14.01_E500 - SCHEDULES, DETAILS AND SINGLE-LINE DIAGRAM.pdf
PDF 679 KB Posted
- Attached to
- Upgrade 480V Electrical System Federal contract opportunity
- Solicitation number
- 36C24921R0084
About this file
This document includes electrical drawings and schedules for the upgrade of a 480V electrical system at a Department of Veterans Affairs medical center. The project involves installing a new 1150 KVA outdoor transformer to feed 480V switchgear in the sub-basement, correcting wiring deficiencies for CAT scan rooms, and moving electrical feeds for several air handlers, chilled water pumps and controls to emergency power circuits. Key equipment to be provided includes the outdoor transformer, switchgear, panelboards, transfer switches, and wiring as depicted on the drawings. Deductive alternates are listed to remove specific aspects from the scope related to electrical work for various air handlers and pumps. The solicitation number and opportunity type are provided for the related upgrade project at the Veterans Affairs Veterans Health Administration facility.
View the file
Other files for this federal contract opportunity
Show all 50
Upgrade 480V Electrical System has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LINK SEAL
CONDUIT PIPE
WALL SLEEVE
WALL
EXISTING PANEL
EMS-480V
480/277V
EXISTING
SWITCHGEAR
SB-1 480V
E N
200A
200A
260A ATS-9
4P 4W
EF-43 AH-43 S
4#3/0 AWG, #6 GROUND, 2"C.
4#3/0 AWG, #6 GROUND, 2"C.
200A MLO 480V
3PH 4W
PANELBOARD
NEMA 1
FEED THRU LUGS
60A NF DISC.
NEW
BREAKERS
CONNECT GENERATOR START
CONTACTS TO WIRES IN ATS-B
2#12 AWG, 12 GROUND, 3/4" C.
EEQC
60A NF DISC.
200A MLO 480V
3PH 4W
PANELBOARD
NEMA 3R
EEQD4#3/0 AWG, #6 GROUND, 2"C.
SPD
400A 225A 225A
G
800A (EXISTING AND REUSED)
PANEL EDP-480V
480/277V
600A
N E
600A ATS-10
4P 4W
600A
EEQE
600KW
480/277V
1200A
ATS-A ATS-CATS-B
(2 SETS) 4#350 KCMIL, #1 GROUND, 3"C.
(2 SETS) 4#350 KCMIL,
#1 GROUND, 3"C.
SUB-BASEMENT
SUB-BASEMENT
SUB-BASEMENT
SUB-BASEMENT
SPS EXTERIOR
GENERATOR ROOM
NEW
CONNECT GENERATOR START
CONTACTS TO WIRES IN ATS-B
2#12 AWG, 12 GROUND, 3/4" C.
600A MLO 480V
3PH 4W
PANELBOARD
NEMA 1
SPD
(3 SETS) 4#600 KCMIL, #3/0 GROUND, 4"C.NEW PANEL
ATL #4
ATL #2
ATL #1
17,605 A
25,258 A
LENGTH AS REQUIRED
CONDUIT CLAMP.
SIZE AS REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS FOR
QUANTITY & SIZE OF
CONDUITS
GENERAL NOTES:
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING CHANNEL
LONGER THAN 915mm (36") SHALL BE INSTALLED WITH A
CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAY AND BOXES
FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
LOCKING SQUARE
WASHER & LOCKNUT
9.52mm (3/8") MIN
GALVANIZED THREADED
ROD, TYP.
WASHER &
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
4-WAY DUCT LINE2-WAY DUCT LINE
GENERAL NOTES:
1.
2.
3.
4.
5.
CONCRETE SHALL BE 2000 P.S.I. @ 28 DAYS, OR AS SPECIFIED.
PROVIDE #4 REINFORCING RODS ON TOP AND BOTTOM OF DUCTS
WHEN CROSSING OR PLACED IN
ROADWAYS.
MINIMUM COVER TO TOP OF ENVELOPE SHALL BE 610mm (24") OR
AS OTHERWISE SPECIFIED IN SECTION 26 05 41.
