M504 - DETAILS.pdf
PDF 412 KB Posted
- Attached to
- Upgrade HVAC SPS and Hospital Complex Federal contract opportunity
- Solicitation number
- 36C25020B0042_1
About this file
This document includes a federal contract opportunity and related technical specifications for an HVAC upgrade project. The opportunity is a 100% set-aside for service-disabled veteran-owned small businesses to upgrade the heating, ventilation, and air conditioning for the Sterile Processing Service and hospital complex at the Dayton VA Medical Center in Dayton, Ohio. The project magnitude is estimated between $2 million and $5 million. The NAICS code is 236220 for commercial and institutional building construction with a business size standard of $36.5 million. Interested parties should review the attached solicitation notice for additional details on responding to the opportunity. The technical specifications provide requirements for HVAC components, insulation, ductwork, piping, equipment connections, access panels, and pipe supports for the project.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract of Offers - OF 1419A Continuation.pdf | ||
| S06 Bid Abstract 36C25020B0042 0005.pdf | ||
| Bid Abstract - Upgrade HVAC to SPS.pdf | ||
| M405 - BUILDING 330 CHILLER PLANT 1ST FLOOR-REMOVALS NEW WORK.pdf | ||
| M402 - ENLARGED SECOND FLOOR ROOF PLAN - NEW WORK ISOMETRIC.pdf | ||
| M505 - DETAILS.pdf | ||
| S02 36C25020B0042 0004 - Additional RFI Responses.pdf | ||
| S02 36C25020B0042 0003 - Bid Instructions.pdf | ||
| S02 36C25020B0042 0002 - RFI Responses.pdf | ||
| S02 36C25020B0042 0001.pdf | ||
| Upgrade HVAC Sign in Sheet.pdf | ||
| S02 36C25020B0042_1.pdf | ||
| Project Drawings.pdf | ||
| BID DOCS PROJECT MANUAL2.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRAINER
OR STEEL ROOF DECK
CONCRETE ROOF SLAB
WELD PIPE SADDLE SUPPORT
BOLTS OR WELD TO STEEL DECK
(4) 3/8" (10 MM) DIA. EXPANSION
SECURE TO ROOF SLAB WITH
CLAMPING RING
PRE-MOULDED FLEXIBLE PIPE
INSULATION AND
MEMBRANE
ROOF SYSTEM
COUNTER FLASHING
INSULATION INSERT UNDER SHIELD
TIGHT CONNECTION
TO PIPE. PROVIDE WATER
HIGH COMPRESSIVE STRENGTH
SEALANT
WELD PLATE TO PIPE
8"x8"x5/16" (200x200x9 MM)
8" (200 MM)
4" (100 MM)
STEEL PLATE
12" (300 MM)
ROOF
SURFACE
MIN.
INSULATION PROTECTION
PIPE AND INSULATION
SHIELD
IN-LINE PUMPS - CONNECTIONS
AIR HANDLING UNIT
DRAIN TRAP DETAIL
5 FT
6 8 10
9 1110 12
-1312 14 -16 -
1614 17 2219 23
2725 28 3230
20 241814 16128 1064 532 2 1/21 1/21 1 1/4THRU 3/4
7 7
7 98
SIDE VIEW TRAPEZE HANGER FOR UP TO
1000 LB. UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER TYPE 1 - SEE SPECIFICATIONS ADJUSTABLE CLEVIS HANGER TYPE 43 - SEE SPECIFICATIONS
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" MIN.)
BAND
1-5/8" 12 GAUGE CHANNEL
OR 2"x2"x1/4" ANGLE
1/2" DIA. HANGER
RODS WITH 36" MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9
PSF MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
FT.
FT.
M A
X
NOTE: SEE SPECIFICATIONS FOR
DETAILED HANGER REQUIREMENTS
SECTION "A-A"
"B" "B"
NOTES:
1. LATCHES SHALL BE OF THE WEDGE TYPE TO CLOSE DOORS TIGHTLY.
2. HINGES ON THE ACCESS DOORS SHALL HAVE NON-CORROSIVE PINS.
3. SEE SMACNA 2005, FIGURE 9-15
ACCESS PANEL
ACCESS DOOR
CASING
GASKET
HANDLE INSIDE
FLEXIBLE
WASHER
FACTORY
FABRICATED
LATCH
SECTION "B-B"
INSULATION
DUCT
GASKET
INSULATION
INSULATION
"A"
"A"
DRAW THRU
BLOW THRU
2" PLUS X
1" MINIMUM
X
2X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE SAME SIZE
AS THE NIPPLE ON THE DRAIN PAN
PIPING SHALL BE RIGID COPPER TYPE L OR
TYPE M UNLESS NOTE BELOW IS MET
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
FLOOR SINK
DRAIN
PAN
NOTE: 1. CPVC PIPE MAY BE USED ONLY IF APPROVED BY LOCAL VA AND
IS INDOORS AND DOES NOT PASS THROUGH RATED BARRIERS.
2. DIELECTRIC FITTING TO BE USED WHEN TWO DISSIMILAR METALS ARE
TO BE CONNECTED.
A B
DIELECTRIC
FITTING
WOODEN SUPPORT
PIPE ROLLER
STAND
LEVELED GRAVEL
BASE
INSULATED PIPE
WITH PROTECTIVE
JACKET
INSULATION SADDLE
DETAIL FOR SUPPORTING PIPE ON ROOF
PIPE HANGERS
ACCESS PANEL AND DOOR DETAIL
PIPE SUPPORT ON GRADE
PIPE HANGERS - PROVIDE DOUBLE
DEFLECTION NEOPRENE (TYPE HN)
FOR FIRST TWO ON EACH SIDE OF
PUMP (SEE NOTE NO. 1)
PRESSURE GAGE
1/2" [15mm]
FLEXIBLE
CONNECTION
BALL OR BUTTERFLY TYP.
NOTES:
1. SUPPORT PUMP FROM PIPING ONLY. DO NOT SUPPORT PUMP FROM MOTOR.
BALANCING DEVICE
NOTES:
1. PROVIDE SUPPORT MINIMUM EVERY 8'-0" AND AT EVERY CHANGE OF DIRECTION. REFER TO
SHEET M404 FOR ROUTING.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FO RM 08 - 6231
A
Office of Construction and Facilities Management
U.S. D epartm ent of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
HEAPY PROJECT No.: 2018-05154 OHIO COA No.: 01528
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN . 46204
317.800.6388 | W W W .GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
/2
/2
:1
:5
P
M
M504
DETAILS UPGRADE HVAC FOR SPS
DAYTON, OHIO
552-19-101
VA Project Director
7/22/2020 DTR BES
BID DOCUMENTS
FULLY SPRINKLERED
Revisions: Date:
| Sheets |
| M504 - DETAILS |
File details come from the government source that posted it. Updated .