This document contains construction drawings and specifications for Project 621-332 to expand an existing parking garage and add an overhead walkway at the James H. Quillen VA Medical Center in Mountain Home, Tennessee. The project involves adding two new levels to the parking garage and constructing an overhead pedestrian walkway according to the drawings and specifications provided. Work will take place in a medical environment, so infection control, demolition, noise control, dust control, and other specialized facility requirements for working in a hospital setting must be addressed. The estimated value of construction is between $5 million and $10 million.
The related pre-solicitation notice is for construction services for the same project. The opportunity is a 100% SDVOSB set-aside to be awarded under FAR Part 15 using LPTA procedures. The solicitation is expected to be released on or by January 15, 2021. Only SDVOSBs verified in the CVE database and listed in SAM will be considered. The awarded contractor must enroll in VETS-4212 and pass a responsibility determination. Questions may only be submitted in writing to the named contracting officer prior to solicitation with the required reference information.
View the file
Other files
Show 40 more
Latest 50 of 174 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PARTIAL RISER DIAGRAM - TELECOM
EMERGENCY TELEPHONE RISER DIAGRAM AND NOTES
BUILDING 160 PACS DIAGRAM AND NOTES
COURTYARD CAMERAS SYSTEM (FUTURE)
SYSTEMS RISER DIAGRAM
E302
APPROVED FOR CONSTRUCTION
FINAL CONSTRUCTION DRAWINGS
ARCHITECT/ENGINEERS: CONSULTANTS:
CONSULTANTS
WALKERDesign, Inc.
REISSUED
SHEET NOTES
SHEET KEYNOTES
OF 143137PAGE
AutoCAD SHX Text EMERGENCY PHONE NOTES: 1. INSTALL EMERGENCY SPEAKER PHONES NEAR STAIR ENTRIES (AND ELEVATOR LANDING) ON INSTALL EMERGENCY SPEAKER PHONES NEAR STAIR ENTRIES (AND ELEVATOR LANDING) ON EACH FLOOR, AS INDICATED ON FLOOR PLANS, SUCH THAT PUSH BUTTON IS LOCATED 48" AFF. 2. ROUTE ONE TWO-TWISTED-PAIR, 24 GAUGE, SHIELDED CABLE FROM THE SPEAKER PHONE ROUTE ONE TWO-TWISTED-PAIR, 24 GAUGE, SHIELDED CABLE FROM THE SPEAKER PHONE IN EACH UNIT TO THE TBB IN THE TELECOM ROOM, 1-1/4"C. MIN. SHIELDS SHALL BE GROUNDED IN TELECOM ROOM. 3. PROVIDE ADDITIONAL SURGE PROTECTION FOR EACH PHONE LINE, AT THE BACKBOARD, PROVIDE ADDITIONAL SURGE PROTECTION FOR EACH PHONE LINE, AT THE BACKBOARD, BETWEEN THE PHONE AND THE DISTRIBUTION BLOCK. 4. ROUTE ONE SPARE CABLE TO THE UPPERMOST EMERGENCY PHONE UNIT AT EACH RISER. ROUTE ONE SPARE CABLE TO THE UPPERMOST EMERGENCY PHONE UNIT AT EACH RISER. 5. PROVIDE ONE COMMON #12 GROUND WIRE IN ALL SIGNAL CONDUITS. TERMINATE ON TMGB PROVIDE ONE COMMON #12 GROUND WIRE IN ALL SIGNAL CONDUITS. TERMINATE ON TMGB AT BACKBOARD IN TELECOM ROOM. 6. ENCLOSURE SHALL BE DIE-CAST ALUMINUM WITH PUSH-BUTTON LATCH, GASKETED DOOR, ENCLOSURE SHALL BE DIE-CAST ALUMINUM WITH PUSH-BUTTON LATCH, GASKETED DOOR, YELLOW FINISH WITH RED 'TELEPHONE' LOGO, BASIS OF DESIGN: ALLEN TEL PROD. BASIS OF DESIGN: ALLEN TEL PROD. ALLEN TEL PROD. ALLEN TEL PROD. #GB90H-04. NEW UNITS SHALL MATCH EXISTING. 7. PHONE SHALL BE LINE-POWERED, VANDAL RESISTANT, BLACK FINISH, ALUMINUM FACE PHONE SHALL BE LINE-POWERED, VANDAL RESISTANT, BLACK FINISH, ALUMINUM FACE PLATE WITH HEAVY DUTY METAL CALL BUTTON AND MOUNTING GASKET. PHONE SHALL BE CONSTRUCTED FOR EXTERIOR LOCATIONS PRONE TO LOW TEMPERATURES, CONDENSATION AND OCCASIONAL WATER DROPS. BASIS OF DESIGN: VIKING #E-10A-EWP. PROVIDE BASIS OF DESIGN: VIKING #E-10A-EWP. PROVIDE VIKING #E-10A-EWP. PROVIDE MOUNTING PLATE (W/ BLACK FINISH) AS REQ'D TO MOUNT PHONE IN ENCLOSURE. NEW UNITS SHALL MATCH EXISTING. 8. NEW POWER HOMERUNS TO PNL ELA SHALL CONSIST OF 2#10 AND 1#10G IN 3/4"C.NEW POWER HOMERUNS TO PNL ELA SHALL CONSIST OF 2#10 AND 1#10G IN 3/4"C.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
EXIST. TO BLDG 160 TELECOM ROOM
AutoCAD SHX Text
%%UGL TELECOM ROOM
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
%%UGROUND LEVEL
AutoCAD SHX Text
%%USECOND LEVEL
AutoCAD SHX Text
%%UTHIRD LEVEL
AutoCAD SHX Text
TBB IN TELECOM RM. (GROUND LEVEL)
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text "CALL FOR EMERGENCY ASSISTANCE" SIGN. SEE LIGHTING FIXTURE SCHEDULE ON SHEET E400. (TYP.)
