

RATING

HDWE

SET

CARD

READER REMARKSRM RM TYPE MAT'L

SIZE

TYPE MAT'L HEAD JAMB# W H T

A201 A202 A201 F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 2.0 Yes

A235 C*2*1 A235 F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 5.0 Existing with New Hardware

A253 C*2*3 A253 F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 3.0 Existing with New Hardware

A2020 C*2*15 A2020 F HM 2 4'-0" 7'-0" 1 3/4" 1 HM H1 J1 6.0 Existing with New Hardware

C200 C*2*1 C200 F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 1.0 Yes

C200A C200 C200A F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 4.0

C200B C200 C200B F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 4.0

C200C C200C C200 F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 3.0

C201 C*2*1 C201 F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 1.1 No

C203 C*2*1 C203 F WD 1 3'-0" 7'-0" 1 3/4" 1 HM H1 J1 4.0

NOTES

2.03 Existing wall to remain.

2.04 Existing concrete floor.

2.09 Existing storefront window to remain.

2.10 Existing storefront glazing to remain.

2.11 Existing storefront spandral glazing to remain.

6.08 Fire retardant treated wood blocking.

6.27 Check-In counter. See Interior Elevations & Details.

7.82 Continuous acoustic sealant @ non-rated walls.

7.83 Continuous sealant each side.

7.89 Continuous sealant along aluminum frame and solid surface window sill joint.

8.02 Hollow metal frame.

8.04 Hospital stops @ all interior hollow metal frames.

8.08 Double egress hollow metal frame.

8.24 Clear anodized aluminum frame closure end cap.

8.26 4-1/2" clear anodized aluminum window frame.

8.50 Install translucent vinyl film on inside face of glazing on the bottom portion of the storefront windows.

8.51 1/4" tempered glass.

8.55 Laminated glass with translucent frosted interlayer with 40% opacity.

8.63 90 degree glazing clamp wall mounted bracket.

9.08 Metal framing box header.

9.09 Double metal framing at jambs, typ.

9.21 5/8" Type X gypsum board.

9.28 Gypsum board ceiling.

9.34 Solid surface window sill trim (SS-1).

9.60 Resilient base. See Room Finish Schedule.

9.80 Acoustic insulation

Scale: 1 1/2" = 1'-0"

H.M. FRAME DETAILS

N.T.S.Scale:

H.M. FRAME TYPES

N.T.S.Scale:

DOOR TYPES

Scale: 1/2" = 1'-0"

WINDOW TYPES

Scale: 1 1/2" = 1'-0"1

WINDOW HEAD

Scale: 1 1/2" = 1'-0"2

WINDOW JAMB

Scale: 1 1/2" = 1'-0"3

WINDOW SILL

Scale: 3" = 1'-0"7

BRACKET DETAIL

Scale: 1 1/2" = 1'-0"4

WINDOW HEAD

Scale: 1 1/2" = 1'-0"5

WINDOW HEAD

Scale: 1 1/2" = 1'-0"6

WINDOW SILL

G

Scale: 1 1/2" = 1'-0"8

BREAK RM SILL

Revisions Date

1 Addendum 0006 07.19.2021

SC

SC

SC

SC

AP

V

AP

V

AP

T

SC

SC

SC

AP

V

SC

AP

V

AP

V

SCAP

V

AP

T

SC

DD

D

D

D

SC

D

D

D D

DDD

D

R

66" MH

CR

AP

AP

AP

AP

AP

AP

AP

HA HA

N N

T

D

D

46" MH

D

CR

R

66" MH

D D

CR

EDC

EDC

CR

R

66" MH

D

D

R

66" MH

66" MH

R

66" MH

R

D D D

D

46" MH

AP

D

D

D

D

D D

66" MH

R

TN101

Waiting

A202

Reading Rm

C201

Office C203

Office

C200B Office

C200A

QC Tech Rm

A240

Men's Toilet

A236

Uptake Prep Room

C204C

Echo Rm

C250

Stair 1

S*2*1 Signal Closet

A239

Elec.

A239A

Toilet

A266B

Toilet

A2002B

Women Staff

A2003

Men Staff

A2004

Signal

A2005

Toilet

A2024A

Storage

A2026Chage Area

A2002A

Ultrasound A266

Waiting

C202

Reading Rm

C250A

Greeter Station-1 A234-1

Women's Toilet

A235

Check-In A201

Waiting

A2000

C200-1

Nuc. Med.

