14.03_E600 - PANEL SCHEDULES.pdf

PDF 251 KB Posted

Attached to
Upgrade 480V Electrical System Federal contract opportunity
Solicitation number
36C24921R0084
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9

About this file

This document package includes engineering drawings and specifications for upgrading an electrical system at a Department of Veterans Affairs medical facility. The project involves installing a new 1150 KVA outdoor transformer to feed 480V switchgear, correcting wiring deficiencies for CAT scan rooms, and moving several air handlers and associated chilled water pumps and controls to emergency power circuits. Key equipment to be provided includes the outdoor transformer, associated pad and barrier walls, and upgrades to the 480V electrical system. The contractor shall furnish all material, equipment, and labor to complete the installation per specifications and drawings. Deductive alternates are listed to remove specific aspects from the scope of work. Relevant engineering drawings cover site plans, floor plans, schedules, details and diagrams for the electrical upgrades.

View the file

Other files for this federal contract opportunity

Other files attached to Upgrade 480V Electrical System, newest first.
File Type Posted
36C24921R0084 0003.pdf PDF
RFIs May 24.docx DOCX document
36C24921R0084 0002.pdf PDF
S02-Price Schedule (Project 603-20-505) FY2021.xlsx XLSX spreadsheet
265600 Ext Lighting.pdf PDF
312011 Earthwork.pdf PDF
260526 Grounding and Bonding.pdf PDF
260533 Raceway and Boxes.pdf PDF
262413 Distribution Switchboard.pdf PDF
260513 Med Voltage Cables.pdf PDF
018113 Sustainable Construction Requirements.pdf PDF
040516 Masonry Grouting2.pdf PDF
14.10_EP101 - FIRST FLOOR ELECTRICAL PLAN.pdf PDF
14.14_EP400 - OVERALL FOURTH FLOOR PLAN.pdf PDF
14.05_EP0001 - SUB-BASEMENT ELECTRICAL PLAN.pdf PDF
14.19_EP900 - OVERALL NINTH FLOOR PLAN.pdf PDF
14.12_EP201 - SECOND FLOOR ELECTRICAL PLAN.pdf PDF
14.01_E500 - SCHEDULES, DETAILS AND SINGLE-LINE DIAGRAM.pdf PDF
S15-PPQ-Template (Project 603-20-505) Upgrade 480V Electrical System.pdf PDF
323113 Chain Link Gates.pdf PDF
010000 Gen Requirments Rev 2.pdf PDF
000115 List Drawing.pdf PDF
040513 Masonry Mortaring.pdf PDF
042000 Unit Masonry.pdf PDF
017419 Const Waste Management.pdf PDF
000110 TOC.pdf PDF
00.00_GI000 - COVER SHEET AND SHEET INDEX.pdf PDF
14.07_EP001A - BASEMENT ELECTRICAL PLAN-A.pdf PDF
07.00_AE101 - SCREEN WALL DETAILS.pdf PDF
14.06_EP000 - OVERALL BASEMENT ELECTRICAL PLAN.pdf PDF
14.02_E501 - PARTIAL MEDIUM VOLTAGE SINGLE-LINE DIAGRAM.pdf PDF
S02-36C24921R0084_1.pdf PDF
263623 ATS.pdf PDF
264313 Surge Prot Dev.pdf PDF
260541 Underground Elec Const.pdf PDF
262416 Panelboards.pdf PDF
260573 Overcurrent Prot Device Study.pdf PDF
078400 Firestopping.pdf PDF
013526 Safety Req.pdf PDF
079200 Joint Sealants.pdf PDF
0000 cover Rev 1.pdf PDF
047200 CAST STONE MASONRY.pdf PDF
024100 Demolition.pdf PDF
014529 Testing Laboratory Services.pdf PDF
Combined Drawings.pdf PDF
14.11_EP200 - OVERALL SECOND FLOOR PLAN.pdf PDF
14.16_EP600 - OVERALL SIXTH FLOOR PLAN.pdf PDF
14.13_EP300 - OVERALL THIRD FLOOR PLAN.pdf PDF
14.04_EP0000 - OVERALL SUB-BASEMENT PLAN.pdf PDF
S03-Successful FBO Posting-36C24921R0084 (603-20-505).pdf PDF
Show all 50

