14.05_EP0001 - SUB-BASEMENT ELECTRICAL PLAN.pdf
PDF 1 MB Posted
- Attached to
- Upgrade 480V Electrical System Federal contract opportunity
- Solicitation number
- 36C24921R0084
About this file
This document includes plans and specifications for an electrical upgrade project at a Department of Veterans Affairs medical facility. The project involves installing a new 1150 KVA outdoor transformer to feed upgraded 480V switchgear in the sub-basement, correcting wiring deficiencies for CAT scan rooms, and moving electrical feeds for several air handlers and associated chilled water pumps and controls to emergency power circuits. The drawings and specifications provide details on the new transformer installation, switchgear upgrades, conduit routing, and panel and equipment locations. Deductive alternates are included to remove specific scopes of work related to various air handlers, chilled water pumps, and HVAC controls from the project.
The related federal contract opportunity is a pre-solicitation to furnish all material, equipment, and labor necessary to complete the electrical upgrade per the specifications and drawings. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9.
View the file
Other files for this federal contract opportunity
Show all 50
Upgrade 480V Electrical System has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP STAIRWELL #1
SUB-BAS
A-
STAIRWELL #2
A-
STAIRWELL #1
SUB-BAS
A-
STAIRWELL #2
A-
DUCTILE IRON
P-3
P-2
P-1
SUB-BASEMENT
SB-4
ATS-1 PANEL EEQ PANEL EEQA PANEL ELP
ATS-4
PANEL EEQB
ATS-7
N1TIP-1
N1TIP-2
EEQ1SB
ATS-3
ATS-2
EMS
PANEL NMS
STREET
LIGHTS PANEL
ST LIGHTS
CONTROL
PANEL ELS
208/120V SB-2
480/277V SB-1
EP 480/1
EP 480
ATS-A
EMS 480V
ATS-B ATS-C
N1TP2
EEQ1SB2
EEQC
ATS-9
SB-1
TAPPED
BUS
EP0001
EP0001
FIRE
ALARM
PANEL
SECTION 3 SECTION 1
OLD T1C
ALT #2
ALT #2
ALT #2
ALT. #1
NEW XFMR T1C
SB-1
SB-2
DRILL WALL INTO SUB-
BASEMENT FOR CONDUIT.
PROVIDE LINK SEALS IN
WALL PENETRATIONS.
PROVIDE UNISTRUT
RACKS TO SUPPORT
CONDUIT FROM CEILING
WALKABLE CRAWL SPACE
JUNCTION BOX
CHWP-1
HRCP-1
TEMP CONTROL
PANEL
EEQ1SB-9
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956
STAMPCONSULTANT
321 4 5 6 7 8 9 10
603-20-505
Louisville, KY
UPGRADE 480V
ELECTRICAL SYSTEM
C :\U se rs
\J ac k\ D oc um en ts
\L ou is vi lle
U pg ra de
V El ec S ys te m (2
8)
_j ac k.
bo nb rig ht T4
3D B.
rv t
3/
/2
8:
:2
AM
EP0001
SUB-BASEMENT ELECTRICAL
PLAN
03/01/21 JB HT
1/4" = 1'-0"3 SUB-BASEMENT-SWITCHBOARD ROOM-EAST
K E Y N O T E S
1 PROVIDE NEW 200A CIRCUIT BREAKERS IN PANELS EMS-480V (SQUARE D,
I-LINE) CKT #17, 19, 21 & SB-1 (EATON) CKT. #13. RATED 65KA.
2 EMPTY AND DISPOSE SILICON OIL FROM TRANSFORMER. THIS OIL MAY
CONTAIN PCBS. ABANDON TRANSFORMER IN PLACE. DISCONNECT AND
REMOVE WIRING TO THE MAIN CIRCUIT BREAKER IN SB-1.
3 USE 1600A BKR IN SB-1 TO CONNECT TO NEW TRANSFORMER T1C,
PROVIDE NECESSARY CONDUITS AND FITTINGS TO CONNECT CONDUIT
TO MAIN CABINET. PRODUCE PROPER BONDING, BONDING BUSHINGS,
LUGS, BONDING GROUND WIRE, ETC.
4 NEW (4) SETS (4) 600KCMIL, 4"C.
5 PROVIDE UNISTRUT TO MOUNT ATS-9 AND PANEL EEQC. FOLLOW
INSTALLATION AS SHOWN IN PHOTO 4/EP0001 FOR PANELS.
6 REMOVE MEDIUM VOLTAGE SWITCH. DISCONNECT 15KV CABLE AND
REMOVE BACK TO MANHOLE AND TO TRANSFORMER.
7 LOCATION OF NEW ATS-9. PROVIDE UNISTRUT SUPPORT FRAME.
8 RELOCATE 20A/3P CIRCUIT FOR PUMPS AH-17, 23, & 43 TO PANEL EEQC.
3#12 AWG, 12 GROUND, 3/4"C.
9 PROVIDE BREAKERS FOR HVAC CONTROL PANELS. (ALT #1)
10 LABEL TRANSFORMER "ABANDONED - LOCATION OF NEW TRANSFORMER
T1C OUTSIDE SOUTH OF PATIENT ADVOCATE SUITE.
11 DISCONNECT EXISTING CIRCUIT FOR TEMPERATURE CONTROL PANEL
FOR AHU-43. MARK CIRCUIT AS 'SPARE'. POWER TEMPERATURE
CONTROL PANEL FROM EEQ1SB-9.
1/16" = 1'-0"2 SUB-BASEMENT-CONDUIT ROUTING
1/8" = 1'-0"1 SUB-BASEMENT-MECH EQPMT-WEST
4 SUB-BASEMENT ATS AND PANEL LOCATION5
ABANDONED UNIT SUBSTATION TRANSFORMER AND MEDIUM VOLTAGE
SWITCH
Revisions: Date:
SCHEMATIC DESIGN 25% 11/06/20
BID DOCUMENTS 100% 03/12/21
G E N E R A L N O T E S
03/12/2021
BASE BID:
PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS
DEDUCT ALTERNATES
ALT #1:
DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).
DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY
FAN & EXHAUST FAN.
ALT #2:
DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.
ALT #3:
DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).
PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.
ALT #4:
DEDUCT ALL ELECTRICAL WORK FOR AHU - 42 AND DX - 42 (PANELBOARD DP)
| Sheets |
| E501 - PARTIAL MEDIUM VOLTAGE SINGLE-LINE DIAGRAM |
| EP0001 - SUB-BASEMENT ELECTRICAL PLAN |
| EP300 - OVERALL THIRD FLOOR PLAN |
File details come from the government source that posted it. Updated .