Admin.-1

Room

C206

Room

C214

Pat Rm

A266A

Corridor-1

C*2*1-1

Space

C*2*2Space

C*2*3

Space C*2*4

TN102

"x

4"x4" 4"x4"

"x

5 1/2"x1 1/2"

"x

4"x1 1/2"

4"x4"

4"x4"

CABLE TRAY

4"x1 1/2"

4"x4"

"x

12"x4"

12"x4"

"x

"x

A201

C200

Check-In-2

C200C-2

Scheduling Office

A253

Shared Break Room

A2020

P: 937-224-0861 www.heapy.com

3131 Newmark Drive, Suite 200 Miamisburg, Ohio 45342 |www.johnpoe.com| 937.461.3290

VA Project No.

JPA Project No.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Office of Construction and Facilities Management

PROJECT NO.

STATE COA FIRM NO.

SD 35% SCHEMATIC DESIGN 07.24.2020

DD 65% DESIGN DEVELOPMENT 09.02.2020

CD 95% CONSTUCTION DOCUMENTS 10.02.2020

CD 100% CONSTUCTION DOCUMENTS 10.30.2020

BID 100% CONSTUCTION DOCUMENTS 11.04.2020

/1

/2

:0

:2

P M

Reconfigure 2nd Floor Waiting & Check-In

11/04/2020

SECOND FLOOR PLAN - NEW

WORK - TECHNOLOGY

TA101

JMCJDK

20003.00

539-21-210

Cincinnati VA

JOSH SCHNEIDER - COR

100% CONSTRUCTION

DOCUMENTS

2020-05057

01528

Scale: 1/8" = 1'-0"1

NEW WORK PLAN - AREA A

Scale: 1/8" = 1'-0"2

NEW WORK PLAN - AREA B

Scale: 1/8" = 1'-0"3

NEW WORK PLAN - AREA C

GENERAL NOTES

A. ALL NEW DATA CABLING FOR DEVICES IN AREAS A AND B SHALL BE

TERMINATED IN SIGNALS CLOSET A239.

B. ALL NEW DATA CABLING FOR DEVICES IN AREA C SHALL BE

TERMINATED IN SIGNALS CLOSET A2005.

PLAN NOTES

1. REINSTALL EXISTING CARD READER AT THIS LOCATION.

2. EXISTING WAP SHALL BE REINSTALLED AT THIS LOCATION. PROVIDE

NEW BOX, CONDUIT, AND CABLE PER DIVISION 27.

3. REINSTALL NURSE CALL DEVICE AT THIS LOCATION.

4. REINSTALL HAND WAVE DOOR ACTUATOR AT THIS LOCATION.

5. LOCATION OF EXISTING ACCESS CONTROL PANELS SERVING AREA OF

RENOVATION.

6. PROVIDE NEW VALCOM V-9022 SERIES CEILING PAGING SPEAKER.

PROVIDE ASSOCIATED WIRING, BACKBOXES, AND CONDUIT FOR A

COMPLETE INSTALLATION. SPEAKER SHALL BE AN EXTENSION OF THE

EXISTING VALCOM PAGING SYSTEM, COORDINATE EXISTING TIE IN

LOCATIONS WITH OWNER. REFER TO DETAIL 2, SHEET T500 FOR

MORE INFORMATION.

KEYPLAN

Revisions Date

1 Addendum 0006 07.19.2021

539-21-210 DOOR HARDWARE

Reconfigure 2nd Floor Waiting & Check-In 04-20

VAMC Cincinnati, OH

08 71 00-1

SECTION 08 71 00

DOOR HARDWARE

PART 1 - GENERAL

1.1 DESCRIPTION

A. Door hardware and related items necessary for complete installation and operation of doors.

1.2 RELATED WORK

A. Caulking: Section 07 92 00 JOINT SEALANTS.

B. Application of Hardware: Section 08 14 00, WOOD DOORS Section 08 11 13, HOLLOW METAL DOORS AND FRAMES

C. Painting: Section 09 91 00, PAINTING.

D. Electrical: Division 26, ELECTRICAL.

E. Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.

1.3 GENERAL

A. All hardware shall comply with ABAAS, (Architectural Barriers Act

Accessibity Standard) unless specified otherwise.

B. Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).

C. Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.

D. Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.

E. The following items shall be of the same manufacturer, except as otherwise specified:

1. Mortise locksets.

2. Hinges for hollow metal and wood doors.

3. Surface applied overhead door closers.

4. Exit devices.

5. Floor closers.

08 71 00-2

1.4 WARRANTY

A. Automatic door operators shall be subject to the terms of FAR Clause

52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:

1. Locks, latchsets, and panic hardware: 5 years.

2. Door closers and continuous hinges: 10 years.

1.5 MAINTENANCE MANUALS

A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.