PROVIDE MINIMUM 152mm (6") SPACE BETWEEN POWER AND
TELECOMMUNICATION DUCTS. INCREASE SIZE AS REQUIRED.
INNERDUCT QUANTITY AND SIZE AS INDICATED ON
PLANS.
(3")
(3") 76mm
(3 m m (3 m m
76mm
(3") 76mm
(3 m m
(3 m m (3 m m
(3")
(3") 76mm
(3") 76mm76mm
(T
YP
1 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
2:
:1
PM
E500
SCHEDULES, DETAILS AND
SINGLE-LINE DIAGRAM
03/01/21 JB HT
LIGHTING FIXTURE SCHEDULE
IMAGE MARK Description
MOUNTING
LOAD
(VA)
LUMINOUS
FLUX
COLOR
TEMPERATURE CRI
S-SURFACE
R-RECESSED
SM-STEM MTD
WM-WALL MTD
C-CHAIN MTD
UC-UNDER CAB
CS-CEIL SURFACE
W1 SURFACE MOUNTED LED WALL LUMINAIRE WITH SWITCH. WEATHERPROOF HOUSING. 120V.
DARK BRONZE.
S 12 3000 lm 4000 K 70
4 LINK SEAL DETAIL
3 EMERGENCY SINGLE-LINE DIAGRAM
5 CONDUIT TRAPEZE MOUNTING DETAIL
1 DUCT BANK DETAILS2 EXISTING PANEL EDP-480V
Revisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
G E N E R A L N O T E S
BASE BID:
PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS
DEDUCT ALTERNATES
ALT #1:
DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).
DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY
FAN & EXHAUST FAN.
ALT #2:
DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.
ALT #3:
DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).
PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.
ALT #4:
DEDUCT ALL ELECTRICAL WORK FOR AHU - 42 AND DX - 42 (PANELBOARD DP)
K E Y N O T E S
1 TRANSFER SWITCHES SHALL BE ASCO 4000 SERIES 4-POLE 4-WIRE.
NON-OVERLAPPING NEUTRALS. NO BYPASS ISOLATION. WITHSTAND
AND CLOSE RATING 42KA AT 480V. RATING FOR ANY BREAKER. SEE
SPECS FOR FURTHER DETAILS.
2 PROVIDE FEED-THRU LUGS IN PANEL EEQC. FEED WIRE FOR PANEL
EEQD TO BE EXTENDED FROM THESE LUGS.
03/12/2021
| Sheets |
| AE101 - SCREEN WALL DETAILS |
| E001 - LEGEND |
| E500 - SCHEDULES, DETAILS AND SINGLE-LINE DIAGRAM |
| E501 - PARTIAL MEDIUM VOLTAGE SINGLE-LINE DIAGRAM |
| E600 - PANEL SCHEDULES |
| EP000 - OVERALL BASEMENT ELECTRICAL PLAN |
| EP0000 - OVERALL SUB-BASEMENT PLAN |
| EP0001 - SUB-BASEMENT ELECTRICAL PLAN |
| EP001A - BASEMENT ELECTRICAL PLAN-A |
| EP001B - BASEMENT ELECTRICAL PLAN-B |
| EP100 - OVERALL FIRST FLOOR PLAN |
| EP101 - FIRST FLOOR ELECTRICAL PLAN |
| EP200 - OVERALL SECOND FLOOR PLAN |
| EP201 - SECOND FLOOR ELECTRICAL PLAN |
| EP300 - OVERALL THIRD FLOOR PLAN |
| EP400 - OVERALL FOURTH FLOOR PLAN |
| EP500 - OVERALL FIFTH FLOOR PLAN |
| EP600 - OVERALL SIXTH FLOOR PLAN |
| EP700 - OVERALL SEVENTH FLOOR PLAN |
| EP800 - OVERALL EIGHT FLOOR PLAN |
| EP900 - OVERALL NINTH FLOOR PLAN |
| ES100 - ELECTRICAL SITE PLAN |
| GI000 - COVER SHEET AND SHEET INDEX |
File details come from the government source that posted it. Updated .