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
EM. 120V PNL ELA
AutoCAD SHX Text
EM. 120V PNL ELA (EXIST. CKT)
AutoCAD SHX Text J
AutoCAD SHX Text
%%UFOURTH LEVEL
AutoCAD SHX Text J
AutoCAD SHX Text
%%UTOP LEVEL
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
%%USTAIR NO. 1
AutoCAD SHX Text
%%USTAIR NO. 3
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
STAIR NO. 4 & ELEVATORS NO. 4
AutoCAD SHX Text
ELEVATORS NOS. 2A & 2B
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
SIGNAL CONDUIT. SEE NOTES ABOVE. (TYP.)
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text J
AutoCAD SHX Text
EM. 120V PNL ELA
AutoCAD SHX Text
AutoCAD SHX Text
TMGB
AutoCAD SHX Text
AutoCAD SHX Text
TO EMERGENCY ASSISTANCE PHONE RISERS (QTY. AS REQ'D)
AutoCAD SHX Text
EM. 120V PNL ELA (EXIST. CKT)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PACS CP
AutoCAD SHX Text PHYSICAL ACCESS CONTROL SYSTEM NOTES: 1. ALL COMPONENTS OF THE ACCESS CONTROL SYSTEM SHALL BE UL294 LISTED. ALL COMPONENTS OF THE ACCESS CONTROL SYSTEM SHALL BE UL294 LISTED. 2. 1/2"C. PERMITTED FOR CABLING ROUTING WITHIN VESTIBULE. 1/2"C. PERMITTED FOR CABLING ROUTING WITHIN VESTIBULE. 3. REFER TO ARCHITECTURAL SPECS AND DRAWINGS FOR DOORS, FRAMES, HARDWARE AND REFER TO ARCHITECTURAL SPECS AND DRAWINGS FOR DOORS, FRAMES, HARDWARE AND LOCKING HARDWARE. 4. LATCH AND HINGE SIDES OF DOORS ARE VARIED FOR INDIVIDUAL DOORS. VERIFY LATCH LATCH AND HINGE SIDES OF DOORS ARE VARIED FOR INDIVIDUAL DOORS. VERIFY LATCH AND HINGE SIDE FOR EACH DOOR PRIOR TO ROUGH-IN. 5. SEE ARCHITECTURAL PLANS FOR EXACT LOCATION OF CARD READERS AND PUSH PLATES. SEE ARCHITECTURAL PLANS FOR EXACT LOCATION OF CARD READERS AND PUSH PLATES. 6. VERIFY ALL CONDUIT SIZES, BOX SIZES AND CONNECTIVITY WITH ELECTRONIC SECURITY VERIFY ALL CONDUIT SIZES, BOX SIZES AND CONNECTIVITY WITH ELECTRONIC SECURITY SYSTEM INSTALLER PRIOR TO ROUGH-IN. ANY CHANGES REQUIRED AFTER ROUGH-IN SHALL BE PERFORMED AT NO ADDITIONAL COST TO THE GOVERNMENT. 7. CABLING AND CONDUIT SHALL NOT BE ROUTED EXPOSED. COORDINATE WITH TRADES AS CABLING AND CONDUIT SHALL NOT BE ROUTED EXPOSED. COORDINATE WITH TRADES AS REQUIRED TO ROUTE CABLING IN MULLIONS AND STRUCTURAL ELEMENTS. 8. CONTRACTOR SHALL PROVIDE ACCESS CONTROL CONDUCTORS AND INTERCONNECTION CONTRACTOR SHALL PROVIDE ACCESS CONTROL CONDUCTORS AND INTERCONNECTION CONDUCTORS AND ACCESSORIES AS REQUIRED FOR A COMPLETE AND FUNCTIONAL INSTALLATION. COORDINATE WITH DOOR AND LOCKING HARDWARE APPROVED SHOP DRAWINGS.