1.6 SUBMITTALS

A. Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. Submit 6 copies of the schedule per Section

01 33 23. Submit 2 final copies of the final approved schedules to VAMC

Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).

B. Hardware Schedule: Prepare and submit hardware schedule in the following form:

Hardware

Item

Quantity Size Reference

Publication

Type No.

Finish Mfr.

Name and

Catalog

No.

Key

Control

Symbols

UL Mark

(if fire rated and listed)

ANSI/BHMA

Finish

Designation

C. Samples and Manufacturers' Literature:

1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers

Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.

2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.

08 71 00-3

D. Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.

1.7 DELIVERY AND MARKING

A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to

COR for reference purposes. Tag shall identify items by Project

Specification number and manufacturer's catalog number. These items shall remain on file in COR’s office until all other similar items have been installed in project, at which time the COR will deliver items on file to Contractor for installation in predetermined locations on the project.

1.8 PREINSTALLATION MEETING

A. Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, COR and VA Locksmith, Hardware Consultant, and Hardware Manufacturer’s

Representative. Review the following:

1. Inspection of door hardware.

2. Job and surface readiness.

3. Coordination with other work.

4. Protection of hardware surfaces.

5. Substrate surface protection.

6. Installation.

7. Adjusting.

8. Repair.

9. Field quality control.

10. Cleaning.

1.9 INSTRUCTIONS

A. Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols.

08 71 00-4

Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.

B. Keying: All cylinders shall be keyed into existing Corbin Russwin Great

Grand Master Key System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset. Cylinders shall be 7 pin type. Keying information shall be furnished at a later date by the COR.

1.10 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.

B. American Society for Testing and Materials (ASTM):

F883-04.................Padlocks

E2180-07................Standard Test Method for Determining the

Activity of Incorporated Antimicrobial Agent(s)

In Polymeric or Hydrophobic Materials

C. American National Standards Institute/Builders Hardware Manufacturers

Association (ANSI/BHMA):

A156.1-06...............Butts and Hinges

A156.2-03...............Bored and Pre-assembled Locks and Latches

A156.3-08...............Exit Devices, Coordinators, and Auto Flush

Bolts

A156.4-08...............Door Controls (Closers)

A156.5-14...............Cylinders and Input Devices for Locks.

A156.6-05...............Architectural Door Trim

A156.8-05...............Door Controls-Overhead Stops and Holders

A156.11-14..............Cabinet Locks

A156.12-05 .............Interconnected Locks and Latches

A156.13-05..............Mortise Locks and Latches Series 1000

A156.14-07 .............Sliding and Folding Door Hardware

A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical

A156.16-08..............Auxiliary Hardware

08 71 00-5

A156.17-04 .............Self-Closing Hinges and Pivots

A156.18-06..............Materials and Finishes

A156.20-06 .............Strap and Tee Hinges, and Hasps

A156.21-09..............Thresholds

A156.22-05..............Door Gasketing and Edge Seal Systems

A156.23-04..............Electromagnetic Locks

A156.24-03..............Delayed Egress Locking Systems

A156.25-07 .............Electrified Locking Devices

A156.26-06..............Continuous Hinges

A156.28-07 .............Master Keying Systems

A156.29-07 .............Exit Locks and Alarms

A156.30-03 .............High Security Cylinders

A156.31-07 .............Electric Strikes and Frame Mounted Actuators

A156.36-10..............Auxiliary Locks

A250.8-03...............Standard Steel Doors and Frames

D. National Fire Protection Association (NFPA):

80-10...................Fire Doors and Other Opening Protectives

101-09..................Life Safety Code

E. Underwriters Laboratories, Inc. (UL):

Building Materials Directory (2008)

PART 2 - PRODUCTS

2.1 BUTT HINGES

A. ANSI A156.1. Provide only three-knuckle hinges, except five-knuckle where the required hinge type is not available in a three-knuckle version (e.g., some types of swing-clear hinges). The following types of butt hinges shall be used for the types of doors listed, except where otherwise specified:

1. Interior Doors: Type A8112/A5112 for doors 900 mm (3 feet) wide or less and Type A8111/A5111 for doors over 900 mm (3 feet) wide.

Hinges for doors exposed to high humidity areas (shower rooms, toilet rooms, kitchens, janitor rooms, etc. shall be of stainless steel material.

