- Upgrade 480V Electrical System Federal contract opportunity
- Solicitation number
- 36C24921R0084
About this file
This solicitation requests proposals to upgrade the 480V electrical system at a Department of Veterans Affairs medical center. The scope of work includes installing a new 1150 KVA pad-mounted transformer with associated barrier walls, upgrading switchgear in the sub-basement, correcting wiring deficiencies for CAT scan rooms, and moving electrical feeds for several air handlers and their associated chilled water pumps and controls to emergency power circuits. The contractor will furnish all material, equipment, and labor to complete this work in accordance with provided specifications and drawings.
View the file
Other files for this federal contract opportunity
Show all 50
Upgrade 480V Electrical System has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. SEE GENERAL PROJECT NOTES FOR NEW WORK FOR ADDITIONAL REQUIREMENTS FOR WORK WITHIN THE EXISTING FACILITY.
2. THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND FIELD CONDITIONS PRIOR TO DEMOLITION AND CONSTRUCTION. IF PROVIDED, THE CONTRACTOR SHALL CAREFULLY
EXAMINE EXISTING BUILDING DOCUMENTS. THE CONTRACTOR SHALL BRING ANY DISCREPANCIES TO THE IMMEDIATE ATTENTION OF THE ARCHITECT AND C.O.R.
3. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF EXISTING ITEMS TO REMAIN DURING DEMOLITION AND CONSTRUCTION.
4. MAINTAIN EXIT EGRESS PATHS TO EXISTING EXIT DOORS DURING CONSTRUCTION.
5. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL CONSTRUCTION ROUTES BEYOND THE AREAS OF WORK AND THE ROUTES MUST BE RETURNED TO THEIR ORIGINAL
CONDITION AT THE END OF THE PROJECT.
6. MAINTAIN THE BUILDING IN A WEATHERTIGHT CONDITION AT ALL TIMES.
7. ALL DEMOLITION AND CONSTRUCTION ACTIVITIES SHALL BE COORDINATED WITH THE C.O.R. TO MINIMIZE DISRUPTIONS OF NORMAL FUNCTIONS OF THE VA'S OCCUPIED AREAS.
8. IF CONSTRUCTION NOISE IS ANTICIPATED, SUBMIT A WRITTEN REQUEST TO THE C.O.R. 48 HOURS BEFORE THE SCHEDULED TIME OF THE CONSTRUCTION ACTIVITIES. NO WORK SHALL
BE DONE WITHOUT THE WRITTEN APPROVAL OF THE C.O.R. THE C.O.R. RESERVES THE RIGHT TO DISCONTINUE NOISY CONSTRUCTION AT ANY TIME. NO RADIOS SHALL BE PERMITTED
AT ANY TIME IN WORK AREAS ADJACENT TO OCCUPIED SPACES.
9. ALL EXISTING SERVICES AND UTILITIES SHALL BE MAINTAINED TO ADJACENT DEPARTMENTS OR AREAS THAT ARE IN OPERATION AND SERVED BY THEM. COORDINATE ALL DISRUPTIONS OR DISCONTINUATIONS OF UTILITIES AND SERVICES WITH THE C.O.R. NO SHUT DOWN OF EXISTING SERVICES IS ALLOWED TO OCCUR UNTIL RECEIVING THE C.O.R.'S WRITTEN APPROVAL OF THE SHUT DOWN SCHEDULE. PROVIDE TEMPORARY SERVICES AND/OR UTILITIES DURING INTERRUPTIONS AS REQUIRED AND APPROVED BY THE C.O.R.
10. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE VA'S OCCUPIED AREAS ADJACENT TO NEW CONSTRUCTION OR OCCUPIED AREAS WHERE VARIOUS SYSTEM CONNECTIONS OR EXTENSIONS ARE REQUIRED. IN THESE AREAS, THE CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY LACK OF SUFFICIENT PROTECTION FROM THE WEATHER AND FROM THE RESULTS OF ALL CONSTRUCTION ACTIVITY INCLUDING BUT NOT LIMITED TO DUST AND WATER.
11. THE CONTRACTOR SHALL RECEIVE WRITTEN APPROVAL FROM THE C.O.R. BEFORE GRINDING, USING OPEN FLAMES, WELDING RODS AND TORCHES. THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS TO PROHIBIT THE MIGRATION OF SMOKE AND OTHER PRODUCTS OF COMBUSTION INTO OCCUPIED AREAS OF THE EXISTING BUILDING
AND FOR OBTAINING ALL REQUIRED PERMITS RELATED TO HOT WORK.
12. PROVIDE FIRE PROTECTION IN ACCORDANCE WITH THE REQUIREMENTS OF THE GOVERNING AUTHORITY.
13. IT IS THE CONTRACTORS RESPONSIBILITY TO PATCH ALL SPRAY-ON FIRE PROTECTION AT REMOVALS, AT ANY EXISTING LOCATIONS WHICH ARE VOID OF PROTECTION WITHIN THE
AREA OF WORK AND AT NEW CONSTRUCTION WHICH DISTURBS EXISTING FIRE PROTECTION. FIREPROOFING MUST BE CONTINUOUS AND UNOBSTRUCTED.
14. DO NOT OVERLOAD THE EXISTING BUILDING STRUCTURE. MAINTAIN THE STRUCTURAL INTEGRITY OF ALL STRUCTURAL FRAMING MEMBERS AND SYSTEMS AT ALL TIMES.
15. ALL DEMOLISHED MATERIAL, EXCEPT MATERIAL THAT IS LISTED OR MARKED BY THE ARCHITECT OR THE C.O.R. FOR RETENTION, SHALL BECOME THE PROPERTY OF THE
CONTRACTOR AND IT SHALL BE DISPOSED OF. NO DEBRIS RESULTING FROM WORK SHALL BE LEFT IN THE CONSTRUCTION ROUTES BEYOND THE AREAS OF WORK. THE WEIGHT AND COST OF DISPOSAL FOR ALL CONTROLLED SUBSTANCES SUCH AS LEAD AND ASBESTOS SHALL BE TRACKED AND REPORTED. THE CONTRACTOR SHALL NOT USE THE VA TRASH
COMPACTOR.
16. REMOVAL OF A PARTICULAR ITEM IS TO INCLUDE ALL RELATED ITEMS, SUCH AS REMOVAL OF WALLS WOULD INCLUDE ASSOCIATED DOORS, HARDWARE, ELECTRICAL, PLUMBING, MECHANICAL, ETC. REFER TO DEMOLITION DRAWINGS FOR MORE INFORMATION. FOR ALL REMOVALS, THE CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES
INCLUDING BUT NOT LIMITED TO MECHANICAL, ELECTRICAL AND PLUMBING.
17. WHERE CEILINGS ARE SHOWN TO BE REMOVED, ALL UNUSED SUSPENDED EQUIPMENT, WIRES, ANGLES, ETC. SHALL BE REMOVED. SEE DEMOLITION DRAWINGS FOR ADDITIONAL INFORMATION. EXISTING LIGHTS MAY BE MAINTAINED AS TEMPORARY CONSTRUCTION LIGHTING.
18. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT DEMOLISHED OR REMOVED AS REQUIRED UNTIL PERMANENT SUPPORT IS PROVIDED IN THE FINAL
CONSTRUCTION.
19. ALL OPENINGS IN EXISTING WALLS, CEILINGS AND FLOORS, WHICH ARE THE RESULT OF REMOVALS AND OTHER NEW CONSTRUCTION ACTIVITY, SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE EXISTING MATERIALS. IF THE PATCH IS TO BE MADE IN FIRE RATED CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE PATCH
SHALL BE FINISHED TO A LIKE NEW CONDITION TO MATCH THE EXISTING FINISH.
20. ALL EXISTING OPENINGS IN CEILINGS, FLOORS AND WALLS DISCOVERED IN THE EXISTING STRUCTURE SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE EXISTING MATERIALS. IF THE PATCH IS TO BE MADE IN FIRE RATED CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE PATCH SHALL BE FINISHED TO A LIKE NEW CONDITION TO MATCH THE EXISTING FINISH. USE ONE FIRE STOPPING SYSTEM FOR ALL SUB-CONTRACTORS.
21. WHERE EXISTING SURFACES ARE TO BE REFINISHED OR ARE TO SERVE AS SUBSTRATE FOR THE ATTACHMENT OR APPLICATION OF NEW MATERIALS OR CONSTRUCTION, PREPARE OR ALTER THE EXISTING SURFACES AS NECESSARY TO PROPERLY ACCOMMODATE THE NEW MATERIALS.
22. FIELD VERIFY SIZES AND DIMENSIONS OF ALL EXISTING UTILITIES THAT IMPACT THE NEW WORK. DETERMINE THE SIZE AND LOCATION THE PENETRATIONS FROM THE EXISTING
UTILITIES WITHIN THE NEW WORK. SEAL TIGHT TO ALL PENETRATIONS AND CAULK.
23. PENETRATIONS THROUGH EXISTING FIRE RATED CONSTRUCTION MUST BE PROPERLY CLOSED AND FIRE SAFE'D TO ACHIEVE THE PROPER FIRE RATING BY THE END OF
CONSTRUCTION OPERATIONS FOR EACH DAY.
