This document includes a federal contract opportunity and related technical specifications for an HVAC upgrade project. The opportunity is a 100% set-aside for service-disabled veteran-owned small businesses to upgrade the heating, ventilation, and air conditioning for the Sterile Processing Service and hospital complex at the Dayton VA Medical Center in Dayton, Ohio. The project magnitude is estimated between $2 million and $5 million. The NAICS code is 236220 for commercial and institutional building construction with a business size standard of $36.5 million. Interested parties should review the attached solicitation notice for additional details on responding to the opportunity. The technical specifications provide requirements for HVAC components, insulation, ductwork, piping, equipment connections, access panels, and pipe supports for the project.

View the file

Other files for this federal contract opportunity

Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STRAINER

OR STEEL ROOF DECK

CONCRETE ROOF SLAB

WELD PIPE SADDLE SUPPORT

BOLTS OR WELD TO STEEL DECK

(4) 3/8" (10 MM) DIA. EXPANSION

SECURE TO ROOF SLAB WITH

CLAMPING RING

PRE-MOULDED FLEXIBLE PIPE

INSULATION AND

MEMBRANE

ROOF SYSTEM

COUNTER FLASHING

INSULATION INSERT UNDER SHIELD

TIGHT CONNECTION

TO PIPE. PROVIDE WATER

HIGH COMPRESSIVE STRENGTH

SEALANT

WELD PLATE TO PIPE

8"x8"x5/16" (200x200x9 MM)

8" (200 MM)

4" (100 MM)

STEEL PLATE

12" (300 MM)

ROOF

SURFACE

MIN.

INSULATION PROTECTION

PIPE AND INSULATION

SHIELD

IN-LINE PUMPS - CONNECTIONS

AIR HANDLING UNIT

DRAIN TRAP DETAIL

5 FT

6 8 10

9 1110 12

-1312 14 -16 -

1614 17 2219 23

2725 28 3230

20 241814 16128 1064 532 2 1/21 1/21 1 1/4THRU 3/4

7 7

7 98

SIDE VIEW TRAPEZE HANGER FOR UP TO

1000 LB. UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE SPECIFICATIONS ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE SPECIFICATIONS

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING

(8" MIN.)

BAND

1-5/8" 12 GAUGE CHANNEL

OR 2"x2"x1/4" ANGLE

1/2" DIA. HANGER

RODS WITH 36" MAX.

SPACING ON EACH

CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9

PSF MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

IN.

FT.

FT.

M A

X

NOTE: SEE SPECIFICATIONS FOR

DETAILED HANGER REQUIREMENTS

SECTION "A-A"

"B" "B"

NOTES:

1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.

2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.

3. SEE SMACNA 2005, FIGURE 9-15

ACCESS PANEL

ACCESS DOOR

CASING

GASKET

HANDLE INSIDE

FLEXIBLE

WASHER

FACTORY

FABRICATED

LATCH

SECTION "B-B"

INSULATION

DUCT

GASKET

INSULATION

INSULATION

"A"

"A"

DRAW THRU

BLOW THRU

2" PLUS X

1" MINIMUM

X

2X

UNIT TYPE A B

WHERE X = STATIC PRESSURE IN PAN

DRAIN LINE SHALL BE AT LEAST THE SAME SIZE

AS THE NIPPLE ON THE DRAIN PAN

PIPING SHALL BE RIGID COPPER TYPE L OR

TYPE M UNLESS NOTE BELOW IS MET

PITCH DOWN

TOWARD DRAIN

CLEAN OUT

FLOOR SINK

DRAIN

PAN

NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND

IS INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.

2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE

TO BE CONNECTED.

A B

DIELECTRIC

FITTING

WOODEN SUPPORT

PIPE ROLLER

STAND

LEVELED GRAVEL

BASE

INSULATED PIPE

WITH PROTECTIVE

JACKET

INSULATION SADDLE

DETAIL FOR SUPPORTING PIPE ON ROOF

PIPE HANGERS

ACCESS PANEL AND DOOR DETAIL

PIPE SUPPORT ON GRADE

PIPE HANGERS - PROVIDE DOUBLE

DEFLECTION NEOPRENE (TYPE HN)

FOR FIRST TWO ON EACH SIDE OF

PUMP (SEE NOTE NO. 1)

PRESSURE GAGE

1/2" [15mm]

FLEXIBLE

CONNECTION

BALL OR BUTTERFLY TYP.

NOTES:

1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.

BALANCING DEVICE

NOTES:

1. PROVIDE SUPPORT MINIMUM EVERY 8'-0" AND AT EVERY CHANGE OF DIRECTION. REFER TO

SHEET M404 FOR ROUTING.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FO RM 08 - 6231

A

Office of Construction and Facilities Management

U.S. D epartm ent of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

HEAPY PROJECT No.: 2018-05154 OHIO COA No.: 01528

GUIDON DESIGN INC.

905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN . 46204

317.800.6388 | W W W .GUIDONDESIGN.COM

SUSTAINABLE ARCHITECTURE + ENGINEERING

PROJECT LEAD

Architect, Structural Engineer, Civil Engineer

/2

/2

:1

:5

P

M

M504

DETAILS UPGRADE HVAC FOR SPS

DAYTON, OHIO

552-19-101

VA Project Director

7/22/2020 DTR BES

BID DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

Sheets
M504 - DETAILS

File details come from the government source that posted it. Updated .