B. Provide quantity and size of hinges per door leaf as follows:

1. Doors up to 1210 mm (4 feet) high: 2 hinges.

2. Doors 1210 mm (4 feet) to 2260 mm (7 feet 5 inches) high: 3 hinges minimum.

08 71 00-6

3. Doors greater than 2260 mm (7 feet 5 inches) high: 4 hinges.

4. Doors up to 900 mm (3 feet) wide, standard weight: 114 mm x 114 mm

(4-1/2 inches x 4-1/2 inches) hinges.

5. Doors over 900 mm (3 feet) to 1065 mm (3 feet 6 inches) wide, standard weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

6. Doors over 1065 mm (3 feet 6 inches) to 1210 mm (4 feet), heavy weight: 127 mm x 114 mm (5 inches x 4-1/2 inches).

7. Provide heavy-weight hinges where specified.

8. At doors weighing 330 kg (150 lbs.) or more, furnish 127 mm (5 inch) high hinges.

C. See Articles "MISCELLANEOUS HARDWARE" and "HARDWARE SETS" for pivots and hinges other than butts specified above and continuous hinges specified below.

2.2 DOOR CLOSING DEVICES

A. Closing devices shall be products of one manufacturer for each type specified.

2.3 OVERHEAD CLOSERS

A. Conform to ANSI A156.4, Grade 1.

B. Closers shall conform to the following:

1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.

2. Where specified, closer shall have hold-open feature.

3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.

4. Material of closer body shall be forged or cast.

5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.

6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.

7. Closers shall have full size metal cover; plastic covers will not be accepted.

08 71 00-7

8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.

9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.

10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.

11. Provide parallel arm closers with heavy duty rigid arm.

12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.

13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.

14. All closers shall have a 1 ½” (38mm) minimum piston diameter.

2.4 DOOR STOPS

A. Conform to ANSI A156.16.

B. Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use lead expansion shields for mounting door stops.

C. Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.

D. Provide floor stops (Type L02141 or L02161 in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.

E. Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.

08 71 00-8

F. Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.

G. Omit stops where floor mounted door holders are required and where automatic operated doors occur.

H. Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.

I. Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.

J. Provide overhead surface applied stop Type C02541, ANSI A156.8 on patient toilet doors in bedrooms where toilet door could come in contact with the bedroom door.

K. Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.

L. Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).

2.5 OVERHEAD DOOR STOPS AND HOLDERS

A. Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.

2.6 LOCKS AND LATCHES

A. Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall be Corbin

Russwin, seven pin, large format interchangeable cores (LFIC).

Cylinders for all locksets shall be removable core type. Cylinder shall be removable by special key or tool. Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the

Great Grand Master Key System. Disassembly of lever or lockset shall

08 71 00-9 not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.

B. In addition to above requirements, locks and latches shall comply with following requirements:

1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2. All locksets and latchsets shall have lever handles fabricated from cast stainless steel. Provide sectional (lever x rose) lever design matching

Corbin Russwin NSA. No substitute lever material shall be accepted.

All locks and latchsets shall be furnished with 122.55 mm (4-7/8-inch) curved lip strike and wrought box. At outswing pairs with overlapping astragals, provide flat lip strip with 21mm (7/8-inch) lip-to-center dimension. Lock function F02 shall be furnished with emergency tools/keys for emergency entrance. Where mortise locks are installed in high-humidity locations or where exposed to the exterior on both sides of the opening, provide non-ferrous mortise lock case.

2. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.

2.7 PUSH-BUTTON COMBINATION LOCKS

A. ANSI/BHMA A156.5, Grade 1. Battery operated pushbutton entry.

B. Construction: Heavy duty mortise lock housing conforming to ANSI/BHMA

A156.13, Grade 1. Lever handles and operating components in compliance with the ABAAS and the ADA Accessibility Guidelines. Match lever handles of locks and latchsets on adjacent doors.

C. Special Features: Key override to permit a master keyed security system and a pushbutton security code activated passage feature to allow access without using the entry code.

2.8 ELECTRIC STRIKES

A. ANSI/ BHMA A156.31 Grade 1.

B. General: Use fail-secure electric strikes at fire-rated doors.

08 71 00-10

2.9 KEYS

A. Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:

Locks/Keys Quantity

Cylinder locks 2 keys each

Cylinder lock change key blanks

100 each different key way

Master-keyed sets 6 keys each

Grand Master sets 6 keys each

Great Grand Master set 5 keys

Control key 2 keys

2.10 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING

A. Conform to ANSI Standard A156.6.

B. Provide protective plates and door edging as specified below:

1. Kick plates, mop plates and armor plates of metal, Type J100 series.

2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates

25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.