24. NEW HOLES IN EXISTING ELEVATED FLOOR AND ROOF STRUCTURES FOR NEW WORK MUST BE COORDINATED WITH THE EXISTING STRUCTURE SO THAT CRITICAL STRUCTURAL
MEMBERS ARE NOT DAMAGED.
25. UNLESS OTHERWISE NOTED, THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISTING SALVAGED STOCK BEFORE ORDERING NEW MATERIAL.
G E N E R A L N O T E S F O R E X I S T I N G F A C I L I T I E S :
PROJECT EXTENT
1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND FEDERAL AUTHORITIES, CODES, RULES AND REGULATIONS.
2. THESE DOCUMENTS SHOW THE MINIMUM CONSTRUCTION REQUIREMENTS AND THE MINIMUM QUALITY OF WORK EXPECTED. MORE STRINGENT
REQUIREMENTS STIPULATED WITHIN RELEVANT MANUFACTURER’S INSTALLATION INSTRUCTIONS WILL SUPERSEDE.
3. ANY UNFORESEEN OR UNCLEAR CONDITIONS SHALL BE REPORTED TO THE COR AND ARCHITECT PRIOR TO PROCEEDING WITH WORK.
4. ANY CONFLICTS WITHIN THE DRAWINGS, BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, OR BETWEEN THE DRAWINGS AND THE ACTUAL
CONDITIONS AT THE SITE, ARE TO BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR AND ARCHITECT. THE CONTRACTOR SHALL NOT PROCEED
WITH WORK UNTIL WRITTEN CLARIFICATION FROM THE COR AND ARCHITECT IS RECEIVED.
5. UNLESS OTHERWISE NOTED, ALL MATERIALS AND EQUIPMENT ARE TO BE INSTALLED PER THE APPLICABLE PROVISIONS OF THESE DOCUMENTS AND THE
MANUFACTURER’S INSTRUCTIONS.
6. ALL MATERIALS USED ARE REQUIRED TO BE NEW UNLESS OTHERWISE NOTED AND/OR OF A QUALITY TO MEET OR EXCEED ALL APPLICABLE INDUSTRY STANDARDS. WHERE SPECIFIED PRODUCTS OR MANUFACTURERS ARE NOT NOTED, THE CONTRACTOR IS REQUIRED TO NOTIFY THE COR AND
ARCHITECT TO OBTAIN A MINIMUM STANDARD OF QUALITY.
7. THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS, METHODS AND TECHNIQUES FOR CONSTRUCTION.
8. THE CONTRACTOR IS RESPONSIBLE FOR JOB-SITE SAFETY INCLUDING BUT NOT LIMITED TO THE ADHERENCE TO OSHA REGULATIONS.
9. ALL ELECTRICAL AND MECHANICAL WORK SHALL BE PERFORMED BY PERSONNEL LICENSED IN THE STATE WHERE THIS PROJECT IS LOCATED.
10. REMOVE ALL DEBRIS PROPERLY FROM THE SITE. LOAD DEBRIS DIRECTLY ONTO TRUCKS OR INTO DUMPSTERS FOR REMOVAL. DISPOSE OF DEBRIS
LEGALLY. DO NOT BURN DEBRIS ON THE SITE. DO NOT ALLOW DEBRIS TO ENTER SEWERS. DO NOT ALLOW PILED DEBRIS TO ENDANGER STRUCTURES, BLOCK EXISTS OR ROADWAYS. COMBUSTIBLE WASTE WHICH COULD CREATE A FIRE HAZARD SHALL NOT BE PERMITTED TO ACCUMULATE IN OR AROUND THE CONSTRUCTION SITE. DEBRIS FROM OTHER LOCATIONS SHALL NOT BE BROUGHT ONTO VA PROPERTY.
11. COORDINATE ALL WORK WITH ALL OTHER DISCIPLINES, INCLUDING, BUT NOT LIMITED TO MECHANICAL, ELECTRICAL, PLUMBING & SITE DRAWINGS. EXACT SIZE AND LOCATION OF ALL ROOF AND FLOOR OPENINGS SHOWN ON ARCHITECTURAL DRAWINGS SHALL BE VERIFIED WITH THE ASSOCIATED SUB-
CONTRACTORS PRIOR TO CONSTRUCTION.
12. DO NOT SCALE DRAWINGS. DIMENSIONS SHALL GOVERN. ALL PLAN DIMENSIONS ARE TAKEN TO FINISH FACE OF CONSTRUCTION.
13. LAYOUT AND VERIFY ALL PARTITION LOCATIONS PRIOR TO CONSTRUCTION FOR CLEARANCES AND DIMENSIONS. NOTIFY ARCHITECT OF ANY
DISCREPANCIES.
14. WITHIN ALL METAL STUD PARTITIONS, THE CONTRACTOR IS TO PROVIDE BLOCKING FOR ALL WALL MOUNTED EQUIPMENT AND ACCESSORIES INCLUDING
BUT NOT LIMITED TO: MECHANICAL, ELECTRICAL AND PLUMBING DEVICES, FURNITURE, CASEWORK, MILLWORK AND ALL OTHER WALL MOUNTED ACCESSORIES AND ITEMS. THE LOCATIONS, MOUNTING HEIGHTS AND BLOCKING REQUIREMENTS SHOWN HEREON ARE GIVEN FOR INFORMATIONAL PURPOSES ONLY AND IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THIS INFORMATION WITH THE ASSOCIATED SUB-CONTRACTORS, MANUFACTURERS, OR EQUIPMENT SUPPLIERS.
15. ALL CONCEALED WOOD SHALL BE FIRE RETARDANT TREATED.
16. THE CONTRACTOR SHALL COORDINATE WITH ALL OTHER DISCIPLINES INCLUDING BUT NOT LIMITED TO MECHANICAL, ELECTRICAL AND PLUMBING, TO
DETERMINE THE SIZE AND LOCATION OF ALL PENETRATIONS IN NEW CONSTRUCTION. COORDINATE AND PROVIDE ALL OPENINGS. SEAL CONSTRUCTION
TIGHT TO ALL PENETRATIONS AND CAULK.
17. ALL PENETRATIONS THROUGH FIRE RATED CONSTRUCTION MUST BE FIRE SAFE'D IN ACCORDANCE WITH THE SPECIFICATIONS.
18. PROVIDE CONTROL JOINTS IN GYPSUM WALLBOARD INTERIOR PARTITIONS AT 30 FEET ON CENTER MAXIMUM. WHERE POSSIBLE, LOCATE AT CORNERS
ABOVE OPENINGS. VERIFY LOCATIONS WITH ARCHITECT. SEE THE ASSOCIATED TYPICAL DETAILS INCLUDED IN THESE DOCUMENTS.
19. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL EQUIPMENT INSTALLATION AND VERIFYING ALL REQUIRED ROUGH OPENINGS, AND ROUGH-
IN DIMENSIONS WITH THE EQUIPMENT MANUFACTURER, OWNER AND ARCHITECT PRIOR TO CONSTRUCTION.
G E N E R A L N O T E S F O R N E W W O R K :
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
2:
:4
PM
GI000
COVER SHEET AND SHEET INDEX
03/01/21 PH DB
D R A W I N G I N D E X ROBLEY REX VAMC
UPGRADE 480V ELECTRICAL SYSTEM
DEPARTMENT OF VETERANS AFFAIRS
603-20-505
800 ZORN AVE.
LOUISVILLE, KY 40206
VICINITY MAP SITE LOCATION MAPSITE MAP NTSNTS
Sheet # Sheet Name
GENERAL
GI000 COVER SHEET AND SHEET INDEX
ARCHITECTURAL
AE101 SCREEN WALL DETAILS
ELECTRICAL
E001 LEGEND
E500 SCHEDULES, DETAILS AND SINGLE-LINE DIAGRAM
E501 PARTIAL MEDIUM VOLTAGE SINGLE-LINE DIAGRAM
E600 PANEL SCHEDULES
ES100 ELECTRICAL SITE PLAN
EP0000 OVERALL SUB-BASEMENT PLAN
EP0001 SUB-BASEMENT ELECTRICAL PLAN
EP000 OVERALL BASEMENT ELECTRICAL PLAN
EP001A BASEMENT ELECTRICAL PLAN-A
EP001B BASEMENT ELECTRICAL PLAN-B
EP100 OVERALL FIRST FLOOR PLAN
EP101 FIRST FLOOR ELECTRICAL PLAN
EP200 OVERALL SECOND FLOOR PLAN
EP201 SECOND FLOOR ELECTRICAL PLAN
EP300 OVERALL THIRD FLOOR PLAN
EP400 OVERALL FOURTH FLOOR PLAN
EP500 OVERALL FIFTH FLOOR PLAN
EP600 OVERALL SIXTH FLOOR PLAN
EP700 OVERALL SEVENTH FLOOR PLAN
EP800 OVERALL EIGHT FLOOR PLAN
EP900 OVERALL NINTH FLOOR PLAN
Revisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
10/11/2019
03/12/2021
SPECIALIST OF
HEALTH SYST
A-113d
OFFICE
PATIENT ADVO
SPECIALIST OF
HEALTH SYST
A-113d
OFFICE
PATIENT ADVO
DICKERSON
BARBARA HUFFINES
KELLY MONTGOMERY LINDA BRASHEARS
ELEVATOR
SNACKFROZEN PEPSI
MICRO
WAVE
CHANGE
PE
PS
I
UP
B-122
ROOM
EXAM
F.A.C.