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text
CARD READER
AutoCAD SHX Text
EDO
AutoCAD SHX Text
CR
AutoCAD SHX Text
PP
AutoCAD SHX Text
PUSH PLATE
AutoCAD SHX Text
ELECTRIC DOOR OPERATOR
AutoCAD SHX Text EXISTING PACS CONTROL PANEL, HIRSH M8. NEW CABLES SHALL BE TERMINATED ON EXISTING SPARE TERMINALS IN ACCORDANCE WITH MANUFACTURER INSTRUCTIONS.
AutoCAD SHX Text PLENUM RATED CARD ACCESS COMPOSITE CABLE, YELLOW OVERALL JACKET. SHALL MATCH EXISTING: GENERAL CABLE #454932AYW E335585 CMP 75°C 18/6C SHLD + 18/4CSHLD + 16/2C SHLD + 22/4C SHLD. PROVIDE SLEEVES FOR RATED WALL PENETRATIONS.
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text 3/4"C. W/ 3-CAT5E CABLES TO ELEVATOR CONTROL ROOM. PROVIDE JB INSIDE CONTROL ROOM. CONNECT (1) CABLE TO EACH ELEVATOR CONTROLLER.
AutoCAD SHX Text
PROVIDE ENCLOSURE.
AutoCAD SHX Text RISER DIAGRAM FOR FUTURE COURTYARD CAMERAS: 1. SEE PLANS FOR RACEWAY ROUTING. PROVIDE PULLSTRING IN ALL CONDUITS.SEE PLANS FOR RACEWAY ROUTING. PROVIDE PULLSTRING IN ALL CONDUITS.
AutoCAD SHX Text
UG PB NEAR BRIDGE COLUMN (TYP. OF 2)
AutoCAD SHX Text
(3) BACKBOXES FOR FUTURE CAMERAS AT NEW BRIDGE COLUMN NEAREST B160
AutoCAD SHX Text
(3) BACKBOXES FOR FUTURE CAMERAS AT COLUMN NEAR SOUTHERN EDGE OF COURTYARD
AutoCAD SHX Text
%%UELEC ROOM
AutoCAD SHX Text
%%U2ND LEVEL (N.T.S.)
AutoCAD SHX Text
RISER GUARDS
AutoCAD SHX Text (3)2"C.
AutoCAD SHX Text
%%UL3 TELECOM ROOM
AutoCAD SHX Text
%%U3RD LEVEL (N.T.S.)
AutoCAD SHX Text
TMGB
AutoCAD SHX Text
TBB
AutoCAD SHX Text
(2) EXIST. TBBS
AutoCAD SHX Text
1"C. WITH #6 INSULATED GROUND
AutoCAD SHX Text
DEDUCT ALT. NO. 2 & 3
AutoCAD SHX Text A. SEE SHEET E001 FOR ADDITIONAL SEE SHEET E001 FOR ADDITIONAL E001 FOR ADDITIONAL FOR ADDITIONAL GENERAL NOTES. B. ALL RACEWAY IN ELECTRICAL AND ALL RACEWAY IN ELECTRICAL AND TELECOM ROOMS SHALL BE LABELED TO IDENTIFY THE CONTENTS AND THE TERMINATION POINT OF THE CONDUIT RUN. LABELS SHALL BE ADHESIVE VINYL OR SIMILARLY DURABLE. C. CAT5E CABLE TERMINATIONS SHALL CAT5E CABLE TERMINATIONS SHALL COMPLY WITH VA'S 568A CONFIGURATION. D. CONTRACTOR SHALL PROVIDE PULLBOXES CONTRACTOR SHALL PROVIDE PULLBOXES AS REQUIRED TO ACCOMPLISH PULLS. PLANS AND RISERS DO NOT DEPICT ALL REQUIRED PULLBOXES. E. REFER TO STRUCTURAL SHEETS FOR REFER TO STRUCTURAL SHEETS FOR DISTANCES BETWEEN FLOORS. F. PROTECT VERTICAL CONDUIT RISERS. PROTECT VERTICAL CONDUIT RISERS. SEE DETAIL 6, SHEET E401. G. CONDUITS SHALL NOT BE ROUTED CONDUITS SHALL NOT BE ROUTED THROUGH EXPANSION JOINTS. H. PENETRATIONS SHALL NOT BE MADE PENETRATIONS SHALL NOT BE MADE THROUGH THE TOPS OF WP BOXES OR WP ENCLOSURES.