3. Kick plates and/or mop plates are not required on following door sides:

a. Armor plate side of doors;

b. Exterior side of exterior doors;

c. Closet side of closet doors;

d. Both sides of aluminum entrance doors.

4. Armor plates for doors are listed under Article "Hardware Sets".

Armor plates shall be thickness as noted in the hardware set, 875 mm

(35 inches) high and 38 mm (1-1/2 inches) less than width of doors, 08 71 00-11 except on pairs of metal doors. Provide armor plates beveled on all

4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail.

On doors equipped with panic devices, extend armor plates to within

13 mm (1/2 inch) of panic bolt push bar.

5. Where louver or grille occurs in lower portion of doors, substitute stretcher plate and kick plate in place of armor plate. Size of stretcher plate and kick plate shall be 254 mm (10 inches) high.

6. Provide stainless steel edge guards where so specified at wood doors. Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.

2.11 EXIT DEVICES

A. Conform to ANSI Standard A156.3. Exit devices shall be Grade 1; type and function are specified in hardware sets. Provide flush with finished floor strikes for vertical rod exit devices in interior of building. Trim shall have cast satin stainless steel lever handles of design similar to locksets, unless otherwise specified. Provide key cylinders for keyed operating trim and, where specified, cylinder dogging.

B. Surface vertical rod panics shall only be provided less bottom rod;

provide fire pins as required by exit device and door fire labels. Do not provide surface vertical rod panics at exterior doors.

C. Concealed vertical rod panics shall be provided less bottom rod at interior doors, unless lockable or otherwise specified; provide fire pins as required by exit device and door fire labels. Where concealed vertical rod panics are specified at exterior doors, provide with both top and bottom rods.

08 71 00-12

D. Where removable mullions are specified at pairs with rim panic devices, provide mullion with key-removable feature.

E. At non-rated openings with panic hardware, provide panic hardware with key cylinder dogging feature.

F. Exit devices for fire doors shall comply with Underwriters

Laboratories, Inc., requirements for Fire Exit Hardware. Submit proof of compliance.

2.12 FLUSH BOLTS (AUTOMATIC)

A. Conform to ANSI A156.3. Dimension of flush bolts shall conform to ANSI

A115. Bolts shall conform to Underwriters Laboratories, Inc., requirements for fire door hardware. Flush bolts shall automatically latch and unlatch. Furnish dustproof strikes conforming to ANSI A156.16 for bottom flushbolt. Face plates for dustproof strike shall be rectangular and not less than 38 mm by 90 mm (1-1/2 by 3-1/2 inches).

B. At interior doors, provide auto flush bolts less bottom bolt, unless otherwise specified, except at wood pairs with fire-rating greater than

20 minutes; provide fire pins as required by auto flush bolt and door fire labels.

2.13 DOOR PULLS WITH PLATES

A. Conform to ANSI A156.6. Pull Type J401, 152 mm CTC (6 inches CTC) length by 19 mm (3/4 inches) diameter minimum with plate Type J302, 90 mm by 381 mm (3-1/2 inches by 15 inches), unless otherwise specified.

Provide pull with projection of 57.2 mm (2 1/4 inches) minimum and a clearance of 38.1 mm (1 1/2 inches) minimum. Cut plates of door pull plate for cylinders, or turn pieces where required.

2.14 PUSH PLATES

A. Conform to ANSI A156.6. Metal, Type J302, 203 mm (8 inches) wide by

406.4 mm (16 inches) high. Provide metal Type J302 plates 102 mm (4 inches) wide by 406.4 mm (16 inches) high where push plates are specified for doors with stiles less than 203 mm (8 inches) wide. Cut plates for cylinders, and turn pieces where required.

2.15 COMBINATION PUSH AND PULL PLATES

A. Conform to ANSI 156.6. Type J303, stainless steel 3 mm (1/8 inch) thick, 80 mm (3-1/3 inches) wide by 800 mm (16 inches) high), top and bottom edges shall be rounded. Secure plates to wood doors with 38 mm

08 71 00-13

(1-1/2 inch) long No. 12 wood screws. Cut plates for turn pieces, and cylinders where required. Pull shall be mounted down.