B-130
CLOSET
ELECTRIC
A-113b
SPECIALIST OFFICE
HEALTH SYSTEM
A-113a
OFFICE
PUBLIC AFFAIRS
A-104f
OFFICE
MED SVC
A-104e
OFFICE
MED SVC
A-104m
STORAGE
A-104l
STORAGE
A-120
CLOSET
TELEPHONE
A-111
OFFICE
COMPLIANCE OFFICER
ACTIVATION
OFFICE
A-112
A-104h
EXAM ROOM
OCCUPATIONAL HEALTH
A-104g
OFFICE
OCCUPATIONAL HEALTH
A-104i
OFFICE
OCCUPATIONAL HEALTH
DECEDENT
AFFAIRS
A-109
COMPLIANCE
OFFICE
A-110
A-104k
OFFICE
OCCUPATIONAL HEALTH
A-104j
MULTIPURPOSE ROOM
OCCUPATIONAL HEALTH
A-108
STORAGE
EEO
A-109a
CLOSET
A-113c
OFFICE
PATIENT ADVOCATE
A-114
CLOSET
ELECTRIC
A-118 #2
STAIRWELL
A-117a
STORAGE
A-117
ROOM
STORAGE
F.A.C.
A-126
CLOSET
ELECTRIC
A-102b
ROOM
MULTIPURPOSE
A-102
OPERATOR
TELEPHONE
A-104c
OFFICE
INFECTION CONTROL
A-104d
OFFICE
MED SVC
A-103
OFFICE
A-104
A-107 H.A.C.
A-102a
RESTROOM
A-101a
AREA
VENDING
A-154
CLOSET
ELECTRIC
A-131
LOUNGE
STAFF
A-130
CLOSET
COMM
H.V.A.C.
EQUIPMENT
ROOM
A-125
A-127 #1
STAIRWELL
F.A.C.
A-128 H.A.C. A-129
CLOSET
TELEPHONE
B-104c
CLOSET
TELEPHONE
B-104a
OFFICE
NEUROPSYCH
B-104b
OFFICE
PSYCH-TECH
B-102a
HOLDING ROOM
B-102
VA POLICE
B-103
VENDING
B-104
OFFICE
NEUROPSYCHOLOGY
B-106
CLOSET
COMPUTER
B-105
CLOSET
ELECTRIC
B-172
WAITING
EYE CLINIC
B-107 #8
STAIRWELL
D-102
CLOSET
TELE.
D-101
CLOSET
ELECTRIC
D-105
RESTROOM
STAFF
B-108
STORAGE
B-109
STORAGE
CYLINDER
D-125
RECEPTION
D-121 H.A.C.
D-129
STORAGE
D-128
UTILITY
SOILED
D-118
EXAM ROOM
SCI
B-121
ROOM
CONSULT
D-119
RESTROOM
PATIENT
D-117
LOUNGE
STAFF
D-116 #9
STAIRWELL
CONTROLLED
SUBSTANCE
AREA
A-156g
A-175e
OFFICE
CHIEF OF STAFF
A-175f
OFFICE
DIRECTOR'S
DIRECTOR'S
CONFERENCE
ROOM
A-160
A-175a H.A.C.
A-157a
CLOSET
ELECTRIC
A-101
LOBBY
MAIN
A-175h
ROOM
MULTIPURPOSE
ASSOCIATE
DIRECTOR'S
OFFICE
A-175g
COMPLIANCE OFFICER
OFFICE
A-177 A-176
OFFICE
COMPLIANCE
A-175i
SPECIALIST
HEATH SYSTEM
A-156
PHARMACY
P-3
A-157
LOBBY
SERVICE ELEVATOR
S-5
S-6
P-4
P-2
P-1
A-159
RESTROOM
WOMEN'S
H.V.A.C.
EQUIPMENT
ROOM
A-156k
A-175
SUITE
DIRECTOR'S
A-175c
STORAGE
A-175b
ROOM
MULTIPURPOSE
AO TO
AD OF OPERATIONS
A-173
FACILITY PLANNER
OFFICE
A-174 A-171
OFFICE
NURSING
A-172
OFFICE
NURSING
A-170
ROOM
BREAK
F.A.C.
A-162
RESTROOM
MEN'S
A-161 #6
STAIRWELL
A-165
CLOSET
ELECTRIC
A-163
CLOSET
ELECTRIC
A-164
CONFERENCE ROOM
H.V.A.C.
EQUIPMENT
ROOM
A-167
A-169
OFFICE
NURSING
A-168
OFFICE
NURSING
A-166
OFFICE
NURSING
C-134
ROOM
BREAK
C-149 #5
STAIRWELL
C-139
ROOM
EXAM
C-137
ROOM
EXAM
C-138
ROOM
EXAM
C-135
ROOM
EXAM
C-136
ROOM
EXAM
C-114
RESTROOM
WOMEN'S
C-103
UTILITY
SOILED
C-126
ROOM
EXAM
C-125
ROOM
EXAM
C-123
STATION
NURSE'S
C-124
ROOM
CONSULT
B-137
ROOM
X-RAY
B-154
AREA
RECEPTION
B-155
CASHIER
AGENT
B-157
OFFICE
TRAVEL
B-149
ROOM
X-RAY
B-151
ROOM
DRESSING
A-156i
VAULT
FLAME
A-156h
VAULT
NARCOTICS
B-152 H.A.C. B-150
ROOM
DRESSING
B-148
ROOM
DRESSING
B-153
RESTROOM
B-138a
ROOM
BREAK
B-138
ROOM
BREAK/PROCESSING
B-126
TRIAGE
B-129 #3
STAIRWELL
C-155a
CLOSET
ELECTRIC
FEC
B-125
ROOM
CONSULT
B-124
ROOM
EXAM
P-7 P-8
C-100
ROOM
TREATMENT
B-135
ROOM
DRESSING
BIOMEDICAL
ENGINEERING
OFFICE
B-134
B-136
ROOM
DRESSING
P-9
C-130
RECEPTION
POD B
C-129
ROOM
CONSULT
C-128
TRIAGE
NURSE
C-127
ROOM
EXAM
B-141
ROOM
STERIS
B-143
EXAM
ENT
B-140
ROOM
EXAM
B-142
ROOM
STORAGE
B-147
EXAM
ENT
B-146
EXAM
ENT
B-144
EXAM
ENT
C-116
OFFICE
NURSE'S
B-139
ROOM
X-RAY
C-120
ROOM
EXAM
C-121
ROOM
EXAM
C-122
ROOM
CONSULT
C-131
RECEPTION
POD C
C-117
ROOM
CONSULT
C-118
ROOM
EXAM
C-119
ROOM
EXAM
B-145
EXAM
ENT
C-150
OFFICE
SURGERY ADPAC
FEC
C-132a
CLOSET
ELECTRIC
C-132b
CLOSET
COMPUTER
C-115
OFFICE
ATTENDING
C-132c2
CLOSET
TELEPHONE
C-132
POD D
C-105
ROOM
EXAM
B-123
ROOM
EXAM
C-104
UTILITY
CLEAN
C-106
ROOM
EXAM
C-107
ROOM
EXAM
C-108
ROOM
EXAM
C-110
ROOM
EXAM
C-109
ROOM
EXAM
C-111
ROOM
EXAM
C-113
RESTROOM
MEN'S
C-112
ROOM
EXAM
C-140 #7
STAIRWELL
C-148 H.A.C.
C-146
STORAGE
CLERK
OFFICE
C-147
C-145
RESTROOM
MEN'S
C-144
RESTROOM
WOMEN'S
FEC
C-143
ROOM
EXAM
C-141
ROOM
PROCEDURE
C-142
ROOM
MULTIPURPOSE
OFFICE
A-104a
A-126a
CLOSET
COMM.
VIS
COORDINATOR
OFFICE
A-116
A-113
SUITE
PATIENT ADVOCATE
A-104b
OFFICE
INFECTION CONTROL
A-158
AREA
PHARMACY CONSULT
A-156c
OFFICE
A-156d
OFFICE
A-156b OFFICE A-156f
OFFICE
A-156e
OFFICE
A-156j
BREAK AREA
A-156i
OPTIFILL
PHARMACY
CHIEF'S OFFICE/
CONFERENCE
A-156a
RESTROOM
A-175f1
STORAGE
A-175f2
A-166A
RECEPTION
NURSING
B-154a
WAITING
C-154
WAITING
POD A/B
C-153
WAITING
POD C
C-152
WAITING
POD C
C-151
WAITING
POD D/E
C-133
OFFICE
RN SUPERVISOR
C-132c
OFFICE
C-132c1
CLOSET
MECH
D-100
WAITING
MEN'S
RESTROOM
A-124
WOMEN'S
RESTROOM
A-121
NURSE
OFFICE
A-119
B-111
OPTICIAN
B-113e
STORAGE
B-113c
ROOM
EXAM
B-113d
ROOM
EXAM B-113b
ROOM
LASER
B-113f
ROOM
EXAM
B-113h
FIELDS
VISUAL
B-113g
ROOM
EXAM
B-114
OFFICE
SURGERYB-112
OFFICE
TECHNICIANS
B-116
SHOP
COFFEE
B-115a STORAGEB-113a
ROOM
WAITING
B-113s H.A.C.
