14.05_EP0001 - SUB-BASEMENT ELECTRICAL PLAN.pdf

PDF 1 MB Posted

Attached to
Upgrade 480V Electrical System Federal contract opportunity
Solicitation number
36C24921R0084
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9

About this file

This document includes plans and specifications for an electrical upgrade project at a Department of Veterans Affairs medical facility. The project involves installing a new 1150 KVA outdoor transformer to feed upgraded 480V switchgear in the sub-basement, correcting wiring deficiencies for CAT scan rooms, and moving electrical feeds for several air handlers and associated chilled water pumps and controls to emergency power circuits. The drawings and specifications provide details on the new transformer installation, switchgear upgrades, conduit routing, and panel and equipment locations. Deductive alternates are included to remove specific scopes of work related to various air handlers, chilled water pumps, and HVAC controls from the project.

The related federal contract opportunity is a pre-solicitation to furnish all material, equipment, and labor necessary to complete the electrical upgrade per the specifications and drawings. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 9.

View the file

Other files for this federal contract opportunity

Other files attached to Upgrade 480V Electrical System, newest first.
File Type Posted
KY20210093 Wage Determination.pdf PDF
Pad-mount Med V Xforms.pdf PDF
RFIs May 24.docx DOCX document
36C24921R0084_1.pdf PDF
S02-Price Schedule (Project 603-20-505) FY2021.xlsx XLSX spreadsheet
36C24921R0084 0001.pdf PDF
265600 Ext Lighting.pdf PDF
312011 Earthwork.pdf PDF
260526 Grounding and Bonding.pdf PDF
260533 Raceway and Boxes.pdf PDF
262413 Distribution Switchboard.pdf PDF
260513 Med Voltage Cables.pdf PDF
018113 Sustainable Construction Requirements.pdf PDF
040516 Masonry Grouting2.pdf PDF
14.10_EP101 - FIRST FLOOR ELECTRICAL PLAN.pdf PDF
14.14_EP400 - OVERALL FOURTH FLOOR PLAN.pdf PDF
14.19_EP900 - OVERALL NINTH FLOOR PLAN.pdf PDF
14.12_EP201 - SECOND FLOOR ELECTRICAL PLAN.pdf PDF
14.01_E500 - SCHEDULES, DETAILS AND SINGLE-LINE DIAGRAM.pdf PDF
260511 Req Electric.pdf PDF
033053 Cast in Place Conrete.pdf PDF
013216-15 Schedules 2.pdf PDF
013323 Shop Drawings.pdf PDF
014219 Ref Standards.pdf PDF
14.20_ES100 - ELECTRICAL SITE PLAN.pdf PDF
14.18_EP800 - OVERALL EIGHT FLOOR PLAN.pdf PDF
14.15_EP500 - OVERALL FIFTH FLOOR PLAN.pdf PDF
14.09_EP100 - OVERALL FIRST FLOOR PLAN.pdf PDF
14.17_EP700 - OVERALL SEVENTH FLOOR PLAN.pdf PDF
14.08_EP001B - BASEMENT ELECTRICAL PLAN-B.pdf PDF
14.00_E001 - LEGEND.pdf PDF
264313 Surge Prot Dev.pdf PDF
260541 Underground Elec Const.pdf PDF
262416 Panelboards.pdf PDF
260573 Overcurrent Prot Device Study.pdf PDF
078400 Firestopping.pdf PDF
013526 Safety Req.pdf PDF
079200 Joint Sealants.pdf PDF
0000 cover Rev 1.pdf PDF
047200 CAST STONE MASONRY.pdf PDF
024100 Demolition.pdf PDF
014529 Testing Laboratory Services.pdf PDF
Combined Drawings.pdf PDF
14.11_EP200 - OVERALL SECOND FLOOR PLAN.pdf PDF
14.16_EP600 - OVERALL SIXTH FLOOR PLAN.pdf PDF
14.13_EP300 - OVERALL THIRD FLOOR PLAN.pdf PDF
14.04_EP0000 - OVERALL SUB-BASEMENT PLAN.pdf PDF
14.03_E600 - PANEL SCHEDULES.pdf PDF
S15-PPQ-Template (Project 603-20-505) Upgrade 480V Electrical System.pdf PDF
S03-Successful FBO Posting-36C24921R0084 (603-20-505).pdf PDF
Show all 50

Upgrade 480V Electrical System has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP STAIRWELL #1

SUB-BAS

A-

STAIRWELL #2

A-

STAIRWELL #1

SUB-BAS

A-

STAIRWELL #2

A-

DUCTILE IRON

P-3

P-2

P-1

SUB-BASEMENT

SB-4

ATS-1 PANEL EEQ PANEL EEQA PANEL ELP

ATS-4

PANEL EEQB

ATS-7

N1TIP-1

N1TIP-2

EEQ1SB

ATS-3

ATS-2

EMS

PANEL NMS

STREET

LIGHTS PANEL

ST LIGHTS

CONTROL

PANEL ELS

208/120V SB-2

480/277V SB-1

EP 480/1

EP 480

ATS-A

EMS 480V

ATS-B ATS-C

N1TP2

EEQ1SB2

EEQC

ATS-9

SB-1

TAPPED

BUS

EP0001

EP0001

FIRE

ALARM

PANEL

SECTION 3 SECTION 1

OLD T1C

ALT #2

ALT #2

ALT #2

ALT. #1

NEW XFMR T1C

SB-1

SB-2

DRILL WALL INTO SUB-

BASEMENT FOR CONDUIT.