2.16 COORDINATORS

A. Conform to ANSI A156.16. Coordinators, when specified for fire doors, shall comply with Underwriters Laboratories, Inc., requirements for fire door hardware. Coordinator may be omitted on exterior pairs of doors where either door will close independently regardless of the position of the other door. Coordinator may be omitted on interior pairs of non-labeled open where open back strike is used. Open back strike shall not be used on labeled doors. Paint coordinators to match door frames, unless coordinators are plated. Provide bar type coordinators, except where gravity coordinators are required at acoustic pairs. For bar type coordinators, provide filler bars for full width and, as required, brackets for push-side surface mounted closers, overhead stops, and vertical rod panic strikes.

2.17 THRESHOLDS

A. Conform to ANSI A156.21, mill finish extruded aluminum, except as otherwise specified. In existing construction, thresholds shall be installed in a bed of sealant with ¼-20 stainless steel machine screws and expansion shields. In new construction, embed aluminum anchors coated with epoxy in concrete to secure thresholds. Furnish thresholds for the full width of the openings.

B. For thresholds at elevators entrances see other sections of specifications.

C. At exterior doors and any interior doors exposed to moisture, provide threshold with non-slip abrasive finish.

D. Provide with miter returns where threshold extends more than 12 mm (0.5 inch) beyond face of frame.

2.18 MISCELLANEOUS HARDWARE

A. Access Doors (including Sheet Metal, Screen and Woven Wire Mesh Types):

Except for fire-rated doors and doors to Temperature Control Cabinets, equip each single or double metal access door with Lock Type E07213, conforming to ANSI A156.11. Key locks as directed. Ship lock prepaid to the door manufacturer. Hinges shall be provided by door manufacturer.

B. Cylinders for Various Partitions and Doors: Key cylinders same as entrance doors of area in which partitions and door occur, except as

08 71 00-14 otherwise specified. Provide cylinders to operate locking devices where specified for following partitions and doors:

1. Folding doors and partitions.

2. Wicket door (in roll-up door assemblies).

3. Slide-up doors.

4. Swing-up doors.

5. Fire-rated access doors-Engineer's key set.

6. Doors from corridor to electromagnetic shielded room.

7. Day gate on vault door.

C. Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers

Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames, lead-lined frames and frames for sound-resistant, lightproof and electromagnetically shielded doors. Furnish 3 mutes for single doors and 2 mutes for each pair of doors, except double-acting doors.

Provide 4 mutes or silencers for frames for each Dutch type door.

Provide 2 mutes for each edge of sliding door which would contact door frame.

2.19 FINISHES

A. Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING.

B. 626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.

C. Miscellaneous Finishes:

1. Hinges --interior doors: 652 or 630.

2. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.

3. Thresholds: Mill finish aluminum.

4. Cover plates for floor hinges and pivots: 630.

5. Other primed steel hardware: 600.

D. Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces.

08 71 00-15

E. Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests.

Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.

2.20 BASE METALS

A. Apply specified U.S. Standard finishes on different base metals as following:

Finish Base Metal

652 Steel

626 Brass or bronze

630 Stainless steel

PART 3 - EXECUTION

3.1 HARDWARE HEIGHTS

A. For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA COR for approval.

B. Hardware Heights from Finished Floor:

1. Exit devices centerline of strike (where applicable) 1024 mm (40-

5/16 inches).

2. Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches).

3. Deadlocks centerline of strike 1219 mm (48 inches).

4. Hospital arm pull 1168 mm (46 inches) to centerline of bottom supporting bracket.

5. Centerline of door pulls to be 1016 mm (40 inches).

6. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.

7. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.

8. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.

08 71 00-16

3.2 INSTALLATION

A. Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors except security bedroom, bathroom and anteroom doors which shall have closer installed parallel arm on exterior side of doors.

B. Hinge Size Requirements:

Door Thickness Door Width Hinge Height

45 mm (1-3/4 inch) 900 mm (3 feet) and less 113 mm (4-1/2 inches)

45 mm (1-3/4 inch) Over 900 mm (3 feet) but not more than 1200 mm (4 feet)

125 mm (5 inches)

35 mm (1-3/8 inch)

(hollow core wood doors)

Not over 1200 mm (4 feet) 113 mm (4-1/2 inches)

C. Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.

D. Where new hinges are specified for new doors in existing frames or existing doors in new frames, sizes of new hinges shall match sizes of existing hinges; or, contractor may reuse existing hinges provided hinges are restored to satisfactory operating condition as approved by

COR. Existing hinges shall not be reused on door openings having new doors and new frames. Coordinate preparation for hinge cut-outs and screw-hole locations on doors and frames.