B-113i
ROOM
PROCEDURE
B-113q
RESTROOM
STAFF
B-115
ROOM
CAST
B-117
OFFICE
CLINIC
B-119
ROOM
EXAM
B-118
ROOM
EXAMATTENDING
OFFICE
B-113r
B-110
OFFICE
BROS
B-113k
ROOM
EXAM
B-113j
ROOM
EXAM
B-113l
ROOM
EXAM B-113p
RESTROOM
B-113m
ROOM
EXAM
B-113n
ROOM
EXAM
B-113o
OFFICE
RESIDENT
B-113t
OFFICE/RECEPTION
CLINIC
TRAINING ROOM
HR LINKS
JT USE COPIER
A-115
C-101
TRIAGE
NURSE
C-102
TRIAGE
NURSE
B-128
RESTROOM
C-115a
STORAGE
CLEAN
A-100
VESTIBULE
B-100
VESTIBULE
B-101
INFORMATION
PATIENT
B-113
SUITE
EYE CLINIC
A-131a
RESTROOM
STAFF
A-153k
BAY
ISOLATION
A-153i
OFFICE
STAFF
A-153j
RESTROOM
STAFF
A-153h
BAY
ISOLATION
A-153f
BAY
ER
A-153g
BAY
ER
A-153e
BAY
ER
A-155 H.A.C.
A-153d
BAY
ER
B-159
COORDINATORS
TRANSFER
BRINK, MONTGOMERY
B-156
CLERK
FEE
B-133
WORKER
SOCIAL
B-132 H.A.C.
MEN'S
RESTROOM
B-131
WOMEN'S
RESTROOM
C-155
A-153
NURSES' STATION
EMERGENT CARE
A-153c
RESTROOM
B-158
OFFICE
MEANS
B-171
UTILITY
SOILED
B-170
OFFICE
SUPERVISOR
B-165b
OFFICE
B-165a
ROOM
FILE
B-165
ADMISSIONS
B-166
ROOM
ADMISSIONS
B-167
ROOM
ADMISSIONS
B-168
ROOM
MEANS
B-169
ROOM
PHOTO ID
B-160
OFFICE
ELIGIBILITY
B-161
OFFICE
ELIGIBILITY
B-162
OFFICE
ELIGIBILITY
B-163
OFFICE
NURSING
A-139
WAITING
URGENT
B-164
WAITING
ER
A-140
TRIAGE
A-141
OFFICE
A-142 H.A.C. A-143
UTILITY
SOILED
A-153a
BAY
ER
A-153b
BAY
ER
A-153n
BAY
ER
A-153m
BAY
ER
A-153l
BAY
ER
A-144
UTILITY
CLEAN
A-149
EQUIPMENT
CLEAN
A-148
NURSES' STATION
URGENT CARE
A-147
RESTROOM
A-146
PHLEBOTOMY
A-145
WORKROOM
DOCTORS'
A-138
DECONTAMINATION
A-137
EQUIPMENT
DECONTAMINATION
A-135
ROOM
EXAM
A-136
ROOM
EXAM
A-134
ROOM
EXAM
A-133
ROOM
EXAM
SS1-1
SHELTER-FRONT
SMOKING
A-132
VESTIBULE
AMBULANCE
P-10
ELEVATOR
A-113d
OFFICE
PATIENT ADVOCATE
D-126
RESIDENTS
UofL
D-124
ROOM
EXAM
D-111
EXAM
POLY/MED
D-110
EXAM ROOM
POLY/MED
D-109
EXAM ROOM
POLYD-108
OFFICE
POLY
D-107
EXAM ROOM
POLY
D-106
OFFICE
POLY
D-103
OFFICE
D-104
OFFICE
POLY
D-115
ROOM
EXAM
D-114
OFFICE
SCI
D-113
EXAM ROOM
MED
D-112
EXAM ROOM
POLY/MED
D-131
ROOM
EXAM
D-130
ROOM
EXAM
D-120
ROOM
TA
D-122
ROOM
EXAM
D-127
ROOM
TREATMENT
D-132
ROOM
EXAM
EXAM
ROOM
D-123
B-120
OFFICE
CLINIC MGR
B-127
OFFICE
CLINIC COORDINATOR
ASSOC. DIRECTOR
PATIENT CARE SVCS
OFFICE
A-176a
AO TO
CHIEF OF STAFF
A-175d
E-002
RECEPTION
E-003
VESTIBULE
E-001
LOBBY
WEST ENTRANCE
E-005
GROUP THERAPY
E-004
STAIR
B-016d
STORAGE
ENGINEERING
E-007
MEN E-008
WOMEN
E-006
MECH
E-005a
STORAGE
B-016d1
ELECTRICAL
P
P
P
P
P
P
P
P
A-113d
OFFICE
PATIENT ADVO
A-113d
OFFICE
PATIENT ADVO
W1
14' - 3"
AE101
AE101 3
AE101
10" THICK
CONRETE PAD
3' - 0"3' - 0"
4'
2"
8'
6"
7' - 3"
AE101
5'
ELECTRICAL
TRANSFOMER.
REFER TO ELECTRICAL
SERIES FOR MORE
INFORMATION
AE101
EXISTING
WALKWAY
AE101
TYP.
4' - 7 1/2" 6' - 0" 3' - 7 1/2"
1'
3' - 0"
4'
2"
14' - 3"
5'
FIRST FLOOR
524' - 6"
AE101
EXISITNG BUILDING
2 3 3' - 6" 6' - 2 1/2" 4' - 6"
FIRST FLOOR
524' - 6"
AE101
7'
0" 16' - 6"
EXISTING
BUILDING
FIRST FLOOR
524' - 6"
AE101
14' - 3"
EXISTING
BUILDING
FIRST FLOOR
524' - 6"
4" 6'
8"
BRICK VENEER
TO MATCH EXISTING
ADJACENT
CONSTRUCTION
8" CMU
CAST STONE CAP
ANCHORED TO WALL
1' - 0"
2" GRAVEL
CONCRETE
FOUNDATION
CONCRETE
FOOTING
#4 @ 12" O.C.
(3) #4 BARS CONTINUOUS
3" C
L.
1'
0"
9" 1' - 0" 9"
2'
0" B
EL
O
W G
R
AD
E
HORIZONTAL REINFORCING
AND BRICK TIES
GROUT SOLID
FLASHING WITH WEEPS
TRANSFORMER
TRANSFORMER
PAD
3' - 0"
4"
#4 BAR AND FILL
CELL @ 48" O.C.
#4 @ 12" O.C
(TYP. BOTH SIDES)
2"
EL. = 524' - 10"
AE101
1"
EXPANSION JOINT
BRICK TO MATCH
EXISTING ADJACENT
CONSTRUCTION
8" CMU
EXISTING WALL
CONSTRUCTION
REMOVE EXISTING PLANTING
AS NECESSARY
COMPACTED GRANULAR
BACKFILL
(1) #4 BAR CONT. (TYP.)
#4 @ 12" O.C.
GRAVEL 3/4" CHAMFER4"
(T
YP
SEE PLAN
EL. = 524' - 10"
6"
2'
0"
3" C
L.
1" C
L.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
2:
:0
PM
AE101
SCREEN WALL DETAILS
03/01/21 PH DB
1 FIRST FLOOR PLAN2 SCREEN WALL - EAST
3 SCREEN WALL - SOUTH
4 SCREEN WALL - WEST
5 SECTION AT TYPICAL SCREEN WALL 6 FIRST FLOOR PLAN - OVERALL
K E Y N O T E S
1 BRICK VENEER TO MATCH EXISTING ADJACENT
CONSTRUCTION
2 CHAIN LINK FENCE / GATE
3 CAST STONE CAP
7 ENLARGED PLAN @ TRANSFORMER SCREEN WALL - Callout 1
8 ENLARGED DEMO PLAN @ TRANFORMER SCREEN WALL
9 TRANSFORMER PAD DETAIL
1. ALL CONCRETE WORK SHALL CONFORM TO THE MOST RECENT
EDITION OF ACI301 & ACI318-05 CODE REQUIREMENTS AND
DETAILING STANDARDS.
2. ALL READY MIXED CONCRETE SHALL CONFORM TO ASTM C94.
3. USE AIR ENTRAINED CONCRETE (6% + OR - 1.5%) FOR ALL
AREAS EXPOSED TO WEATHER, FROST IN SOIL, OR FREEZE
THAW CYCLES.
4. ALL CONCRETE SHALL DEVELOP THE COMPRESSIVE
STRENGTHS AT 28 DAYS (F`c) = 4000 psi UNLESS NOTED
OTHERWISE.
5. DETAILING BENDING AND PLACING OF REINFORCING STEEL
SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE
ACI CODE SP-66.
6. PROCEDURES FOR PLACEMENT OF CONCRETE SHALL BE IN
STRICT CONFORMANCE WITH ACI 304 "RECOMMENDED
PRACTICE FOR MEASURING, MIXING, TRANSPORTING, AND
PLACING CONCRETE".
7. REINFORCING STEEL: fy = 60,000 PSI.
G E N E R A L N O T E S
Revisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
ALTERNATE NOTES
03/12/2021
BASE BID:
PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS
DEDUCT ALTERNATES
ALT #1:
DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL
RISER FOR AHU - 3, 5, 6, 7, 9, 12
AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED
WATER PUMP (PANELBOARD HB).
DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7,
9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY FAN & EXHAUST
FAN.
ALT #2:
DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR
AHU - 17, 23, 43.
ALT #3:
DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS
FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).
PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.
ALT #4:
DEDUCT ALL ELECTRICAL WORK FOR AHU - 42 AND DX - 42
(PANELBOARD DP)
A
B
C
D
E
SUBSCRIPT: WP - WEATHERPROOF, GF - GROUND FAULT
CIRCUIT INTERRUPTER
FLUSH FLOOR MOUNTED NEMA 5-20 DUPLEX RECEPTACLE
UNLESS NOTED OTHERWISE
BASED ON MANUFACTURERS RECOMMENDATIONS
NEMA 5-20 DUPLEX RECEPTACLE MOUNTED 18" AFF
UNLESS NOTED OTHERWISE.
JUNCTION BOX
NON-FUSED DISCONNECT SWITCH. SIZE AS SHOWN
FUSED DISCONNECT SWITCH. SIZE FUSES FOR EQUIPMENT
SURFACE MOUNTED PANELBOARD OR AUTOMATIC TRANSFER
SWITCH AS INDICATED.
MOTOR
J
WP/GF
POWER
LIGHTING
FLUSH FLOOR MOUNTED NEMA 5-20 QUAD RECEPTACLE
UNLESS NOTED OTHERWISE
RECESSED MOUNTED PANELBOARD
250 VOLT, 3ø, 30 AMP RECEPTACLE, (L15-30R)
120 VOLT, 1ø, 30 AMP RECEPTACLE, (L5-30R)
A AMPERE
AC ABOVE COUNTER, 42"AFF UNLESS OTHERWISE INDICATED
ADA AMERICANS WITH DISABILITIES ACT
AFF ABOVE FINISHED FLOOR - TO BOTTOM
AL ALUMINUM
1/C ONE CONDUCTOR
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CU COPPER
EF EXHAUST FAN
EMT ELECTRICAL METALLIC TUBING
EWC ELECTRIC WATER COOLER
FACP FIRE ALARM CONTROL PANEL
FM FREQUENCY MODULATION
GF GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
HACR HEATING AIR CONDITIONING REFRIGERATION
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HT HEIGHT
HZ HERTZ
IDS INTRUSION DETECTION SYSTEM
J JUNCTION BOX
KWH KILOWATT HOUR
LED LIGHT EMITTING DIODE
MCB MAIN CIRCUIT BREAKER
MH MOUNTING HEIGHT - TO CENTER
MLO MAIN LUGS ONLY
MTD MOUNTED
NEC NATIONAL ELECTRICAL CODE
NF NON FUSED
NO. NUMBER
OS OCCUPANCY SENSOR
PH PHASE
PIR PASSIVE INFRARED
RGS RIGID GALVANIZED STEEL
SM SINGLE MODE
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
SPD SURGE PROTECTIVE DEVICE
UNO UNLESS NOTED OTHERWISE
V VOLT
VA VOLTAMPERE
VVD VARIABLE VOLUME DAMPER
W WATTS
WP WEATHERPROOF
XFMR TRANSFORMER
ABBREVIATIONS
250 VOLT, 3ø, 50 AMP RECEPTACLE, (L15-50R)
480 VOLT, 3ø, 30 AMP RECEPTACLE, (L16-30R)
250 VOLT, 1ø, 30 AMP RECEPTACLE, (6-30R) a
OS
1' x 4' FIXTURE. UPPERCASE INDICATES TYPE PER THE FIXTURE SCHEDULE. LOWER CASE LETTER "a" INDICATES SWITCH
CONTROLLING FIXTURE. (EX) INDICATES EXISTING LIGHT FIXTURE.
TYPICAL FOR ALL LIGHTING FIXTURES.
OS
LC#
2' x 4' FIXTURE.
WALL MOUNTED FIXTURE.
INDUSTRIAL FIXTURE.
WALL MOUNTED FIXTURE.
EXIT SIGN WITH DIRECTIONAL ARROWS AS INDICATED
RECESSED FIXTURE, DOWNLIGHT
3-WAY, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 42" AFF.
4-WAY, 20 AMP, 125 VOLT TOGGLE SWITCH MOUNTED 42" AFF.
WALL MOUNTED OCCUPANCY SENSOR WITH OVERRIDE SWITCH
CEILING MOUNTED OCCUPANCY SENSOR
20 AMP, 125 VOLT SINGLE-POLE TOGGLE SWITCH
MOUNTED 42" AFF.
a - CONTROLS LIGHTS WITH "a" DESIGNATION
LIGHTING CONTROLLER
D 20A, 125V DIMMER SWITCH MOUNTED 42" AFF
2' x 2' FIXTURE.
A1 a
E EXISTING
COMBINATION STARTER
NEMA 5-20 DUPLEX RECEPTACLE MOUNTED 44" AFF
UNLESS NOTED OTHERWISE.
NEMA 5-20 DOUBLE DUPLEX RECEPTACLE MOUNTED 18" AFF
UNLESS NOTED OTHERWISE.
POWER CONNECTION
FAA FIRE ALARM ANNUNCIATOR
EX EXISTING
G GENERATOR
TRANSFORMER
CURRENT TRANSFORMER
MEDIUM VOLTAGE CIRCUIT BREAKER
CIRCUIT BREAKER
MEDIUM VOLTAGE SWITCH / FUSE
AUTOMATIC TRANSFER SWITCHE N
SURGE PROTECTIVE DEVICE (SPD)
GROUND CONNECTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
2:
:1
PM
E001
LEGEND
03/01/21 JB HTRevisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
G E N E R A L N O T E S
03/12/2021
BASE BID:
PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS
DEDUCT ALTERNATES
ALT #1:
DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).
DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY
FAN & EXHAUST FAN.
ALT #2:
DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.
ALT #3:
DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).
PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.
ALT #4:
DEDUCT ALL ELECTRICAL WORK FOR AHU - 42 AND DX - 42 (PANELBOARD DP)
LINK SEAL
CONDUIT PIPE
WALL SLEEVE
WALL
EXISTING PANEL
EMS-480V
480/277V
EXISTING
SWITCHGEAR
SB-1 480V
E N
200A
200A
260A ATS-9
4P 4W
EF-43 AH-43 S
4#3/0 AWG, #6 GROUND, 2"C.
4#3/0 AWG, #6 GROUND, 2"C.
200A MLO 480V
3PH 4W
PANELBOARD
NEMA 1
FEED THRU LUGS
60A NF DISC.
NEW
BREAKERS
CONNECT GENERATOR START
CONTACTS TO WIRES IN ATS-B
2#12 AWG, 12 GROUND, 3/4" C.
EEQC
60A NF DISC.
200A MLO 480V
3PH 4W
PANELBOARD
NEMA 3R
EEQD4#3/0 AWG, #6 GROUND, 2"C.
SPD
400A 225A 225A
G
800A (EXISTING AND REUSED)
PANEL EDP-480V
480/277V
600A
N E
600A ATS-10
4P 4W
600A
EEQE
600KW
480/277V
1200A
ATS-A ATS-CATS-B
(2 SETS) 4#350 KCMIL, #1 GROUND, 3"C.
(2 SETS) 4#350 KCMIL,
#1 GROUND, 3"C.
SUB-BASEMENT
SUB-BASEMENT
SUB-BASEMENT
SUB-BASEMENT
SPS EXTERIOR
GENERATOR ROOM
NEW
CONNECT GENERATOR START
CONTACTS TO WIRES IN ATS-B
2#12 AWG, 12 GROUND, 3/4" C.
600A MLO 480V
3PH 4W
PANELBOARD
NEMA 1
SPD
(3 SETS) 4#600 KCMIL, #3/0 GROUND, 4"C.NEW PANEL
ATL #4
ATL #2
ATL #1
17,605 A
25,258 A
LENGTH AS REQUIRED
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL
LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A
CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES
FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
LOCKING SQUARE
WASHER & LOCKNUT
9.52mm (3/8") MIN
GALVANIZED THREADED
ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
4-WAY DUCT LINE2-WAY DUCT LINE
GENERAL NOTES:
1.
2.
3.
4.
5.
CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS
WHEN CROSSING OR PLACED IN
ROADWAYS.
MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR
AS OTHERWISE SPECIFIED IN SECTION 26 05 41.
PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND
TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.
INNERDUCT QUANTITY AND SIZE AS INDICATED ON
PLANS.
(3")
(3") 76mm
(3 m m (3 m m
76mm
(3") 76mm
(3 m m
(3 m m (3 m m
(3")
(3") 76mm
(3") 76mm76mm
(T
YP
1 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
2:
:1
PM
E500
SCHEDULES, DETAILS AND
SINGLE-LINE DIAGRAM
03/01/21 JB HT
LIGHTING FIXTURE SCHEDULE
IMAGE MARK Description
MOUNTING
LOAD
(VA)
LUMINOUS
FLUX
COLOR
TEMPERATURE CRI
S-SURFACE
R-RECESSED
SM-STEM MTD
WM-WALL MTD
C-CHAIN MTD
UC-UNDER CAB
CS-CEIL SURFACE
W1 SURFACE MOUNTED LED WALL LUMINAIRE WITH SWITCH. WEATHERPROOF HOUSING. 120V.
DARK BRONZE.