Upgrade 480V Electrical System has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956

STAMPCONSULTANT

321 4 5 6 7 8 9 10

603-20-505

Louisville, KY

UPGRADE 480V

ELECTRICAL SYSTEM

C :\U se rs

\J ac k\ D oc um en ts

\L ou is vi lle

U pg ra de

V El ec S ys te m (2

8)

_j ac k.

bo nb rig ht T4

3D B.

rv t

3/

/2

2:

:2

PM

E600

PANEL SCHEDULES

03/01/21 JB HT

FEED THRU LUGS

Notes:

Total Est. Demand Current: 43 A Total Conn. Current: 43 A

Total Est. Demand: 35825 VA Total Conn. Load: 35825 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 43 A 43 A 43 A Total Load: 11942 VA 11942 VA 11942 VA

41 0 kVA 0 kVA 1 20 A SPARE 42 39 0 kVA 0 kVA 1 20 A SPARE 40

SPD 30 A 3

0 kVA 0 kVA 1 20 A SPARE 38

35 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 36 33 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 34 31 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 32 29 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 30 27 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 28 25 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 26 23 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 24 21 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 22 19 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 20 17 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 18 15 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 16 13 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 14 11 3 kVA 0 kVA 12 9 3 kVA 0 kVA 10

7 CHILLED WATER PUMPS-BSMNT THRU 2ND

FLR 30 A 3

3 kVA 0 kVA

3 20 A PUMPS AH-17, AH-23, AH-43

5 7 kVA 2 kVA 6 3 7 kVA 2 kVA 4

ELEC RISER AHU 3,5,6,7,9,12,13 100 A 3

7 kVA 2 kVA

3 80 A CHILLED WATER PUMPS-3RD THRU 8TH FLR

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating:

Mounting: Surface Wires: 4 Mains Rating: 200 A

Supply From: Phases: 3 Mains Type: MLO Location: Volts: 480/277 Wye A.I.C. Rating: 35,000 A

Branch Panel: EEQC

Notes:

Total Est. Demand Current: 541 A Total Conn. Current: 541 A

Total Est. Demand: 449528 VA Spare 434328 VA 100.00% 434328 VA Total Conn. Load: 449528 VA Motor 15200 VA 100.00% 15200 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

I-LINE HCM PANEL 27" MOUNTING SPACE.

Legend:

Total Amps: 541 A 541 A 541 A Total Load: 149843 VA 149843 VA 149843 VA

41 SPACE -- -- 0.0 kVA 0.0 kVA 42 39 SPACE -- -- 0.0 kVA 0.0 kVA 40 37 SPACE -- -- 0.0 kVA 0.0 kVA

3 30 A SPD

35 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 36 33 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 34 31 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 32 29 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 30 27 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 28 25 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 26 23 SPACE -- -- 0.0 kVA 39.6... 24 21 SPACE -- -- 0.0 kVA 39.6... 22 19 SPACE -- -- 0.0 kVA 39.6...

3 70 A PUMP P4 - AHU-6A, 7A, 8A, 9A

17 5.1 kVA 8.4 kVA 18 15 5.1 kVA 8.4 kVA 16

EF-8 40 A 3

5.1 kVA 8.4 kVA

3 20 A PUMP P2 - AHU 1A,4A, 5A

11 33.3... 39.6... 12 9 33.3... 39.6... 10

DX-42 150 A 3

33.3... 39.6...

3 70 A PUMP P3 - AHU 6A, 7A, 2A, 9A

5 15.5... 8.4 kVA 6 3 15.5... 8.4 kVA 4

AHU-42 70 A 3

15.5... 8.4 kVA

3 20 A PUMP P1- AHU-1A, 4A, 5A

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: 3R Mounting: Surface Wires: 4

Supply From: Phases: 3 Mains: 600 A MLO Location: Volts: 480/277 Wye A.I.C. Rating: 22,000 A

Branch Panel: EEQE

Notes:

Total Est. Demand Current: 0 A Total Conn. Current: 0 A

Total Est. Demand: 0 VA Total Conn. Load: 0 VA

Other 0 VA 0.00% 0 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 0 A 0 A 0 A Total Load: 0 VA 0 VA 0 VA