E. Hinges Required Per Door:

Door Description Number butts

Doors 1500 mm (5 ft) or less in height 2 butts

Doors over 1500 mm (5 ft) high and not over 2280 mm

(7 ft 6 in) high

3 butts

Doors over 2280 mm (7 feet 6 inches) high 4 butts

Dutch type doors 4 butts

Doors with spring hinges 1370 mm (4 feet 6 inches) high or less

2 butts

Doors with spring hinges over 1370 mm (4 feet 6 inches) 3 butts

08 71 00-17

F. Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted.

All fastenings exposed to weather shall be of nonferrous metal.

G. After locks have been installed; show in presence of COR that keys operate their respective locks in accordance with keying requirements.

(All keys, Master Key level and above shall be sent Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the COR for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.

3.3 FINAL INSPECTION

A. Installer to provide letter to VA COR that upon completion, installer has visited the Project and has accomplished the following:

1. Re-adjust hardware.

2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.

3. Identify items that have deteriorated or failed.

4. Submit written report identifying problems.

3.4 DEMONSTRATION

A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of COR and VA Locksmith.

3.5 HARDWARE SETS

A. Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.

B. Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.

C. The hardware sets represent the design intent and direction of the owner and architect. They are a guideline only and should not be considered a detailed hardware schedule. Discrepancies, conflicting hardware and

08 71 00-18 missing items should be brought to the attention of the architect with corrections made prior to the bidding process. Omitted items not included in a hardware set should be scheduled with the appropriate additional hardware required for proper application and functionality.

1. The supplier is responsible for handing and sizing all products.

2. Where multiple options for a piece of hardware are given in a single line item, the supplier shall provide the appropriate application for the opening.

3. At existing openings with new hardware the supplier shall field inspect existing conditions prior to the submittal stage to verify the specified hardware will work as required. Provide alternate solutions and proposals as needed.

D. Manufacturer’s Abbreviations:

1. MK - McKinney

2. RO - Rockwood

3. RU - Corbin Russwin

4. RF - Rixson

5. PE - Pemko

6. SU – Securitron

7. YA - Yale

08 71 00-19

Hardware Sets

Set: 1.0

Doors: C200

Description: Access Control Function 1

2 Hinge, Full Mortise TA2714 (size per spec) US26D MK

1 Hinge, Full Mortise TA2714 QC (size per spec) US26D MK

1 Fail Secure Lock w/ RX ML20906-SEC NSA M92 59A1 C7 626 RU

1 Surface Closer DC6200 689 RU

1 Kick Plate K1050 10" HGT x BEV x CSK US32D RO

1 Door Stop 400 series as req'd US26D RO

1 Gasketing S88 PE

1 Wiring Harness - Frame QC-C3000P MK

1 Wiring Harness - Door QC-CxxxP length as req'd MK

1 Card Reader By Security Contractor

1 Position Switch DPS-M SU

1 Power Supply AQL series as req'd SU

Notes:

Entry by valid input at reader or manual key. Free egress at all times.

Door position switch to monitor opening status, as required. Lockset has RX feature to signal egress.

Coordinate with electrical and security contractors.

https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=167999461,168612583, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168811825, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168811825, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211938577,211938373,211938563, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211942096, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211888528, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=114112091, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168874097, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168811883, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168811883, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=120413932,211929302, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=187746469,187746486, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=187746475,211949569, 08 71 00-20

Set: 1.1

Doors: C201

Description: Keypad Lockset Control Function

3 Hinge, Full Mortise TA2714 (size per spec) US26D MK

1 KEYPAD MORTISE LOCKSET AUR NTM610 NR LC 626 YA

1 Surface Closer DC6200 689 RU

1 Kick Plate K1050 10" HGT x BEV x CSK US32D RO

1 Door Stop 400 series as req'd US26D RO

1 Gasketing S88 PE

1 CYLINDER HOUSING

Mortise Cylinder Housing

Corbin LFIC – with proper cam for above lock

RU

1 LFIC CYLINDER CORE

Core to Match 59A1 LFIC keyway

RU

Entering valid pin code to keypad lockset will release lever for entry.