S 12 3000 lm 4000 K 70
4 LINK SEAL DETAIL
3 EMERGENCY SINGLE-LINE DIAGRAM
5 CONDUIT TRAPEZE MOUNTING DETAIL
1 DUCT BANK DETAILS2 EXISTING PANEL EDP-480V
Revisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
G E N E R A L N O T E S
BASE BID:
PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS
DEDUCT ALTERNATES
ALT #1:
DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).
DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY
FAN & EXHAUST FAN.
ALT #2:
DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.
ALT #3:
DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).
PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.
ALT #4:
DEDUCT ALL ELECTRICAL WORK FOR AHU - 42 AND DX - 42 (PANELBOARD DP)
K E Y N O T E S
1 TRANSFER SWITCHES SHALL BE ASCO 4000 SERIES 4-POLE 4-WIRE.
NON-OVERLAPPING NEUTRALS. NO BYPASS ISOLATION. WITHSTAND
AND CLOSE RATING 42KA AT 480V. RATING FOR ANY BREAKER. SEE
SPECS FOR FURTHER DETAILS.
2 PROVIDE FEED-THRU LUGS IN PANEL EEQC. FEED WIRE FOR PANEL
EEQD TO BE EXTENDED FROM THESE LUGS.
03/12/2021
BREAKER #5
480/277V E
1600A
SB-1
E
T1C 13,800V - 480Y/277V 1150 kVA
PAD-MOUNT TRANSFORMER
6.1 %Z MINIMUM IMPEDANCE
PRIMARY TAP SELECTOR
SWITCH
SEED OIL FILLED
T1C SWITCH IN
TRANSFORMER
E SB-1
1600A E
DEMO
OLD TIC
DEMO
DEMO
E
ABANDON
IN PLACE
13,800V
HILLCREST BUSE
GROUND RELAY
OVERCURRENT RELAY
HILLSCREST-MAIN
TAP FEEDER IN MANHOLE
PROVIDE LOAD BREAK ELBOWS.
T1C SWITCH
BLDG #1
UNIT SUB
SB-1
DEMO
TO
XFMR T4
TO
XFMR T1
TAP
MAIN SUBSTATION SWITCHGEAR
BLDG 15
HILLCREST UTILITY FEEDER
13,800V
C O
GROUND RELAY
OVERCURRENT RELAY
3#2 MV-105 15kV CABLE, #2 600V, CU GROUND
CONNECT TO SB-1 MAIN BREAKER
EX EX
REMOVE OLD FEEDER
100E BAY-O-NET FUSE
LIGHTNING ARRESTORS
CURRENT LIMITING FUSE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
8:
:1
AM
E501
PARTIAL MEDIUM VOLTAGE
SINGLE-LINE DIAGRAM
03/01/21 JB HTRevisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
1 PARTIAL MEDIUM VOLTAGE SINGLE-LINE DIAGRAM
G E N E R A L N O T E S
03/12/2021
BASE BID:
PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS
DEDUCT ALTERNATES
ALT #1:
DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).
DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY
FAN & EXHAUST FAN.
ALT #2:
DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.
ALT #3:
DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).
PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
2:
:2
PM
E600
PANEL SCHEDULES
03/01/21 JB HT
FEED THRU LUGS
Notes:
Total Est. Demand Current: 43 A Total Conn. Current: 43 A
Total Est. Demand: 35825 VA Total Conn. Load: 35825 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 43 A 43 A 43 A Total Load: 11942 VA 11942 VA 11942 VA
41 0 kVA 0 kVA 1 20 A SPARE 42 39 0 kVA 0 kVA 1 20 A SPARE 40
SPD 30 A 3
0 kVA 0 kVA 1 20 A SPARE 38
35 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 36 33 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 34 31 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 32 29 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 30 27 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 28 25 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 26 23 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 24 21 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 22 19 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 20 17 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 18 15 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 16 13 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 14 11 3 kVA 0 kVA 12 9 3 kVA 0 kVA 10
7 CHILLED WATER PUMPS-BSMNT THRU 2ND
FLR 30 A 3
3 kVA 0 kVA
3 20 A PUMPS AH-17, AH-23, AH-43
5 7 kVA 2 kVA 6 3 7 kVA 2 kVA 4
ELEC RISER AHU 3,5,6,7,9,12,13 100 A 3
7 kVA 2 kVA
3 80 A CHILLED WATER PUMPS-3RD THRU 8TH FLR
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 200 A
Supply From: Phases: 3 Mains Type: MLO Location: Volts: 480/277 Wye A.I.C. Rating: 35,000 A
Branch Panel: EEQC
Notes:
Total Est. Demand Current: 541 A Total Conn. Current: 541 A
Total Est. Demand: 449528 VA Spare 434328 VA 100.00% 434328 VA Total Conn. Load: 449528 VA Motor 15200 VA 100.00% 15200 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
I-LINE HCM PANEL 27" MOUNTING SPACE.
Legend:
Total Amps: 541 A 541 A 541 A Total Load: 149843 VA 149843 VA 149843 VA
41 SPACE -- -- 0.0 kVA 0.0 kVA 42 39 SPACE -- -- 0.0 kVA 0.0 kVA 40 37 SPACE -- -- 0.0 kVA 0.0 kVA
3 30 A SPD
35 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 36 33 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 34 31 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 32 29 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 30 27 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 28 25 SPACE -- -- 0.0 kVA 0.0 kVA -- -- SPACE 26 23 SPACE -- -- 0.0 kVA 39.6... 24 21 SPACE -- -- 0.0 kVA 39.6... 22 19 SPACE -- -- 0.0 kVA 39.6...
3 70 A PUMP P4 - AHU-6A, 7A, 8A, 9A
17 5.1 kVA 8.4 kVA 18 15 5.1 kVA 8.4 kVA 16
EF-8 40 A 3
5.1 kVA 8.4 kVA
3 20 A PUMP P2 - AHU 1A,4A, 5A
11 33.3... 39.6... 12 9 33.3... 39.6... 10
DX-42 150 A 3
33.3... 39.6...
3 70 A PUMP P3 - AHU 6A, 7A, 2A, 9A
5 15.5... 8.4 kVA 6 3 15.5... 8.4 kVA 4
AHU-42 70 A 3
15.5... 8.4 kVA
3 20 A PUMP P1- AHU-1A, 4A, 5A
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: 3R Mounting: Surface Wires: 4
Supply From: Phases: 3 Mains: 600 A MLO Location: Volts: 480/277 Wye A.I.C. Rating: 22,000 A
Branch Panel: EEQE
Notes:
Total Est. Demand Current: 0 A Total Conn. Current: 0 A
Total Est. Demand: 0 VA Total Conn. Load: 0 VA
Other 0 VA 0.00% 0 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A Total Load: 0 VA 0 VA 0 VA
41 0 kVA 0 kVA -- -- SPACE 42 39 0 kVA 0 kVA -- -- SPACE 40
MAIN FOR PNL 9-AE(EXISTING) 20 A 3
0 kVA 0 kVA 1 20 A A-950 RCPT(EXISTING) 38
35 A950(EXISTING) 20 A 1 0 kVA 0 kVA -- -- SPACE 36 33 SPACE -- -- 0 kVA 0 kVA 34 31 A914 RCPT/ELEV/LTNG(EXISTING) 20 A 1 0 kVA 0 kVA 32 29 RCPT UNDER PANEL(EXISTING) 20 A 1 0 kVA 0 kVA
3 20 A MAIN FOR PNL 9-AE(EXISTING)
