RFI 2 New FCU with Existing Reheat Coil - Response.pdf

PDF 29 KB Posted

Attached to
Z1DA--Upgrade 1W Building 506-20-201
Solicitation number
36C25020B0046
Issued by

About this file

This document contains a request for information and related federal contract opportunity. The request for information regards upgrading an existing fan coil unit to work in conjunction with a new fan coil unit for a room at the VA Ann Arbor Medical Center. It solicits feedback on installing a duct temperature sensor downstream of existing reheat coils to control supply air discharge temperature based on outside air temperature. The related federal contract opportunity is a solicitation to upgrade approximately 4,200 square feet of existing audiology and ENT clinic space on the first floor of Building 1W at the VA Ann Arbor Medical Center. The renovation includes structural, architectural, electrical, mechanical, fire protection, interior design and other work. Construction must be completed within 180 calendar days of receiving the notice to proceed and adhere to building codes, VA standards, LEED green design principles, and energy conservation goals. The solicitation is issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.

View the file

Other files

File Type Posted
36C25020B0046 0004.pdf PDF
RFI 005 - Response.docx DOCX document
RFI 1 work hours - response.docx DOCX document
RFI 004 - response.docx DOCX document
S02RFIFORM50620201.docx DOCX document
WAGE DET MI20200100 08072020 REV3.pdf PDF
RFI 3 project phasing - response.docx DOCX document
IMS RFI 02 responseS.docx DOCX document
IMS-RFI 01 response.docx DOCX document
36C25020B0046 0003.pdf PDF
Contractor Addresses -.doc DOC document
RFI 001 (response).docx DOCX document
_506-20-201 VA Ann Arbor - 1W Upgrades - Addendum 01.pdf PDF
Sign In Sheet 506-20-201.pdf PDF
033000.pdf PDF
RFI Form 2 8-3-2020 - response.docx DOCX document
S04 - Pre-Bid Site Visit Agenda 506-20-201.pdf PDF
RFI 1. - Response.pdf PDF
36C25020B0046 0002.pdf PDF
36C25020B0046 0001.pdf PDF
Contractor EMR Certification Form 2020.docx DOCX document
S02 506-20-201 1W Upgrades - 100 Percent DRAWINGS_Part2.pdf PDF
506-20-201_PROJECT MANUAL_VOL1_032019 SPECS.pdf PDF
S02 506-20-201 1W Upgrades - 100 Percent DRAWINGS_Part3.pdf PDF
506-20-201_PROJECT MANUAL_VOL2_032019 SPECS.pdf PDF
S02 506-20-201 1W Upgrades - 100 Percent DRAWINGS_Part1.pdf PDF
S02 506-20-201 1W Upgrades - 100 Percent DRAWINGS_Part4.pdf PDF
WAGE DET MI20200100 07032020 REV2.pdf PDF
S02 - RFI Form 506-20-201.docx DOCX document
36C25020B0046_1.pdf PDF
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Unrestricted Revised 7/26/01

Siemens Industry, Inc

Request for Information

Job Name: VA Ann Arbor 1 West Building 1W Job Number: VA# 506-20-201

Requested By: Richard A. Darnell RFI Number: 2

Contact: richard.darnell@siemens.com Date: 8/11/2020

To: VA Ann Arbor

Attn: Kyle Lipper kyle.lipper@va.gov

Spec. Number

Sketch (if required) Drawing: Rev:

System: FCU with existing reheat coil

Location: Bldg: Bldg 1W

Level:

Other Drawing Affected:

No:

Cost Impact: unknown

Time Delay: No

Description of Problem: If a room that is getting a new fan coil unit is also fed by an existing reheat coil should the existing reheat coil be reconfigured to work in conjunction with the new FCU using the controller and room sensor for the new FCU?

Resolution of Problem:

Accepted:

General Cont.: Date:

Arch/Eng: Date:

PROVIDE/INSTALL DUCT TEMPERATURE SENSOR DOWNSTREAM OF REHEAT COILS. CONTROL TO SUPPLY AIR DISCHARGE TEMPERATURE. RESET LEAVING AIR TEMPERATURE BASED ON OUTSIDE AIR TEMPERATURE:

SEQUENCE OF OPERATION: IF THE DISCHARGE AIR TEMPERATURE FALLS BELOW ITS SETPOINT, THE HEATING HOT WATER CONTROL VALVE SHALL MODULATE TO MAINTAIN THE DISCHARGE AIR TEPMERATURE SETPOINT, 55 TO 70 ADJ.

8/12/2020Jeffrey D. Kane PE Mechanical Engineer