PROVIDE LINK SEALS IN

WALL PENETRATIONS.

PROVIDE UNISTRUT

RACKS TO SUPPORT

CONDUIT FROM CEILING

WALKABLE CRAWL SPACE

JUNCTION BOX

CHWP-1

HRCP-1

TEMP CONTROL

PANEL

EEQ1SB-9

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD FFE Inc Engineering and Technical Services 110 Boggs Lane, Suite 170 Springdale, OH 45246 513-522-0956

STAMPCONSULTANT

321 4 5 6 7 8 9 10

603-20-505

Louisville, KY

UPGRADE 480V

ELECTRICAL SYSTEM

C :\U se rs

\J ac k\ D oc um en ts

\L ou is vi lle

U pg ra de

V El ec S ys te m (2

8)

_j ac k.

bo nb rig ht T4

3D B.

rv t

3/

/2

8:

:2

AM

EP0001

SUB-BASEMENT ELECTRICAL

PLAN

03/01/21 JB HT

1/4" = 1'-0"3 SUB-BASEMENT-SWITCHBOARD ROOM-EAST

K E Y N O T E S

1 PROVIDE NEW 200A CIRCUIT BREAKERS IN PANELS EMS-480V (SQUARE D,

I-LINE) CKT #17, 19, 21 & SB-1 (EATON) CKT. #13. RATED 65KA.

2 EMPTY AND DISPOSE SILICON OIL FROM TRANSFORMER. THIS OIL MAY

CONTAIN PCBS. ABANDON TRANSFORMER IN PLACE. DISCONNECT AND

REMOVE WIRING TO THE MAIN CIRCUIT BREAKER IN SB-1.

3 USE 1600A BKR IN SB-1 TO CONNECT TO NEW TRANSFORMER T1C,

PROVIDE NECESSARY CONDUITS AND FITTINGS TO CONNECT CONDUIT

TO MAIN CABINET. PRODUCE PROPER BONDING, BONDING BUSHINGS,

LUGS, BONDING GROUND WIRE, ETC.

4 NEW (4) SETS (4) 600KCMIL, 4"C.

5 PROVIDE UNISTRUT TO MOUNT ATS-9 AND PANEL EEQC. FOLLOW

INSTALLATION AS SHOWN IN PHOTO 4/EP0001 FOR PANELS.

6 REMOVE MEDIUM VOLTAGE SWITCH. DISCONNECT 15KV CABLE AND

REMOVE BACK TO MANHOLE AND TO TRANSFORMER.

7 LOCATION OF NEW ATS-9. PROVIDE UNISTRUT SUPPORT FRAME.

8 RELOCATE 20A/3P CIRCUIT FOR PUMPS AH-17, 23, & 43 TO PANEL EEQC.

3#12 AWG, 12 GROUND, 3/4"C.

9 PROVIDE BREAKERS FOR HVAC CONTROL PANELS. (ALT #1)

10 LABEL TRANSFORMER "ABANDONED - LOCATION OF NEW TRANSFORMER

T1C OUTSIDE SOUTH OF PATIENT ADVOCATE SUITE.

11 DISCONNECT EXISTING CIRCUIT FOR TEMPERATURE CONTROL PANEL

FOR AHU-43. MARK CIRCUIT AS 'SPARE'. POWER TEMPERATURE

CONTROL PANEL FROM EEQ1SB-9.

1/16" = 1'-0"2 SUB-BASEMENT-CONDUIT ROUTING

1/8" = 1'-0"1 SUB-BASEMENT-MECH EQPMT-WEST

4 SUB-BASEMENT ATS AND PANEL LOCATION5

ABANDONED UNIT SUBSTATION TRANSFORMER AND MEDIUM VOLTAGE

SWITCH

Revisions: Date:

SCHEMATIC DESIGN 25% 11/06/20

BID DOCUMENTS 100% 03/12/21

G E N E R A L N O T E S

03/12/2021

BASE BID:

PROVIDE ALL WORK SHOWN ON DRAWINGS AND SPECIFICATIONS

DEDUCT ALTERNATES

ALT #1:

DEDUCT ALL ELECTRICAL WORK ASSOCIATED FOR ELECTRICAL RISER FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. (PANELBOARD DAC-S) ELECTRICAL RISER FOR CHILLED WATER PUMP (PANELBOARD HB).

DEDUCT WORK FOR HVAC PUMPS. CONTROLS FOR AHU - 3, 5, 6, 7, 9, 12 AND 13. DEDUCT WORK FOR AHU-43 SUPPLY

FAN & EXHAUST FAN.

ALT #2:

DEDUCT ALL ELECTRICAL WORK CHILLED WATER PUMPS FOR AHU - 17, 23, 43.

ALT #3:

DEDUCT ALL ELECTRICAL WORK FOR CHILLED WATER PUMPS FOR AHU - 4A AND AHU - 8A (MCC IN ROOMS M-003).

PUMPS P1, P2, P3, P4. AHU - 8A AND EF8 MCC IN ROOM C-220.

ALT #4:

DEDUCT ALL ELECTRICAL WORK FOR AHU - 42 AND DX - 42 (PANELBOARD DP)

Sheets
E501 - PARTIAL MEDIUM VOLTAGE SINGLE-LINE DIAGRAM
EP0001 - SUB-BASEMENT ELECTRICAL PLAN
EP300 - OVERALL THIRD FLOOR PLAN

File details come from the government source that posted it. Updated .