27 A-935 RCPT/LTNG(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A MED AIR VAC SYS(EXISTING) 28 25 A-935 ELEV LTNG(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A RM B906 LTNG(EXISTING) 26 23 RCPT A-901(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A SPARE 24 21 RCPT IN DATA CLOSET A-933(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A RADIO EQPMT 10TH FLR/MED AIR(EXISTING) 22 19 SERV ELEV LOBBY RCPT(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A SPARE 20 17 SPACE -- -- 0 kVA 0 kVA 1 20 A RM A-931 LTNG RCPT(EXISTING) 18 15 SPARE 20 A 1 0 kVA 0 kVA 1 20 A RM A-905 RCPT.(EXISTING) 16 13 RCPT B-909(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A RM A-905 RCPT.(EXISTING) 14 11 FA PANEL ON 9TH FLR(EXISTING) 20 A 1 0 kVA 0 kVA 1 20 A RM A-905 RCPT.(EXISTING) 12 9 CKT. FOR PANEL A AND PANEL B 20 A 1 0 kVA 0 kVA 1 20 A RM A-922 DATA,RCPT/LTS(EXISTING) 10 7 10TH FLR TV AMP/LTS/MED GAS ALARM(EX)... 20 A 1 0 kVA 0 kVA 8 5 RCPT IN B-902,903,906(EXISTING) 20 A 1 0 kVA 0 kVA 2 20 A RM A-915 FREEZER(EXISTING) 6 3 EMS 208V 10TH FLOOR(EXISTING) 20 A 1 0 kVA 0 kVA 4 1 EMS 208V 10TH FLOOR(EXISTING) 20 A 1 0 kVA 0 kVA 2 20 A RM A-905 CENTRIFUGES(EXISTING) 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: Phases: 3 Mains Type: MCB Location: Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: 9AE
Notes:
Total Est. Demand Current: 0 A Total Conn. Current: 0 A
Total Est. Demand: 50 VA Total Conn. Load: 50 VA
Other 50 VA 100.00% 50 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 0 A 0 A 0 A Total Load: 0 VA 0 VA 50 VA
41 0 kVA 0 kVA 1 20 A SPARE 42 39 0 kVA 0 kVA 1 20 A SPARE 40
ACCU41B(EXISTING) 20 A 3
0 kVA 0 kVA 1 20 A SPARE 38
35 0 kVA 0 kVA 1 20 A SPARE 36 33 0 kVA 0 kVA 1 20 A SPARE 34
ACCU41A(EXISTING) 20 A 3
0 kVA 0 kVA 32
29 SPARE 20 A 1 0 kVA 0 kVA 2 20 A AC-341(EXISTING) 30 27 SPARE 20 A 1 0 kVA 0 kVA 28 25 SPARE 20 A 1 0 kVA 0 kVA 2 20 A AC-231(EXISTING) 26 23 SPARE 20 A 1 0 kVA 0 kVA 24 21 SPARE 20 A 1 0 kVA 0 kVA 2 20 A AC-126(EXISTING) 22 19 SPARE 20 A 1 0 kVA 0 kVA 20 17 SPARE 20 A 1 0 kVA 0 kVA 2 20 A AC-013(EXISTING) 18 15 SPARE 20 A 1 0 kVA 0 kVA 1 20 A SPARE 16 13 SPARE 20 A 1 0 kVA 0 kVA 1 20 A CONTROL PANEL FOR AHU-7,6 14 11 JOHNSON CONTROL A-343, A-823 20 A 1 0 kVA 0 kVA 1 20 A CONTROL PANEL AHU-13, 12,9,8 12 9 TEMP. CONTROL PANEL RM SB-4 20 A 1 0 kVA 0 kVA 1 20 A GF1WP(EXISTING) 10 7 0 kVA 0 kVA 8 5 A-231(EXISTING) 30 A 2 0 kVA 0 kVA 2 30 A A-341(EXISTING) 6 3 0 kVA 0 kVA 4 1 A-013 (EXISTING) 30 A 2 0 kVA 0 kVA 2 30 A A-126(EXISTING) 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type: MCB Location: Volts: 120/208 Wye A.I.C. Rating:
Branch Panel: EEQ1SB
SUB-BASEMENT SWITCHBOARD ROOM
ATS-9 ATS-10
ELECTRICAL EQUIPMENT ROOM B-013
SUB-BASEMENT SWITCHBOARD ROOM SB-2
EEQB PANEL 8AE LIFE SAFETY
NINTH FLOOR, RM A-932
Revisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
G E N E R A L N O T E S
NEW
ALT #1
ALT #1
ALT #1
ALT #2
NEW
ALT #4: DELETE PANEL
ALT #4
ALT #4
ALT #3
ALT #3
ALT #2: DELETE PANEL
EXISTING
ALT #1 ALT #1
BREAKERS BECOME
SPARES
ALT #1: REMOVE CIRCUITS FOR 9TH FLOOR CONTROL PANEL CIRCUIT
EXISTING
Notes: SQUARE D, I-LINE PANEL
Total Load: 0.00 kVA 0.00 kVA 0.00 kVA 17 0 kVA 0 kVA 18 15 0 kVA 0 kVA 16
SPACE 0 A 3
0 kVA 0 kVA
3 0 A SPACE
11 0 kVA 0 kVA 12 9 0 kVA 0 kVA 10
SPACE 0 A 3
0 kVA 0 kVA
3 0 A SPACE
5 0 kVA 0 kVA 6 3 0 kVA 0 kVA 4
EMS-480 800 A 3
0 kVA 0 kVA
3 600 A ATS-10
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
0 kVA Total Connected Load
Voltage: 480/277 Wye-3PH-4W Mains Rating: 1200 A Supply From: NEMA Type: Type 1 Mains Type: MLO
Location: Mounting: Surface SC Rating: 35,000 A Panel: EDP-480
NEW
REUSE BREAKER
03/12/2021
ALT #3 ALT #3
ALT #3
BASE BID:
PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS
DEDUCT ALTERNATES
ALT #1:
DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).
DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY
FAN & EXHAUST FAN.
ALT #2:
DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.
ALT #3:
DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).
PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.
DUCTILE IRON
UP
UP
UPF.A.C.
B-
BASEMENT
SUB-
M-
M-
STORAGE
B-
LINEN
SOILED
M-
STORAGE
MECH RM/
STAIRWELL
#8
S-5
S-5
P-4
P-3
P-2
P-1
A- #6
STAIRWELL
F.A.C.
A-
BASEMENT
SUB-
B-
ROOM
LOCKER
B-
BASEMENT
SUB-
B- #3
STAIRWELL
B-
ROOM
EQUIPMENT
TELEPHONE
EQUIPMENT
ROOM
B-
P-7 P-8 P-9
F.A.C.
LIFT
F.A.C.
B-
EQUIPMENT
ELECTRICAL
B-
RESTROOM
B-
BASEMENT
SUB-
B- #5
STAIRWELL
STAIRWELL #1
SUB-BAS
A-
STAIRWELL #2
A-
SUB-BASEMENT
SB-6
#7
STAIRWELL
OFFICE
B-
B-
ROOM
EQUIPMENT
DOCK
SUB-BASEMENT
SB-4
DUCTILE IRON
UP
UP
UPF.A.C.
B-
BASEMENT
SUB-
M-
M-
STORAGE
B-
LINEN
SOILED
M-
STORAGE
MECH RM/
STAIRWELL
#8
S-5
S-5
P-4
P-3
P-2
P-1
A- #6
STAIRWELL
F.A.C.
A-
BASEMENT
SUB-
B-
ROOM
LOCKER
B-
BASEMENT
SUB-
B- #3
STAIRWELL
B-
ROOM
EQUIPMENT
TELEPHONE
EQUIPMENT
ROOM
B-
P-7 P-8 P-9
F.A.C.
LIFT
F.A.C.
B-
EQUIPMENT
ELECTRICAL
B-
RESTROOM
B-
BASEMENT
SUB-
B- #5
STAIRWELL
STAIRWELL #1
SUB-BAS
A-
STAIRWELL #2
A-
SUB-BASEMENT
SB-6
#7
STAIRWELL
OFFICE
B-
B-
ROOM
EQUIPMENT
DOCK
SUB-BASEMENT
SB-4
EP0001
EP0001
EP0001
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
2:
:3
PM
EP0000
OVERALL SUB-BASEMENT PLAN
03/01/21 JB HT
1" = 20'-0"1 OVERALL SUB-BASEMENT PLAN
Revisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
G E N E R A L N O T E S
03/12/2021
BASE BID:
PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS
DEDUCT ALTERNATES
ALT #1:
DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).
DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY
FAN & EXHAUST FAN.
ALT #2:
DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.
ALT #3:
DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).
PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.
UP STAIRWELL #1
SUB-BAS
A-
STAIRWELL #2
A-
STAIRWELL #1
SUB-BAS
A-
STAIRWELL #2
A-
DUCTILE IRON
P-3
P-2
P-1
SUB-BASEMENT
SB-4
ATS-1 PANEL EEQ PANEL EEQA PANEL ELP
ATS-4
PANEL EEQB
ATS-7
N1TIP-1
N1TIP-2
EEQ1SB
ATS-3
ATS-2
EMS
PANEL NMS
STREET
LIGHTS PANEL
ST LIGHTS
CONTROL
PANEL ELS
208/120V SB-2
480/277V SB-1
EP 480/1
EP 480
ATS-A
EMS 480V
ATS-B ATS-C
N1TP2
EEQ1SB2
EEQC
ATS-9
SB-1
TAPPED
BUS
EP0001
EP0001
FIRE
ALARM
PANEL
SECTION 3 SECTION 1
OLD T1C
ALT #2
ALT #2
ALT #2
ALT. #1
NEW XFMR T1C
SB-1
SB-2
DRILL WALL INTO SUB-
BASEMENT FOR CONDUIT.
PROVIDE LINK SEALS IN
WALL PENETRATIONS.
PROVIDE UNISTRUT
RACKS TO SUPPORT
CONDUIT FROM CEILING
WALKABLE CRAWL SPACE
JUNCTION BOX
CHWP-1
HRCP-1
TEMP CONTROL
PANEL
EEQ1SB-9
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
8:
:2
AM
EP0001
SUB-BASEMENT ELECTRICAL
PLAN
03/01/21 JB HT
1/4" = 1'-0"3 SUB-BASEMENT-SWITCHBOARD ROOM-EAST
K E Y N O T E S
1 PROVIDE NEW 200A CIRCUIT BREAKERS IN PANELS EMS-480V (SQUARE D,
I-LINE) CKT #17, 19, 21 & SB-1 (EATON) CKT. #13. RATED 65KA.
2 EMPTY AND DISPOSE SILICON OIL FROM TRANSFORMER. THIS OIL MAY
CONTAIN PCBS. ABANDON TRANSFORMER IN PLACE. DISCONNECT AND
REMOVE WIRING TO THE MAIN CIRCUIT BREAKER IN SB-1.
3 USE 1600A BKR IN SB-1 TO CONNECT TO NEW TRANSFORMER T1C,
PROVIDE NECESSARY CONDUITS AND FITTINGS TO CONNECT CONDUIT
TO MAIN CABINET. PRODUCE PROPER BONDING, BONDING BUSHINGS,
LUGS, BONDING GROUND WIRE, ETC.