41 0 kVA 0 kVA -- -- SPACE 42 39 0 kVA 0 kVA -- -- SPACE 40

MAIN FOR PNL 9-AE(EXISTING) 20 A 3

0 kVA 0 kVA 1 20 A A-950 RCPT(EXISTING) 38

35 A950(EXISTING) 20 A 1 0 kVA 0 kVA -- -- SPACE 36 33 SPACE -- -- 0 kVA 0 kVA 34 31 A914 RCPT/ELEV/LTNG(EXISTING) 20 A 1 0 kVA 0 kVA 32 29 RCPT UNDER PANEL(EXISTING) 20 A 1 0 kVA 0 kVA

3 20 A MAIN FOR PNL 9-AE(EXISTING)

27 A-935 RCPT/LTNG(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A MED AIR VAC SYS(EXISTING) 28 25 A-935 ELEV LTNG(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A RM B906 LTNG(EXISTING) 26 23 RCPT A-901(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A SPARE 24 21 RCPT IN DATA CLOSET A-933(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A RADIO EQPMT 10TH FLR/MED AIR(EXISTING) 22 19 SERV ELEV LOBBY RCPT(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A SPARE 20 17 SPACE -- -- 0 kVA 0 kVA 1 20 A RM A-931 LTNG RCPT(EXISTING) 18 15 SPARE 20 A 1 0 kVA 0 kVA 1 20 A RM A-905 RCPT.(EXISTING) 16 13 RCPT B-909(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A RM A-905 RCPT.(EXISTING) 14 11 FA PANEL ON 9TH FLR(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A RM A-905 RCPT.(EXISTING) 12 9 CKT. FOR PANEL A AND PANEL B 20 A 1 0 kVA 0 kVA 1 20 A RM A-922 DATA,RCPT/LTS(EXISTING) 10 7 10TH FLR TV AMP/LTS/MED GAS ALARM(EX)... 20 A 1 0 kVA 0 kVA 8 5 RCPT IN B-902,903,906(EXISTING) 20 A 1 0 kVA 0 kVA 2 20 A RM A-915 FREEZER(EXISTING) 6 3 EMS 208V 10TH FLOOR(EXISTING) 20 A 1 0 kVA 0 kVA 4 1 EMS 208V 10TH FLOOR(EXISTING) 20 A 1 0 kVA 0 kVA 2 20 A RM A-905 CENTRIFUGES(EXISTING) 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating:

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: Phases: 3 Mains Type: MCB Location: Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: 9AE

Notes:

Total Est. Demand Current: 0 A Total Conn. Current: 0 A

Total Est. Demand: 50 VA Total Conn. Load: 50 VA

Other 50 VA 100.00% 50 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 0 A 0 A 0 A Total Load: 0 VA 0 VA 50 VA

41 0 kVA 0 kVA 1 20 A SPARE 42 39 0 kVA 0 kVA 1 20 A SPARE 40

ACCU41B(EXISTING) 20 A 3

0 kVA 0 kVA 1 20 A SPARE 38

35 0 kVA 0 kVA 1 20 A SPARE 36 33 0 kVA 0 kVA 1 20 A SPARE 34

ACCU41A(EXISTING) 20 A 3

0 kVA 0 kVA 32

29 SPARE 20 A 1 0 kVA 0 kVA 2 20 A AC-341(EXISTING) 30 27 SPARE 20 A 1 0 kVA 0 kVA 28 25 SPARE 20 A 1 0 kVA 0 kVA 2 20 A AC-231(EXISTING) 26 23 SPARE 20 A 1 0 kVA 0 kVA 24 21 SPARE 20 A 1 0 kVA 0 kVA 2 20 A AC-126(EXISTING) 22 19 SPARE 20 A 1 0 kVA 0 kVA 20 17 SPARE 20 A 1 0 kVA 0 kVA 2 20 A AC-013(EXISTING) 18 15 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 16 13 SPARE 20 A 1 0 kVA 0 kVA 1 20 A CONTROL PANEL FOR AHU-7,6 14 11 JOHNSON CONTROL A-343, A-823 20 A 1 0 kVA 0 kVA 1 20 A CONTROL PANEL AHU-13, 12,9,8 12 9 TEMP. CONTROL PANEL RM SB-4 20 A 1 0 kVA 0 kVA 1 20 A GF1WP(EXISTING) 10 7 0 kVA 0 kVA 8 5 A-231(EXISTING) 30 A 2 0 kVA 0 kVA 2 30 A A-341(EXISTING) 6 3 0 kVA 0 kVA 4 1 A-013 (EXISTING) 30 A 2 0 kVA 0 kVA 2 30 A A-126(EXISTING) 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating:

