14.02_E501 - PARTIAL MEDIUM VOLTAGE SINGLE-LINE DIAGRAM.pdf
PDF 230 KB Posted
- Attached to
- Upgrade 480V Electrical System Federal contract opportunity
- Solicitation number
- 36C24921R0084
About this file
This document package includes drawings and specifications for an electrical system upgrade project. The contractor will be required to install a new 1150 KVA outdoor transformer to feed the 480V switchgear in Sub-basement 1 of the facility. Additionally, the contractor will correct wiring deficiencies for CAT Scan rooms and move the electrical feeds for several air handlers and associated chilled water pumps and controls to emergency power circuits. The project drawings provide details on the new transformer installation, medium voltage single line diagram, and floor plans to guide the electrical system upgrade work. The related pre-solicitation lists the Department of Veterans Affairs as the contracting agency and provides additional context that the intent is to address deficiencies and improve the 480V electrical system at the Louisville, KY location.
View the file
Other files for this federal contract opportunity
Show all 50
Upgrade 480V Electrical System has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BREAKER #5
480/277V E
1600A
SB-1
E
T1C 13,800V - 480Y/277V 1150 kVA
PAD-MOUNT TRANSFORMER
6.1 %Z MINIMUM IMPEDANCE
PRIMARY TAP SELECTOR
SWITCH
SEED OIL FILLED
T1C SWITCH IN
TRANSFORMER
E SB-1
1600A E
DEMO
OLD TIC
DEMO
DEMO
E
ABANDON
IN PLACE
13,800V
HILLCREST BUSE
GROUND RELAY
OVERCURRENT RELAY
HILLSCREST-MAIN
TAP FEEDER IN MANHOLE
PROVIDE LOAD BREAK ELBOWS.
T1C SWITCH
BLDG #1
UNIT SUB
SB-1
DEMO
TO
XFMR T4
TO
XFMR T1
TAP
MAIN SUBSTATION SWITCHGEAR
BLDG 15
HILLCREST UTILITY FEEDER
13,800V
C O
GROUND RELAY
OVERCURRENT RELAY
3#2 MV-105 15kV CABLE, #2 600V, CU GROUND
CONNECT TO SB-1 MAIN BREAKER
EX EX
REMOVE OLD FEEDER
100E BAY-O-NET FUSE
LIGHTNING ARRESTORS
CURRENT LIMITING FUSE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
8:
:1
AM
E501
PARTIAL MEDIUM VOLTAGE
SINGLE-LINE DIAGRAM
03/01/21 JB HTRevisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
1 PARTIAL MEDIUM VOLTAGE SINGLE-LINE DIAGRAM
G E N E R A L N O T E S
03/12/2021
BASE BID:
PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS
DEDUCT ALTERNATES
ALT #1:
DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).
DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY
FAN & EXHAUST FAN.
ALT #2:
DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.
ALT #3:
DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).
PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.
ALT #4:
DEDUCT ALL ELECTRICAL WORK FOR AHU - 42 AND DX - 42 (PANELBOARD DP)