Free egress at all times.

https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211942096, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211888528, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=114112091, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168874097, 08 71 00-21

Set: 2.0

Doors: A201

Description: Access Control Function 2

2 Hinge, Full Mortise TA2714 (size per spec) US26D MK

1 Hinge, Full Mortise TA2714 QC (size per spec) US26D MK

1 Fail Secure Lock w/ RX ML20906-SEC NSA M92 59A1 C7 626 RU

1 Surf Overhead Stop 10-336 652 RF

1 Surface Closer DC6200 689 RU

1 Kick Plate K1050 10" HGT x BEV x CSK US32D RO

1 Gasketing S88 PE

1 Wiring Harness - Frame QC-C3000P MK

1 Wiring Harness - Door QC-CxxxP length as req'd MK

1 Card Reader By Security Contractor

1 Position Switch DPS-M SU

1 Power Supply AQL series as req'd SU

Entry by valid input at reader or manual key. Free egress at all times.

Door position switch to monitor opening status, as required. Lockset has RX feature to signal egress.

Coordinate with electrical and security contractors.

https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211948678,168624536, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168811825, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211938577,211938373,211938563, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=70787234, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211942096, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211888528, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168874097, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168811883, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168811883, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=120413932,211929302, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=187746469,187746486, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=187746475,211949569, 08 71 00-22

Set: 3.0

Doors: A253, C200C

Description: Office Function x Closer

1 Office Lock ML2053 NSA 59A1 C7 626 RU

1 Surface Closer DC6200 689 RU

1 Kick Plate K1050 10" HGT x BEV x CSK US32D RO

1 Door Stop 400 series as req'd US26D RO

1 Gasketing S88 PE

1 Coat Hook RM811 US26D RO

Set: 4.0

Doors: C200A, C200B, C203

Description: Office Function

1 Office Lock ML2053 NSA 59A1 C7 626 RU

1 Door Stop 400 series as req'd US26D RO

3 Silencer 608/609 RO

1 Coat Hook RM811 US26D RO https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211938574,211938358,211938495, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211942096, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211888528, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=114112091, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168874097, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=167999461,168612583, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=167999461,168612583, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=167999461,168612583, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168811825, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211938574,211938358,211938495, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=114112091, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168873950, 08 71 00-23

Set: 5.0

Doors: A235

Description: Privacy Function w/ Occupancy Indicator x Closer

3 Hinge, Full Mortise TA2314 (size per spec) US26D MK

1 Privacy Lock w/ Indicator ML2060 NSA V20 626 RU

1 Surface Closer DC6200 689 RU

1 Kick Plate K1050 10" HGT x BEV x CSK US32D RO

1 Door Stop 400 series as req'd US26D RO

Set: 6.0

Doors: A2020

Description: Existing Door Pair - Hardware Replacement

6 Hinge, Full Mortise TA2714 (size per spec) US26D MK

1 Auto Flush Bolt Set 2845 US26D RO

1 Classroom Lock ML2003 NSA 59A1 C7 626 RU

1 Surface Closer DC6200 689 RU

2 Armor Plate K1050 34" HGT x BEV x CSK US32D RO

2 Door Stop 400 series as req'd US26D RO

1 Astragal S772 PE

Notes: Complete hardware set listed for reference only. Field verify existing doors, frame and hardware.

Replace existing items with hardware that is a direct retrofit where possible.

Alter hardware set as required to achieve a code-compliant hardware upgrade.

- - - E N D - - -https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168811825, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211938574,211938358,211938509, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211942096, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211888528, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=114112091, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168874097, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168811825, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=114050792, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211938574,211938358,211938460, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211942096, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=211888528, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=114112091, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168874097, https://www.openingsstudio.com/AAOS/AAOS/CutSheetViewer.jsp?IDS=168875935, 539-21-210 05-01-21

22 11 00 - 1

SECTION 22 11 00

FACILITY WATER DISTRIBUTION

PART 1 - GENERAL

1.1 DESCRIPTION

A. Domestic water systems, including piping, equipment and all necessary accessories as designated in this section.

B. A complete listing of all acronyms and abbreviations are included in

Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.

1.2 RELATED WORK

A. Section 01 00 00, GENERAL REQUIREMENTS.

B. Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

C. Section 07 84 00, FIRESTOPPING.

D. Section 07 92 00, JOINT SEALANTS.

E. Section 09 91 00, PAINTING.

F. Section 22 05 11, COMMON WORK RESULTS FOR PLUMBING.

G. Section 22 07 11, PLUMBING INSULATION.

1.3 APPLICABLE PUBLICATIONS

A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.

B. American Society of Mechanical Engineers (ASME):

A13.1-2007 (R2013)......Scheme for Identification of Piping Systems

B16.3-2011..............Malleable Iron Threaded Fittings: Classes 150 and 300

B16.9-2012..............Factory-Made Wrought Buttwelding Fittings

B16.11-2011.............Forged Fittings, Socket-Welding and…