AutoCAD SHX Text
1. CABLE SHIELDS SHALL BE BONDED TO CABLE SHIELDS SHALL BE BONDED TO GROUND. 2. EXISTING CIRCA TELECON PROTECTED EXISTING CIRCA TELECON PROTECTED ENTRANCE TERMINALS. 3. PROVIDE ADDITIONAL 110-STYLE BLOCKS PROVIDE ADDITIONAL 110-STYLE BLOCKS AND CROSS CONNECTS AS REQUIRED FOR TERMINATING PHONE CABLING. 4. EXISTING 50-PAIR CABLE. EXISTING 50-PAIR CABLE. 5. CABLE SHALL NOT BE RUN EXPOSED CABLE SHALL NOT BE RUN EXPOSED ON WALLS. TERMINATE CONDUITS BELOW TOP OF BACKBOARD. 6. GROUND CONDUCTORS SHALL BE GROUND CONDUCTORS SHALL BE BONDED TO CONDUIT VIA GROUNDING BUSHING AND BONDED TO TMGB. 7. APPLY FIRE RESISTANT PAINT TO APPLY FIRE RESISTANT PAINT TO EXISTING TBB (2-4'X8' PLYWOOD BOARDS). 8. PROVIDE LINE PROTECTION MODULES PROVIDE LINE PROTECTION MODULES FOR ALL NEW SIGNAL CONDUCTORS.
AutoCAD SHX Text one-quarter inch = one foot
AutoCAD SHX Text Revisions
AutoCAD SHX Text Date
AutoCAD SHX Text one-eighth inch = one foot
AutoCAD SHX Text
VA FORM 08-6231, DEC 1989
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text F
AutoCAD SHX Text three-eighths inch = one foot
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one-half inch = one foot
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text one and one-half inches = one foot
AutoCAD SHX Text one inch = one foot
AutoCAD SHX Text three-quarters inch = one foot
AutoCAD SHX Text D
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text three inches = one foot
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Approved: Chief, Engineering Service
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text C.O.T.R.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Engineering Planning & Analysis
AutoCAD SHX Text Engineering Health & Safety
AutoCAD SHX Text Engineering Operation Foreman
AutoCAD SHX Text Engineering Bldg. Maint. Foreman
AutoCAD SHX Text Asst. Chief, Engineering Service
AutoCAD SHX Text Approved:
AutoCAD SHX Text Approved: Service Chief
AutoCAD SHX Text Drawing Title
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
VAMC MOUNTAIN HOME, TENNESSEE
AutoCAD SHX Text Location
AutoCAD SHX Text Project Title
AutoCAD SHX Text Building Number
AutoCAD SHX Text Checked
AutoCAD SHX Text
ADD OVERHEAD WALKWAY
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text Drawn
AutoCAD SHX Text Date
AutoCAD SHX Text 621-332
AutoCAD SHX Text
AUGUST 10, 2020
AutoCAD SHX Text Department of
AutoCAD SHX Text Veterans Affairs
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text D
AutoCAD SHX Text C
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text A
AutoCAD SHX Text Dwg. File
AutoCAD SHX Text
EXPAND PARKING GARAGE &
AutoCAD SHX Text
AutoCAD SHX Text 4904 Eisenhower Blvd Suite 150 Tampa, FL 33634 PH: (813) 888-5800 FAX: (813) 502-5726 BE-0003840 www.walkerconsultants.com
AutoCAD SHX Text
PH: (850) 433-3023
AutoCAD SHX Text
FAX: (850) 433-3025
AutoCAD SHX Text
FRANK DAUGHTRY
AutoCAD SHX Text a r c h i t e c t
AutoCAD SHX Text Pensacola, FL 32502
AutoCAD SHX Text email: frank@frankda.com
AutoCAD SHX Text 200 E. Government Street
AutoCAD SHX Text Suite 240-A
AutoCAD SHX Text Project No.
AutoCAD SHX Text CONTRACT No. 36C249-19-C-0168
AutoCAD SHX Text P.O. No. 621Z90002
AutoCAD SHX Text
SEAL
AutoCAD SHX Text
AKEA DESIGN, INC.
AutoCAD SHX Text
RANDALL A. HENSLEY, P.E. FLORIDA P.E. NO. 37944
AutoCAD SHX Text 3603 NW 98TH ST., SUITE B GAINESVILLE, FLORIDA 32606 PH: (352) 474-6124 FAX: (352) 553-4437 CERT OF AUTH: FL #29758 AKEA Design Project No. AD177-19
AutoCAD SHX Text This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.