Mounting: Surface Wires: 4 Mains Rating: 400 A

Supply From: Phases: 3 Mains Type: MCB Location: Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: EEQ1SB

SUB-BASEMENT SWITCHBOARD ROOM

ATS-9 ATS-10

ELECTRICAL EQUIPMENT ROOM B-013

SUB-BASEMENT SWITCHBOARD ROOM SB-2

EEQB PANEL 8AE LIFE SAFETY

NINTH FLOOR, RM A-932

Revisions: Date:

SCHEMATIC DESIGN 25% 11/06/20

BID DOCUMENTS 100% 03/12/21

G E N E R A L N O T E S

NEW

ALT #1

ALT #1

ALT #1

ALT #2

NEW

ALT #4: DELETE PANEL

ALT #4

ALT #4

ALT #3

ALT #3

ALT #2: DELETE PANEL

EXISTING

ALT #1 ALT #1

BREAKERS BECOME

SPARES

ALT #1: REMOVE CIRCUITS FOR 9TH FLOOR CONTROL PANEL CIRCUIT

EXISTING

Notes: SQUARE D, I-LINE PANEL

Total Load: 0.00 kVA 0.00 kVA 0.00 kVA 17 0 kVA 0 kVA 18 15 0 kVA 0 kVA 16

SPACE 0 A 3

0 kVA 0 kVA

3 0 A SPACE

11 0 kVA 0 kVA 12 9 0 kVA 0 kVA 10

SPACE 0 A 3

0 kVA 0 kVA

3 0 A SPACE

5 0 kVA 0 kVA 6 3 0 kVA 0 kVA 4

EMS-480 800 A 3

0 kVA 0 kVA

3 600 A ATS-10

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

0 kVA Total Connected Load

Voltage: 480/277 Wye-3PH-4W Mains Rating: 1200 A Supply From: NEMA Type: Type 1 Mains Type: MLO

Location: Mounting: Surface SC Rating: 35,000 A Panel: EDP-480

NEW

REUSE BREAKER

03/12/2021

ALT #3 ALT #3

ALT #3

BASE BID:

PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS

DEDUCT ALTERNATES

ALT #1:

DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).

DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY

FAN & EXHAUST FAN.

ALT #2:

DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.

ALT #3:

DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).

PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.

ALT #4:

DEDUCT ALL ELECTRICAL WORK FOR AHU - 42 AND DX - 42 (PANELBOARD DP)

Sheets
AE101 - SCREEN WALL DETAILS
E001 - LEGEND
E500 - SCHEDULES, DETAILS AND SINGLE-LINE DIAGRAM
E501 - PARTIAL MEDIUM VOLTAGE SINGLE-LINE DIAGRAM
E600 - PANEL SCHEDULES
EP000 - OVERALL BASEMENT ELECTRICAL PLAN
EP0000 - OVERALL SUB-BASEMENT PLAN
EP0001 - SUB-BASEMENT ELECTRICAL PLAN
EP001A - BASEMENT ELECTRICAL PLAN-A
EP001B - BASEMENT ELECTRICAL PLAN-B
EP100 - OVERALL FIRST FLOOR PLAN
EP101 - FIRST FLOOR ELECTRICAL PLAN
EP200 - OVERALL SECOND FLOOR PLAN
EP201 - SECOND FLOOR ELECTRICAL PLAN
EP300 - OVERALL THIRD FLOOR PLAN
EP400 - OVERALL FOURTH FLOOR PLAN
EP500 - OVERALL FIFTH FLOOR PLAN
EP600 - OVERALL SIXTH FLOOR PLAN
EP700 - OVERALL SEVENTH FLOOR PLAN
EP800 - OVERALL EIGHT FLOOR PLAN
EP900 - OVERALL NINTH FLOOR PLAN
ES100 - ELECTRICAL SITE PLAN
GI000 - COVER SHEET AND SHEET INDEX