4 NEW (4) SETS (4) 600KCMIL, 4"C.
5 PROVIDE UNISTRUT TO MOUNT ATS-9 AND PANEL EEQC. FOLLOW
INSTALLATION AS SHOWN IN PHOTO 4/EP0001 FOR PANELS.
6 REMOVE MEDIUM VOLTAGE SWITCH. DISCONNECT 15KV CABLE AND
REMOVE BACK TO MANHOLE AND TO TRANSFORMER.
7 LOCATION OF NEW ATS-9. PROVIDE UNISTRUT SUPPORT FRAME.
8 RELOCATE 20A/3P CIRCUIT FOR PUMPS AH-17, 23, & 43 TO PANEL EEQC.
3#12 AWG, 12 GROUND, 3/4"C.
9 PROVIDE BREAKERS FOR HVAC CONTROL PANELS. (ALT #1)
10 LABEL TRANSFORMER "ABANDONED - LOCATION OF NEW TRANSFORMER
T1C OUTSIDE SOUTH OF PATIENT ADVOCATE SUITE.
11 DISCONNECT EXISTING CIRCUIT FOR TEMPERATURE CONTROL PANEL
FOR AHU-43. MARK CIRCUIT AS 'SPARE'. POWER TEMPERATURE
CONTROL PANEL FROM EEQ1SB-9.
1/16" = 1'-0"2 SUB-BASEMENT-CONDUIT ROUTING
1/8" = 1'-0"1 SUB-BASEMENT-MECH EQPMT-WEST
4 SUB-BASEMENT ATS AND PANEL LOCATION5
ABANDONED UNIT SUBSTATION TRANSFORMER AND MEDIUM VOLTAGE
SWITCH
Revisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
G E N E R A L N O T E S
03/12/2021
BASE BID:
PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS
DEDUCT ALTERNATES
ALT #1:
DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).
DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY
FAN & EXHAUST FAN.
ALT #2:
DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.
ALT #3:
DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).
PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.
BVA
ELEVATOR
3/4" MP
3/ 4"
M P
3/ 4"
M P
3/ 4"
M P3/ 4"
M P
3/ 4"
M P
1-1/4" MP
3/4" MP
3/4" MP
COR BA1(CENTER)-1
COR BA2(SOUTH)-1 COR BA1(NORTH)-1
COR BB1(MORGUE)-1
COR BB2(WEST ENTR)-1
COR BD1(PROSTH)-1
C O
R B
A1 (F
IT
N
ES
S)
-1
NINA TURNER
CRAWFORD/LIVERS
ALEXANDER, 2 QA FOLKS
GARY SMITH SMITH/GUDGEON
EAGLE/TACKETT
SHERRELL PAYNE
FERNANDO RIOS
ED GREGORY
CAROLYN LANHAMWALT CARPENTER TERE SCHOEMEHL
ANDERSON/MADDOX/ORR
6 STAFF
TOM WHALEN ET AL
MARYJANE CROWDER
RHONDA SMITH DON PFANNENSTIEL SVC OFFICERS
BROWN/HOLLAND
LARRY MARTIN
JOHN TALLEY
CRUZ/CROUCH
SHELLY HOUSE
TOM HAYDEN
THOMPSON/HEAD/TURPIN
JOHN KOENIG
MARCIA SMITH
SERVICE OFFICERSRITA FLOWERS
MYRA SMITH
SANDY COOPER
NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGNNO
SIGN NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
SIGN
NO #
SIGN
NO #
NO
SIGN
NO
SIGN
NO
SIGN
UP.
SIGN
# NO
SIGN
UP.
SIGN
UP.
SIGN
NO
SIGN
UP.
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
# NO
SIGN
NO
SIGN
NO
SIGN
SIGN
NO #
NO
SIGN
UP.
SIGN
UP.
SIGN # NO
SIGN
UP.
SIGN
UP.
SIGN
# NO
SIGN
NO
SIGN
NO
SIGN
# NO
SIGN
# NO
SIGN
# NO
SIGN
# NO
SIGN
NO
SIGN
NO
SIGN
NO
SIGN
UP DOWN
UP
UP
UP
UP
UP
FIRE
EQUIPMENT
CLOSET
A-021
F.A.C.
A-020 H.A.C.
H.V.A.C.
EQUIPMENT
ROOM
A-005c
A-012
CLOSET
ELECTRIC
A-001
A&MM
A-017a
REPRODUCTION
MAIL ROOM
D-002b
CLOSET
TELE.
D-002a
CLOSET
ELECT.
B-002d
BASEMENT
SUB-
M-001
M-002a
STORAGE
SPD
B-004
DUMBWAITER
MACHINE
ROOM
B-002g
B-002c
ROOM
SEWING
B-002b
STORAGE
EMS
B-002
ROOM
LINEN
A.C.
EQUIPMENT
ROOM
B-002f
B-002e
RESTROOM
B-001a
STORAGE
B-001
OFFICE
B-002a
ROOM
LOCKER
B-003
LINEN
SOILED
B-008
CLOSET
ELECTRIC
M-002
STORAGE
MECH RM/
B-005
SPD
M-003
ROOM
MECHANICAL
D-004
TREATMENT CENTER
CHIEF, PROSTHETIC
D-001
STORAGE
ORTHO
STAIRWELL
#8
D-002
MAIL ROOM
BREAK/
D-005a
OFFICE
LAB
D-010
CLASSROOM
D-005 P & O
D-010c
VESTIBULE
D-010d
RESTROOM
D-010b #9
STAIRWELL
A-018
ROOM
DECONTAMINATION
A-031d
STORAGE
A-033b
CLOSET
NARCOTICS
H.V.A.C.
EQUIPMENT
ROOM
A-033a
INCOMING
INSPECTION
ROOM
A-027
A-033h
CLOSET
ELECTRIC
A-033e
AREA
WORK
A-034
ROOM
BREAK
S-5
S-5
P-4
A-022
LOBBY
ELEVATOR
A-022a
CLOSET
ELECTRIC
A-033f
OFFICE
A-033g
OFFICE
A-024
ROOM
EQUIPMENT
A-025
STORAGE
SAFETY
P-3
P-2
P-1
A-033
PHARMACY
IN-PATIENT
A-032
LINEN
SOILED
A-026
STORAGE
A-028
BREAK ROOM
PHARMACY
A-031e
STORAGE
A-029 #6
STAIRWELL
F.A.C.
A-029a
BASEMENT
SUB-
A-030
ROOM
EQUIP.
A-031c
A-031
VENDING STORAGE
CANTEEN
A-031b
STORAGE
A-031a
STORAGE
B-016c1
ROOM
LOCKER
B-016c
LOUNGE
B-018
ADMIN
A&MM
B-019a
CLOSET
TELEPHONE
B-006a
BASEMENT
SUB-
B-039a
OFFICE
SPD
A-018a
STORAGE
B-042a
STORAGE
B-041
SHOWER
WOMEN'S
B-009
STORAGE
ENG
B-042
SHOWER
MEN'S
B-007
CLOSET
ELECTRIC
B-006 #3
STAIRWELL
B-010
ROOM
EQUIPMENT
BREAK
ROOM
B-040
HAZARDOUS
MATERIAL
STORAGE
B-039b
INSTRUMENT
PREPARATION
ROOM
B-039
TELEPHONE
EQUIPMENT
ROOM
B-019
B-005b
SPD
B-005c
OFFICE
P-7 P-8 P-9
F.A.C.
B-011b
STORAGE
ENGINEERING
A&MM
STORAGE
B-021
B-038
HOLDING
LIFT
B-037
MORGUE
B-020
RECOVERY
SILVER
B-036
ROOM
SPECIMEN
F.A.C.
B-022
SUPERVISER
MAINT. OPERATION
EMS
EQUIPMENT
STORAGE
B-017
B-015
STORAGE
ENGINEERING
B-013
EQUIPMENT
ELECTRICAL
B-016
SHOP/STORAGE
ENGINEERING
M-004
ROOM
GENERATOR
B-034
SECRETARY
EMS
B-036b
STORAGE
B-035
OFFICE
CHIEF, EMS
B-036a
RESTROOM
EMS
SIGNAGE
ROOM
B-023
EMS
OFFICE
B-024
B-025a
BASEMENT
SUB-
INTERIOR
DESIGNER'S
OFFICE
B-034a
EMS
SUPERVISOR'S
OFFICE
B-032
B-031
RESTROOM
WOMEN'S
B-033
ROOM
MULTIPURPOSE
MEN'S
LOCKER
ROOM
B-026
B-026a
RESTROOM
B-025 #5
STAIRWELL
B-026b
SHOWERS
B-027
ENGINEERING
BIOMEDICAL
WOMEN'S
LOCKER
ROOM
B-030
B-030a
SHOWERS
B-029
ENGINEERING
BIOMEDICAL
B-027a
STORAGE
BIOMED
P.M. & R.
FITNESS
ROOM
B-028
PATIENT
SERVICES
SECTION
D-003
M-005
ROOM
GENERATOR
B-016a
CLOSET
COMMUNICATIONS
PHARMACY DRUG
VAULT
CLOSET
ENG
A-017d
B-002a1
ARMORY
D-010a
STO…